Foreword
1. Model description
The structural type of the MXPR-600Hb series protection is Hb. MLPR-610Hb
2. Standards referenced
General specification for static protection, security and automatic equipment, DL
478-2001
GB/T 14285-2006
GB50062-92
3. Caution
Negative sequence voltage involved in this series of protection is combined with
phase voltage, all of low voltage component depend on line voltage in compound
voltage block, if one of the three line voltages is lower than low voltage setting, low
voltage component will operates and unblock over current protection.
There are 4 standard curves of inverse protection involved in this series of protection,
if the fault current is higher than 15 times of rated current, the inverse protection
component as if the current is 15 times of rated current.
The appearance should be inspected before power is applied, to ensure that the
panel is OK without scratch, the screws are tightened, the device is grounded firmly,
all screws of plug-ins are tightened and in good contact.
When power is applied, the ―Run‖ indicator on the panel should flash, digital tube
displays primary measuring result in cycle, protection and measuring data are
displayed on the lcd in cycle.
The terminal D25 ~ D28 are measuring circuit of 4 ~ 20mA DC signal, when
1
testing(Can be selected or not)
signal should be supplied by special equipment, direct apply signal of relay protection
tester is prohibited.
When the device is equipped with ungrounded system, terminal D07,D08 are zero
sequence small current input terminal, the ac current input should be limited to within
2A, the measuring current input should be limited to 6A, pay attention to the signal
input when testing to avoid large signal applied so as to avoid damage to
components.
Operating circuit inside the device is only applicable to DC power supply, if AC power
is used, it should be applied with rectifier and filter.
It is prohibited to plug or unplug the plug-ins, in order to avoid damage to the device.
It is prohibited to do digital output test when the device is running with primary
equipments.
2
Foreword
1. Product description
1.1 Scope of application
The MLPR-600Hb microcomputer line protection and monitoring device applies to the
line protection and monitoring in ungrounded systems or systems grounded via resistor
with voltage ratings of below 66kV. It can also be used as a current voltage protection and
3
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
Rated data
Power supply: DC/AC 86~265V
Operating voltage: DC 220V or DC 110V
4
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
Power consumption
DC circuit: <10W (normal operation); <15W (protection operation)
AC voltage circuit: <0.5VA/phase
AC current circuit: <1VA/phase (In = 5A); <0.5VA/phase (In = 1A).
Overload capability
AC voltage circuit: 1.2Un, continuous operation
Current measuring circuit: 1.2 In, continuous operation
Protective current circuit: 2In, continuous operation
10In, allowing 10s
40In, allowing 1s
Measuring accuracy
AC current: Class 0.2
AC voltage: Class 0.2
4~20mA DC quantity input: ≤±1%
Power: Class 0.5
Integral energy: Class 1 (active), Class 2 (reactive)
Frequency: ≤±0.02Hz
SOE resolution: ≤2ms
Pulse width of pulse quantity: ≥10ms
4~20mA DC quantity output: ≤±1%
5
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
Environmental conditions
Ambient temperature:
Operating:-20℃~+55℃。
Storage:-25℃~+70℃, rainproof and snow-proof rooms with relative humidity not
greater than 80%, ambient air free of acid, alkaline or other corrosive and explosive gas;
no excitation quality is applied at the limits, the device shall not have any irreversible
change; after temperature restoration, the device shall operate properly.
Relative humidity: The average relative humidity of the most humid month shall not
be greater than 90%, the average minimum temperature of this month not lower than 25 ℃
and there shall be no surface condensation; at the highest temperature of +40 ℃, the
average maximum humidity shall not exceed 50%.
Atmospheric pressure: 80kPa~110kPa (below relative altitude of 2wc)
Devices fabricated on-screen steps: first release on-screen stents unfastening screws,
6
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
remove the stents; installed the device on the screen from the front and push until close to
the fixed plate; install the stent 2, and then stent 1, and then use fastening screw to
insertion hole from rear of stent1, and then screwed into stent 2 and tighten screw; the
stents from up and down are installed in the same way; use grounding screws to connect
grounding line.
