Professional Documents
Culture Documents
Manual EQ PDF
Manual EQ PDF
Eagle Quantum™
Fire and Gas Detection/Releasing System
Eagle Quantum
Fire and Gas
Detection/Releasing System
IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or operating the
Eagle Quantum System. Only qualified personnel
should install, maintain or operate the Eagle
Quantum System.
WARNING
The hazardous area must be de-classified prior to
removing a junction box cover or opening a
detector assembly with power applied.
CAUTION
1. The wiring procedures in this manual are
intended to ensure proper functioning of the
devices under normal conditions. However,
because of the many variations in wiring codes
and regulations, total compliance to these
ordinances cannot be guaranteed. Be certain Section I
that all wiring complies with the NEC as well as System Overview
all local ordinances. If in doubt, consult a
qualified official before wiring the system. SYSTEM DESCRIPTION
2. Some Eagle Quantum devices contain The Eagle Quantum System serves multiple roles in the
semiconductor devices that are susceptible to monitoring and protection of hazardous areas. It is a
damage by electrostatic discharge. An “fire detection and extinguishing agent release system”
electrostatic charge can build up on the skin and combined with a “hazardous gas monitoring system,”
discharge when an object is touched. Always integrated on a fault tolerant digital communication
observe the normal precautions for handling network. The Eagle Quantum system utilizes an
electrostatic sensitive devices, i.e. use of a wrist advanced distributed architecture that is equally adept
strap (if available) and proper grounding. at monitoring analog process signals like combustible
or toxic gas concentrations, and discrete “contact
3. To prevent unwanted actuation, alarms and closure” type devices such as manual fire alarm “call
extinguishing devices must be secured prior to boxes” and heat detectors, as well as Det-Tronics
performing system tests. optical flame detection. This sensor information is then
transmitted to the control unit to execute the fire
suppression logic, to control agent release, signaling,
and annunciation outputs, and to communicate with
*oi is Detector Electronics' Trademark for its patented Optical
external operator interface systems for configuration
Integrity Systems, U.S. Patent 3,952,196, United Kingdom Patent
1,534,969, Canada Patent 1,059,598. and monitoring.
AGENT
POWER NETWORK FLAME FIRE
IDCs DCUs RELEASE
MONITORS EXTENDERS DETECTORS SUPRESSION
MODULES
SIGNAL VISUAL/
AUDIBLE AUDIBLE
MODULES INDICATORS
LON/SLC LON/SLC
LOCAL CONTROL UNIT (LCU)
LOGIC ISOLATION
CONTROLLER GATEWAY MODULE
OIS
PLC/DCS
LOCAL
AUDIBLE OUTPUT VISUAL
INDICATORS UNIT INDICATORS
(LIOU)
FIRE
SUPPRESSION
C1899
I–2
that perform all the communication, command, and If a “Fire Alarm” is detected by a Flame Detector or
control functions for the system. It includes all the Initiating Device Circuit (IDC), the affected node will
required operator interface controls for a fire alarm send a special Acknowledged Exception Report (AER)
system (silence, acknowledge, reset, isolate), directly to the Logic Controller. The AER is transmitted
annunciation relays, a local information display, and as soon as an alarm is detected to maximize system
communication interfaces for computer based performance. When the Logic Controller receives the
configuration and monitoring of the system. AER, it sends the originating node a message
acknowledging its receipt. If the node originating the
LOCAL OUTPUT UNIT (LIOU) AER does not receive an acknowledgement, it will re-
transmit the AER until it receives an acknowledgement.
The LIOU consists of a rack controlled by the LCU that This exchange of messages is used to ensure that
can hold up to six FenwalNet 2000 modules. These critical messages are received at all appropriate
modules allow the control of Notification Appliance registers throughout the system.
Circuits (NACs), fire suppression agent release (CO2,
Halon, FM200) using supervised relays, as well as Once the Logic Controller receives a Fire Alarm
unsupervised relays for other needs. message from a field device, “fixed logic” will activate
built-in annunciation circuits, which consist of both a
THEORY OF OPERATION visible and audible alarm. The “programmable logic”
will execute any specified voting, timing, and/or zone
During normal operation, each node on the network logic and subsequently activate the appropriate output
monitors its attached sensor or other input, determines if circuits for Notification Appliance Circuits (NACs), agent
it has an alarm condition, analyzes its own health, release circuits, and unsupervised relay outputs.
checks network integrity, and then packages up this
information for transmission to the communication The faceplate of the Logic Controller has two
gateway, located in the LCU. This Standard Periodic pushbuttons. “ACKNOWLEDGE” will silence the built in
Report (SPR) contains 16 pieces of “discrete” audible alarm and illuminate the “Acknowledge LED”
information on the status of the node and, where located on the faceplate next to the “Acknowledge”
applicable, also contains the analog value of its sensor. pushbutton. “SILENCE” will silence selected NACs in
At the time of node configuration, the report rate of the the field and illuminate the “Silence LED” located on the
SPR can be set to anywhere between 1 and 10 faceplate next to the “Silence” pushbutton. The Logic
seconds. Controller also features a keyswitch to reset the system
after the event is over.
In the LCU the Communication Gateway collects all of
the incoming SPRs from the field devices and puts the NETWORK OPERATION DURING A
information into “datatables.” Datatables are organized FAULT CONDITION
areas of memory in the gateway that can be “read” by
external “host devices” using one of the gateway’s serial The Eagle Quantum system utilizes a unique patented
ports. If any of the SPRs indicate an out of tolerance technique for detecting problems in the communication
condition, the gateway will display this information on its network wiring. This state-of-the-art feature minimizes
integrated faceplate display. The gateway also has four the possibility of a communication breakdown in the
programmable relays whose action can be event of a wiring fault in the communication loop and
programmed to events in the SPRs of the monitored can also serve as an aid in troubleshooting.
nodes.
The communication network is constructed as a loop
In addition to SPRs, nodes used as a part of the fire that starts and ends at a pair of communication ports
detection and suppression system, such as fire located at the LCU. The nodes communicate with the
detectors or Initiating Device Circuits (IDCs) interfaced LCU over the LON/SLC as shown in Figure I-2.
with heat detectors, manual call points, etc. send a
separate Standard Supervisory Report (SSR) to the Each field device node contains both the hardware and
Logic Controller, located in the Local Control Unit. The software necessary to isolate and re-route
Logic Controller, which manages the fire suppression communication in the event of a network wiring fault.
logic, uses these SSR messages to verify that the nodes When a problem occurs somewhere within the network
used in the fire alarm and suppression logic are active wiring, the communication gateway located in the LCU
and able to communicate. If the Logic Controller does annunciates the fault, while the fault isolation circuitry in
not receive SSRs from a required node, it will the affected nodes isolates the section of the network
annunciate a “trouble” condition. where the fault has occurred. Communication is
I–3 95-8470
thereby ensured and will continue over the network. NODE 4 NODE 5
See Figure I-3. NODE 3 NODE 6
MULTIPLE WIRING FAULTS Figure I–2—Normal Communication over the Digital Highway
but the faults will prevent them from communicating with NODE 3 NODE 6
the gateway. See Figure I-4. In this example, nodes 1
to 4 communicate using one gateway port (path A) and
nodes 7 and 8 use the other gateway port (path B). NODE 2 PATH A PATH B NODE 7
All Eagle Quantum field devices are designed so that a Figure I–4—Communication with Multiple Wiring Faults
“pass-through” circuit is created for the network wiring on the Network
on a loss of power to the node. This ensures network
integrity even when a node is down for service or has
been damaged. The Communication Gateway in the
LCU will report powered-down nodes as “not-
communicating.”
IMPORTANT
Since it is impossible to predict where a network
fault might occur or exactly what effect it will have
on actual system operation, it is important to
diagnose and repair any fault as soon as possible
after it is detected to ensure reliable system
operation.
I–4
Section II OPTIONAL LCU VERSIONS
Local Control Unit (LCU) and An optional EQ2101LCU is available with provisions for
Power Supplies two 24 vdc power inputs. Two reliable and independent
24 vdc supplies, in accordance with ANSI/NFPA 72
OVERVIEW section 1-5.2, must be supplied. If either of the supplies
is missing or a wiring problem occurs, a trouble
The Local Control Unit (LCU) is the “heart” of the Eagle condition will be annunciated.
Quantum system. External host devices such as PLC’s
or DCS’s interface through the LCU, the fire detection Logic controllers can be added to the communication
and releasing logic resides in the LCU, control of the network to segment it into logical groups. Up to four
releasing, signaling, and annunciation outputs are logic controllers can be used on each network.
handled by the LCU, and the Local Operating
Network/Signaling Line Circuit (LON/SLC), through Auxiliary gateways can be added to provide additional
which all field devices communicate, starts and ends its relays or serial port connections to PLCs or DCSs. Up to
loop at the LCU. Physically, the LCU consists of a three three auxiliary gateways can be added to the Quantum
slot rack style enclosure that houses the Communication network. Gateways located outside the LCU can be
Gateway, Logic Controller, and Isolation Module. These turned off without disrupting LON/SLC communication
three modules plug into the backplane and are secured with the LCU.
with thumb screws. All external wiring is routed through
conduit entries at the bottom and sides of the unit. The
wiring terminals are protected by a removable cover. EQ2100CG COMMUNICATION
The LCU can be installed in Class I, Division 2 GATEWAY
hazardous locations. Refer to Appendix A (FMRC) and
Appendix B (CSA) for details. FEATURES
DEVICE ADDRESS
DIGITAL DISPLAY
All three digits are on and the decimal point for each
BAR GRAPH DISPLAY
digit is also on. Up to 250 addresses are available
100 (displayed 0.0.1. to 2.5.0.).
RELAY 1 90
80
RELAY 1 LED 70
60
DEVICE IDENTIFICATION CODE
RELAY 2
50
RELAY 2 LED 40
30 See Table II-1 for device identification codes.
RELAY 3 20
10
RELAY 3 LED
RELAY 4 DEVICE PERCENT FULL SCALE/FAULT
RESET PUSHBUTTON
FAULT RELAY 4 LED CODE/CALIBRATE
RESET
EAGLE QUANTUM™ FAULT LED
GATEWAY The display follows the sensor input in percent of full
scale up to 100% full scale. A negative sign is used to
indicate a negative zero drift condition. See Table II-2
for the status codes used by the gateway display.
F10 Fault
F11 Low Voltage Fault
F13 Input 1 Open
F14 Input 2 Open
IDC F20 Not Communicating, Com 1 or Com 2 fault
F60 Invalid Configuration or Unable to Configure
A10 Input 1 is Active
A01 Input 2 is Active
A11 Both Inputs are Active
F10 Fault
F11 Low Voltage Fault
F13 Input 1 Open or Short
F14 Input 2 Open or Short
IDCSC F20 Not Communicating, Com 1 or Com 2 fault
F60 Invalid Configuration or Unable to Configure
A10 Input 1 is Active
A01 Input 2 is Active
A11 Both Inputs are Active
F10 Fault
F11 Low Voltage Fault
F13 Ground Fault “–”
F14 Input Open
IDCGF F20 Not Communicating, Com 1 or Com 2 fault
F60 Invalid Configuration or Unable to Configure
A10 Ground Fault “+”
A01 Input is Active
A11 Input Active and Ground Fault “+”
F10 Fault
F11 Low Voltage Fault
F12 oi Fault
UV Detector F13 290 Volt Fault
F20 Not Communicating, Com 1 or Com 2 fault
F60 Invalid Configuration or Unable to Configure
cps Counts Per Second, Displayed During Alarm and Pre-Alarm
F10 Fault
F11 Low Voltage Fault
UV/IR Detector F20 Not Communicating, Com 1 or Com 2 fault
F60 Invalid Configuration or Unable to Configure
cps* Counts Per Second, Displayed During Alarm
* Can be either UV counts or IR counts, depending on the mode selected at the OIS.
F10 Trouble
F17 Ground fault
Logic F20 Not Communicating, Upper Transceiver Fault or Lower Transceiver Fault
Controller F60 Invalid Configuration or Unable to Configure
ALA Alarm
Bytes Bytes Remaining for Non-volatile Memory Write
II–3 95-8470
Table II–2—Status Codes used by Gateway Digital Display (Continued)
Aud Signal Audible display code
F11 Low Voltage Fault
F12 Low Auxiliary Voltage Fault
F13 Open/Short on Circuit 1
SAM F14 Open/Short on Circuit 2
F20 Not Communicating, Com 1 or Com 2 fault
F21 Network Variable Input Fault
F60 Invalid Configuration or Unable to Configure
The bar graph indicates 0 to 100% full scale, which Automatic Diagnostics
corresponds to the 4 to 20 ma signal for all gas sensors
except oxygen. The 4 to 20 ma signal from an oxygen The gateway features self-testing circuitry that
sensor corresponds to 0 to 25% oxygen. Sensor output continuously checks for problems that could prevent
(measured in counts per second) is displayed for UV proper system response. The gateway performs three
and UV/IR detectors. forms of diagnostics: self-diagnostics, LON/SLC
diagnostics, and device diagnostics.
LEDS
Self-diagnostic tests monitor the condition of the
Five faceplate LEDs are provided for indicating the gateway. LON/SLC diagnostics check for shorts and
status of the gateway relays. When a relay is reset, the opens in the LON/SLC wiring. In the event of a
corresponding LED is also reset. problem, the fault is annunciated in the gateway status
word and the gateway fault relay is activated.
RELAYS
For device diagnostics, the gateway provides a
The communication gateway is provided with five watchdog timer for each configured device on the loop.
relays. Four of the relays are general purpose relays. Each time the device reports to the gateway, the timer
The fifth relay functions as a fault relay, responding only accumulator is reset to zero and the timer starts over. If
to gateway or LON network faults. The relays have form a device does not respond before its watchdog timer
C contacts rated 5 amperes resistive at 30 vdc. expires, the gateway sets the “not communicating” bit in
the status word for that device.
The specific function of the four general purpose relays
is programmable through Det-Tronics software. The Fault Tolerant Communication
relays are selectable for latching or non-latching
operation and can be configured for normally energized Fault tolerance is provided by constructing the
or de-energized operation. LON/SLC as a loop that starts and ends at a pair of
network communication ports on the gateway. If a fault
CAUTION occurs somewhere in the network wiring, fault isolation
When the relays are used as gas alarm outputs in circuitry in the communication modules isolates the
the non-latching mode, they must be connected to problem section of the network. When the gateway
another device that will perform the latching detects the fault, it is immediately annunciated. The
function. gateway then reconfigures the network so data can be
transmitted to all devices.
RESET PUSHBUTTON
This feature minimizes the possibility of a
The programmable relays can be reset by pressing the communication breakdown in the event of an open or
reset pushbutton or external reset (resetting all latching short in the communication loop. A single open or short
relays) or by a command from the EagleVision NT on the LON/SLC will not affect system communication
software (resetting individual relays). The reset function performance. In the event of multiple opens or shorts,
resets the relay, regardless of the status of the initiating only those detectors between the opens and shorts will
device. This allows additional events to trigger the not be able to communicate with the LCU, even though
same relay, even though the first device may still be in a they will continue to function.
triggering mode.
II–4
DET-TRONICS
® The logic controller receives configuration information
through the gateway by means of its serial connection
POWER
ALARM
to the operator interface system.
TROUBLE
POWER FAULT Faceplate Description
SUPERVISORY
Normal
C1854
Figure II–2—Logic Controller Faceplate In the normal mode, the controller’s program is running
and the outputs are enabled.
Reset
DESCRIPTION
In the reset mode, normal operation is inhibited and a
The logic controller provides the control function for the reset signal is sent to the LIOU and field output devices.
fire detection portion of the Eagle Quantum fire and gas
safety system. It monitors messages from the devices This mode is also used for programming. In the
on the loop that are configured to report to that program mode, normal operation is inhibited. This is
controller (up to 120 in combination) and generates the the only mode that allows configuration information to
appropriate output(s) in response to the input be downloaded to the logic controller from the gateway.
conditions. The logic controller supports ANSI/NFPA 72 When the program mode is exited, configuration
Class A, Style 7 communication with the field devices. information is sent to the LIOU.
II–5 95-8470
Isolate POWER FAULT (Yellow)
In the isolate mode, normal operation continues while Indicates that a power supply fault has been detected.
the logic controller sends an isolate command to all the This could involve any of the following:
agent release outputs in the LIOU. The Isolate LED
— ground fault
turns on in a steady state if all release outputs are
— low or missing AC input voltage
isolated. The LED is off when none of the outputs are
— 24 vdc power supply
isolated and blinks if only some of the outputs are
— battery related fault
isolated.
— power supply monitor
— IDCGF.
NOTE
User logic is required to isolate LON based agent
SUPERVISORY (Yellow)
release modules.
Follows the status of the Supervisory relay.
PUSHBUTTON SWITCHES
ACKNOWLEDGE (Yellow)
Acknowledge
Illuminated when the acknowledge switch is pressed
Pressing the acknowledge pushbutton with
and remains lit until the unit is reset.
Acknowledge/Silence enabled acknowledges the
current status condition(s) and turns off the internal
SILENCE (Yellow)
buzzer.
Illuminated when the silence switch is pressed and
Silence
remains on until the unit is reset.
Pressing the silence pushbutton silences the selected
PROGRAM (Yellow)
signaling outputs in the LIOU. (The specific LIOU
outputs that are affected by the silence button are
Indicates that the logic controller is in the
selected at the time of system configuration.)
Reset/Program mode.
NOTE
ISOLATE (Yellow)
Signaling devices connected to LON based Signal
Audible Modules must be silenced via user logic.
Indicates that the logic controller is in the Isolate mode.
LEDS
Relays
Nine faceplate LEDs are provided for indicating system
The Logic Controller has three relay outputs,
status conditions.
responding to the following status conditions:
POWER (Green) — Fire alarm (Activated when any device that is
configured as a fire alarm input is active. This
Indicates that power is applied to the device. includes all flame detectors and IDCs that are
configured as alarm type inputs.)
ALARM (Red)
— Supervisory (Activated when a supervisory fault
occurs at any LON device that is configured to
Indicates that the Fire Alarm relay is actuated.
report to the Logic Controller as a supervisory
input.)
TROUBLE (Yellow)
— Trouble (Normally energized). Activated when any
Illuminated when a trouble condition occurs in the wiring of the following occurs:
or devices associated with the fire system. (Trouble LIOU communication, wiring or other fault
relay is active). All logic controller faults are latching AC input failure
and must be cleared by resetting with the key switch. Battery fault
Det-Tronics configuration software should be used to Power supply fault
determine the specific problem. Invalid configuration
LON fault
LON device communication fault
Gateway LON fault
RAM fault.
II–6
EQ2100IM ISOLATION MODULE
0.5 SEC 0.5 SEC 1.5 SEC
FEATURES
— Trouble
LON ISOLATOR
— Supervisory.
GROUND FAULT
In the normal mode with no events occurring, the buzzer POWER +
is off. If an alarm, trouble or supervisory event occurs, POWER –
the appropriate tone is generated. In the event of
multiple events, the order of priority is alarm,
GROUND FAULT
supervisory, then trouble. Refer to Figure II-3 for the COM 1
tone patterns that identify each type of event. COM 2
NOTE
If a trouble condition has been acknowledged and
the condition exists for more than 24 hours, the
buzzer will again sound. B1856
II–7 95-8470
Table II-3A—Power Supply Ground Fault resides on the communication loop (LON), any trouble
“Power +” ground fault occurs if: condition related to system power will immediately be
- Resistance of “Power +” to earth is <136K ohms. reported through the Local Control Unit. Status
- DC voltage is below +19.0 vdc (with 26 vdc supply voltage). conditions being monitored include power supply
- Current >0.14 ma between “+” wire and earth. failure, loss of AC power, loss of battery power, power
ground fault, AC voltage, DC voltage and battery
“Power –” ground fault occurs if: charging current levels.
- Resistance of “Power –” to earth is <15K ohms.
- DC voltage is below –4.9 vdc (with 26 vdc supply voltage).
- Current >0.1 ma between “–” wire and earth.
The output of the power supply monitor is a status
message that is sent along the communication loop to
Table II-3B—LON Ground Fault the gateway and logic controller in the Local Control
Unit (LCU). System response to the message is
“COM 1 / COM 2” ground fault occurs if: determined at the time of configuration. The power
- “LON B” wire resistance to earth is <4K ohms.
supply monitor supports ANSI/NFPA 72 Class A, Style 7
- “LON B” wire DC voltage is below –4.0 vdc.
- Current >1.0 ma between “LON B” wire and earth.
communication with the LCU.
—OR—
- “LON A” wire resistance to earth is <2K ohms. Enclosure
- “LON A” wire DC voltage is below +2.0 vdc.
- Current >1.0 ma between “LON A” wire and earth. The power supply monitor must be located in a
controlled non-hazardous area and must be mounted in
Note: Voltages are nominal and may vary slightly (voltages referenced to
earth). a suitable metallic nationally recognized test laboratory
Resistance/voltage levels between sides are different — same (NRTL) labeled NEMA rated enclosure.
readings indicate they are shorted together.
II–8
Section III The yellow LED also turns on if:
EQ2100LIOU – An output fault occurs (signal audible and agent
Local Output Unit release modules only). The LED is reset automatically
when the fault clears.
OVERVIEW – A microprocessor fault occurs.
The Local Output Unit (LIOU) consists of a six position – The card is not configured.
card rack. Available modules include: – A loss of communication with the LCU occurs (RS-
Relay Module — four independently programmable 485). If an output is on during a loss of
unsupervised relay contacts. communication, the output will remain in the current
state and can only be reset using the reset switch on
Release Module — one release circuit and three the Logic Controller.
signaling circuits.
