Client : M/s Tamil Nadu Generation and Distribution Corportion 
Ltd. (Tangedco.) Eastern Wing 
  Contractor :  L&T LIMITED (L&T‐ECC MANAPAKKAM) 
Projects :  Coastal disaster Risk Reduction Project (CDRRP) Over   
Head to Under Ground Conversion 
Consultant : N _ARC Consulting New Delhi   
  Specification no. CMKL/835/19‐20  REV.   0  DATE:  17.05.2019 
 
S. No.  DESCRIPTION  UNIT  VALUE 
1.0  SYSTEM DESIGN DATA 
1.1  DESIGN AMBIENT  °C  40 
1.2  AC SUPPLY 
a)  Rated Voltage  V  415 
b)  Rated Frequency  Hz 50
c)  Voltage Variation (permissible)  %  +10%  to ‐10% 
d)  Frequency  Variation (permissible)  %  +5%  to ‐5% 
e)  Combined voltage & frequency     
variation (sum of absolutes  %  10% 
permissible) 
f)  System Fault level & duration  kA, Sec.  As per drawing 10ka For 1Sec 
2.0  APPLICABLE STANDARDS 
IEC 60439/IS 8623  Low voltage switchgear & controlgrear assemblies  
IEC 60529          Degrees of protection provided by enclosures 
IS 60947            Low voltage switchgear & control gear 
IS 13703            Low voltage fuses for voltages not exceeding 1000V AC or 1500V 
IS 10118            Code practice for selection, installation, and maintenance of  
                           Switchgears and control gear 
IS 60898            Electrical accessories – circuit breakers for over protection for  
                           household and similar installations 
IS 60079            Explosive atmospheres  
IS 2551              Danger notice plates 
 
 
 
 
 
 
 

DATA SHEET Page 1


 
Sensitivity: LNT Construction Internal Use 
 
Client : M/s Tamil Nadu Generation and Distribution Corportion 
Ltd. (Tangedco.) Eastern Wing 
  Contractor :  L&T LIMITED (L&T‐ECC MANAPAKKAM) 
Projects :  Coastal disaster Risk Reduction Project (CDRRP) Over   
Head to Under Ground Conversion 
Consultant : N _ARC Consulting New Delhi   
  Specification no. CMKL/835/19‐20  REV.   0  DATE:  17.05.2019 
 
S. No.  DESCRIPTION  UNIT  VALUE 
       

3.0  SERVICE PILLAR‐S1 
3.1  Operational Front    Single front 
3.2  Type of Execution of modules    Fixed  
(functional unit) 
3.3  Type of installation  Floor mounted, Legs at the base 
height max 300mm 
3.4  Type of sheet steel    HR Sheet (Hot Dip Galvanized) 
a)  Load bearing members  mm  3.0 HR sheet (hot dip galvanized) 
b)  Frames  mm 90‐125 microns (tolerance as per 
c)  Door  mm applicable is) 
d)  Angle iron stand  mm  75x75x6mm with hot dip 
galvanized.  
e)  Apron    3.0 HR sheet (hot dip galvanized) 
3.6  Cable Entry  mm Bottom
3.7  Bus Bar 
a)  Material    Aluminum (E91E grade) 
b)  Size  mm Phase‐ 50x10mm/EQ. cross section
Neutral‐38x6mm/EQ. cross section 
c)  Conical bushing material  Powermat
3.8  Earth Bus bar Material  Earthing Stud M10 
3.9  Degree of Protection    IP‐55 for Outdoor 
3.10  Gland Plate Thickness  mm  3.0mm Galvanized Steel Sheet 
(275GSM) With Knock out Punch for 
Suitable Cable   

DATA SHEET Page 2


 
Sensitivity: LNT Construction Internal Use 
 
Client : M/s Tamil Nadu Generation and Distribution Corportion 
Ltd. (Tangedco.) Eastern Wing 
  Contractor :  L&T LIMITED (L&T‐ECC MANAPAKKAM) 
Projects :  Coastal disaster Risk Reduction Project (CDRRP) Over   
Head to Under Ground Conversion 
Consultant : N _ARC Consulting New Delhi   
  Specification no. CMKL/835/19‐20  REV.   0  DATE:  17.05.2019 
 
3.11  Rewireable fuse      3 nos 100A rewireable fuse (Kitkat 
type) with 200A Fuse unit (fuse 
base & Fuse Holder) made of 
porcelain shall be provided. Tined 
copper wire for fuse 14swg or 
higher as per requirement 
3.12  Incomer Cable Size   1Rx4Cx185/150 /95/50Sq.mm AL 
Armoured XLPE Cable x 2nos. 
3.13  Outgoing Cable Size  1Rx4Cx35/25/16Sq.mm & 
2Cx16/10Sq.mm AL Armoured  
XLPE Cable x 10 outgoings per 
phase ‐ 3phase or 1 phase 
requirements as per site condition) 
 
3.14  lock    2 nos. panel lock (quarter turn 
triangle type) with open close 
sticker 
       

4  REWIREABLE FUSE   
a)  Rating     100A Rewireable Fuse with 200A 
Fuse unit (Fuse base & Fuse Holder) 
made of porcelain 
b)  Make    INDOASIAN/PC INDUSTRIES/CMKL 
 

DATA SHEET Page 3


 