2. Function of device
2.1 3-step compound voltage block directional overcurrent protection
(Three-step OC)
Each step can be set that it is blocked by compound voltage(the negative sequence
voltage is synthesized from the phase voltages, and minimum line voltage is used for
undervoltage block)and direction. The operation logic diagram of the compound voltage
block directional overcurrent protection is shown in Figure 2-1. When the ―Overcurrent
negative direction‖ is switched on, the operation zone of overcurrent step III is opposite
to that only when overcurrent step III direction is switched on.
Compounded voltage lock On/Off
Ia>Igl
Direction judgement &
Protection On/OFF Trip
Tgl
Ib>Igl & output
Direction judgement & ≥
Ic>Igl
Direction judgement &
Direction judgment On/Off
7
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
Arg(Uφφ/Iφ)=-125°~35°,the boundary value is not very exact and the error is less
than ±2°.
10º I
90º 160º
45º
10º
IT overcurrent On/Off
Output sequence
8
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
In major grounding systems, the ground current is relatively high, the zero sequence
overcurrent protection of Step I, II trips directly, and that of Step III can be set as alarm or
trip for ungrounded systems. All the 3 steps of the zero sequence overcurrent protection
can be set to block in the direction of the zero sequence voltage. For ungrounded systems,
the zero sequence current is directly collected from the low current signal of the special zero
sequence CT.
The zero sequence Step III can switch on either alarm or trip. When both are
switched on, the trip function is enabled, the alarm function is released automatically.
For ungrounded systems, when a ground fault occurs in the system, the zero
sequence current of the ground fault point is basically a capacitive current with small
amplitude. If a zero sequence overcurrent relay is used to protect it from ground faults, its
selectivity can hardly be guaranteed. The device uploads the amplitu de and direction of
the zero sequence current by communication, and the upper computer performs low
current ground wire selection.
The directional zero sequence overcurrent operation logic is shown in Figure 2-4.
I0>I0gl
Zero-sequence Zero-sequence over-current
U0>U0bs voltage lock On/Off protection On/Off T Trip output/alarm
& output
Zero-sequence over-
current direction judgment
Zero-sequence over-current
direction judgment On/Off
9
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
2-5.
U0>Ugdy
Zero sequence
over-voltage On/off Tgdy Trip/alarm output
&
Circuit breaker at
closed position
Low-frequency unloading
On/Off Low-frequency
unloading protection
output sequence
10
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
Maximum phase
current < 0.1In
Reclosing start
Switch open position &
Tzdchz
Reclosing charging &
indication =1
Reclosing lock
& Reclosing On/Off Automatic reclosing
output
Automatic reclosing
Frequency
difference <0.5Hz
Reclosing lock
& 15s Reclosing charging
Circuit breaker at closed position indication =1
2.8 Post-acceleration
A one-step overcurrent post-acceleration and zero sequence overcurrent
post-acceleration protection is provided, which can be closed manually or remotely and
started by reclosing, with an opening time of 3s. The overcurrent acceleration and zero
sequence acceleration can be switched On/Off separately, and their current and delay can
be set separately. The operation logic of post-acceleration is shown in Figure 2-9.
On/Off
Post-accel eration input Post-accel eration
operation message
2.9 PT failure
The judgment criterion of PT failure depends on the wiring mode. When the PT failure
block function is switched on, if PT failure occurs, the under voltage protection will block
the compound voltage component and current directional component. The judgment
criterion of PT failure is as follows:
V-V wiring mode
The current value of the phase with the maximum current is less than the maximum
load current (using the setting value of the overload current).
11
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
① Maximum inter-phase voltage < 30V, and current of any phase > 0.1In;
② Negative sequence voltage > 8V
If any of the above conditions is met, the delay (settable) will report PT failure, and will
return when failure disappears.
Y-Y wiring mode
The current value of the phase with the maximum current is less than the maximum
load current (using the setting value of the overload current).