Signal Audible Module — four independently
programmable signaling circuits. RELAY MODULE
These modules can be installed in the rack in any FEATURES
position. The Local Control Unit (LCU) automatically
reads the output module’s type and address on power- • Four independently programmable relays
up. It is recommended that modules performing like
functions be inserted adjacent to each other to facilitate • SPDT dry contacts
identification and field wiring runs. • Supervised module
The LIOU must be located in a controlled non- The relay module is housed and secured in the LIOU. A
hazardous area and must be mounted in a suitable maximum of 8 relay modules can be installed in the
metallic nationally recognized test laboratory (NRTL) system.
labeled NEMA rated enclosure.
NOTE
FAULT LED AND RESET SWITCH It is not recommended to configure relay outputs
as Normally Energized/Open on Alarm.
Each card in the LIOU is furnished with a yellow fault
LED and a Reset switch. During Normal operation, the
LED is off. The yellow LED turns on when the Reset
button is pressed or a fault occurs. Pressing the Reset
button resets the microprocessor on the card, causing it
to re-initialize. At this time, the Trouble light on the LCU
is also turned on.
III-1 95-8470
RELEASE MODULE Each signal circuit delivers up to 2 amperes at 24 vdc
— enough to meet the power requirements of today’s
FEATURES ADA/UL 1971 Signaling Appliances. The three signal
outputs are individually programmable to allow
• One programmable releasing output signaling of each phase of the release sequence.
• Three independently programmable signal circuit
The agent release output circuit is rated for 24 vdc
outputs (style “Y” wiring)
control devices. Each release output can supervise and
• FM200, FE-13, CO2, Halon, water mist, dry and wet activate up to two solenoid control heads. Tables III-1
chemical compatible, deluge and pre-action and III-2 identify the devices that can be controlled by
the releasing output. Refer to Section VII for specific
• Programmable for initiators or solenoid type releasing
wiring information.
devices for 90 sec., 10 min., 15 min., continuous.
Each circuit on the release module is furnished with a
DESCRIPTION self-restoring fuse to provide protection from short
circuit conditions. The three signaling circuits are
The release module is a convenient and economical supervised for open and short circuit conditions. The
means of providing signaling and agent release release circuit is supervised for open circuit conditions.
capability for the Eagle Quantum System. The release If a trouble condition occurs, it will be indicated at the
module is located in the LIOU and provides one LCU.
programmable release circuit and three Style “Y”
signaling circuits. The release circuit is compatible with The connection of the release module to the system is
all solenoid or initiator based Fenwal suppression supervised by the LCU. In the event of module removal,
systems. the system will display a trouble condition at the LCU.
Used in conjunction with the Eagle Quantum’s The release module is housed and secured in the LIOU.
programmable logic, each release circuit can be A maximum of 8 release modules can be installed in the
programmed for “Single,” “Cross” or “Counting” Zone system.
Style initiation. Optional time delay, abort and manual
release sequences allow the output to be programmed
for use in unique applications.
Table III–1—Solenoid Compatibility with Release Module for Table III-2—Solenoid Compatibility with Release Module for Deluge
Releasing Applications and Pre-Action Applications
Solenoids
Manufacturer Model
Fenwal part no. 486500-001
Fenwal part no. 890181 Skinner LV2LBX25
Fenwal part no. 897494 ASCO 8210A107
Fenwal part no. 899175
ASCO 8210G207
Fenwal part no. 895630-000
Fenwal part no. 31-199932-004 Skinner 73218BN4UNLVNOC111C2
Skinner 73212BN4TNLVNOC322C2
Skinner 71395SN2ENJ1NOH111C2
T0037B
III-2
SIGNAL AUDIBLE MODULE The Signal Audible Module is located in the LIOU and is
supervised by the LCU. In the event of module removal,
FEATURES the system displays a trouble condition at the LCU.
• Four independently programmable indicating circuits The Eagle Quantum system supports up to eight signal
audible modules, providing a maximum of 32 signal
• NFPA Style “Y” or “Z” wiring
outputs per system. Each module provides auxiliary
• 24 vdc power limited outputs input terminals for additional 24 vdc signaling power
where required. All four module outputs are
• Self-restoring output design
synchronized for accurate activation of visual signaling
• Four optional coded outputs per circuit. appliances.
The signal audible module can support four NFPA Style 4. Temporal pattern.
“Y” or two Style “Z” field wiring circuits. Each output
circuit is supervised for open and short circuit The signal audible module is housed and secured in the
conditions. The outputs operate in the reverse polarity LIOU. A maximum of eight signal audible modules can
fashion when activated. Each output delivers up to 2 be installed in the system.
amperes at 24 vdc — enough to meet the power
requirements of today’s ADA/UL 1971 signaling
appliances.
III-3 95-8470
Section IV Addressability
Addressable Field Devices Device identification is accomplished by setting
switches on an eight position DIP switch (valid address
EQ2200IDC SERIES range is 5 to 250).
INITIATING DEVICE CIRCUIT (IDC)
Status LEDs
DESCRIPTION
Three LEDs are located at the center of the
Three IDC models are available: communication module circuit board and are visible
when the cover is removed.
The EQ2200IDC allows discrete inputs from smoke/heat
detectors, manual call stations or other contact devices. The green LED serves as a power-on indicator and is
the only LED illuminated during normal operation (no
The EQ2200IDCGF Initiating Device Circuit Ground faults or alarms occurring).
Fault Monitor responds to the presence of a ground fault
within the power circuitry of the Eagle Quantum system. The red LED is used to indicate an alarm or fault
It provides a supervised dry contact input and ground condition. The flashing rate of the red LED indicates the
fault monitoring circuitry for indicating a power supply following conditions:
trouble condition. It is intended for use with a third party
power supply. On steady = one of the inputs is active
Blinking = fault condition such as an open input
The EQ2200IDCSC Initiating Device Circuit Short Circuit circuit or not configured.
(IDCSC) provides two supervised digital inputs for
monitoring the system for shorts circuits. The IDCSC The amber LED is provided for factory diagnostic
supports ANSI/NFPA 72 Class B Style C (3 state, purposes and is not used by the customer. Illumination
open/short circuit) supervised input circuits. of the amber LED normally indicates a failure in the
communication chip. Replacement of the communication
Inputs module circuit board is required.
Each IDC accepts two dry contact inputs for use with Alarm Log
devices such as relays, pushbuttons, key switches, etc.
The IDC supports ANSI/NFPA 72 Class B Style B The module tracks when either of its input circuits are
supervised input circuits (Class B Style C for IDCSC). activated and will store these changes in non-volatile
memory. The time, date, and circuit number is stored
Each circuit requires its own end of line (EOL) resistor for the last eight events.
for monitoring circuit continuity. Nominal resistance of
the resistor is 10 k ohms. Enclosure
Outputs
EQ2200UV UV FLAME DETECTOR
The output of the device is a status message that is sent
to the gateway and logic controller in the Local Control DESCRIPTION
Unit along the LON/SLC. System response to the
message is determined at the time of configuration. The The EQ2200UV Series UV Flame Detector contains a UV
IDC supports ANSI/NFPA 72 Class A, Style 7 sensor module and control circuitry in an explosion-
communication with the LCU. proof, watertight enclosure. The detector is equipped
with both automatic and manual optical integrity (oi) test
A Standard Periodic Report (SPR) is sent to the gateway capability.
at the rate determined at the time of configuration.
When programmed for response to a fire alarm Detector status is indicated by red LEDs visible through
condition, a special Acknowledged Exception Report the detector’s viewing window. Table IV-1 indicates the
(AER) is immediately sent to the Logic Controller. condition of the LEDs for each detector status.
IV-1 95-8470
Table IV–1—EQ2200UV Detector Status/Indications
Status LEDs
Normal with automatic oi selected Blink every 5 seconds
Normal with manual oi selected Blink every 10 seconds
Fault (General) Off
Power supply fault Off
oi fault Off
UV being detected, but time delay not yet satisfied LEDs continue blinking
Fire On
T0005A
The output of the device is a status message that is sent The operating mode determines the type of logic that
to the gateway and logic controller in the Local Control the UV flame detector will use for processing fire signals
Unit along the communication loop. System response (either standard or arc rejection).
to the message is determined at the time of
configuration. The UV detector supports ANSI/NFPA 72 ARC REJECTION MODE
Class A, Style 7 communication with the LCU.
The arc rejection mode (recommended) enables the
A Standard Periodic Report (SPR) is sent to the gateway detector to prevent nuisance fire alarms caused by UV
at the rate determined at the time of configuration. from short-duration electrical arcs or electrostatic
When programmed for response to a fire alarm discharge, while maintaining the ability to reliably detect
condition, a special Acknowledged Exception Report the UV given off by a flame. The arc rejection mode is
(AER) is immediately sent to the Logic Controller. not recommended unless these false alarm sources are
present within the application to be protected. Typical
Addressability applications that benefit from arc rejection logic include
electrostatic coating processes and uncontrolled
Device identification is accomplished by setting environments where transient UV sources can be
switches on an eight position DIP switch (valid address present, such as many typical outdoor applications.
range is 5 to 250).
STANDARD MODE
Alarm Log
In the standard processing mode, the detector output
Each detector maintains an alarm log in non-volatile (measured in counts per second) is compared to the
memory. The time and date for the last eight alarms are fire threshold (the “sensitivity” setting as described
logged. below). If the radiant energy level from the fire exceeds
the selected alarm threshold level, the time delay
Terminal Wiring Board begins (if a time delay is selected). If the radiant energy
level from the fire remains above the selected sensitivity
All external wiring is connected to screw terminal level for the duration of the time delay, the fire alarm
connectors on the terminal wiring board located inside output is activated. In every application, it is crucial to
the detector housing. ensure that the radiant ultraviolet energy level from the
expected fire at the required distance from the detector
Enclosure will exceed the selected sensitivity level.
SOFTWARE SELECTABLE OPTIONS The arc rejection algorithm examines the radiant energy
level detected within a specified unit of time (timed
The following software selectable options are available gate). Detector output is determined by three variables:
through a PC running Det-Tronics configuration — sensitivity level
software. — gate length
— number of consecutive gates required.
IV-2
Different combinations of these variables allow for Time Delay
various levels of transient arc rejection capability. There
are four arc rejection levels (very high, high, medium, Arc rejection mode — If the fire signal meets the
and low) that are selectable for each detector through programmed arc rejection requirements, the time delay
the PC. Refer to Table IV-2. begins. A fire output is generated if the fire signal
continues for the duration of the time delay.
The proper arc rejection setting for a given application
must be determined through testing. For indoor Standard mode — A fire output is generated only if the
applications with known electrostatic energy fields fire signal exceeds the sensitivity setting for the entire
within 15 feet of the detector, an arc rejection setting of duration of the programmed time delay.
“very high” or “high” is typical. For outdoor
applications, “medium” or “low” arc rejection settings Automatic or Manual oi
are typical.
The o i system uses an internally generated UV test
It is recommended that each detector be thoroughly signal to determine the relative condition of the detector
tested at the programmed arc rejection setting within and its optical surfaces.
the ambient conditions that will be present during
normal operation. This will help to ensure that the If automatic o i testing is selected, the o i test is
selected arc rejection setting is proper for the automatically performed once every minute. The
application. automatic oi test does not generate an alarm output or
interfere with normal detector operation.
Sensitivity
The manual oi test is initiated using a button on the
Whether the Standard or Arc Rejection mode is point display screen at the PC. The manual oi test can
selected, the sensitivity setting must always be be used in addition to automatic oi to verify correct
programmed. The selected sensitivity level determines system operation.
the fire alarm threshold setpoint. The higher the
sensitivity level, the greater the detection range, but the Fire Output Latching
possibility of false alarms will be increased. Four
sensitivity levels are selectable. Refer to Table IV-3. When latching operation is selected, the fire alarm
signal is cleared by removing input power for a
The sensitivity setting must be appropriate for the minimum of 0.1 second.
anticipated fire size at the required distance from the
detector.
Arc Rejection Level Consecutive Gates Gate Length Sensitivity* Min. Processing Time
Very High 8 1/16 Second Very High (8 CPS) 0.5 Second
High 4 1/16 Second Very High (8 CPS) 0.25 Second
Medium 4 1/8 Second Very High (8 CPS) 0.5 Second
Low 4 1/4 Second Very High (8 CPS) 1.0 Second
IV-3 95-8470
Fault Latching EQ2200UVIR FLAME DETECTOR
If the fault output is set for latching, the fault will not DESCRIPTION
clear until it is corrected and the unit is reset. If a fire
occurs, the unit will indicate a fire, over-riding the fault The EQ2200UVIR Series Flame Detector is designed to
condition, i.e., the fault signal will clear if not latched. If provide reliable fire protection in applications where the
a fault is still present after the fire has been use of either ultraviolet (UV) or infrared (IR) detectors
extinguished, the unit will again indicate a fault until the alone can result in false alarms. When used alone, a UV
problem has been corrected and the unit is reset. detector can respond to sources of ultraviolet radiation
besides fire, such as lightning, x-rays or arc welding.
Likewise, an IR detector can respond to various hot
EQ2200UVHT HIGH TEMPERATURE objects, such as flickering or chopped radiation from
UV FLAME DETECTOR electric heaters or exhaust manifolds. The
microprocessor based EQ2200UVIR combines both a
DESCRIPTION UV and a single frequency IR sensor in a single
detector and requires simultaneous response of both
The EQ2200UVHT UV Flame Detector provides UV sensors to generate a fire alarm. These two detecting
flame protection in continuous duty high temperature elements monitor different portions of the radiation
applications, such as turbine compartments, spectrum and have virtually no common sources of
enclosures, generator rooms, etc. where ambient false alarms. This enables the detector to respond to a
temperatures can continuously exceed +75°C (+167°F). real fire while ignoring potential false alarm sources
such as arc welding, x-rays, or hot vibrating objects.
The EQ2200UVHT is an electronic module assembly
that is used in conjunction with a high temperature rated Microprocessor based circuitry located inside the
C7050B UV detector (with DE1888K3 high temperature detector junction box continuously monitors the two
rated UV sensor tube). The two devices are mounted in sensors, evaluating the signal(s) with fire and fault
separate explosion-proof, watertight enclosures. algorithms to determine the current status of the
detector. When both sensors simultaneously detect the
The UV detector is rated for continuous duty in presence of fire, the microprocessor generates a fire
environments up to +125°C (+257°F). The electronic signal, which is immediately sent over the LON/SLC to
module is rated up to +75°C (+167°F). the logic controller in the Local Control Unit (LCU). The
LEDs, visible through the UV sensor viewing window,
NOTE are also immediately illuminated. In addition, a
The electronic module cannot be located in the watchdog timer assures that the detector’s operating
high temperature area. program is running properly.
IV-4
Addressability SOFTWARE SELECTABLE OPTIONS
Device identification is accomplished by setting rocker The following options are selectable through a PC
switches on an eight position DIP switch (valid address running Det-Tronics configuration software:
range is 5 to 250).
Processing Mode
Alarm Log
The UV portion of the detector offers a choice of two
Each detector maintains an alarm log in non-volatile different types of logic that can be used for processing
memory. The time and date for the last 8 alarms are fire signals — either standard or arc rejection.
logged.
ARC REJECTION MODE
Enclosure
The arc rejection mode (recommended) enables the
The explosion-proof NEMA/Type 4X enclosure is detector to prevent nuisance fire alarms caused by
available in either aluminum or stainless steel and is short-duration electrical arcs or electrostatic discharge,
designed for use in a variety of hazardous locations. while maintaining the ability to reliably detect a flame.
The arc rejection mode is not recommended unless
LEDs these false alarm sources are present within the
application to be protected. Typical applications that
Detector status is indicated by a pair of red LEDs benefit from arc rejection logic include any uncontrolled
(illuminated simultaneously) that are visible through the environments where transient radiation sources can be
viewing window of the UV sensor. present, such as many typical outdoor applications.
Table IV-4 indicates the condition of the LEDs for each The arc rejection algorithm examines the radiant energy
detector status. level detected within a specified unit of time (timed
gate). The output of the detector is determined by three
Automatic Diagnostics variables:
— sensitivity level
The microprocessor based detector is equipped with — gate length
advanced fault detection and diagnostic capabilities. — number of consecutive gates required.
The LED indicators on the UV sensor module provide
the user with visual annunciation of the problem area. Different combinations of these variables allow for
In addition, the point display screen at the OIS provides various levels of transient arc rejection capability. There
a variety of information regarding detector status as well are two arc rejection levels (medium and high) that are
as the actual UV and IR signal levels present at the selectable for the detector through the OIS. The proper
detector. Refer to Table IV-5 for a list of status arc rejection setting for a given application must be
conditions. determined through testing.
Fault Off
Automatic oi On for 0.25 second every 5 seconds
Manual oi On for 0.25 second every 10 seconds
UV only On for 50 milliseconds — off for 500 milliseconds
IR only On for 200 milliseconds — off for 500 milliseconds
Alarm On steady
T0030
IV-5 95-8470
Table IV–5—Status Conditions of UV/IR Detector
UV 290 volt fault Internal power problem. Replace detector terminal board.
IV-6
It is recommended that each detector be thoroughly Automatic or Manual oi
tested at the programmed arc rejection setting within
the ambient conditions that will be present during The EQ2200UVIR is equipped with the Optical Integrity
normal operation. This will help to ensure that the (oi) feature. The oi test is performed on both the UV
selected arc rejection setting is proper for the and IR sensors to check the cleanliness of the detector
application. optics, as well as the proper functioning of the sensors
and electronic components of the detector. If a
STANDARD MODE problem should occur, it is quickly detected.
In the standard processing mode, the UV sensor output The detector is user programmable (from a PC running
(measured in counts per second) is compared to the Det-Tronics configuration software) for automatic o i
fire threshold (the “sensitivity” setting as described testing. If automatic testing is selected, the oi test is
below). If the radiant energy level from the fire exceeds automatically performed on each sensor. The rate for
the selected alarm threshold level, the time delay the UV sensor test is once per minute. The rate for the
begins (if a time delay is selected). If the radiant energy IR sensor is field selectable from once a minute to once
level from the fire remains above the selected sensitivity every four hours. If a fault is detected, a trouble signal
level for the duration of the time delay, a fire alarm is sent to the LCU over the LON/SLC. A fault condition
signal is generated. In every application, it is crucial to is indicated at the logic controller and the gateway and
ensure that the radiant energy level from the expected also by the LEDs on the detector’s UV sensor. The
fire at the required distance from the detector will automatic oi test does not generate an alarm output or
exceed the selected sensitivity level. interfere with normal detector operation.
Standard signal processing is recommended for The manual oi test is initiated using a button on the
controlled indoor applications only. point display screen at the OIS. A successful test is
signaled by the OIS. The manual oi test can be used in
Sensitivity addition to automatic o i to verify correct detector
operation.
Whether Arc Rejection or Standard mode is selected,
the sensitivity setting must always be programmed. The NOTE
selected sensitivity level determines the fire alarm The manual oi test does not generate an alarm
threshold setpoint. The higher the sensitivity level, the output or actuate any system outputs.
greater the detection range, but the possibility of false
alarms will be increased. Four sensitivity levels are Fire Output Latching
selectable. (Sensitivity levels for UV and IR are selected
separately.) When latching operation is selected, the fire alarm
signal is present until cleared by a reset command from
The sensitivity setting must be appropriate for the the PC.
anticipated fire size at the required distance from the
detector. Refer to the “Specifications” section of this
manual for additional information. EQ2200DCU AND EQ2200DCUEX
Time Delay DIGITAL COMMUNICATION UNIT
If the fire signal meets the programmed arc rejection Designed for use with the Eagle Quantum system, the
requirements, the time delay begins. A fire output is DCU provides a unique technique for detecting and
generated if the fire signal continues for the duration of isolating opens or shorts in the Local Operating
the time delay. Network/Signaling Line Circuit (LON/SLC) wiring. This
IV-7 95-8470
fault isolation method allows for communication integrity The red LED is used to indicate a calibration, power-up,
in the event of a single wiring fault in the LON/SLC fault or alarm condition. The flashing rate of the red
wiring. LED indicates the following conditions:
Status LEDs A log of low and high alarms is stored in each DCU.
Time, date and alarm type are logged for each alarm
Three LEDs are located at the center of the event. A maximum of eight events can be stored. If
communication module circuit board and are visible more than eight events are logged, the oldest event will
through the window on the enclosure cover. be overwritten.
IV-8
Enclosure Each output is rated at 2 amperes. Auxiliary input
terminals are provided for additional 24 vdc output
The explosion-proof, watertight NEMA/Type 4X power where needed.
enclosure is designed for use in a variety of hazardous
locations. The cover is furnished with a window to allow Solenoids/Initiators
the operator to view the three status indicator LEDs on
the communication module PC board. The releasing output devices listed in Table IV-6 are
recommended for use with the Agent Release Module.
Terminal Wiring Board
The solenoids listed in Table IV-7 are compatible with
All external wiring is connected to screw terminal the Agent Release Module for deluge and pre-action
connectors on the terminal wiring board located inside applications.
the junction box.
Addressability
EQ2500ARM AGENT RELEASE
MODULE Device identification is accomplished by setting
switches on an eight position DIP switch (valid address
DESCRIPTION range is 5 to 250).
Manufacturer Model
Table IV-7—Solenoid Compatibility with Agent Release Module for
Fenwal 890181 Deluge and Pre-Action Applications
(2.4 A. max., 10 Ω, momentary)
Fenwal 899175 Manufacturer Model
(2.4 A. max., 10.8 Ω, momentary) Skinner LV2LBX25
Fenwal 895630-000 ASCO 8210A107
(2 A. max., 12 Ω, momentary)
ASCO 8210G207
Fenwal 897494
(1.5 A. max., 15.9 Ω, continuous) Skinner 73218BN4UNLVNOC111C2
Fenwal 486500-001 Skinner 73212BN4TNLVNOC322C2
(240 ma max., 103 Ω, momentary)
Skinner 71395SN2ENJ1NOH111C2
Fenwal 31-199932-004
(2.4 A. max., 10 Ω, momentary) T0037B
IV-9 95-8470
Alarm Log Status LEDs
Time and date are logged each time that a release Three LEDs located at the center of the circuit board
occurs. Data for the last eight events is stored in non- provide a visual indication of device status conditions.
volatile memory.
Green — On when power is applied to the device.
Terminal Wiring Board
Red — On steady indicates an active condition.
All external wiring is connected to screw terminal
Blinking indicates a local trouble condition
connectors on the terminal wiring board located inside
such as an open or shorted output circuit or
the device enclosure.
low output supply voltage.
2. 60 beats per minute The EQ2400NE Series Network Extender expands the
capabilities of the Eagle Quantum system by allowing
3. 120 beats per minute additional nodes as well as additional wiring to be
added to the LON/SLC (communication loop). Without a
4. Temporal pattern. network extender, the communication network is limited
to 60 nodes on a 2000 meter loop. Each network
The outputs operate in the reverse polarity fashion when extender, however, increases the capacity of the loop
activated. Each output is rated at 2 amperes. Auxiliary by up to 40 nodes and 2000 meters of wiring, up to a
input terminals are provided for additional 24 vdc maximum of 244 field nodes and 10,000 meters of
signaling power where required. wiring.
IV-10
The green LED indicates that power is applied and If the fastest possible communication response time is
flashes to indicate that messages are being transferred an important criteria for a large system, it is
over the network. recommended that the number of nodes on an
individual loop be kept as small as practical. Consider
The two yellow LEDs correspond to the two using multiple loops with fewer nodes per loop rather
communication transceivers and are illuminated to than one large loop.
indicate that an internal fault has been detected.
LCU
The gateway requires a finite length of time to process
each bit of information that is transferred along the
communication network. As the number of nodes
increases, so does the amount of data that is being NOTES: 1. BASIC LOOP WITHOUT A NETWORK EXTENDER
CANNOT EXCEED 60 NODES AND 2000 METERS
processed as well as the time required for processing OF WIRE.
2. NO MORE THAN 40 NODES AND 2000 METERS OF
the data. As a result, the update time for each node WIRE BETWEEN NETWORK EXTENDERS OR
BETWEEN A NETWORK EXTENDER AND THE LCU.
should be increased to accommodate the extra traffic 3. NO MORE THAN 244 FIELD NODES AND 10,000
for a large system (one second minimum for each 50 METERS OF WIRE ON THE LOOP.
nodes). A1946
IV-11 95-8470
Section V pressure. It is also insensitive to the ultraviolet
component of solar radiation.
Detector Application
Information UV radiation generated by periodic lightning or sparks
in the area can be effectively ignored by the detector
UV DETECTORS using the arc rejection feature or time delay.
In applying any type of sensing device as a fire UV detectors should not be positioned so that their cone
detector, it is important to know of any conditions that of vision can scan the horizon. Rather, they should be
can prevent the device from responding to a fire, and directed down over the designated hazardous area to
also to know what other sources besides fire will cause reduce the likelihood of picking up UV radiation from
the device to respond. distant sources.
WINDOWS
Table V-1—UV and IR Absorbing Gases and Vapors
Glass and plexiglas windows significantly attenuate UV
radiation and must not be located between the detector
and a potential flame source. If the window cannot be The following is a partial list of compounds that exhibit
eliminated or the detector location changed, contact significant UV absorption characteristics. These are also
usually hazardous vapors. While generally of little
Detector Electronics for recommendations regarding
consequence in small amounts, these gases can restrict
window materials that will not attenuate UV radiation. UV detection if they are in the atmosphere in heavy
concentrations. It should also be determined whether or
OBSTRUCTIONS not large amounts of these gases may be released as a
result of a fire-causing occurrence.
For an ultraviolet detector, dust, dirt and other films, UV
Acetaldehyde Methyl Methacrylate
absorbing gases or vapors as well as physical
Acetone Alpha-Methylstyrene
obstructions must not be allowed to come between the Acrylonitrile Naphthalene
detector and the protected hazard (see Table V-1). Ethyl Acrylate Nitroethane
Methyl Acrylate Nitrobenzene
SMOKE Ethanol Nitromethane
Ammonia 1-Nitropropane
Smoke will absorb UV radiation, and if accumulations of Aniline 2-Nitropropane
dense smoke can be expected to precede the Benzene 2-Pentanone
presence of flame, then ultraviolet detectors that are 1,3 Butadiene Phenol
used in enclosed areas should be mounted on the wall 2—Butanone Phenyl Clycide Ether
approximately 3 feet (1 meter) from the ceiling where Butylamine Pyridine
Chlorobenzene Hydrogen Sulfide
the accumulation of smoke is reduced.
1-Chloro-1-Nitropropane Styrene
Chloroprene Tetrachloroethylene
ARC WELDING Cumene Toluene
Cyclopentadiene Trichloroethylene
Electric arc welding is a source of intense ultraviolet O-Dichlorobenzene Vinyl Toluene
radiation, and care must be taken to ensure that arc P-Dichlorobenzene Xylene
welding is not performed in the protected area without
If UV-absorbing gases may be a factor in a given
securing the fire detection system. UV radiation from application, precautionary measures should be taken.
arc welding readily scatters and can deflect across Detectors can be placed closer to the potential hazard
significant distances, even when direct obstructions area, and/or the sensitivity of the detection system can be
exist. Any open door or window can allow nuisance UV increased. Contact the factory for further details.
radiation from arc welding to enter an enclosed area.
Substances such as methane, propane, butane, hexane,
camphor and octane are not UV absorbing.
When x-rays or radioactive substances are present in
the area being protected, the UV system must be Absorption of infrared radiation in the range of 4.2 to 4.7
disabled until those sources are removed. microns is not a significant problem with most organic
vapors, with the exception of those compounds that have
COMMON ENVIRONMENTAL CONDITIONS triple bonds such as acetylene, nitriles, silane, or
isocyanates. Carbon dioxide concentrations higher than
normally present in the atmosphere can also cause
The detector is not affected by environmental conditions substantial loss of fire detection sensitivity.
such as wind, rain or extremes of temperature and
V-1 95-8470
UV DETECTOR POSITIONING
Detectors should be positioned to provide the best
CENTER AXIS
unobstructed view of the area to be protected. The OF DETECTOR
FIELD OF VIEW
following factors should be taken into consideration:
• Identify all high risk fire ignition sources.
• Be sure that enough detectors are used to adequately
cover the hazardous area. INCORRECT
• For outdoor applications, the detector should be NOTE: DETECTOR MUST ALWAYS BE AIMED
DOWNWARD AT LEAST 10 TO 20 DEGREES.
aimed downward at least 10 to 20 degrees to prevent
it from scanning the horizon. This minimizes response Figure 1—Detector Orientation Relative to Horizon
to distant UV sources outside the protected area. See
Figure 1.
Any object having a temperature greater than 0°
• Dense fog, rain or ice will absorb UV radiation and
Kelvin (–273°C) emits infrared radiation. The hotter
reduce the sensitivity of the detector.
the object, the greater the intensity of the emitted
• If smoke is expected before flame, it is recommended radiation. The closer the infrared source is to the
that smoke or other additional detectors be used in detector, the greater the potential for a false alarm.
conjunction with the UV detector. The IR sensor can respond to IR radiation sources
that can meet the amplitude and flicker
If possible, fire tests should be conducted to verify requirements of the detector such as vibrating hot
correct detector positioning and coverage. objects.
V-2
The UV/IR detector does not respond to arc welding UV/IR DETECTOR POSITIONING
beyond 10 feet from the detector. However, a UV only
signal will be generated in response to the intense UV IMPORTANT
radiation generated by the arc welding, and at Detectors should not be positioned so that their
distances closer than 10 feet the heated metal from the cone of vision can scan the horizon. Rather, they
welding can become a false alarm source for the IR should be directed down over the designated
sensor. hazardous area to reduce the likelihood of picking
up radiation from distant sources. See Figure 1.
FACTORS INHIBITING DETECTOR RESPONSE
Detectors should be located in positions best suited for
Windows covering the area to be protected. Whenever practical,
they should be placed where they will be easily
Glass and Plexiglas windows significantly attenuate accessible for cleaning and other periodic servicing.
radiation and must not be located between the detector Particular attention should also be paid to potential false
and a potential flame source. If the window cannot be alarm sources within the cone of vision of the detector,
eliminated or the detector location changed, contact such as distant arc welding, or the rotating blades of a
Detector Electronics for recommendations regarding fan or surface vibration of an IR source, which could
window materials that will not attenuate radiation. allow a flickering IR signal to reach the detector. Rain
or ice can absorb radiation, which can reduce the
Obstructions capability of the detector. For outdoor applications, aim
the detector downward to minimize the buildup of water
Radiation must be able to reach the detector in order for or ice on the detector viewing windows and to prevent
it to respond. Care must be taken to keep physical the cone of vision from scanning the horizon. This
obstructions out of the line of view of the detector. In minimizes response to distant radiation sources outside
addition, UV or IR absorbing gases or vapors must not the protected area.
be allowed to accumulate between the detector and the
protected hazard. See Table V-1 for a list of these
substances. GAS DETECTOR POSITIONING
Smoke The sensor must be properly located to enable it to
provide maximum protection. The formula for
Smoke will absorb radiation. If accumulations of dense determining the most effective number and placement
smoke can be expected to precede the presence of a of sensors varies depending on the conditions at the job
flame, then detectors that are used in enclosed areas site. The individual performing the installation must rely
should be mounted on the wall approximately 3 feet (1 on experience and common sense to determine the
meter) from the ceiling where the accumulation of quantity of sensors and the best sensor locations to
smoke is reduced. adequately protect the area.
Detector Viewing Windows The following factors should be considered for every
installation:
It is important to keep the detector viewing windows as
free of contaminants as possible in order to maintain 1. What kind of gas is to be detected? If it is lighter
maximum sensitivity. Commonly encountered than air (acetylene, hydrogen, methane, etc.), place
substances that can significantly attenuate UV and/or IR the sensor above the potential source. Place the
radiation include, but are certainly not limited to, the sensor close to the floor for gases that are heavier
following: than air (benzene, butane, butylene, propane,
hexane, pentane, etc.) or for vapors resulting from
Silicones
flammable liquid spills. However, note that air
Oils and greases
currents can cause a gas that is heavier than air to
Ice buildup
rise. In addition, if the gas is hotter than ambient
Dust and dirt buildup
air, it could also rise.
Paint overspray.
2. How rapidly will the gas diffuse into the air? Select
a location for the sensor as close as practical to the
anticipated source of a gas leak.
V-3 95-8470
3. Ventilation characteristics of the immediate area When a sensor is exposed to a different or new
must also be considered. Movement of air will environment, calibration should be checked frequently
cause gas to accumulate more heavily in one area to determine the proper interval between periodic
than another. The sensor should be placed in the calibrations.
area where the most concentrated accumulation of
gas is anticipated. Also consider the fact that many Before performing calibration, the operator should
ventilation systems do not operate continuously. examine the sensor filter (flame arrester) to be sure that
it is not missing or damaged. If the filter is defective or
4. The sensor should be pointed down to prevent the missing, it must be replaced. In some cases, an
buildup of moisture or contaminants on the filter and exposed sensing element can act as an ignition source.
to ensure proper operation. For PointWatch, refer to It should also be noted that a dirty cover can
instruction manual 95-8440. significantly reduce the sensitivity of the sensor.
5. The sensor must be accessible for testing and CATALYTIC SENSOR OPERATION
calibration. The use of the Sensor Separation Kit
will be required in some installations. The sensing element used in the combustible gas
sensor consists of a pair of elements. One is an active
6. Catalytic sensors should be located where they are catalytic sensing element, and the other is inactive and
safe from potential sources of contamination that acts as a temperature compensating reference element.
can poison the sensing element. Both elements are composed of a wire coil encased in
ceramic. The active element has a catalytic coating
7. Exposure to excessive heat or vibration can result in applied to its surface, however, the reference element is
premature failure of any electronic device and glazed so that it does not react to the presence of a
should be avoided if possible. Shielding the device combustible gas/air mixture. The pair is computer
from intense sunlight will reduce solar heating and matched to have the same electrical resistance.
can increase the life of the unit.
In the presence of a combustible gas/air mixture, the
For additional information on determining quantity and resistance of the active sensing element increases in
placement for sensors in a specific application, refer to proportion to the concentration of gas at the sensor.
Instrument Society of America (ISA) Transaction Volume The change in resistance of the active sensing element,
20, Number 2, titled “The Use of Combustible Detectors relative to that of the reference element, is used to
in Protecting Facilities from Flammable Hazards.” determine the actual level of combustible gas present at
the sensor.
CATALYTIC GAS SENSORS Both elements operate at a high temperature and are
enclosed by a porous stainless steel cup (flame
CAUTION arrester). See Figure V-2. This cup allows the diffusion
Exposure to a high level of gas can have an of gas to and from the sensing element, but prevents
adverse effect on the sensitivity of catalytic sensing the ignition of the atmosphere outside the sensor should
elements. If the level of gas at the sensor should the combustible gas concentration exceed its LFL.
reach 100% LFL, it is important that it be tested
and recalibrated if required. In some cases, it may A barrier is placed between the element pair to prevent
be necessary to replace the sensor. thermal interaction and to prevent the transfer of
catalytic material from the active element to the surface
If an over-range condition should occur, the user of the reference element.
must exercise caution, since a highly explosive
condition could exist. The hazardous area should All catalytic type sensors require oxygen to detect
be checked with a portable detection instrument to combustible gases. The sensor response will decrease
determine the actual level of combustible gas if enough combustible gas displaces the normal oxygen
present. present in air. The sensor should not be used where the
oxygen level is less than 10%. See Figure V-3.
For best calibration results, allow a new sensor to
operate for several hours to ensure a stable output Figure V-4 shows the response of a typical sensor to
before performing calibration. For the highest degree of various levels of combustible gas. Note that a reading of
accuracy, perform a second calibration after 24 hours. 40% LFL will be given at 2.0% methane (40% LFL) and
V-4
also at 80.0% methane, well above the upper flammable
limit of methane. Although gas levels above the upper
flammable limit will not propagate a flame, it stands to
reason that somewhere between the leak and clear air
WHT
RED
BLK
there will be a flammable mixture.
CAUTION
It is possible for the display to drop to a low % LFL
reading after going into high alarm and still have an
unsafe level of combustible gas present.
Therefore, precautions should be taken to ensure
that the combustible gas has been cleared before
classifying the area as safe.
90
80
70
CONTROLLER 50
DISPLAY
READING
(%LFL)
40
30
20
10
0
0 5 10 15 20 30 40 50 60 70 80 90 100
Figure V–3—Effect of Oxygen Enriched and Deficient Atmosphere on the Response of a Typical Catalytic Sensor
V-5 95-8470
180
160
140
120
DISPLAY 100
READING
(%LFL)
80
LOWER FLAMMABLE LIMIT
(100% LFL)
60
20
0
0 5 10 15 20 30 40 50 60 70 80 90 100
Figure V–4—Typical Response of Catalytic Sensor to All Possible Mixtures of Methane and Air
A dust cover should be installed to protect the This occurs in the presence of volatile metal
flame arrester whenever these conditions exist. organics, gases, or vapors of hydrides, and volatile
compounds containing phosphorous, boron,
The dust cover can be cleaned as part of routine silicone, etc.
maintenance. This can be accomplished using
an organic solvent and an ultrasonic bath. Examples:
RTV silicone sealants
2. Corrosive products. Silicone oils and greases
Tetraethyl lead
This occurs when substances such as Cl 2 Phosphine
(Chlorine) or HCl are present. A dust cover Diborane
provides some protection. The dust cover Silane
should be replaced as part of routine Trimethyl chlorsilane
maintenance. Hydrogen fluoride
Boron trifluoride
3. Flame arrester clogged as a result of painting Phosphate esters
or house cleaning.
V-6
C. Materials that remove the catalytic metals from the CALIBRATION GAS
active element of the sensor.
Before calibrating a sensor, check the label on the
Some substances react with the catalytic metal calibration gas cylinder to ensure that the correct gas
forming a volatile compound. This erodes the metal type and concentration are being used. If a different
from the surface. With sufficient exposure, most or gas type is being used for calibration, refer to Det-
all of the metal catalyst can be removed from the Tronics Technical Note No. GTN01 for “K-Factor”
surface of the active element of the sensor. information (Det-Tronics form number 99-1068-02).
Examples:
Chlorine
Bromine
Iodine
Hydrogen Chloride, Bromide or Iodide
Organic halides:
Trichloroethylene
Dichlorobenzene
Vinyl chloride
Freons
Halon 1301
(Bromotrifluoromethane).
V-7 95-8470
Section VI POWER WIRING
General Wiring Requirements The input voltage at the field devices must be 18 vdc
minimum to ensure proper operation of the devices.
GENERAL INFORMATION Therefore, it is important to consider both the size
(gauge) of the power wiring and the wiring distance
WARNING
from the power supply. As the wiring distance
Do not open any junction box or device enclosure
increases, larger diameter wire is required to maintain a
when power is applied without first de-classifying
minimum of 18 vdc at the device.
the hazardous area.
Refer to Table VI-1 to determine the minimum wire size
CAUTION
needed to prevent excessive voltage drop from power
Any deviation from the recommended wiring
supply to device for a given current load.
practices can compromise system operation.
Consult the factory if different wire types or
To use Table VI-1, first determine the total current load
methods are being considered.
for the circuit and the maximum allowable voltage drop.
Then look under the appropriate Amp Load column to
NOTE
determine the minimum wire size that will not allow the
All wiring must be marked per NFPA 70 Article
voltage drop to exceed the maximum allowable.
760.
For example:
NOTE
Specific installation requirements may differ
What wire size is required to power ten DCUs at a
depending on local installation practices and
distance of 100 feet from the power supply, assuming a
compliance with third party certifications. For local
24 VDC power supply and a minimum of 18 VDC
installation practices, consult the local authority
needed to power the DCUs?
having jurisdiction. For compliance with third party
certifications, consult the appropriate appendix in
Maximum allowable voltage drop is 6 VDC.
this manual for additional specific installation
(24 – 18 = 6)
requirements.
Table VI-1—Voltage Drop Per Pair in Volts DC per 100 Feet from Power Supply to Device
AWG 1 AMP LOAD 2 AMP LOAD 3 AMP LOAD 4 AMP LOAD 5 AMP LOAD
NOTES: This table is for reference only and does not replace good engineering practice.
Use Ohms Law when designing the power distribution system.
Voltage drop and wiring distance are proportional.
Consult factory for assistance with system wiring requirements.
VI-1 95-8470
A combustible gas DCU draws approximately 500 mA Table VI–3—Communication Loop Wiring Cable
at startup, therefore, the total current load is 5 amps.
(10 units x 500 mA = 5 amps) Cable Type Maximum Length
Feet Meters
Refer to the 5 Amp Load column in the table. Since the
Belden 8719 6500 2000
maximum allowable voltage drop is 6 volts, 16 AWG (or Belden 85231 6500 2000
larger) wire is required. Level IV, 22 AWG 4500 1370
JY (St) 2x2x0.8 3000 900
IMPORTANT
Be sure that selected cable meets all job specifications.
To ensure proper operation of field devices, the If necessary, consult factory for further suggested cable types.
voltage input to the device (measured at the
device) must be within the range indicated for that
device in the “Specifications” section of this
manual. between a network extender and the LCU. The use of
other cable types can degrade system operation. For
optimum fault isolation performance, the maximum
NETWORK WIRING LON/SLC wiring length should not exceed 1600 feet
(500 meters).
All devices on the LON/SLC are wired in a loop that
starts and ends at the LCU. To ensure proper SHIELD GROUNDING
operation, the LON/SLC should be wired using high
speed communication grade cable. Cable meeting the Two shield ground terminals are provided inside the
specifications listed in Table VI-2 is suitable for junction box of each field device and also at the LCU.
distances up to 2000 meters. Any of the cable types Connect the shield ends to the terminals provided (not
listed in Table VI-3 can be used for wiring the LON/SLC to each other) inside the junction box.
for the distances indicated. If no network extenders are
used, the distances listed are for the entire loop. If CAUTION
network extenders are used, the distances listed are for Insulate the shields to prevent shorting to the
the wiring length between network extenders or device housing or to any other conductor.
VI-2
JUNCTION BOX GROUNDING In applications where the wiring cable is installed in
conduit, the use of watertight conduit seals, drains,
Junction boxes should be electrically connected to breathers, or equivalent is recommended to prevent
earth ground. damage to electrical connections caused by
condensation within the conduit.
RS-485 LINK WIRING
ELECTROSTATIC DISCHARGE
The RS-485 link connecting the LCU and LIOU requires
termination at both ends. The LCU provides termination Many system electronic modules contain semiconductor
for the beginning of the RS-485 link. All other devices, devices that are susceptible to damage by electrostatic
except for the device at the end of the line, shall have discharge. An electrostatic charge can build up on the
their termination resistor removed. The LIOU uses a skin and discharge when an object is touched.
termination resistor that must be removed if it is not at Therefore, use caution when handling, taking care not to
the end of the line. touch the terminals or electronic components. For more
information on proper handling, refer to Service Memo
All devices sharing a common RS-485 link must have a form 75-1005.
common power return.