① When |Ua+Ub+Uc|>7V, and the modulus difference between the maximum and
minimum line voltages is greater than 18V, it is thought one or 2 phases have PT failure;
② |Ua+Ub+Uc∣> 7V, the minimum line voltage is less than 18V, used for detecting
2-phase failure.
③ When MAX{Uab,Ubc,Uca}<7V,and the current of any phase > 0.1In, it is regarded
as PT 3-phase failure.
If any of the above conditions is met, the delay (settable) will report PT failure, and will
return when failure disappears.
Max{Ia,Ib,Ic}<Igfh
MaxU<30V
&
Max{Ia,Ib,Ic}>0.1*In
≥
U2>8V PT failure On/Off
& &
PT failure component
V-V wiring
≥
| U a U b U c | 7V
|MaxU-MinU|>18V &
TPT PT failure
| U a U b U c | 7V information
≥
&
MinU<18V &
MaxU<7V
MaxU=Max(Uab,Ubc,Uca)
& MinU=Min(Uab,Ubc,Uca)
Max{Ia,Ib,Ic}>0.1*In
12
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
Umax>30V
Umax<Uddy Low-voltage On/Off Tddy Protection output
PT break lock & sequence
PT break
Circuit breaker at
closed position
I>Iset
Bus charging On/Off
Manual closure T
& Output sequence
Remote closure ≥
3s opening time
13
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
14
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
DA1~2 adjustment
0.5-1.5 Adjust parameters of D/A Channels 1~2 (4-20mA)
Factor
(Inst.PROT)
Delay Instantaneous Protect
On/Off 1/0 1/0:On/Off (factory default Off)
(Delay Inst.PROT)
Definite Time Overcurrent On/Off
1/0 1/0:On/Off (factory default Off)
(DT Overcurrent)
15
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
16
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
17
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
18
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
19
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
20
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
Terminals D23、D24 Line voltage (UL) Add 50V, displayed deviation not exceeding 0.5%
4~20mA DC Input
Terminals D25、D26 Add 10mA, displayed deviation not exceeding 3%
1
4~20mA DC Input
Terminals D27、D28 Add 10mA, displayed deviation not exceeding 3%
2
Terminals D09、D10;
D13、D14 add current Add a single rating to current and 100V to line voltage
3-phase active
by polarity;D15、D16; Alter phase angle, displayed power deviation not
power
exceeding 0.5%
D17、D18;D19、D20
add voltage by polarity
21
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
Terminals D09、D10;
D13、D14 add current Add a single rating to current and 100V to line voltage
3-phase reactive
by polarity;D15、D16; Alter phase angle, displayed power deviation not
power
exceeding 2%
D17、D18;D19、D20
add voltage by polarity
Terminals C12 and
C16(common terminal Pulse 1(MC1) Connect each point once, add 1 to the count
of pulse +24V)
Terminals C13 and
C16(common terminal Pulse 2(MC2) Connect each point once, add 1 to the count
of pulse +24V)
Terminals C14 and
C16(common terminal Pulse 3(MC3) Connect each point once, add 1 to the count
of pulse +24V)
Terminals C15 and
C16(common terminal Pulse 4(MC4) Connect each point once, add 1 to the count
of pulse +24V)
B06 Spring is not energized [Binary input] menu in the [State Display],
22
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
B12 Input 11
B13 Chk.Sync.Manu.
B14 Positive terminal of internal
24V power supply
open) Output 10
B35-B36
A22-A23 Remote Close
A22-A24 Remote Trip
5. Operation instructions
5.1 Control panel of device
23
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
128*64 matrix LCD (The LCD will go off after a period of absence of keyboard operation;
the LCD will be illuminated automatically when any key is pressed or in case of
protection trip or alarm.)
Signal indicator: operation, communication, operation, alarm, reclosure, fault (of the
device)
Circuit breaker state indication: indicating the current state of the circuit breaker (―Open‖,
―Close‖ position indication)
Remote/local selection signal, local opening/closing button
Key pad: , , , , Cancel, -, +, Enter, Revert
The 6-bit nixie tube displays the primary measured values in real time: IA, IB, IC, Uab,
Ubc, Uca, P, Q, Cosφ. (Please set the PT, CT transformation ratios properly in the System
Parameters menu). The maximum display range of the power on the nixie tube is: 99999.