Device Type Number of Devices Standby Current Total Current for Device Type
LCU 1 X 0.300 = 0.300
Release Module X 0.070 =
Signal Audible X 0.033 =
Relay Module X 0.020 =
P. S. Monitor X 0.060 =
IDC/IDCGF/IDCSC X 0.055 =
UV Detector X 0.100 =
UV/IR Detector X 0.100 =
DCUEX X 0.145 =
DCU with H2S X 0.060 =
VI-3 95-8470
Table VI–5—Alarm Current Requirements at 24 vdc
Device Type Number of Devices Alarm Current Total Current for Device Type
LCU 1 X 0.340 = 0.340
Release Module X 0.165 =
Signal Audible X 0.120 =
Relay Module X 0.090 =
P. S. Monitor X 0.060 =
IDC/IDCGF/IDCSC X 0.090 =
UV Detector X 0.120 =
UV/IR Detector X 0.120 =
DCUEX X 0.160 =
DCU with H2S X 0.075 =
T0013B
Power Supply
Characteristic
EQ2110PS EQ2130PS EQ2175PS
Input Frequency 60 Hz 60 or 50 Hz 60 or 50 Hz
VI-4
Table VI–7—Backup Battery Requirements for Automatic Release of Extinguishing Systems Except Deluge
VI-5 95-8470
Section VII EQ2100PSM POWER SUPPLY
System Wiring MONITOR USED WITH EQ2110PS,
EQ2130PS AND EQ2175PS POWER
SUPPLIES
NOTE
Specific installation requirements may differ WIRING
depending on local installation practices and
compliance with third party certifications. For local 1. Mount the power supply monitor in a Nationally
installation practices, consult the local authority Recognized Test Laboratory (NRTL) labeled
having jurisdiction. For compliance with third party enclosure. Refer to the “Specifications” section for
certifications, consult the appropriate appendix in mounting dimensions.
this manual for additional specific installation
requirements. NOTE
Power supplies require unrestricted air flow for
proper cooling.
J1: POWER AND LON WIRING LON ADDRESS SWITCHES J3: AC INPUT
+ +
1 TERMINAL NO. 1
+ + 1
SWITCH NO. 1
+
+ +
+
+
+ +
1
+ +
+
+
1
+ YELLOW LED
GREEN LED
A1949
TERMINAL NO. 1
J2: CURRENT TEST POINTS
TERMINAL "C"
TERMINAL "B"
Figure VII-1—Location of Terminals, LEDs and Switches on the Power Supply Monitor
VII-1 95-8470
WARNING Connect the shield to the designated
Do not connect or disconnect wires with power "shield" terminal. (The two shield terminals
applied. are connected internally.) Do not ground
any shield at the monitor / power
distribution cabinet. Insulate the shields
4. Connect the 24 vdc power wires and the LON
to prevent shorting to the device housing
network cable to the appropriate points on J1, the
or any other conductor.
Power & LON Wiring terminal block. See Figure VII-
2.
5. Connect a two wire cable between the AC input of
the power supply and terminals 1 and 4 on J3, the
COM 1 - Communication network connections:
AC input terminal block on the power supply
Connect to COM 2 terminals of the next
monitor. See Figure VII-3.
device on the loop, A to A and B to B.
6. Connect the “B” terminal on the power supply
COM 2 - Communication network connections:
monitor to the negative (–) side of the backup
Connect to COM 1 terminals of the
battery. Connect a correctly sized circuit breaker or
previous device on the loop, A to A and B
disconnect switch in the battery circuit as shown in
to B.
Figure VII-4. If a circuit breaker is used, it must be
rated between 150% and 250% of the total load.
24 VDC - Connect the "+" terminal to the positive
side of the 24 vdc power source. (Both "+"
7. Connect the “C” terminal on the power supply
terminals are connected internally.)
monitor to the negative (–) side of the power supply.
Connect the "-" terminal to the negative
8. Wire the power distribution circuit breakers to the
side of the 24 vdc power source. (Both "-"
output of the power supply. Circuit breaker ratings
terminals are connected internally.)
must be between 150% and 250% of the full load
rating.
10. Set the LON address for the power supply monitor.
2 A COM 1 Refer to Figure VII-1 for rocker switch location.
Refer to “LON/SLC Device Address Switch Setting”
3 B in the “Switch Setting” section (Section VIII) of the
Eagle Quantum system manual (form number 95-
4 SHIELD 8470) for complete information regarding the switch
setting procedure.
5 +
11. Connect the mounting frame to chassis (earth)
6 – ground.
24 VDC
7 –
8 +
9 SHIELD
1 AC INPUT 120 / 240 VAC
10 A
2 NOT USED
11 B COM 2
3 NOT USED
12 SHIELD
4 AC INPUT 120 / 240 VAC
A1947 A1950
VII-2
POWER SUPPLY MONITOR 12
11
10
1 9
AC MONITOR 8
4 7
6
5
4
C 3
2
B 1
H – –
24 VDC
N
OUTPUT
G + + + POWER DIST CKT #1 –
NOTES
1. AC INPUT SELECTABLE (THROUGH THE OIS)
FOR 120 / 208 / 240 VAC.
– + – + 2. BATTERY SIZE CALCULATED BASED ON
SYSTEM LOAD.
12 VDC 12 VDC 3. CIRCUIT BREAKER RATINGS MUST BE BETWEEN
150% AND 250% OF FULL LOAD RATING.
4. REMOVAL OF TERMINAL PLUG WITH POWER
APPLIED TO TERMINALS B AND C WILL DAMAGE
C1951 BACKUP BATTERIES THE POWER SUPPLY MONITOR.
Figure VII-4—A Typical Application — Wiring Connections for a Power Supply Monitor, Power Supply and Backup Batteries
1 CURRENT SENSE +
2 CURRENT SENSE –
3 BATTERY –
4 BATTERY +
A1952
VII-3 95-8470
EQ2100LCU SERIES NOTE
LOCAL CONTROL UNIT EOL terminals are provided to allow convenient
installation of EOL resistors. Installing an EOL
All external wiring to the LCU is connected to the resistor at terminals 1D and 1E or 2D and 2E
terminal blocks that are an integral part of the LCU places it across the normally open and common
backplane, extending below the card rack. To access contacts of the alarm and supervisory relays. Note
the terminals, the cover must be removed. that the Trouble relay is energized during normal
operation, therefore the EOL resistor goes across
The terminals are arranged in three rows and numbered the normally closed contacts at 3D and 3E. To
from left to right. Row “A” is closest to the bottom of the insert the resistor lead into the terminal, depress
board, row “B” in the center, and row “C” on top. the orange lever.
SUPER
GND FLT
AUX 24V
RS-485
EOL
FAULT
P2
P1
DC2
DC1
ROW D
1D
2D
3D
1E
2E
3E
K1
K2
K3
K4
{
{
EARTH
CHASSIS
INPUT 3
INPUT 2
INPUT 1
SHIELD
RXD
RESET
TXD
RXD
TXD
NC
NC
COM
COM
ROW C
+
R+
T+
14
15
16
17
18
A
A
–
–
1
COM2
COM
COM
ROW B
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
1
COM1
NO
NO
ROW A
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
1
TO
TO OIS COMMUNICATION
NETWORK
GATEWAY RELAY CONTACTS
VII-4
Terminal 7 — System power. contacts etc. Wire the
contacts between the “A” and
When used with the standard “B” terminals. These inputs
LCU rack (EQ2100LCU), can be used in the
terminals A7 and B7 are power programmable logic.
input terminals for supplying
the 24 vdc power from the Terminal 13 — Remote reset.
power supply to the LCU.
When used with the optional Connect a normally open,
LCU rack (EQ2101LCU), momentary closure switch
terminals A7 and B7 are power between terminals A13 and
output terminals for supplying B13 to reset the gateway
isolated power with ground relays from a remote location
fault monitoring from the LCU when the relays are
to the main power terminals on programmed for latching
the LIOU and field devices. operation.
Output current must not
exceed 2.8 amperes. Terminals 14 to 18 — Gateway relay contacts.
VII-5 95-8470
NOTE NOTE
Connection to Port 2 can also be made using the B23 is connected directly to chassis ground. A23
9-pin (DB9) connector P7. is connected to chassis ground through a filter
Pin 2 = TXD = B19 network.
Pin 3 = RXD = B20
Pin 5 = COM = A19 IMPORTANT
When installing the three modules in the LCU rack,
the Logic Controller must be in the left hand
WARNING
position, the Gateway in the center position, and
Do not plug or unplug the connector unless the
the LON Isolator in the right hand position.
area is known to be non-hazardous.
VII-6
EQ2100LIOU LOCAL OUTPUT UNIT POWER WIRING
Power and communication wiring to the LIOU is Auxiliary Power Input (+): Connect to the (+) auxiliary
connected to the terminal block on the LIOU backplane. terminal of the EQ2101LCU
See Figure VII-7. (terminal B6).
RS-485 LINK WIRING Auxiliary Power Output: These terminals are provided
J3, J4, J5 to distribute 24 vdc auxiliary
The assembly is controlled and supervised by the Local power to the auxiliary power
Control Unit (LCU) using an RS-485 serial terminals on the release and
communication link. Up to four LIOU’s can be signal audible modules.
controlled by the LCU adding a maximum of 24 output Maximum total current must
modules to the system. not exceed 8 amperes.
The RS-485 link connecting the LCU and LIOU requires Chassis Ground: Connect to earth ground.
termination at both ends. The LCU provides termination
Module Wiring
for the beginning of the RS-485 link. If the LIOU is not
the last unit in the line, termination resistor R1 must be
Wiring to the external devices that are controlled by the
removed. See Figure VII-7 for location.
LIOU modules is connected to the terminal strip on the
corresponding module.
Two sets of RS-485 terminals are provided to allow
daisy-chained wiring. “A” terminals are connected to
“A” terminals and “B” terminals to “B” terminals of the
next device on the link.
VII-7 95-8470
RELAY MODULE
WIRING
SWITCH SETTING
1 2 1 2
}
S2
MODULE ADDRESS SWITCHES
S1
2 K1
TB1
3
RELAY MODULE
4
5 K2
12
6
7
A1862
8 K3
10
NOTES:
1. ALL RELAY OUTPUTS ARE SHOWN IN NORMAL STANDBY CONDITION.
2. ALL CONTACTS ARE THE DRY CONTACT TYPE.
3. OUTPUTS OF ALL RELAYS ARE NOT SUPERVISED.
4. RATINGS ARE 2A MAXIMUM AT 24 VDC; 1A AT 120 VAC.
5. THE MAXIMUM NUMBER OF BOARDS PER SYSTEM IS EIGHT.
Table VII–1—Switch Positions for Relay Module Addresses
6. THE MAXIMUM WIRE SIZE IS 12 AWG, ONE WIRE PER TERMINAL. B1861
VII-8
RELEASE MODULE SWITCH SETTING
JUMPERS
RELEASE SOLENOIDS
TB1
1 3
+ AUXILIARY POWER +
2 4
– – ONE SOLENOID SEE NOTE 3.
3 5
+ +
4 6
– RELEASE CIRCUITS –
5
+
6
–
7
–
8
+ TB1
9 3
– SIGNAL CIRCUITS + SOLENOID ONE
10 4
+ – SEE NOTE 3.
11 5
– + SOLENOID TWO
12 6
+ –
VII-9 95-8470
ON
1 2 1 2
S2 S4
RESET SWITCH MODULE ADDRESS ASSIGNMENT
S3
TROUBLE LED
DS1
Table VII-3—Maximum Wiring Length for FM Approved Solenoids for Deluge and Pre-Action Applications
Skinner LV2LBX25 800 (244) 500 (152) 310 (94) 200 (61)
ASCO 8210A107 520 (158) 325 (99) 200 (61) 130 (40)
ASCO 8210G207 825 (251) 520 (158) 325 (99) 205 (62)
Skinner 73218BN4UNLVNOC111C2 860 (262) 540 (165) 340 (104) 215 (66)
Skinner 73212BN4TNLVNOC322C2 400 (122) 250 (76) 160 (49) 100 (30)
Skinner 71395SN2ENJ1NOH111C2 860 (262) 540 (165) 340 (104) 215 (66)
T0041B
VII-10
SIGNAL AUDIBLE MODULE TB1
+24VDC 1
AUXILIARY POWER
WIRING RET
2
8
+
NOTE 9
–
Polarity shown is for activated condition. Polarity
10
is reversed for monitoring condition. 10K EOL
–
CIRCUIT 3
11
+
JUMPERS/SWITCHES
TB1
TB1
+24VDC 1 TB1
AUXILIARY POWER +24VDC
RET 1
2
AUXILIARY POWER
RET
2
5
–
6 5
– –
10K EOL CIRCUIT 1 CIRCUIT 1
7 6
+ –
10K EOL 10K EOL CIRCUIT 2
8 7
+ +
9 8
– +
CIRCUIT 3
10 9
– –
10K EOL 10K EOL CIRCUIT 4 CIRCUIT 3
11 10
+ –
10K EOL 10K EOL CIRCUIT 4
11
+12 +
12
+
JUMPERS SWITCHES
W1 W2 W3 W4 W5 W6 W7 W8 SW2–1 SW3–2
JUMPERS SWITCHES
OFF OFF OFF ON ON ON ON OFF OFF ON C1865
W1 W2 W3 W4 W5 W6 W7 W8 SW2–1 SW3–2
OFF
ON ON ON OFF ON ON ON OFF ON ON C1868
Figure VII–12—One Style “Z” and Two Style “Y” Circuits
for Signal Audible Module Figure VII–15—Four Style “Y” Circuits for Signal Audible Module
VII-11 95-8470
Table VII–6—Maximum Wiring Length
from Nominal 24 VDC Power Source to Signaling Device
W11
U1
MICROCONTROLLER
ON
RESET SWITCH SW4
}
1 2 1 2 1 2
SW1
WITH EPROM
SW3
J1
W3 W4
W9
W1
1 W10
W2
TB1
W5
W6
12
W7 W8
A1869
VII-12
FIELD DEVICES
EQ2200IDC SERIES INITIATING DEVICE CIRCUIT
GND
WARNING
The hazardous area must be de-classified prior to
11
12
removing a junction box cover with power applied.
13
10
14
9
8
7
1. Remove the cover from the junction box.
6
5
4
3
2. Connect external system wiring to the appropriate
2
1
terminals on the terminal block inside the junction
box. See Figure VII-17 for terminal block location
and Figure VII-18 for terminal identification. The
input to the IDC consists of one or more normally
open switches (momentary pushbuttons are not
recommended), with a 10K ohm, 1/4 watt EOL A1870
+ 1
4. Set the node address for the device. Refer to CIRCUIT 1 EOL (10K)
“Device Address Switch Setting” in the “Switch – 2
Setting” section (Section VIII) of this manual for
complete information regarding the switch setting + 3
procedure. CIRCUIT 2 EOL (10K)
– 4
5. Install the communication module inside the
junction box. Be sure that the keyed ribbon cable is A 5
properly connected. COM 2
B 6
6. Inspect the junction box O-ring to be sure that it is
in good condition and properly installed. Lubricate 7 14 –
the O-ring and the threads of the junction box cover COM SHIELD
with a thin coat of an appropriate grease to ease 8 13 –
installation and ensure a watertight enclosure. The 24 VDC
recommended lubricant is a silicone free grease, A 9 12 +
available from Det-Tronics. Place the cover on the COM 1
junction box. Tighten only until snug. Do not over B 10 11 +
tighten. A1871
VII-13 95-8470
EQ2200IDCGF SERIES INITIATING DEVICE RELAY CONTACT
FOR MONITORING BATTERY.
CIRCUIT GROUND FAULT CONTACT OPENS
WITH BATTERY TROUBLE CONDITION.
+ 3
68K OHM
INPUT
1. Securely mount the aluminum enclosure. The RESISTOR
– 4
enclosure should be electrically connected to earth
ground. A 5
RELAY CONTACT
FOR MONITORING AC POWER.
CONTACT CLOSES
COM 2 ON LOSS OF AC POWER.
2. Connect the external wiring to the appropriate B 6
VII-14
4. Set the node address for the device. Refer to EQ2200UV UV FLAME DETECTOR
“Device Address Switch Setting” in the “Switch
Setting” section (Section VIII) of this manual for 1. Remove the sensor housing from the bulkhead (turn
complete information regarding the switch setting counterclockwise). Install the sensor module and
procedure. replace the sensor housing. See Figure VII-20.
A
7. Install the electronic module, ensuring that the
5
connector is aligned correctly. Tighten the three
COM 2
B
captive screws that hold the electronic module in
6
place. See Figures VII-20 and VII-23.
7 14 –
8. Replace the rear housing and hand tighten to ensure
COM SHIELDS
proper sealing. See Figures VII-20 and VII-21.
8 13 –
24 VDC
9. Aim the detector at the potential hazard and tighten
A 9 12 +
the nut.
COM 1
B 10 11 +
A2076
10. Check the viewing window surface (Figure VII-24)
and ensure that:
Figure VII-19B—Terminal Identification for EQ2200IDCSC A) the oi source (UV test lamp opening) is located
on top
B) the split in the oi reflective ring is not aligned
with the UV test lamp opening on the detector
module
C) the split in the oi ring is directed downward to
prevent a buildup of contaminants between the
oi ring and the viewing window.
VII-15 95-8470
CONDUIT ENTRY
BULKHEAD
SENSOR MODULE
SENSOR HOUSING
REAR HOUSING
ELECTRONIC MODULE
O-RING
CONDUIT ENTRY
O-RING
A1840
oi RING DETECTOR WINDOW
COVER
CATCH SCREW LOCKING
ASSEMBLY
STRAP
A1841
VII-16
11. Clean the viewing window and oi ring using the
procedure described in the “Maintenance” section.
– COM 2
1 2 5 6 7
EQ2200UVHT HIGH TEMPERATURE UV FLAME
3 4 8 9 10 DETECTOR
SPLIT IN oi RING
(MUST BE POSITIONED
ON THE DOWNWARD SIDE
OF UNIT WHEN MOUNTED)
A1992
LEDs
* UV TEST LAMP OPENING MUST NOT BE ALIGNED WITH SPLIT IN oi RING B1891
VII-17 95-8470
LOOSEN TWO SCREWS TO P2
REMOVE TERMINAL WIRING BOARD
1 SHIELD
2 A COM 1
3 B
4 SHIELD
5 +
6 –
24 VDC
UV FLAME DETECTOR 7 –
A1993
TERMINAL BLOCK P3
A 1 8 +
Figure VII-26— Terminal Wiring Board with Electronic Module
Removed B 2 9 SHIELD
C 3 10 A
NOTE D 4 11 B COM 2
Terminals 4 and 9 (shield) are connected
internally, as are terminals 5 and 8 (24 vdc +) and 5 12 SHIELD
A1989
terminals 6 and 7 (24 vdc –).
6. Re-install the terminal wiring board inside the Figure VII-27— EQ2200UVHT Wiring Terminal
junction box.
7. Set the rocker switches on the DIP switch assembly aiming and wiring of the detector. Armored flexible
on the electronic module for the desired address. conduit should be used for the final 3 feet (one
Refer to “LON/SLC Device Address Switch Setting” meter) of the cable run to allow for aiming and
in the “Switch Setting” section of this manual for alignment of the detector.
complete information regarding the switch setting
procedure. 2. Attach the detector to the Swivel Mounting Bracket.
8. Re-install the electronic module, ensuring that the 3. Disassemble the detector enclosure by turning the
connector is aligned correctly. Tighten the three housing cover counterclockwise. See Figure VII-28.
captive screws that hold the electronic module in
place. NOTE
If the detector is equipped with a cover locking
9. Replace the junction box cover and hand tighten to device, it must be loosened using a hexagonal
ensure proper sealing. (Allen) wrench.
VII-18
7. Re-assemble the detector housing. If the detectors EQ2200UVIR UV/IR FLAME DETECTOR
are equipped with cover locking devices, loosen the
clamp sufficiently so that the “catch” can be seated 1. Mount and wire the detector.
in the blind hole provided on the terminal cap. The
A. Mount the detector and mounting bracket
clamp must then be fastened securely around the
assembly on the wall or ceiling. Observe the
detector barrel by tightening with the proper tool.
following guidelines:
8. Clean the viewing window and o i ring using the — The mounting surface should be free of
procedure described in the “Maintenance” section. excessive heat and vibration.
— Allow adequate space around the swivel to
9. Check the viewing window surface (Figure VII-24) facilitate aiming and wiring of the detector.
and ensure that: — Armored flexible conduit should be used
for the final 3 feet (one meter) of the cable
A) The oi source (UV test lamp opening) is located run to allow for aiming and alignment of the
on top. detector.
B) The split in the oi reflective ring is not aligned — Position the conduit below the detector and
with the UV test lamp opening on the detector orient the detector with the conduit entry at
module. the bottom or either side of the detector
C) The split in the oi ring is directed downward to (never at the top). This will prevent
prevent a buildup of contaminants between the condensation in the conduit from entering
oi ring and the viewing window. the detector junction box.
B. Remove the junction box cover.
10. Aim the detector at the potential hazard and tighten
the nut on the swivel mounting bracket. C. Connect the leadwires to the appropriate screw
terminals on the terminal block inside the
11. Install any optional accessories (such as air shields). junction box. See Figures VII-29 and VII-30 for
location of the terminal block and Figure VII-31
for terminal identification. Connect the shield of
the power cable to earth ground at the power
source. Connect the shields for the LON/SLC
cable as indicated. Do not ground the shields
at the detector housing.
TERMINAL BLOCK
A1994
HOUSING COVER
VII-19 95-8470
JUNCTION BOX
IR CONNECTOR PLUG
IR SENSOR MODULE
O-RING
IR SENSOR HOUSING
UV TERMINAL BLOCK
BANANA PLUG
IR oi RING
UV SENSOR MODULE
oi TEST LAMP
LED (2)
O-RING
UV SENSOR HOUSING
A1913 UV oi RING
A1912
TERMINAL BLOCK LON/SLC ADDRESS SWITCHES
SERVICE SWITCH *
LED **
NOTES: ** SERVICE SWITCH NOT FOR USE IN THE FIELD.
NOTES: ** ILLUMINATION OF LED INDICATES AN ELECTRONIC MALFUNCTION.
VII-20
2. Set the rocker switches.
+ 1
A. Set the rocker switches on the DIP switch
+ 2 assembly for the desired LON/SLC address.
POWER Refer to “LON/SLC Device Address Switch
– 3 Setting” in Section VIII — Switch Setting.
B. Re-install the junction box cover. The six
– 4
screws must be tight to ensure the explosion-
proof and watertight integrity of the junction
A 5
box.
COM 1 B 6 3. Complete the installation.
A. Aim the detector at the potential hazard.
SHIELD 7
B. Inspect and clean (if necessary) the detector
A 8 viewing windows and oi rings by following the
instructions in the Maintenance section of this
COM 2 B 9 manual.
C. Check the detector viewing windows (Figure
SHIELD 10
A1914
VII-32) and ensure that:
— the oi test lamps are located at the top or
side of the sensor module (when viewed
Figure VII–31—EQ2200UVIR Detector Wiring Terminals from the front)
— the opening in the oi ring is at the bottom.
*oi TEST LAMPS AT TOP OR SIDE
This will ensure proper operation of the oi
system and also minimize the accumulation
of moisture and contaminants between the
oi TEST LAMP oi ring and the viewing window.
LED (2)
D. Install any optional accessories (such as air
shields).
UV SENSOR
HOUSING
oi RING
OPENING
DOWN
IR SENSOR
HOUSING
DETECTOR MUST
BE ORIENTED WITH
CABLE/CONDUIT ENTRY
AT BOTTOM (PREFERRED)
OR SIDE TO ELIMINATE
DRAINAGE INTO
JUNCTION BOX.
H1327
VII-21 95-8470
EQ2200DCU DIGITAL COMMUNICATION UNIT USED
WITH DET-TRONICS H2S/O2 SENSORS OR OTHER
TWO-WIRE 4 TO 20 MA DEVICES COMMUNICATION MODULE
WARNING
Do not apply power to the system with the cover
removed unless the area has been verified to be
free of combustible gases or vapors. STANDOFFS (4)
VII-22
EQ2200DCU DIGITAL COMMUNICATION UNIT USED
WITH POINTWATCH
POINTWATCH CALIBRATE 1
Table VII–8—
Maximum Separation Distances — Electrochemical Sensor to DCU
VII-23 95-8470
EQ2200DCUEX DIGITAL COMMUNICATION UNIT
DCU POINTWATCH
USED WITH DET-TRONICS COMBUSTIBLE GAS
POINTWATCH CALIBRATE
SENSORS
1 YELLOW
4 TO 20 MA IN
Determine the best mounting locations for the detectors.
2 WHITE
Whenever practical, detectors should be placed where
–
they are easily accessible for calibration. Always orient
3 BLACK
the junction box with the sensor pointing down.
SENSOR POWER
+ 4 RED
WARNING
A
Do not apply power to the system with the cover
5 GREEN
removed unless the area has been verified to be
COM 2
B
free of combustible gases or vapors.
6
14 –
The DCUEX uses the following:
7
VII-24
CAUTION
COMMUNICATION MODULE The sensor threads can be coated with an
appropriate grease to ease both the initial
installation and future replacement of the sensor.
SWITCHES ON SAME SIDE Detector Electronics offers a silicone free grease
(RIGHT)
that is especially suited for use with catalytic type
combustible gas sensors (see “Ordering
Information” for part number). The use of other
TRANSMITTER BOARD
lubricants is not recommended, since some
materials can cause irreversible damage to the
sensing element. SILICONE based lubricants or
TERMINAL WIRING BOARD compounds must NEVER be used.
N G
SWITCHES ON OPPOSITE SIDES
(WRONG)
Set the address for the device. Refer to “Device
R O
TRANSMITTER BOARD
Address Switch Setting” in the “Switch Setting” section
of this manual for complete information regarding the
switch setting procedure.
W
TERMINAL WIRING BOARD
DCU TERMINAL BOARD DCU TRANSMITTER BOARD1
(MIDDLE BOARD)
POINTWATCH CALIBRATE 1
2
– 3 –
SENSOR POWER
2
+ 4 +
A 5
COMMUNICATION MODULE
COM 2
B 6
7 14 –
TRANSMITTER BOARD COM SHIELD
8 13 –
24 VDC
STANDOFFS (4) A 9 12 +
COM 1
TERMINAL WIRING BOARD B 10 11 +
B1877
Figure VII–37—Printed Circuit Boards in Combustible Gas DCU Figure VII–38—DCU Transmitter Board Connected
to Terminal Wiring Board
VII-25 95-8470
Sensor Separation with DCUEX
–
guidelines.
GR
N
+
When separating a combustible gas sensor from the
–
1. Preferred Method
Mount the transmitter PC board inside the sensor
ELECTROCHEMICAL SENSOR separation junction box. This assembly can be
separated from the DCUEX by up to 1000 feet using
three conductor 18 AWG shielded cable.
(Regardless of separation distance, operating
voltage at the transmitter MUST be at least 18 vdc
SPARE CHASSIS
CAL CAL
to ensure proper operation.) See Figure VII-39.
4-20 4-20
RET RET Assemble the DCUEX without the transmitter board
GND
+24 +24
similar to the DCU as shown in Figure VII-33. Plug
the sensor into P2 on the transmitter board. Use a
three conductor 18 AWG shielded cable to connect
P1 on the transmitter board to terminals 2, 3 and 4
on the DCU terminal board (see Figure VII-39).
Connect the shield to the ground terminal in the
POINTWATCH DCUEX junction box.
2. Alternate Method.
P1
If the transmitter board must be mounted separate
from the sensor (high temperature applications,
etc.), separate the sensor only, leaving the
transmitter PC board inside the DCUEX enclosure.
When using this installation option, see Table VII-9
for maximum wiring distances.
+
– Mount the sensor directly to the separation kit
4 TO 20 TRANSMITTER BOARD
junction box. Use three conductor shielded cable
for the connection between the terminal block in the
P2
separation kit junction box and P1 on the transmitter
NOTE: ALWAYS ORIENT
board. A plug with screw terminals is provided for
JUNCTION BOX WITH
CATALYTIC SENSOR
connecting the cable to P1 on the transmitter board.
POINTING DOWN. Observe the wiring color code. Connect the shield
SENSOR to the ground terminal in the DCUEX junction box.
B1878
CATALYTIC SENSOR
VII-26
EQ2500ARM SERIES AGENT RELEASE MODULE Table VII–10—Maximum Wiring Length for Release Applications
CAUTION
Do not intermix different types of initiators in the
release circuit.
Table VII-11—Maximum Wiring Length for FM Approved Solenoids for Deluge and Pre-Action Applications
Skinner LV2LBX25 800 (244) 500 (152) 310 (94) 200 (61)
ASCO 8210A107 520 (158) 325 (99) 200 (61) 130 (40)
ASCO 8210G207 825 (251) 520 (158) 325 (99) 205 (62)
Skinner 73218BN4UNLVNOC111C2 860 (262) 540 (165) 340 (104) 215 (66)
Skinner 73212BN4TNLVNOC322C2 400 (122) 250 (76) 160 (49) 100 (30)
Skinner 71395SN2ENJ1NOH111C2 860 (262) 540 (165) 340 (104) 215 (66)
T0041B
VII-27 95-8470
Terminals 11 to 14 — 24 vdc power input Jumpers
Connect the module power Terminals 13 and 14 are connected by jumper JP2 and
supply to terminals 12 and 13. terminals 11 and 12 are connected by jumper JP3.
If an auxiliary output supply is These two jumpers (JP2 and JP3) must be cut if an
used for powering solenoids, it auxiliary output power supply is being used. See Figure
should be connected to VII-41 for the locations of jumpers on the circuit board.
terminals 11 and 14.
When an explosive initiator is being used, jumper JP1
must be cut. If a solenoid is used, the jumper must
remain in.
SINGLE DUAL
SOLENOID SOLENOIDS
Address Switch Setting
+ 1
7 14 –
COM SHIELD
8 13 –
24 VDC
A 9 12 +
COM 1
B 10 11 +
JP1
NOTE:
TERMINALS 12 AND 13 ARE FOR MODULE POWER SUPPLY.
TERMINALS 11 AND 14 ARE FOR AUXILIARY OUTPUT POWER SUPPLY. JP2
11 12 13 14
JUMPERS JP2 AND JP3 MUST BE REMOVED IF AN AUXILIARY POWER SUPPLY IS USED. JP3
SEE NOTE 2.
2 A1902
NOTES:
1. JUMPER JP1 MUST BE REMOVED IF EXPLOSIVE INITIATOR IS USED.
VII-28
EQ2500SAM SERIES SIGNAL AUDIBLE MODULE Table VII–12—Maximum Wiring Length
from Nominal 24 VDC Power Source to Signaling Device
Wiring Maximum Wire Length in Feet (Meters)
To ensure adequate operating voltage for the signaling 12 AWG 14 AWG 16 AWG
(4 mm2)* (2.5 mm2)* (1.5 mm2)*
device, the maximum wiring length from the power
source to the output device must not exceed the values One 2 Ampere Load 190 (58) 120 (37) 75 (23)
shown in Table VII-12. (This wire length includes both the Two 2 Ampere Loads 95 (29) 60 (18) 35 (11)
wiring from the power supply to the signal audible module
and the wiring from the module to the signaling device.) * Approximate Metric Equivalent. T0029A
– 2
terminals 3 and 4. – 4
8 13 –
24 VDC
Terminals 5 to 10 — LON/SLC signaling circuit
terminals A 9 12 +
COM 1
VII-29 95-8470
EQ2400NE SERIES NETWORK EXTENDER
1 2 3 4 5 6 7 8 9 10
3. Connect the 24 vdc power lead wires and the
communication network cable to the appropriate
points on the terminal block. See Figure VII-44A for
terminal location within the junction box and Figure
B1903
VII-44B for terminal identification. Refer to Table VII-
Figure VII–43—Signal Audible Module Wiring Terminals and Jumpers 13 to determine maximum wiring length.
TERMINAL NO. 1
1 SHIELD
2 A COM 1
3 B
4 SHIELD
5 +
6 –
24 VDC
7 –
8 +
9 SHIELD
10 A
11 B COM 2
12 SHIELD
A1947
VII-30
COM 1 - Communication network connections: TYPICAL APPLICATIONS
Connect to COM 2 terminals of the next
device on the loop, A to A and B to B. Figure VII-45 shows a power supply monitor wired on a
LON between a UV detector and a DCU.
COM 2 - Communication network connections:
Connect to COM 1 terminals of the Figure VII-46 illustrates the power and communication
previous device on the loop, A to A and B wiring for a UV detector, an IDC and a DCU, connected
to B. to a standard LCU (EQ2100LCU) and an LIOU.
24 VDC - Connect the "+" terminal to the positive Figure VII-47 illustrates the power and communication
side of the 24 vdc power source. (Both "+" wiring for a UV detector, an IDC and a DCU, connected
terminals are connected internally.) to the optional LCU (EQ2101LCU) and an LIOU.
Connect the "-" terminal to the negative Figure VII-48 shows the power and communication
side of the 24 vdc power source. (Both "-" wiring for a UV/IR detector, an EQ2500SAM and an
terminals are connected internally.) EQ2500ARM, connected to a standard LCU
(EQ2100LCU) and an LIOU.
4. Connect the shields to the two designated "shield"
terminals. The two shield terminals are connected Figure VII-49 shows a network extender wired between
internally to ensure shield continuity. Do not ground a UV detector and a DCU.
either shield at the network extender enclosure.
Insulate the shields to prevent shorting to the Figure VII-50 shows a high temperature UV detector
device housing or any other conductor. wired between a standard UV detector and a DCU.
VII-31 95-8470
INSTALLATION CHECKLIST 5. Sensor and LON/SLC wiring is correct.
The following checklist is provided as a means of 6. Power wiring is installed and power source is
double checking the system to be sure that all phases operational.
of system installation are complete and have been
performed correctly. 7. External loads are properly connected and EOL
resistors are installed.
1. Junction boxes are mounted securely and detectors
are pointing in the proper direction. 8. DIP switches are set correctly. Record this
information for future reference.
2. All cable shields are properly insulated and
grounded. 9. Devices are properly installed in the mounting
racks.
3. All junction box covers are tightly installed.
10. Proper ventilation is provided (if needed) to prevent
4. Explosion-proof and watertight electrical fittings equipment over-heating.
have been installed at all junction box entries as
required for the hazardous location. Proceed to System Startup.
POINTWATCH CALIBRATE
4 TO 20 MA IN
– POWER
+ SENSOR
A
B
SHIELD
SHIELD
A
B
COM 2
COM 1
24 VDC
COM 2
COM 1
G
TO NEXT LON DEVICE
B1953
Figure VII-45—A Typical Application — LON Connections for a Power Supply Monitor Wired Between a UV Detector and a DCU
VII-32
EQ2100LCU EQ2200UV EQ2200IDC EQ2200DCU
COM2
COM1 TO GAS DETECTOR
POWER SUPPLY
A 25 24 VOLTS DC 24 VOLTS DC
24 VDC A B SHIELD – – + + – – + +
1 2 5 6 7
B 24
+ COM 1
SHIELD 23
3 4 8 9 10
– COM 2 14 13 12 11 14 13 12 11
RXD +
22 1 2 3 4 5 6 7 8 9 10
RXD – 1 2 3 4 5 6 7 8 9 10
P1 COM
21
TXD –
TXD +
20
RXD
–
A
B
A
B
P2 COM
–
–
A
B
A
B
+
+
19
TXD
SHIELD
SHIELD
SHIELD
SHIELD
COM 2
COM 1
POWER
COM 2
COM 1
FAULT
SENSOR
18
4 TO 20 MA IN
CIRCUIT 1
CIRCUIT 2
K4
17
K3
16
POINTWATCH CALIBRATE
K2
15
GATEWAY RELAYS
K1
14
NC NO
COM
G
RESET 13
INPUT 1 12
INPUT 2 11
INPUT 3 10
VII-33
A
RS-485 9
B
CHASSIS
GND FLT 8
EARTH EQ2100LIOU
–
MAIN 24V 7
+
B
–
A
J3
AUX 24V
J1
+
–
DC1
+
RS-485
–
J4
DC2
+
AUX POWER
J2
3E
J5
TROUBLE 3D 3
2E
MAIN AUX
SUPER 2D 2
–
BATTERY
+
1E CKT BREAKER
+
ALARM 1D 1
NC NO
G
COM
ROW C ROW A
ROW B
C 12 11 10 9 8 7 6 5 4 3 2 1 J1
–
–
+
+
BUS
B
A
B
A
BAR
B
SHIELD
SHIELD
SHIELD
SHIELD
+ – + –
SYSTEM J3
24 VOLT
BATTERY POWER 1
BACKUP SUPPLY
COM 2
24 VDC
COM 1
2
3 C1879
4
H N POWER SUPPLY MONITOR
A C LINE
95-8470
Figure VII–46—A Typical System — Field Devices Connected to EQ2100LCU (Standard)
EQ2101LCU EQ2200UV EQ2200IDC EQ2200DCU
COM2
COM1 TO GAS DETECTOR
POWER SUPPLY
A 25 24 VOLTS DC 24 VOLTS DC
24 VDC A B SHIELD – – + + – – + +
1 2 5 6 7
B 24
+ COM 1
SHIELD 23
3 4 8 9 10
– COM 2 14 13 12 11 14 13 12 11
RXD +
22 1 2 3 4 5 6 7 8 9 10
RXD – 1 2 3 4 5 6 7 8 9 10
P1 COM
21
TXD –
TXD +
20
RXD
–
A
B
A
B
P2 COM
–
–
A
B
A
B
+
+
19
TXD
SHIELD
SHIELD
SHIELD
SHIELD
COM 2
COM 1
POWER
COM 2
COM 1
FAULT
SENSOR
18
4 TO 20 MA IN
CIRCUIT 1
CIRCUIT 2
K4
17
K3
16
POINTWATCH CALIBRATE
K2
15
GATEWAY RELAYS
K1
14
NC NO
COM
G
RESET 13
INPUT 1 12
INPUT 2 11
VII-34
INPUT 3 10
A
RS-485 9
B
CHASSIS
GND FLT 8
EARTH EQ2100LIOU
–
MAIN 24V 7
+
B
–
J3
AUX 24V 6
J1
+
–
DC1 5
+
RS-485
–
J4
DC2 4
+
AUX POWER
J2
3E
J5
TROUBLE 3D 3
2E
MAIN AUX
SUPER 2D 2
–
1E
–
+
ALARM 1D 1
NC NO
COM
ROW C ROW A G
ROW B
+
–
TWO 24VOLT DC
POWER SUPPLIES
PER NFPA 72
+
B1880
–
A 25 SINGLE SOLENOID
24 VOLTS DC 24 VOLTS DC
– – + + – – + +
B 24
COM 1
COM 2
SHIELD 23 DUAL SOLENOIDS
14 13 12 11 14 13 12 11
+
+
–
–
A
B
SHIELD
A
B
SHIELD
RXD +
22 1 2 3 4 5 6 7 8 9 10
RXD – 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
P1 COM
21
TXD –
TXD +
20
RXD
–
–
A
B
A
B
+
+
P2 COM
–
–
A
B
A
B
+
+
19
TXD
SHIELD
SHIELD
SHIELD
SHIELD
COM 2
COM 1
COM 2
COM 1
FAULT
18
OUTPUT 1
OUTPUT 2
K4
17
K3
16
K2
15
GATEWAY RELAYS
K1
14
NC NO
COM
G
RESET 13
INPUT 1 12
INPUT 2 11
INPUT 3 10
VII-35
A
RS-485 9
B
CHASSIS
GND FLT 8
EARTH EQ2100LIOU
–
MAIN 24V 7
+
B
–
A
J3
AUX 24V
J1
+
–
DC1
+
RS-485
–
J4
DC2
+
AUX POWER
J2
3E
J5
TROUBLE 3D 3
2E
MAIN AUX
SUPER 2D 2
–
1E
+
BATTERY
–
C 12 11 10 9 8 7 6 5 4 3 2 1
–
–
+
+
BUS
B
A
B
A
BAR
B
SHIELD
SHIELD
SHIELD
SHIELD
+ – + –
SYSTEM J3
24 VOLT
BATTERY POWER 1
BACKUP SUPPLY
COM 2
24 VDC
COM 1
2
C1910
3
4
H N POWER SUPPLY MONITOR
A C LINE
95-8470
Figure VII–48—A Typical System — UV/IR Detector, EQ2500SAM and EQ2500ARM Connected to a Standard EQ2100LCU
EQ2100LCU EQ2200UV EQ2401NE EQ2200DCU
COM2
COM1 TO GAS DETECTOR
POWER SUPPLY
A 25 24 VOLTS DC
24 VDC A B SHIELD – – + +
1 2 5 6 7
B 24
+ COM 1
SHIELD 23
3 4 8 9 10
– COM 2 14 13 12 11
RXD +
22 1 2 3 4 5 6 7 8 9 10
RXD – 12 11 10 9 8 7 6 5 4 3 2 1
P1 COM
21
TXD –
–
–
B
A
B
A
+
+
TXD +
20
RXD
SHIELD
SHIELD
SHIELD
SHIELD
–
A
B
A
B
P2 COM
19
TXD
SHIELD
SHIELD
COM 2
24 VDC
COM 1
COM 2
COM 1
POWER
FAULT
SENSOR
18
4 TO 20 MA IN
K4
17
K3
16
POINTWATCH CALIBRATE
K2
15
GATEWAY RELAYS
K1
14
NC NO
COM
G
RESET 13
INPUT 1 12
INPUT 2 11
INPUT 3 10
VII-36
A
RS-485 9
B
CHASSIS
GND FLT 8
EARTH EQ2100LIOU
–
MAIN 24V 7
+
B
–
A
J3
AUX 24V
J1
+
–
DC1
+
RS-485
–
J4
DC2
+
AUX POWER
J2
3E
J5
TROUBLE 3D 3
2E
MAIN AUX
SUPER 2D 2
–
1E
+
BATTERY
ALARM 1D 1 CKT BREAKER
NC NO G
COM
ROW C ROW A
ROW B
C 12 11 10 9 8 7 6 5 4 3 2 1
–
–
+
+
BUS
B
A
B
A
BAR
B
SHIELD
SHIELD
SHIELD
SHIELD
+ – + –
SYSTEM J3
24 VOLT
BATTERY POWER 1
BACKUP SUPPLY
COM 2
24 VDC
COM 1
2 C1940
3
4
H N POWER SUPPLY MONITOR
A C LINE
Figure VII-49—A Typical System - Network Extender Wired Between UV Detector and DCU
EQ2200UVHT
EQ2100LCU EQ2200UV EQ2200DCU
COM2
COM1 TO GAS DETECTOR
D C B A
POWER SUPPLY
A 25 24 VOLTS DC
24 VDC A B SHIELD – – + +
1 2 5 6 7
B 24
+ COM 1
SHIELD 23
5 4 3 2 1
3 4 8 9 10
– COM 2 14 13 12 11
RXD +
22 1 2 3 4 5 6 7 8 9 10
RXD – 12 11 10 9 8 7 6 5 4 3 2 1
P1 COM
21
TXD –
–
–
B
A
B
A
+
+
TXD +
20
RXD
SHIELD
SHIELD
SHIELD
SHIELD
–
A
B
A
B
P2 COM
19
TXD
SHIELD
SHIELD
COM 2
24 VDC
COM 1
COM 2
COM 1
POWER
FAULT
SENSOR
18
4 TO 20 MA IN
K4
17
K3
16
POINTWATCH CALIBRATE
K2
15
GATEWAY RELAYS
K1
14
NC NO
COM
G
RESET 13
INPUT 1 12
INPUT 2 11
INPUT 3 10
VII-37
A
RS-485 9
B
CHASSIS
GND FLT 8
EARTH EQ2100LIOU
–
MAIN 24V 7
+
B
–
A
J3
AUX 24V
J1
+
–
DC1
+
RS-485
–
J4
DC2
+
AUX POWER
J2
3E
J5
TROUBLE 3D 3 BATTERY
2E CKT BREAKER
MAIN AUX
SUPER 2D 2
–
1E
+
ALARM 1D 1
NC NO
COM G
ROW C ROW A C 12 11 10 9 8 7 6 5 4 3 2 1
–
–
+
+
ROW B BUS
B
A
B
A
BAR
B
SHIELD
SHIELD
SHIELD
SHIELD
+ – + –
SYSTEM J3
24 VOLT
BATTERY POWER 1
BACKUP SUPPLY
COM 2
24 VDC
COM 1
2
3
4
H N POWER SUPPLY MONITOR B1990
A C LINE
95-8470
Figure 50—A Typical System – EQ2200UVHT Wired Between a Standard UV Detector and a DCU
Section VIII S5 — Hardware Serial Port Configuration
Switch Setting Verify that S5 switches are set as follows:
GATEWAY 1 — Open
The gateway contains four 8-position DIP switch 2 — Closed
assemblies that are used for: 3 — Closed
— Selecting serial port 1 software parameters 4 — Open
— Setting the gateway Modbus/Allen Bradley address 5 and 6 — Closed
— Selecting gateway relay operation (latching/non-
latching) 7 and 8 — Open.