Note: Measurement IA: AA, measurement IB: bA, measurement
IC: CA,
voltage Uab: AbKV, voltage Ubc: bCKV, voltage Uca: CAKV,
active power: PKW, reactive power: qKVar, power factor: H
24
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
a menu, continue to press the ――, ―― key to select the desired entry, press the ―Enter‖
key to enter the next level of screen, and press the ―Cancel‖ key to return to the next
higher level of menu. If there is no menu screen, be sure to press the ― Cancel‖ key to
return to the next higher level of menu. The main menu is shown at the center of the
following figure, with the corresponding submenus on both sides.
The main interface displays the primary operating parameters in turn. The maximum
displayed value of the primary is 6000.0A. For systems with a rated current of 5A, the set
CT transformation ratio shall not exceed 2000. If the primary power is greater than
1000kW, the display unit is MW, otherwise is kW.
1.State Disp 4.Output Test
Protection Data Device Failure
Pulse Energy
Phase Angle
1·State Display Chk.Sync.Manu.
Output 5
PROT Output 1
2·Signal Revert
Harmonic Data
DC Input Data PROT Output 2
Trip Report
BinaryReport 5·SYS Parameters 5.Parameters
Setting Zero No.
Event Report
Comm. Setting
Report Clear
6·Setting Value B. Parameters
6.Settings(Note 1) D/A Setting
Protect On/Off
。。。。。
。
7·Clock Setting Pulse Energy
Trip Times Clear
8·Password
Note: See protection Channel Coef.
9·Version Info
setting menus □□□□
Note 1: For the Setting menu, see the description of each device.
State Display
25
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
The [State Display] menu contains 8 submenus, including protection data, measuring
data, binary input, pulse energy, angle display, harmonic data, DC measurement and trip
statistics. It is described as follows:
↑ ↓
Protection Data
Ia = □□□·□□ A
Ib = □□□·□□ A Protection CT secondary current value
Ic = □□□·□□ A
Uab = □□□·□□ V
Ubc = □□□·□□ V PT secondary line voltage value
Uca = □□□·□□ V
U2 = □□□·□□ V Negative seque.voltage
U0 = □□□·□□ V Zero sequence voltage
I0 = □□□·□□ A Zero sequence current
。。。。。。
Measuring Data ↑ ↓
IA = □□□·□□ A
IB = □□□·□□ A Measuring CT secondary current value
IC = □□□·□□ A
Ua = □□□·□□ V
PT secondary phase voltage value
Ub = □□□·□□ V
Uc = □□□·□□ V
Converted to PT, CT secondary active power
P = □□□□·□ W
Q = □□□□·□ var Converted to PT, CT secondary reactive power
Cosφ = □·□□□ Cosine function for included angle of voltage and
。。。。。。 current; for -90°<φ<90°, COSφ is positive; for 90°<
φ<270°, COSφ is negative
Note: In the standard configurations, the input circuit has the connection to an
external 220VDC control power supply. When no DC control power supply or control
system is available on site, but a 110VDC control power supply is available, a 110VDC
control power supply may be used for direct connection through local hardware
26
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
adjustment, or the 24V power supply of the device may be used as the input power supply
(when the input common terminal is +24V, terminal number: B14, Terminal B01 is kept
float). However, this must be specified upon ordering.
↑ ↓
Pulse Energy
MC1:□□□□□□□□□□
MC2:□□□□□□□□□□
External pulse energyinput counting (4-way)
MC3:□□□□□□□□□□
MC4:□□□□□□□□□□
+□□□□□□□·□□□kWh
Accumulation of the device’s real-time active and reactive
+□□□□□□□·□□□kvh
calculations over time, + for positive direction, - for negative
-□□□□□□□·□□□kWh
direction.
-□□□□□□□·□□□kvh
Phase Angle ↑ ↓
Phase angle relative to Ua, Ua as 0° by default.