— Setting the gateway type and address.
S6 — Software Serial Port Configuration for Port 1
Refer to Figure VIII-1 to identify the function of the DIP
switches. Refer to Figure VIII-2 to locate the DIP switch 1, 2, and 3 — Determine the desired baud
assemblies on the side of the gateway. rate, then refer to Table VIII-1
for the proper switch settings.
(19,200 is recommended and
cannot be exceeded in the
S8 LON CONFIGURATION
LCU.)
1 2 3 4 5 6 7 8
CLOSED
OPEN
4 — Parity enable.
NON-LATCHING GATEWAY RELAYS
SELECT CONFIGURATION PORT Open = no parity.
PORT 2 OPERATION
PORT 1 OPERATION Closed = parity enabled.
GATEWAY ADDRESS BIT 1 (MSB)
GATEWAY ADDRESS BIT 0 (LSB)
5 — Parity type.
S7 MODBUS ADDRESS
1 2 3 4 5 6 7 8 Open = odd.
MODBUS ADDRESS BIT 7 (MSB)
Closed = even.
MODBUS ADDRESS BIT 6
MODBUS ADDRESS BIT 5
MODBUS ADDRESS BIT 4 6 — Stop bits.
MODBUS ADDRESS BIT 3
MODBUS ADDRESS BIT 2
MODBUS ADDRESS BIT 1
Open = 1 stop bit.
MODBUS ADDRESS BIT 0 (LSB) Closed = 2 stop bits.
S6 SOFTWARE SERIAL PORT CONFIGURATION (CHANNEL 1 ONLY)
1 2 3 4 5 6 7 8
OPEN
NUMBER OF DATA BITS (OFF = 7, ON = 8)
NUMBER OF STOP BITS (OFF = 1, ON = 2)
PARITY TYPE (OFF = ODD, ON = EVEN)
PARITY ENABLE (OFF = NO PARITY, ON = PARITY ENABLED)
BAUD RATE BIT 2 (MSB) 0 = 1200
BAUD RATE BIT 1 1 = 2400
BAUD RATE BIT 0 (LSB) 2 = 9600
3 = 19200
1 2 3 4 5 6 7 8
OPEN
OPEN
CLOSED
CLOSED OPEN = OFF
OPEN CLOSED = ON
CLOSED
CLOSED
OPEN C1888
VIII-1 95-8470
7 — Data bits. Table VIII–1—Baud Rate Selection - Switches S6-1, S6-2, S6-3
NOTE
Serial port 2 is fixed at 9600 baud, one stop bit and
even parity.
Table VIII–2—Gateway Address Switch Settings
S7 — Port 1: Modbus/Allen Bradley Address
Gateway Address S8-1 S8-2
Set switches to match the
1 Op Op
required slave address. “0” is
not a valid address. Refer to 2 Cl Op
“Address Switch Settings” in
3 Op Cl
the Appendix.
4 Cl Cl
S8 — Network Configuration T0023A
Op = Open
1 and 2 — Gateway LON/SLC address. Cl = Closed
See Table VIII-2. Gateway
address 1 is recommended.
3 — Port 1 operation:
Open = Modbus RTU Slave
Closed = Allen Bradley DF1
Slave
4 — Port 2 operation:
Open = Modbus RTU Slave
Closed = Modbus RTU
Master (to PLC)
6 — Relay Operation.
Open = Latching
Closed = Non-latching.
8 — Gateway type.
Open = Reserved
Closed = Main gateway.
VIII-2
LOGIC CONTROLLER LON/SLC DEVICE ADDRESS SWITCH
SETTING
The logic controller contains three 8-position DIP switch
assemblies that are used for: Each individual device on the LON/SLC must be
assigned a unique address. Addresses 1 to 4 are
— Serial port configuration reserved for gateway use. Address 1 is for the main
— Communication parameters gateway. Valid addresses for field devices are from 5 to
— Setting the LON/SLC address. 250. If the address is set to zero or an address above
250, the communication module will ignore the switch
S5 — Hardware Serial Port Configuration setting. Duplicated addresses are not automatically
detected. All modules with the same address will report
Verify that S5 switches are set as follows: on that address. The status word will show the latest
update, which could be from any of the reporting
1 — Closed modules at that address.
2 — Open
NOTE
3 — Open Logic controllers utilize two consecutive LON/SLC
4 — Closed addresses, the first of which must be an odd
5 — Open number, i. e. a Logic Controller with an address of
7 will occupy both 7 and 8 on the LON/SLC.
6 — Open
7 — Closed Selection of the node address for field devices is
8 — Open. accomplished by setting rocker switches on a DIP
switch assembly. (Note that only the first eight of the 12
S6 — Diagnostic Serial Port Configuration switches are used for selecting the address.) The
address number is binary encoded with rocker switch
Diagnostic serial port is No. 1 on the 8 position switch assembly being the LSB
intended for factory use only. (least significant bit). Each rocker switch has a specific
Switch settings will not affect binary value, as shown in Figure VIII-3. The node
normal operation. address is equal to the added value of all closed rocker
switches. All open switches are ignored. For example:
S7 — LON/SLC Address for node No. 5, close rocker switches 1 and 3 (binary
values 1 + 4); for node No. 25, close rocker switches 1,
Set switches for the LON/SLC 4 and 5 (binary values 1 + 8 + 16).
address. Valid addresses are
from 5 to 247, and must be an Power must be cycled before the new address will take
odd number. If an address effect.
outside this range is selected,
the address will default to 5. For your convenience in setting the address switches,
S7-1 = LSB, S7-8 = MSB. refer to the table “Address Switch Settings” at the back
of this manual.
OPEN OPEN
Determine the type of LCU being used (Refer to the
}
BINARY
label on the LCU mounting cage.) Set SW1 as follows: VALUE 1 2 4 8 16 32 64 128
LEAVE IN
Off — EQ2100LCU OPEN POSITION
VIII-3 95-8470
Section IX The last device requires an EOL resistor.
System Startup All devices sharing a common RS-485 link must have a
common system power return.
PRE-COMMISSIONING CHECKLIST
GENERAL LIOU
Insulate all shields to prevent shorting to the device Verify correct jumper positions and switch settings.
housing or to any other conductor.
Never disconnect the circuit ground between the LIOU
Place alarm/release output in “Bypass/Isolate” when and the LCU.
servicing devices.
Check signal circuits for correct polarity.
Maintain a log book containing the type and serial
Check for correct installation of EOL resistors.
numbers of devices as well as the location and date of
installation.
Maintain a log of maintenance activities. POWER SUPPLIES AND POWER MONITORS
Observe normal precautions for handling electrostatic
Verify all earth ground connections as specified in the
sensitive devices.
wiring instructions.
Verify correct ac power to supply.
LON
Check power distribution to ensure that all devices are
Rocker switches for each LON device must be set to the receiving power.
desired address prior to power-up.
Check power trouble indicator by introducing a short
Test the loop with no power applied and all and an open.
communication modules removed. DC resistance
should be equal on A and B.
FLAME DETECTORS
Check polarity on A and B (no rolls). COM 1 connects
to COM 2 ; COM 2 connects to COM 1. A connects to
Check for potential false alarm sources.
A and B to B.
Check detector aiming and ensure that mounting
Measure voltage. A to chassis ground measures
brackets are tight.
approximately +7.5 vdc. B to ground measures
approximately –7.5 vdc. Check for objects that can block the detector’s view.
Measure signal (400 mv P-P min.). Detectors can be checked for proper response using
the test described in this manual.
Check fault tolerance by introducing a short and an
open.
DCUs
LCU
Check modules for correct orientation.
Verify correct switch positions. Check for the presence of contaminants or poisoning
agents.
All configuration data must be downloaded to the
device and written to the EPROM after any change is Device should be oriented with the sensor pointing
made. Changes to the logic controller also require down.
downloading via the key switch.
Chassis ground stud must be connected to earth
IDCs
ground.
Check RS-485 connections and polarity. Check for correct installation of EOL resistors.
IX-1 95-8470
ARMs CALIBRATION
Check jumpers. To ensure optimum performance, calibration must be
performed on a regularly scheduled basis. Since each
application is different, the length of time between
SAMs regularly scheduled recalibrations can vary from one
installation to the next. In general, the more frequently a
Check signal circuits for correct polarity. system is checked, the greater the reliability.
Check for correct installation of EOL resistors.
IMPORTANT
Check jumpers. 4 to 20 ma devices not manufactured by Det-
Tronics must be pre-calibrated. To ensure
adequate protection, calibration must be performed
on a regularly scheduled basis.
IX-2
13. The calibration is complete. The calibrate LED
turns off.
11
12
13
10
14
Sensor Replacement
9
8
7
SW1
6
5
WARNING
4
3
MAGNETIC REED SWITCH * The hazardous area must be de-classified prior to
2
1
removing a junction box cover with power applied.
Figure IX–1—DCU Terminal Wiring Board Mounted 3. Replace the sensor and apply the zero input (4 ma).
in Six-Port Junction Box
4. Activate the reed switch. The red LED blinks at a 2
Hz rate for 3 seconds while the reed switch is
4. Activate the reed switch. The red LED will blink at a closed.
2 Hz rate for 3 seconds while the reed switch is
closed. 5. The communication module records the
uncalibrated value in position one of the calibration
5. After the reed switch has been closed for 3 log and calibrates the zero value. The calibrate
seconds, the communication module records the LED goes on steady.
uncalibrated value in the calibration log and
calibrates the zero value. The calibrate LED goes 6. Apply the calibration gas.
on steady.
7. The calibrate LED blinks at a 1 Hz rate when the
6. Apply the calibration gas. input increases.
7. The calibrate LED blinks at a 1 Hz rate when the 8. Activate the reed switch. The red LED blinks at a 2
input increases. Hz rate for 3 seconds while the reed switch is
closed.
8. Activate the reed switch. The red LED blinks at a 2
Hz rate while the reed switch is closed. 9. The communication module records the
uncalibrated value in the first register of the
9. The communication module records the calibration log and calibrates the span value.
uncalibrated value in the calibration log and
calibrates the span value after the reed switch is on 10. The calibrate LED goes on steady.
for 3 seconds.
11. Remove the span gas and return the analog input to
10. The calibrate LED goes on steady. normal.
11. Remove the span gas and return the analog input to 12. Activate the reed switch. The red LED blinks at a 2
normal. Hz rate for 3 seconds while the reed switch is
closed.
12. Activate the reed switch. The red LED blinks at a 2
Hz rate for 3 seconds while the reed switch is 13. The calibration is complete. The calibrate LED
closed. turns off.
IX-3 95-8470
Pressing the sensor replacement switch aborts the Sensor Replacement — Combustible Gas
calibration and starts over. Resetting the
communication module will abort sensor replacement. NOTE
When replacing a sensor, compare part numbers
to be sure that the correct replacement sensor is
CALIBRATION ALGORITHM C being used.
FOR COMBUSTIBLE GAS DCUs AND
WARNING
AUTOMATIC CALIBRATION OF UNIVERSAL DCUs
The hazardous area must be de-classified prior to
removing a junction box cover with power applied.
NOTE
After exposure of the H 2 S sensor to high
1. Remove the cover from the DCU enclosure.
concentrations of gas, it is recommended that it be
exposed to fresh air for at least 30 minutes and
2. Press the sensor replacement switch on the
then re-calibrated.
communication module for about 1 second. The
calibrate LED on the communication module blinks
Routine Calibration
at a 1 Hz rate, indicating that it is ready for the zero
input.
1. Apply the zero gas.
NOTE
2. Activate the reed switch for at least 4 seconds. The
Pressing the sensor replacement switch prevents
red LED blinks at a 2 Hz rate for 3 seconds while
the communication module from generating a fault
the reed switch is activated.
signal when the input drops to zero due to
removing the sensor. In addition, the calibration
3. The calibrate LED on the communication module
will not be aborted if the calibration procedure is
blinks at a 1 Hz rate, indicating it is ready for the
not completed within 12 minutes.
zero input.
3. Place the calibration switch on the transmitter board
4. Wait until the calibrate LED goes on steady
in the “calibrate” position.
(approximately 4 seconds). The communication
module records the uncalibrated value in the
4. Replace the sensor.
calibration log and calibrates the zero value during
this time.
5. Connect a volt meter to the test points on the
transmitter board. Connect the “+” lead to TP1
5. Apply the calibration gas. The calibrate LED blinks
(red). Connect the “–” lead to TP2 (black).
at a 1 Hz rate when the sensor detects gas.
6. Wait at least 5 minutes for the sensor output to
6. When the sensor input has been stable for 30
stabilize, then adjust R2 for a reading of 0.40 vdc (4
seconds, the communication module records the
ma) on the meter.
uncalibrated value in the calibration log and
calibrates the span value.
NOTE
Do not make adjustments to R1 when calibrating
7. The calibrate LED goes on steady.
the sensor.
8. Remove the calibration gas.
7. Place the calibrate switch on the transmitter board
in the “normal” position.
9. The communication module waits until the sensor
input drops below 4% full scale.
8. Activate the reed switch for 4 seconds. The red
LED blinks at a 2 Hz rate for 3 seconds while the
10. The calibration is complete. The calibrate LED
reed switch is activated. The communication
turns off.
module records the uncalibrated value in position
one of the calibration log and calibrates the zero
NOTE
value. The calibrate LED goes on steady.
If the calibration is not completed within 12
minutes, the calibration will be aborted and the
9. Place the calibration switch on the transmitter board
detector will revert back to the previous calibration
in the “calibrate” position.
values. The red LED will blink at a 4 Hz rate. The
calibration will be logged as aborted.
IX-4
10. Apply the calibration gas and wait for the output to 3. Replace the sensor.
stabilize.
4. Wait at least 5 minutes for the sensor output to
11. With 50% LFL calibration gas applied to the sensor, stabilize.
adjust R3 for a reading of 1.2 vdc (12 ma) on the
meter. 5. Activate the reed switch. The red LED blinks at a 2
Hz rate for 3 seconds while the reed switch is
12. Place the calibrate switch on the transmitter board activated. The communication module records the
in the “normal” position. The red LED blinks at a 1 uncalibrated value in position one of the calibration
Hz rate. log and calibrates the zero value. The calibrate
LED goes on steady.
13. Activate the reed switch. The red LED blinks at a 2
Hz rate for 3 seconds while the reed switch is 6. Apply the calibration gas. The calibrate LED blinks
activated. at a 1 Hz rate when the input increases.
14. The communication module records the 7. Activate the reed switch. The red LED blinks at a 2
uncalibrated value in the first register of the Hz rate for 3 seconds while the reed switch is
calibration log and calibrates the span value. The activated.
calibrate LED goes on steady.
8. The communication module records the
15. Remove the calibration gas and place the cover uncalibrated value in the first register of the
back on the DCU enclosure. calibration log and calibrates the span value. The
calibrate LED goes on steady.
16. The communication module waits until the analog
value drops below 4% full scale. The calibration is 9. Remove the calibration gas and place the cover
complete. The calibrate LED turns off. back on the DCU enclosure.
Pressing the sensor replacement switch aborts the 10. The communication module waits until the analog
calibration and starts over. value drops below 4% full scale. The calibration is
complete. The calibrate LED turns off.
Sensor Replacement — Toxic Gas
Pressing the sensor replacement switch aborts the
NOTE calibration and starts over.
When replacing a sensor, compare part numbers
to be sure that the correct replacement sensor is
being used. CALIBRATION ALGORITHM D
FOR UNIVERSAL DCUs WITH O2 SENSOR
WARNING
The hazardous area must be de-classified prior to Normal Calibration
removing a junction box cover with power applied.
1. Apply clean air (20.9% oxygen).
1. Remove the cover from the DCU enclosure.
2. Activate the reed switch for at least 4 seconds. The
2. Press the sensor replacement switch on the red LED blinks at a 2 Hz rate for 3 seconds while
communication module for about 1 second. The the reed switch is closed.
calibrate LED on the communication module blinks
at a 1 Hz rate, indicating that it is ready for the zero 3. The calibrate LED blinks at a 1 Hz rate, indicating
input. that calibration has begun.
IX-5 95-8470
7. The communication module waits 3 seconds. CALIBRATION ALGORITHM G
FOR DCUs WITH POINTWATCH
8. The calibration is complete. The calibrate LED
turns off. Routine Calibration
1. Open the junction box cover and press the sensor 3. The calibrate LED on the communication module
replacement switch. blinks at a 1 Hz rate, indicating it is ready for the
zero input.
2. The calibrate LED on the communication module
blinks at a 1 Hz rate, indicating that it is ready for 4. When a steady zero reading is obtained, the
the zero input. communication module records the uncalibrated
value in the calibration log and calibrates the zero
3. Replace the sensor and set the sensor switch value during this time. The LED turns on steady.
(located on the sensor cell) to zero.
5. Apply the calibration gas. The calibrate LED blinks
4. Activate the reed switch. The red LED blinks at a 2 at a 1 Hz rate when the sensor detects gas.
Hz rate for 3 seconds while the reed switch is
closed. 6. When the sensor input has been stable for 30
seconds, the communication module records the
5. The communication module records the uncalibrated value in the calibration log and
uncalibrated value in position one of the calibration calibrates the span value.
log and calibrates the zero value. The calibrate
LED is on steady. 7. The calibrate LED goes on steady.
6. Set the zero switch on the sensor to normal. Apply 8. Remove the calibration gas.
clean air (20.9% oxygen) to set the sensor analog
span value. 9. The communication module waits until the sensor
input drops below 4% full scale.
7. The calibrate LED blinks at a 1 Hz rate when the
input goes high. 10. The calibration is complete. The calibrate LED
turns off.
8. Activate the reed switch. The red LED blinks at a 2
Hz rate for 3 seconds while the reed switch is NOTE
closed. If the calibration is not completed within 12
minutes, the calibration will be aborted and the
9. The communication module records the detector will revert back to the previous calibration
uncalibrated value in the first register of the values. The red LED will blink at a 4 Hz rate. The
calibration log and calibrates the span value. calibration will be logged as aborted.
IX-6
NOTE FALSE ALARM TEST
Pressing the sensor replacement switch prevents
the communication module from generating a fault 1. Disable all alarm response equipment.
signal when the input drops to zero. In addition,
the calibration will not be aborted if the calibration 2. Allow the system to monitor the protected area for a
procedure is not completed within 12 minutes. period of time with all the normal operations in the
area taking place. If the detector responds
2. Apply zero gas. (indicating a fire when no fire has occurred), check
the area to see if UV sources are present. If
3. The calibrate LED on the communication module possible, remove the sources, or reposition the
blinks at a 1 Hz rate, indicating that it is ready for detectors so that the sources fall outside of the
the zero input. detector’s cone of vision. If problems still occur,
adjust the time delay, sensitivity or arc rejection
4. Continue from step 4 of the PointWatch routine settings.
calibration procedure described above.
The model U7656 Hand-Held UV Monitor is
available from Detector Electronics for conveniently
scanning the protected area and pin-pointing the
UV DETECTOR TEST exact source of UV radiation.
CAUTION
3. Recycle power and test again as described above.
To prevent unwanted actuation, alarm and
extinguishing devices must be disconnected prior
4. Once the correct settings are obtained, turn on all
to performing detection system tests.
alarm and extinguishing equipment that is
connected to the system. Record all switch settings
for future reference.
FIRE ALARM TEST
IX-7 95-8470
If a fire signal was not generated and the LEDs indicate IR Fault
response by neither sensor, both sensors have failed to
respond. To correct an IR oi fault, clean the viewing window and
— Check input power and external wiring. oi ring of the IR sensor, and also check the module and
— Check the cleanliness of both viewing windows. oi ring opening for proper orientation. If the fault does
— If the detector still does not respond: not clear (fault reoccurs), a faulty sensor or electrical
— If using a test lamp, check the battery, window, etc. problem is indicated. Check the connection of the
to be sure that the test lamp is working properly. connector plug on the IR module. Also check the
— If the detector still does not respond, replace the condition of the wires. Repair or replace if needed. If
detector. the problem persists, replace the IR sensor module. If
the problem still persists, replace the detector.