Ua:□□□·□□°
Ub:□□□·□□° When wiring method is VV, it displays line voltages
Uc:□□□·□□° relative to Uab, the same as follows
Ia:□□□·□□°
Ib:□□□·□□° Phase angle of protection current relative to Ua
Ic:□□□·□□°
IA:□□□·□□°
IB:□□□·□□° Phase angle of measuring current relative to
IC:□□□·□□°
Ua
UL:□□□·□□°
。。。。。。
Harmonic ↑ ↓
I2: □□□·□□%
I3: □□□·□□%
I4: □□□·□□% 2~31st harmonics for which analog channels have been
selectedinsystem
I5: □□□·□□%
。。。。。。
I11: □□□·□□%
DC Input ↑ ↓
DC1:□□□·□□mA
External DCinput 4~20mA (2-way)
DC2:□□□·□□mA
Trip Times
27
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
Signal revert
In the [Signal Revert] menu, press the ―Enter‖ key, the signal relay and the ―Operation‖
indicator on the panel will be reset.
Report Display
The [Report Display] menu includes 4 submenus, including trip report, binary report,
event report and report clear. Event recording includes: device self-check fault, device
setting value modification, system parameter modification and setting zone number
modification, etc. Trip report can be record for the last 50 events, binary report for 100,
event report for 30 at most. Beyond this, the latest report will overwrite the earliest one.
Press the ―Enter‖ key to enter the corresponding [To view xx report, please enter report
number: 00 ] menu, and enter any figure within storage volume, press the ―Enter‖ key to
display the contents of that report. The screen is as follows:
Operation values
Output test
After entering the [Output Test] menu, the correct password is required to enter the
[Output Test] menu. It displays the following:
4.Output test ↑ ↓
Device Failure
Trip Signal
Alarm Signal Press ―Enter‖ key
Chk. Sync. Manu
Output 5 ——————>
PRO Output1
PRO Output2 Device Failure
<——————
。。。。。。 Close Open
Press ―Cancel‖ key
Operate All
(Note: When the test is performed on the 6 protection outputs, the starting relay will
be in the ―Closed‖ state automatically. The ―+‖, ―-‖ keys are used for switching between the
―Close/Open‖ control.)
System parameters
After entering the [SYS Parameters] menu, the correct password is required to enter
the [SYS Parameters] menu. It displays the following:
28
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
5.Parameters ↑↓
Setting Zone No.
Comm. Setting
Basic Parameters
D/A setting
Pulse Energy
Trip Time Clear
Channel Coef.
Setting Zone No.: range 00~07.
Comm. setting
Comm. setting ↑ ↓
RS485 Address
□□ Communicationaddress ofdevice 01~99
RS485 Baud rate
00:2.4KB;01:4.8KB;02:9.6KB;03:
□□
Pulse Input Time 19.2KB;04:38.4KB;05:115.2KB
□□□□ms Confirmation time of 4-way pulse
IP Address energy, >10mS, < impulse width of
□□□. □□□. □□□. □□□
kilowatt-hour meter
Subnet Mask
□□□. □□□. □□□. □□□ For Ethernet communication
K W Default
□□□. □□□. □□□. □□□
Setting of basic parameters (see the description of the protection device for basic
parameters)
B. Parameters: ↑↓
Rating Current
□□ Setting the CT secondary current rating 00: 5A; 01: 1A
PT Ratio
□□□□ Setting the PT transformation ratio: 1~1500
CT Ratio
□□□□ Setting the CT transformation ratio: 1~5000
CT Wiring Mode
□□ Setting the CT secondary wiring mode00: 3-phase; 01: 2-phase
PT Wiring Mode
□□ Setting the PT secondary wiring mode00: Y-Y; 01: V-V
Harmonic Channel
Setting analog quantity channels 0~12 for harmonic monitoring,
□□
□ select 0 to exit from the harmonic calculation function
。。。。。。
29
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
D/A setting
The device has two 4~20mA outputs. The DA1~DA2 adjustment factor is used to
adjust the accuracy of the channel output. The DA1~DA2 channel selection is used to
select the corresponding analog quantity channel (see the description of the protection
device for specific reference quantities). In the accuracy test, make sure the field ground is
in good contact; otherwise the accuracy might be affected.
Pulse energy setting
Energy base numbers can be set, including Pulse 1, Pulse 2, Pulse 3, Pulse 4,
positive active energy, positive reactive energy, negative active energy and negative
reactive energy.
Clear trip times
It is used to clear the trip times.
Settings
After entering the password, you can enter the [Setting Value] menu. See the settings
description of the protection device for the detailed description.
Clock setting
A battery-back real-time clock is provided in the device, which can perform time
adjust remotely via the communication network or in-site time adjust in the [Time Setting]
menu.
Enter this menu and press the ―Enter‖
7.Clock setting
Date:20□□-□□-□□ key, the clock will stop refreshing and a
Time: □□:□□:□□ cursor will appear. Move the cursor to the
desired position for modification by pressing
the ――, ―― keys, modify to the desired
value with the ―+‖, ―-‖ keys. Press the
―Enter‖ key to complete setting. If the
―Cancel‖ key is pressed, the setting will be
cancelled and the screen continues to
refresh the clock.
Password
The [Password] menu is used to modify the password for entry into the Settings,
System parameters and Output Test submenus. The initial password is provided by the
factory. The universal password is ―1000‖.
Input password Move the cursor to the desired
position for modification by pressing the
0 0 0 0
――, ―― keys, modify to the desired
password with the ―+‖, ―-‖ keys. Press the
30
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
Version Info
In the main menu, after entering the [9. Version Info] menu, the model, software
version and date of the device will be displayed.
Note: For a corresponding nonstandard model, the device’s displayed model does not
have to be changed.
MLPR-610Hb
Ia(Ib、Ic) D1(3,5)
Ua D15
Power supply
Ub D17
Uc D19 A02
Ua’(Ub’、Uc’) D16(18,20)
14(16,18)
Figure 6-1
See the following table and set. To measure operation current value and keep a
record in the following table. The measuring terminals B17-B18,B25-B26,B27-B28 should
31
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
32
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
33
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
On/Off separately. Their principle is same, now take the zero sequence overcurrent phase
I for example. To wire as Figure 6-2 and switch on zero sequence overcurrent phase I
protection and zero sequence direction. It will have zero sequence voltage block function
when zero sequence voltage block is switched on.
MLPR-610Hb
Ua D15
3I0 D07
D08
3I0’
Figure 6-2
See the following table and set. Measure operation current value and keep a record in
the following table. The measuring terminals B17-B18, B25-B26, B27-B28 should be
shorted when the zero sequence protection operates. (YY connection is taken for
example.)
Open U0(V) ≥15 ≥15 ≥15 ≥15
Calculate 3U0(=UA) ≥15 ≥15 ≥15 ≥15
Setting value of zero
0.20 0.50 1.00 1.50
sequence current(A)
Operation value
Operation zone
MLPR-610Hb
U0 D21 A01
-WC B01
Figure 6-3
34
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
See the following table and set. Measure operation current value and keep a record in
the following table. The measuring terminals B19-B20 should be shorted when zero
sequence voltage alarm operates.
Setting value of zero
10 20 30 50
sequence voltage(V)
Zero sequence
1 10 50 100
voltage delay(s)
Zero sequence
voltage operation value(V)
Zero sequence
voltage operation time(s)
MLPR-610Hb
Power supply
Figure 6-4
See the following table and set. Measure operation current value and keep a record in
the following table. The measuring terminals B19-B20 should be shorted when overload
alarm operates.
Setting value of overload(A) 5 10 15 20
Overload delay(s) 10 5 2 1
Overload operation value(A)
Overload operation time (s)
frequency of voltage Uab. It has frequency slip block (Which can be On/Off) and under
current block against load feedback. To prevent fast voltage drop from wrong operation of
35
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
needed, switch on slip block. Slip block should be switched off so as not to affect
MLPR-610Hb
Ia D1
A01
Ia’ D2
Power supply
Ua(Ub) D15(17)
A02
Ua’(Ub’) D16(18)
Figure 6-5
See the following table and set. Measure operation value and keep a record in the
following table. The measuring terminals B17-B18、B25-B26、B27-B28 should be shorted
when under-frequency unloading protection operates.