MANUAL oi
General Fault
When manual oi is selected, the automatically initiated
oi test is disabled. If a general fault is indicated, check input power to the
detector as well as continuity of system wiring. Also
Regardless of the o i selection, internal diagnostic check the detector viewing windows for contamination
circuitry will respond to failures such as a loss of input such as paint overspray, snow, etc. that could
power or to certain electronic failures. These failures simultaneously affect both sensors. Since simultaneous
will be indicated at the LCU and also by the detector’s failure of both sensor modules is unlikely, the problem is
LEDs. If such a failure occurs, check the operation of most likely caused by loss of input power or failure of
the power source and the continuity of the detector the detector’s electronic circuitry.
wiring. If the detector appears to be “dead” with power
applied, it must be returned to the factory for repair. Background Radiation
IX-8
Section X I/O PORTS—
The LCU provides two electrically isolated RS-232 serial
Specifications ports, port “1” and port “2,” both of which can be active
simultaneously. Port “1” can be configured as either a
CERTIFICATIONS Modbus RTU slave, or an Allen Bradley DF1 slave. Port
FMRC Approval – See Appendix A. “2” can be either a Modbus RTU slave or master.
CSA Certification – See Appendix B.
CENELEC and CE Mark – See Appendix C.
Two 78.5 kb LON/SLC ports provide the start and end of
EQ2100LCU LOCAL CONTROL UNIT the communication loop for the detection devices. The
wiring is transformer coupled to protect the
INPUT VOLTAGE— transceivers. The LON/SLC is monitored for ground
18 to 30 vdc. 10% overvoltage will not cause damage faults.
to the equipment.
4.00 6.97
(10.2) (17.7)
12.25
(31.1)
6.50
(16.5)
8.68 (22.0)
A1882
X-1 95-8470
TERMINAL
STRIP
REAR
13.2
(33.5)
FRONT
7.0 4.0
(17.7) (10.2) FRONT
19.0
(48.3)
DET-TRONICS
®
DET-TRONICS DET-TRONICS
® ®
POWER
LON INSOLATOR
ALARM
TROUBLE
POWER FAULT GROUND FAULT
SUPERVISORY 100 POWER +
RELAY 1 90
POWER –
80
70
ACKNOWLEGDE
60
RELAY 2
50
40 GROUND FAULT
SILENCE 30 COM 1
RELAY 3 20 COM 2
10
PROGRAM
RELAY 4
ISOLATE
FAULT
RESET
EAGLE QUANTUM™ EAGLE QUANTUM™ EAGLE QUANTUM™
LOGIC CONTROLLER GATEWAY LON ISOLATOR
NORMAL
ACKNOWLEDGE
& SILENCE
ENABLE
RESET
ISOLATE
B2044
SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7 SLOT 8
X-2
EQ2200IDC/IDCGF/IDCSC EQ2200UV and EQ2200UVHT UV
INITIATING DEVICE CIRCUIT FLAME DETECTORS
INPUT VOLTAGE— INPUT VOLTAGE—
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not 24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not
cause damage to the equipment. cause damage to the equipment.
OUTPUTS— EQ2200UVHT
Digital communication, transformer isolated (78.5 kbps). Electronic Module: –40°F to +167°F (–40°C to +75°C).
UV Detector: –40°F to +257°F (–40°C to +125°C).
TEMPERATURE RANGE— Storage: –67°F to +185°F (–55°C to +85°C).
Operating: –40°F to +167°F (–40°C to +75°C).
Storage: –-67°F to +185°F (–55°C to +85°C). HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
HUMIDITY RANGE— condensing humidity for short periods of time.
0 to 95% RH, non-condensing.
SPECTRAL SENSITIVITY RANGE—
VIBRATION— UV radiation over the wavelength of 1850 to 2450
Meets MIL SPEC 810C, method 514.2, curve AW. angstroms (solar blind).
30° 90 30°
80
45° 45°
70
0.32 (0.81) OVAL SLOT MOUNTING
(TYPICAL FOUR PLACES) 60
DETECTION 50
DISTANCE
(PERCENT) 40
30
6.6
(16.8)
20
10
D573
X-3 95-8470
FLAME SENSITIVITY— 5/16-18 UNC
Meets MIL SPEC 810C, method 514.2, curve AW. 120° ±2° (2)
DIMENSIONS—
See Figures X-4A and X–4B for the standard UV
detector. For the high temperature UV detector, see
Figures X-5A and X-5B (UV detector) and Figure X-6
(electronic module).
2.5 (6.4) DIA. A1986 0.25 (0.64) DIA. (3)
5.25 (13.3)
1/2 INCH NPT
4.75 (12.06)
OR 20 MM
2.5 (6.4)
A1987
X-4
COVER LOCKING CLAMPS (BASEEFA)
9 (228.6)
5
(127)
4 2.5
(101.6) (63.5)
4.375
(111.1)
4.66
(11.8)
0.28
(0.71)
3.39
(8.6)
5.20 2.69
(13.21) (6.83)
6.62
(16.8)
1.28
(3.25)
A1887
X-5 95-8470
EQ2200UVIR UV/IR DETECTOR 100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A GIVEN FIRE.
THE SENSITIVITY INCREASES AS THE ANGLE OF INCIDENCE DECREASES.
0°
INPUT VOLTAGE— 15°
100
15°
DETECTION 50
TEMPERATURE RANGE— DISTANCE
(PERCENT) 40
Operating: –40°F to +167°F (–40°C to +75°C).
Storage: –40°F to +185°F (–40°C to +85°C). 30
20
HUMIDITY RANGE— 10
0 to 95% RH. Can withstand 100% condensing
D573
humidity for short periods of time.
Figure X–8—Cone of Vision of UV/IR Detector
SPECTRAL SENSITIVITY RANGE—
UV: 0.185 to 0.245 microns (solar blind).
IR: 4.45 microns (solar blind).
Figure X-7 illustrates the spectral response range of the RESPONSE TIME—
UV and IR sensors. Selectable for a 0 to 7 second time delay. Fastest
response time is 0.5 second.
CONE OF VISION—
90 degree cone of vision using gasoline fuel (1 sq. ft). OUTPUTS—
80 degree cone of vision using methane fuel (30 inch). Digital communication, transformer isolated (78.5 k
See Figure X-8. bps).
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.5 2.0 3.0 4.0 5.0
WAVELENGTH (MICRONS)
X-6
Table X–1—UV/IR Detector Maximum Response Distances in Feet
UV Standard Low 40 30 15
Medium 60 45 20
High 80 65 35
Very High 100 100 55
IR Low 40 65 40
Medium 55 75 45
High 65 90 55
Very High 90 100 60
X-7 95-8470
JUNCTION BOX MOUNTING
BRACKET (ATTACHES
WITH TWO ENCLOSED
FLATHEAD SCREWS)
5-1/4 INCHES
(133 MM)
MOUNTING BASE
2-1/2 INCHES
(64 MM) B1303
120° ± 2° (2)
2.5 DIA.
(64 MM)
7.81
(198 MM)
5.25
(133 MM)
X-8
EQ2200DCU AND EQ2200DCUEX EQ2500ARM AGENT RELEASE
DIGITAL COMMUNICATION UNIT MODULE
INPUT VOLTAGE— RELEASE OUTPUT RATING—
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not 2 amperes at 30 vdc maximum.
cause damage to the equipment.
SUPERVISORY CURRENT—
POWER CONSUMPTION— 2.0 ma, ±1.0 ma each circuit.
DCU with toxic gas sensor/transmitter:
95 ma maximum. INPUT VOLTAGE—
24 vdc nominal.
DCU with transmitter and combustible gas sensor:
180 ma maximum during normal operation, 500 ma INPUT CURRENT—
during startup. Standby: 75 ma maximum at 24 vdc.
Alarm: 120 ma maximum at 24 vdc.
INPUTS—
4 to 20 ma analog signal. STATUS OUTPUTS—
Non-intrusive calibration. Digital communication, transformer isolated (78.5 kbps).
VIBRATION— DIMENSIONS—
Meets MIL SPEC 810C, method 514.2, curve AW. See Figure X-2.
DIMENSIONS—
See Figure X-2.
X-9 95-8470
EQ2500SAM SIGNAL AUDIBLE EQ2400NE NETWORK EXTENDER
MODULE
INPUT VOLTAGE—
OUTPUT RATING— 18 to 30 Vdc.
2 amperes at 30 vdc maximum.
POWER CONSUMPTION—
RESPONSE TIME— 2.2 watts nominal at 24 vdc, 2.7 watts maximum.
Output relay actuates in <0.1 second after
acknowledging an alarm command message. INPUTS/OUTPUTS—
Digital, transformer isolated (78.5k Baud).
SUPERVISORY CURRENT—
3.0 ma ± 2.0ma, each circuit. TEMPERATURE RANGE—
Operating: -40°F to +167°F (-40°C to +75°C)
EOL RESISTORS — Storage: -67°F to +185°F (-55°C to +85°C).
10 kohm ± 2 kohm. Each circuit must have an EOL
resistor. HUMIDITY—
5 to 95% RH at 70°C.
INPUT VOLTAGE—
24 vdc nominal. DIMENSIONS—
See Figure X-11.
INPUT CURRENT (Excluding Output Current)—
Standby: 60 ma maximum at 24 vdc. 0.28 4.66
(0.71) (11.8)
Alarm: 120 ma maximum at 24 vdc.
3.39
(8.6)
STATUS OUTPUT—
Digital communication, transformer isolated (78.5 kbps).
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage: –67°F to +185°F (–55°C to +85°C).
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
5.20 2.69
(13.21) (6.83)
VIBRATION—
Meets MIL SPEC 810C, method 514.2, curve AW.
DIMENSIONS—
See Figure X-2.
3.7
(9.4)
1.28
(3.25)
A1883
X-10
EQ2100PSM POWER SUPPLY EQ2110PS, EQ2130PS AND
MONITOR EQ2175PS POWER SUPPLIES
INPUT VOLTAGE— INPUT VOLTAGE—
24 vdc nominal, 18 to 30 Vdc. Selectable for 120, 208 or 240 vac input power, ±10%.
INPUT CURRENT—
MEASUREMENT RANGE—
EQ2110PS: 4 amps at 120 VAC (60 Hz)
AC Voltage: 240 vac maximum.
EQ2130PS: 11 / 6 / 6 amps at 120 / 208 / 240 VAC*
DC Battery Charging Current: 75 amperes maximum.
EQ2175PS: 24 / 15 / 12 amps at 120 / 208 / 240 VAC*.
*Specify 50 Hz or 60 Hz.
OUTPUT—
Digital communication, transformer isolated (78.5 k
OUTPUT CURRENT—
bps).
EQ2110PS: 10 amperes at 24 VDC
EQ2130PS: 30 amperes at 24 VDC
TEMPERATURE RANGE—
EQ2175PS: 75 amperes at 24 VDC.
Operating: +32°F to +122°F (0°C to +50°C)
Storage: -67°F to +185°F (-55°C to +85°C).
POWER CONSUMPTION—
EQ2110PS: 46 Watts
HUMIDITY RANGE—
EQ2130PS: 140 Watts
5 to 95% RH, non-condensing.
EQ2175PS: 349 Watts.
DIMENSIONS—
TEMPERATURE RANGE—
See Figure X-12.
Operating: +32°F to +122°F (0°C to +50°C)
Storage: -40°F to +185°F (-40°C to +85°C).
9
HUMIDITY RANGE—
(22.9) 5 to 95% RH, non-condensing.
8.5
(21.6) DIMENSIONS—
in Inches (Centimeters)
J3
2.25 Width Height Depth
J1 (5.7)
4
EQ2110PS: 19 (48.3) 7 (17.8) 15 (38.1)
(10.2) EQ2130PS: 19 (48.3) 14 (35.6) 15 (38.1)
EQ2175PS: 19 (48.3) 14 (35.6) 15 (38.1)
B C
NOTE
Power supplies are designed for mounting in a
standard 19 inch rack. Optional mounting hardware
2.5 is available for floor or wall mount applications.
(6.4)
A2038
X-11 95-8470
LIOU (Local Output Unit) LIOU RELEASE MODULE
INPUT VOLTAGE— RELEASE OUTPUT RATING—
24 vdc nominal. 2 amperes at 24 vdc.
12.0 6.0
(30.5) (15.2)
14.25 13.6
(36.2) (34.6)
16.0
(40.6)
A1695
X-12
COMBUSTIBLE GAS SENSOR
Refer to the Combustible Gas Sensor Specification Data
sheet, form 90-1041, for specifications.
ELECTROCHEMICAL SENSORS
Refer to the Electrochemical Gas Sensor Specification
Data sheet, form 90-1079, for specifications.
Electrochemical sensors available from Det-Tronics
include Hydrogen Sulfide, Oxygen, Carbon Monoxide,
Chlorine, Sulfur Dioxide, and Nitrogen Dioxide.
POINTWATCH
Refer to the PointWatch manual, form 95-8440, for
PointWatch specifications.
X-13 95-8470
Section XI FLAME DETECTOR MAINTENANCE
System Maintenance The flame detector requires no periodic calibration.
However, to maintain maximum sensitivity, the viewing
ROUTINE MAINTENANCE window must be kept clean at all times.
To ensure reliable protection, it is important to check
To clean the optical surfaces, remove the oi ring from
and calibrate the system on a regularly scheduled
the detector by gently squeezing the tabs together and
basis. The frequency of these checks is determined by
then pulling out. Clean the viewing window and the
the requirements of the particular installation.
back side of the oi ring using a clean cloth or tissue
and Det-Tronics window cleaning solution. Avoid the
MANUAL CHECK OF OUTPUT DEVICES
use of commercial glass cleaners, since many of them
can leave a UV absorbing residue on the surface.
It is important that response devices be checked initially
Avoid leaving fingerprints on the reflective surface of the
when the system is installed, as well as periodically
o i ring. Re-install the ring so that the opening is
during the on-going maintenance program.
positioned downward.
CAUTION
NOTE
Be sure to secure all output devices that are
If corrosive contaminants in the atmosphere cause
actuated by the system to prevent unwanted
the reflective rings to deteriorate to the extent that
activation of this equipment, and remember to
it is no longer possible to restore them to their
place these same output devices back into service
original condition, they must be replaced.
when the checkout is complete.
To ensure the watertight integrity of the detector, the O-
O-RING MAINTENANCE
rings must be maintained following the guidelines
described above.
WARNING
The hazardous area must be de-classified prior to
GAS SENSOR MAINTENANCE
removing a junction box cover with power applied.
All gas sensors must be calibrated on a regularly
A rubber O-ring is used to ensure that the junction box
scheduled basis, typically every 90 days for catalytic
cover will seal tightly and provide protection against
and electrochemical sensors and annually for
water ingress. Periodically the enclosure should be
PointWatch.
opened and the O-ring should be inspected for breaks,
cracks and dryness. To test the ring, remove it from the
Catalytic sensors have a finite lifespan. If a successful
enclosure and stretch it slightly. If cracks are visible, it
calibration cannot be performed, replace the sensor
should be replaced. If it feels dry, a thin coating of
and recalibrate following the procedure described in the
lubricant should be applied. When re-installing the ring,
“Calibration” section. Exposure of the sensor to high
be sure that it is properly seated in the groove on the
concentrations of combustible gases for extended
housing. It is imperative that this O-ring be properly
periods of time can introduce stress to the sensing
installed and in good condition. Failure to properly
element and seriously affect its performance. After
maintain it can allow water to enter the enclosure and
exposure to a high concentration of combustible gas,
cause premature failure. A coating of lubricant should
recalibration should be performed and, if necessary, the
also be applied to the threads on the cover before re-
sensor should be replaced.
assembling the enclosure. This will both lubricate the
threads and help to prevent moisture from entering the
Electrochemical sensors have a finite lifespan. If a
enclosure.
successful calibration cannot be performed, inspect the
hydrophobic filter. If the filter is plugged, replace it and
CAUTION
recalibrate the sensor. If the filter is in good condition,
The O-rings should be lubricated with a silicone
replace the sensor. Recalibrate following the procedure
free grease. The use of other lubricants is not
described in the “Calibration” section.
recommended, since they can adversely affect the
performance of some sensors. Under no
If the PointWatch fails calibration, refer to the
circumstances should a lubricant or compound
PointWatch manual.
containing silicone be used on systems using
catalytic type combustible gas sensors.
NOTE
Compare part numbers to be sure that the correct
replacement sensor is being used.
XI-1 95-8470
BATTERIES for proper wiring, programming and calibration. If it is
determined that the problem is caused by an electronic
Batteries must be replaced every 48 months, or sooner
defect, the device must be returned to the factory for
if required by local codes. Only sealed batteries are to
repair.
be used.
NOTE
TROUBLESHOOTING When replacing a device, be sure that the rocker
Table XI-1 is intended to serve as an aid in locating the switches on the replacement are set the same as
cause of a system malfunction. If the problem cannot the original. Remove power before removing or
be corrected, contact the factory for assistance. plugging in the replacement unit. When a DCU,
IDC or flame detector is replaced, the point must
REPLACEMENT PARTS be re-configured. If the auto-configure feature is
enabled, configuration is done automatically.
Eagle devices are not designed to be repaired in the
field. If a problem should develop, first carefully check
T0025B
XI-2
DEVICE REPAIR AND RETURN Table XI-2—Combustible Gas Sensors
T0043A
ORDERING INFORMATION
POWER SUPPLIES
When ordering, please specify:
Part Number Description
LCU 006979-001 EQ2100PSM Power Supply Monitor
000604-013 EQ2110PS Power Supply (10 amps)
Part Number Description 000604-014 EQ2130PS Power Supply (30 amps)
006814-001 EQ2100LCU Local Control Unit for 000604-015 EQ2175PS Power Supply (75 amps)
use with EQ21XXPS Series Power
Supplies. COMBUSTIBLE GAS SENSORS
LCU Replacement Parts:
006570-001 EQ2100CG Communication Gateway See Table XI-2.
006566-001 EQ2100LC Logic Controller
006558-001 EQ2100IM Isolation Module H2S SENSOR
006668-001 EQ2100MR Mounting Rack
Part Number Description
LIOU 004539-009 Explosion-Proof H2S Sensor Housing
005434-001 Electrochemical H2S Sensing
Part Number Description Element Assembly
006641-xxx EQ2100LIOU Local Input/Output Unit
102844-001 Relay Module Other toxic gas sensors available. Consult the factory.
102843-001 Release Module
102842-001 Signal Audible Module ACCESSORIES
XI-3 95-8470
CALIBRATION KITS — COMBUSTIBLE GAS Accessories and Replacement Parts
227115-001 H 2 S Calibration Kit (for electro- 006861-xxx EQ22XXUVIR UV/IR Flame Detector
chemical sensors only) includes
regulator, hose, calibration cup, and Accessories and Replacement Parts
two cylinders of calibration gas.
Part Number Description
REPLACEMENT PARTS — H2S 004404-001 Q9001G Swivel Mount Assembly
004273-002 Q1113 Air Shield Assembly (two per
Part Number Description detector)
005434-001 Electrochemical Sensing Element 004000-003 W867 Explosion-proof UV/IR Test
Assembly for H2S Sensor Lamp
004532-002 Hydrophobic Filter for H2S Sensor 002519-001 oi ring for UV detector
107427-034 O-ring (for Hydrophobic Filter) 003525-001 oi ring for IR detector
107427-004 O-ring (for Sensor Housing) 107427-004 O-rings for UV and IR detectors (two
227117-001 Gas Bottle for 227115-001 Calibration O-rings per detector)
Kit - 50 ppm DE1888B2 UV sensor module with LEDs
DE5600-002 IR module with LEDs (standard
UV DETECTOR sensitivity)
001680-001 Window Cleaner (six bottles)
006600-xxx EQ22XXUV UV Flame Detector 003996-001 UV/IR Window Maintenance Kit,
consisting of 2 bottles of
cleaner, 4 UV rings, 4 IR rings
102868-001 Silicone Free Grease
XI-4
APPENDIX A
APPROVAL DESCRIPTION
The Eagle Quantum Fire and Gas Detection/Releasing System (reference Figure A1) has the following FMRC
approved configurations:
• Nonincendive for Class I, Division 2, Groups A, B, C, and D; temperature code T4A Hazardous (Classified)
Locations per FM 3611.
• Operating Temperature Limits 0°C to +60°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.
• Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheres per FM 6320.
• H2S Toxic Gas Performance verified 0 to 20, 50 or 100 ppm per FMRC requirements.
NOTE
FMRC Approval allows the presence and operation of serial communications software in the LCU Gateway
(MODBUS or Allen Bradley protocols, etc.), however, the communications functions are not included in the
Approval.
A-1 95-8470
MODEL EQ2100LIOU LOCAL INPUT/OUTPUT UNIT
Manufacturer Model
Skinner LV2LBX25
ASCO 8210A107
ASCO 8210G207
Skinner 73218BN4UNLVNOC111C2
Skinner 73212BN4TNLVNOC322C2
Skinner 71395SN2ENJ1NOH111C2
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM
3615.
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous (Classified) Locations per FM 3611.
• EQ22EMIDC and EQ22EMIDCGF non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A
Hazardous (Classified) Locations per FM 3611.
• Enclosure Rating NEMA Type 4X per ANSI/NEMA 250.
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.
• The Model EQ2200IDC Series must be used in conjunction with any FMRC Approved device providing relay
contact closure.
A-2
MODEL EQ2200UV & EQ2200UVHT with C7050B SERIES UV FLAME DETECTORS
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM
3615.
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous (Classified) Locations per FM 3611.
• Enclosure Rating NEMA Type 4X per ANSI/NEMA 250.
• Operating Temperature Limits –40°C to +75°C for EQ2200UV and EQ2200UVHT; -40°C to +125°C for C7050B.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.
• Automatic Fire Alarm Signaling Performance verified per FM 3260. A Model EQ2200UV with B2 Module was
verified to comply with the following performance criteria:
Response Characteristics
Response Time
Field of View
A-3 95-8470
UV Arc Rejection
Mounting
Q9001L swivel mount for EQ2200UV; Q9001B swivel mount for C7050B.
• Explosionproof for Class I, Division 1, Groups B, C, & D Hazardous (Classified) Locations per FM 3615.
• Dust-ignitionproof for Class II, Division 1, Groups E, F, & G, Class III Hazardous (Classified) Locations per FM
3615.
• Non-incendive for Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups F and G; Class III;
Temperature Code T4A Hazardous (Classified) Locations per FM 3611.
• Enclosure Rating NEMA Type 4X per ANSI/NEMA 250.
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.
• Automatic Fire Alarm Signaling Performance verified per FM 3260. A Model EQ2200UVIR with UV Module
DE1888B2 and IR Module DE5600-002 was verified to comply with the following performance criteria:
A-4
Response Characteristics
Gasoline 1 Sq. Ft. 100 Ft. Very High (Standard) Very High
Gasoline 1 Sq. Ft. 80 Ft. Very High (Arc Rej.) Very High
Response Time
Field of View
–45° to +45° off centerline in vertical and horizontal planes using gasoline fuel (1 sq. ft.).
–40° to +40° off centerline in vertical and horizontal planes using methane fuel (30 inch).
A-5 95-8470
False Alarm Immunity
• Direct sunlight
• A 150 watt incandescent light at 2 feet (0.6 m)
• Two 60 watt fluorescent bulbs at 2 feet (0.6 m)
• A 500 watt halogen lamp at 4 feet (1.2 m)
• The radiation produced by a Miller Dial-Arc 250-P arcwelder at 10 feet (3m), set at 50 amperes with 1/8 inch Type
601 welding rod.
• Vibration immunity for vertical displacement of 0.02 inch (0.5 mm) at a frequency of 10 to 30 Hz for 4 hours.
• Radio frequency interference (RFI) immunity at 12 inches to 155 MHz and 450 MHz with radiation power levels of
5.0 watts.
Mounting
• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM
3615 (For use with Sensor Separation Kit).
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous (Classified) Locations
per FM 3611.
• Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous (Classified)
Locations per FM 3611. (For use with sensor separation kit.)
• EQ22EMDCU non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous
(Classified) Locations per FM 3611.
• Enclosure Rating NEMA Type 4X per ANSI/NEMA 250 (For use with Sensor Separation Kit).
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Combustible gas performance verified with any FMRC Approved stand alone linear 4 to 20 mA device per FM
6310/6320. Accuracy: ±3% LFL from 0 to 50% LFL, ±5% LFL from 51% to 100% LFL.
• Toxic gas performance verified 0 to 100 ppm per FMRC requirements. Accuracy: ±2 ppm from 0 to 20 ppm,
±10% of concentration from 21 to 100 ppm. Models C7064E4012 and C7064E5012 Hydrogen Sulfide (H2S)
Sensors Explosion-proof for Class I, Div. 1, Groups C and D Hazardous (Classified) Locations per FM 3615. Model
C7064E5014 Hydrogen Sulfide (H2S) Sensors Explosion-proof for Class I, Div. 1, Groups B, C and D Hazardous
(Classified) Locations per FM 3615. Operating temperature limits are –40°C to +40°C.
A-6
NOTE
Sensor cross sensitivity has not been verified by FMRC.
NOTE
FMRC Approval of the 4 to 20 ma input does not include or imply approval of the gas detection apparatus such
as sensors, transmitters, or devices connected to the system. In order to maintain FMRC Approval of the
system, all 4 to 20 ma gas detection instruments connected to the input must also be FMRC Approved.
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM
3615. (For use with Sensor Separation Kit)
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous (Classified) Locations
per FM 3611.
• Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous (Classified)
Locations per FM 3611. (For use with sensor separation kit.)
• EQ22EMDCUEX non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous
(Classified) Locations per FM 3611.
• Enclosure Rating NEMA Type 4X per ANSI/NEMA 250 (For use with Sensor Separation Kit).
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Performance verified for 0 to 100% LFL methane-in-air atmospheres per FM 6310/6320. Accuracy: ±3% LFL from
0 to 50% LFL, ±5% LFL from 51% to 100% LFL.
NOTE
The high temperature characteristic has NOT been FMRC verified above 75°C.
NOTE
Detector Electronics combustible gas detection K factors are not FMRC verified.
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
NOTE
Ensure sensor hazardous (classified) location rating is applicable for the intended use.
A-7 95-8470
MODEL EQ2500ARM SERIES AGENT RELEASE MODULE
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II, Div. 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM 3615.
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous (Classified) Locations per FM 3611.
• EQ25EMARM non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous
(Classified) Locations per FM 3611.
• Enclosure Rating NEMA Type 4X per ANSI/NEMA 250.
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.
• Approved for use with the following automatic deluge and pre-action solenoids:
Manufacturer Model
Skinner LV2LBX25
ASCO 8210A107
ASCO 8210G207
Skinner 73218BN4UNLVNOC111C2
Skinner 73212BN4TNLVNOC322C2
Skinner 71395SN2ENJ1NOH111C2
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II, Div. 1, Groups E, F, and G, Class III Hazardous (Classified) Locations per FM 3615.
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous (Classified) Locations per FM 3611.
• EQ25EMSAM non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous
(Classified) Locations per FM 3611.
• Enclosure Rating NEMA Type 4X per ANSI/NEMA 250.
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996.
A-8
MODEL EQ2400NE SERIES NETWORK EXTENDER
• Explosion-proof for Class I, Division 1, Groups B, C, & D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II, Div. 1, Groups E, F, & G, Class III Hazardous (Classified) Locations per FM 3615.
• Non-incendive for Class I, Div. 2, Groups A, B, C and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous (Classified) Locations per FM 3611.
• EQ24EMNE non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous
(Classified) Locations per FM 3611.
• Enclosure Rating NEMA / Type 4X per ANSI/NEMA 250.
• Operating Temperature Limits -40°C to +75°C.
• Storage Temperature Limits -55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• National Fire Alarm Code Performance verified per ANSI/NFPA 72-1996 and gas performance verified per FM
6310/6320.
OPTIONS
• An optional EQ2101LCU with EQ2101MR Mounting Rack is available with provisions for two 24 vdc power inputs.
The customer must supply two reliable and independent 24 vdc supplies in accordance with ANSI/NFPA 72-1996
section 1-5.2. If either of the supplies is missing due to a broken wire, a trouble condition will be annunciated.
• Operator Interface Station (OIS)
NOTE
Metric straight thread types are for use in non-North American applications.
CALIBRATION
• Calibration of the above listed sensors has been FMRC verified using the respective EQ2200DCU and
EQ2200DCUEX Series with the Det-Tronics 225130-001 (50% LFL methane) and 227115-001 H2S Calibration Kits.
• The EQ2200DCU Series can be used with any FMRC Approved 4 to 20 ma device.
A-9 95-8470
A-10
Figure A1
APPENDIX B
APPROVAL DESCRIPTION]
The Eagle Quantum Fire and Gas Detection/Suppression System (reference Figure B1) has the following CSA
approved configurations:
• Class I, Division 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA C22.2 #213.
• Operating Temperature Limits 0°C to +60°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheres per CSA C22.2 #152.
B-1 95-8470
MODEL EQ2200IDC SERIES INITIATING DEVICE CIRCUIT AND
MODEL EQ2200IDCGF SERIES INITIATING DEVICE CIRCUIT GROUND FAULT
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.
• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
• EQ22EMIDC AND EQ22EMIDCGF non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code
T4A Hazardous Locations per CSA C22.2 #213.
• Enclosure Rating Type 4X per CSA C22.2 #94.
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• The Model EQ2200IDC Series must be used in conjunction with any CSA certified device providing relay contact
closure.
• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.
• Dust-ignitionproof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
• Enclosure Rating Type 4X per CSA C22.2 #94.
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Optional Q9001L Swivel Mount.
• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.
• Dust-ignitionproof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
• Enclosure Rating Type 4X per CSA C22.2 #94.
• Operating Temperature Limits –40°C to +75°C for electronic module, –40°C to +125°C for UV detector.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Optional Q9001B Swivel Mount for UV detector.
B-2
MODEL EQ2200UVIR SERIES UV/IR FLAME DETECTOR
• Explosionproof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.
• Dust-ignitionproof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
• Non-incendive for Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups F and G; Class III;
Temperature Code T4A Hazardous Locations per CSA C22.2 #213.
• Enclosure Rating Type 4X per CSA C22.2 #94.
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Optional Q9001G Swivel Mount.
• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.
• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25
(For use with Sensor Separation Kit).
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA
C22.2 #213.
• Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per
CSA C22.2 #213 (For use with sensor separation kit.)
• EQ22EMDCU non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous
Locations per CSA C22.2 #213.
• Enclosure Rating Type 4X per CSA C22.2 #94 (For use with Sensor Separation Kit).
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Combustible gas performance verified with any CSA Certified stand alone linear 4 to 20 mA device per CSA C22.2
#152. Accuracy ±3% LFL from 0 to 50% LFL, ±5% LFL from 51% to 100% LFL.
B-3 95-8470
MODEL EQ2200DCUEX SERIES DIGITAL COMMUNICATION UNIT
WITH MODEL CGS SERIES COMBUSTIBLE GAS SENSOR
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.
• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25
(For use with Sensor Separation Kit).
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA
C22.2 #213.
• Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per
CSA C22.2 #213 (For use with sensor separation kit.)
• EQ22EMDCUEX non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous
Locations per CSA C22.2 #213.
• Enclosure Rating Type 4X per CSA C22.2 #94 (For use with Sensor Separation Kit).
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Verified for 0 to 100% LFL methane-in-air atmospheres per CSA C22.2 #152. Accuracy: ±3% LFL from 0 to 50%
LFL, ±5% LFL from 51% to 100% LFL.
NOTE
The high temperature characteristic has NOT been CSA verified above 75°C.
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.
NOTE
Ensure sensor hazardous (classified) location rating is applicable for the intended use.
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.
• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
• EQ25EMARM non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous
Locations per CSA C22.2 #213.
• Enclosure Rating NEMA Type 4X per CSA C22.2 #94.
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
B-4
MODEL EQ2500SAM SERIES SIGNAL AUDIBLE MODULE
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.
• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
• EQ25EMSAM non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous
Locations per CSA C22.2 #213.
• Enclosure Rating NEMA Type 4X per CSA C22.2 #94.
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Explosion-proof for Class I, Division 1, Groups B, C, & D Hazardous Locations per CSA C22.2 #30.
• Dust ignition-proof for Class II, Div. 1, Groups E, F, & G, Class III Hazardous Locations per CSA C22.2 #25.
• Non-incendive for Class I, Div.2, Groups A, B, C and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
• EQ24EMNE non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations
per CSA C22.2 #213.
• Enclosure Rating NEMA / Type 4X per CSA C22.2 #94.
• Operating Temperature Limits -40°C to +75°C.
• Storage Temperature Limits -55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Gas performance verified per CSA C22.2 #152.
OPTIONS
• Operator Interface Station (OIS)
NOTE
Metric straight thread types are for use in non-North American applications.
CALIBRATION
• Calibration of the above listed sensors has been CSA verified using the respective EQ2200DCU and
EQ2200DCUEX Series with Det-Tronics 225130-001 (50% LFL methane) and 227115-001 H2S Calibration Kits.
• The Model EQ2200DCU Series can be used with any CSA certified stand alone 4 to 20 ma linear device.
B-5 95-8470
B-6
Figure B1
APPENDIX C
CE MARK
The Eagle Quantum Fire and Gas Detection/Suppression System was tested and found to be compliant with
EN50081-2 and EN50082-2 when wired in conduit or with armoured instrument cable with individual screened
twisted pairs and galvanized steel wire armour. All screen drains shall be terminated to the chassis except for the
LON/SLC screen drains, which are terminated at LCU terminals 23 A and B and the LON/SLC screen termination in
each field device.
Communication wiring between the Local Control Unit (LCU), Local Input/Output Unit (LIOU) and Local Control Unit
Power Supply (LCUPS) shall be limited to a maximum of 3 meters for each section.
CENELEC CERTIFICATION
INITIATING DEVICE CIRCUIT (IDC and IDCGF),
DIGITAL COMMUNICATION UNIT (DCU)
AGENT RELEASE MODULE (ARM),
SIGNAL AUDIBLE MODULE (SAM),
NETWORK EXTENDER (NE):
To obviate the risk of hotspots and capacitor energy storage, the enclosure must not be opened, even when isolated,
when a flammable atmosphere is present.
Cable glands or the conduit entries to be used with this apparatus shall be EEx d approved by a notified body,
relevant to the threads found with the enclosure where they are to be fixed. As guards do not protect the transparent
windows of the devices, care shall be exercised during installation, positioning the face of the apparatus in order to
prevent damage.
UV FLAME DETECTOR:
The detector contains capacitors that could be an ignition source if the enclosure is opened within a hazardous area.
The enclosure must not be opened, even when isolated, when a flammable atmosphere is present. The cable must
only be connected to the enclosure by a flameproof cable entry device certified to EN 50 018. If only one cable entry
is used, any other entries must be closed by a certified flameproof stopping plug. The flame detector can be
delivered in two versions, one for ambient temperatures up to +75°C, and one for temperatures up to +125°C. The
label will indicate the actual maximum allowable ambient temperature.
C-1 95-8470
EQ2200UVHT SERIES UV FLAME DETECTOR
Electronic Module —
EEx d IIC T4 (Tamb = –60°C to +75°C)
EEx d IIC T5 (Tamb = –60°C to +65°C)
EEx d IIC T6 (Tamb = –60°C to +50°C)
IP66.
UV Detector —
EEx d IIB +H2 T4 (Tamb = –55°C to +125°C)
EEx d IIB +H2 T5 (Tamb = –55°C to +90°C)
EEx d IIB +H2 T6 (Tamb = –55°C to +75°C)
IP66.
The cable entry temperature may rise 10°C above the ambient temperature and cable shall be suitable for that
temperature. The flame detector shall be electrically connected by means of a flame-proof cable gland or stopping
box certified to EN 50018. The fused silica lens in this unit is liable to be damabed by impact. The unit should be
installed in such a manner as to protect the lens from mechanical damage.
The UV detector module contains a fused silica window, which can be damaged by impact. The detector should be
installed in such a manner as to prevent the window from receiving mechanical damage.
The sensor can withstand repeated exposures to +125°C for periods up to 12 hours. It is recommended that the
sensor be replaced after a maximum of 500 hours of exposure to the +125°C temperature conditions.
C-2
APPENDIX D
D-1 95-8470
Rocker Switch Table
Node Rocker Switch Node Rocker Switch
Address 1 2 3 4 5 6 7 8 Address 1 2 3 4 5 6 7 8
1 X O O O O O O O 71 X X X O O O X O
2 O X O O O O O O 72 O O O X O O X O
3 X X O O O O O O 73 X O O X O O X O
4 O O X O O O O O 74 O X O X O O X O
5 X O X O O O O O 75 X X O X O O X O
6 O X X O O O O O 76 O O X X O O X O
7 X X X O O O O O 77 X O X X O O X O
8 O O O X O O O O 78 O X X X O O X O
9 X O O X O O O O 79 X X X X O O X O
10 O X O X O O O O 80 O O O O X O X O
11 X X O X O O O O 81 X O O O X O X O
12 O O X X O O O O 82 O X O O X O X O
13 X O X X O O O O 83 X X O O X O X O
14 O X X X O O O O 84 O O X O X O X O
15 X X X X O O O O 85 X O X O X O X O
16 O O O O X O O O 86 O X X O X O X O
17 X O O O X O O O 87 X X X O X O X O
18 O X O O X O O O 88 O O O X X O X O
19 X X O O X O O O 89 X O O X X O X O
20 O O X O X O O O 90 O X O X X O X O
21 X O X O X O O O 91 X X O X X O X O
22 O X X O X O O O 92 O O X X X O X O
23 X X X O X O O O 93 X O X X X O X O
24 O O O X X O O O 94 O X X X X O X O
25 X O O X X O O O 95 X X X X X O X O
26 O X O X X O O O 96 O O O O O X X O
27 X X O X X O O O 97 X O O O O X X O
28 O O X X X O O O 98 O X O O O X X O
29 X O X X X O O O 99 X X O O O X X O
30 O X X X X O O O 100 O O X O O X X O
31 X X X X X O O O 101 X O X O O X X O
32 O O O O O X O O 102 O X X O O X X O
33 X O O O O X O O 103 X X X O O X X O
34 O X O O O X O O 104 O O O X O X X O
35 X X O O O X O O 105 X O O X O X X O
36 O O X O O X O O 106 O X O X O X X O
37 X O X O O X O O 107 X X O X O X X O
38 O X X O O X O O 108 O O X X O X X O
39 X X X O O X O O 109 X O X X O X X O
40 O O O X O X O O 110 O X X X O X X O
41 X O O X O X O O 111 X X X X O X X O
42 O X O X O X O O 112 O O O O X X X O
43 X X O X O X O O 113 X O O O X X X O
44 O O X X O X O O 114 O X O O X X X O
45 X O X X O X O O 115 X X O O X X X O
46 O X X X O X O O 116 O O X O X X X O
47 X X X X O X O O 117 X O X O X X X O
48 O O O O X X O O 118 O X X O X X X O
49 X O O O X X O O 119 X X X O X X X O
50 O X O O X X O O 120 O O O X X X X O
51 X X O O X X O O 121 X O O X X X X O
52 O O X O X X O O 122 O X O X X X X O
53 X O X O X X O O 123 X X O X X X X O
54 O X X O X X O O 124 O O X X X X X O
55 X X X O X X O O 125 X O X X X X X O
56 O O O X X X O O 126 O X X X X X X O
57 X O O X X X O O 127 X X X X X X X O
58 O X O X X X O O 128 O O O O O O O X
59 X X O X X X O O 129 X O O O O O O X
60 O O X X X X O O 130 O X O O O O O X
61 X O X X X X O O 131 X X O O O O O X
62 O X X X X X O O 132 O O X O O O O X
63 X X X X X X O O 133 X O X O O O O X
64 O O O O O O X O 134 O X X O O O O X
65 X O O O O O X O 135 X X X O O O O X
66 O X O O O O X O 136 O O O X O O O X
67 X X O O O O X O 137 X O O X O O O X
68 O O X O O O X O 138 O X O X O O O X
69 X O X O O O X O 139 X X O X O O O X
70 O X X O O O X O 140 O O X X O O O X
D-2
Rocker Switch Table
Node Rocker Switch Node Rocker Switch
Address 1 2 3 4 5 6 7 8 Address 1 2 3 4 5 6 7 8
141 X O X X O O O X 211 X X O O X O X X
142 O X X X O O O X 212 O O X O X O X X
143 X X X X O O O X 213 X O X O X O X X
144 O O O O X O O X 214 O X X O X O X X
145 X O O O X O O X 215 X X X O X O X X
146 O X O O X O O X 216 O O O X X O X X
147 X X O O X O O X 217 X O O X X O X X
148 O O X O X O O X 218 O X O X X O X X
149 X O X O X O O X 219 X X O X X O X X
150 O X X O X O O X 220 O O X X X O X X
151 X X X O X O O X 221 X O X X X O X X
152 O O O X X O O X 222 O X X X X O X X
153 X O O X X O O X 223 X X X X X O X X
154 O X O X X O O X 224 O O O O O X X X
155 X X O X X O O X 225 X O O O O X X X
156 O O X X X O O X 226 O X O O O X X X
157 X O X X X O O X 227 X X O O O X X X
158 O X X X X O O X 228 O O X O O X X X
159 X X X X X O O X 229 X O X O O X X X
160 O O O O O X O X 230 O X X O O X X X
161 X O O O O X O X 231 X X X O O X X X
162 O X O O O X O X 232 O O O X O X X X
163 X X O O O X O X 233 X O O X O X X X
164 O O X O O X O X 234 O X O X O X X X
165 X O X O O X O X 235 X X O X O X X X
166 O X X O O X O X 236 O O X X O X X X
167 X X X O O X O X 237 X O X X O X X X
168 O O O X O X O X 238 O X X X O X X X
169 X O O X O X O X 239 X X X X O X X X
170 O X O X O X O X 240 O O O O X X X X
171 X X O X O X O X 241 X O O O X X X X
172 O O X X O X O X 242 O X O O X X X X
173 X O X X O X O X 243 X X O O X X X X
174 O X X X O X O X 244 O O X O X X X X
175 X X X X O X O X 245 X O X O X X X X
176 O O O O X X O X 246 O X X O X X X X
177 X O O O X X O X 247 X X X O X X X X
178 O X O O X X O X 248 O O O X X X X X
179 X X O O X X O X 249 X O O X X X X X
180 O O X O X X O X 250 O X O X X X X X
181 X O X O X X O X
182 O X X O X X O X
183 X X X O X X O X O = OPEN
184 O O O X X X O X X = CLOSED
185 X O O X X X O X
186 O X O X X X O X
187 X X O X X X O X
188 O O X X X X O X
189 X O X X X X O X
190 O X X X X X O X
191 X X X X X X O X
192 O O O O O O X X
193 X O O O O O X X
194 O X O O O O X X
195 X X O O O O X X
196 O O X O O O X X
197 X O X O O O X X
198 O X X O O O X X
199 X X X O O O X X
200 O O O X O O X X
201 X O O X O O X X
202 O X O X O O X X
203 X X O X O O X X
204 O O X X O O X X
205 X O X X O O X X
206 O X X X O O X X
207 X X X X O O X X
208 O O O O X O X X
209 X O O O X O X X
210 O X O O X O X X
D-3 95-8470
LON® is a registered trademark of Echelon Corporation.
Modbus® is a registered trademark of Modicon Inc.