Setting value of under-frequency(Hz) 49.5 49 48.5 48
Setting value of under current(A) 0.5 0.5 1 1
Setting value of under voltage(V) 10 20 30 60
Setting value of slip block(Hz/s) 3 4 5 7
Setting value of under-frequency
0.5 1 2 3
operation delay(s)
Under-frequency operation value(Hz)
Under-frequency operation time(s)
Slip block value(Hz/s)
MLPR-610Hb
Ia D1 A01
B01 A02
DL
B02
Figure 6-6
36
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
37
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
MLPR-610Hb
Ua D15
A01
Ub D17
Power supply
Uc D19
A02
Ua’(Ub’、Uc’) D16 (18,20)
Figure 6-7
Setting value of
30 50 70 90
undervoltage(V)
Operation value
+WC A20
Figure 6-8
Setting value of
bus charging current 1In 2In 5In 10In
(A)
Operation value
38
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
The remote closure synchronous function is switched on, under the background
monitoring system and after sending closure command, the device will capture
the time of synchronization, the terminals B23-B24 are closed for 600ms and it will send
closure pulse.
MLPR-610Hb
Ua
D15
Ub D17 A01
Uc D19
Ua’(Ub’、Uc’) D16(18,20) Power supply
UL D23 A02
UL’ D24
Figure 6-9
39
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
Net1
B01
D01 Ia Ia' D02
B02
B03 D03 Ib Ib' D04
B04
Net2
B05
ON
D05 Ic Ic' D06
B06
B07 Input 6 D07 I0 I0' D08
COM1
OFF B08
B09
Input 7
B10 Input 9
Run
B11 Input 10 D11 IB IB' D12
B12 Input 11
Debug
D13 IC IC' D14
A01 B13 Chk.Sync.Manu.
40
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
Circuit
breaker
a a b b c c a a b b c c A A B B C C
AC plug-in
monitoring device DCSIn1-
DCSIn2+
DCSIn2-
Net1
Device power+
Net2 Device power-
Shielded ground
Debugging
port Shielded ground
Power off
CPU plug-in unit
COM A Operating
circuit
COM A failure
COM B Trip
I/O plug-in unit position
COM B
Shielded ground Closed position
COM A
Reclose Output
Chk.Sync.Manu.
Output 9 normally
Chk.Sync.Manu.
Reclose Output
Output 10 common
PROT Output 1
PROT Output 1
PROT Output 2
PROT Output 2
Output 9 common
normally closed
Closed position
Alarm signal
Alarm signal
COM A
normally open
normally open
monitoring
Output 5
Output 5
Trip coil
Output 10
Output 10
COM B
9
Trip position
closed
Output
COM B monitoting
Positive active pulse
t
Device Failure
Trip Signal
Input common
Trolley test
Trolley run
Trip Signal
DCSOut1+
Input 11
Input 10
Device panel+WC
terminal-
(+24V)
LARC Lock
Input 9
Input 6
Input 7
Breaker
Spring
signal
signal
DCSOut2- +WC WC
WC
WC
Note:
Figure 7-12 Typical wiring diagram of MLPR-610Hb
1.As shown in the figure,the ZK(remote/local changeover switch) and KK(manual operating switch) are installed on
the switchboard panel.When remote/local changeover switch and manual operating switch of device panel are
used,terminal A21 is connected to +KM.
2.As shown in the figure,PT secondary is star connection,when V-V wiring is present, terminals D 15,D20 are connected
to phase A of PT secondary,terminals D16,D17 to phase B of PT secondary,terminals D18,D19 to phase C of PT
secondary.
41
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
Small bus
Fuse
Closing circuit
TBJ2
ZK KK TBJ
2 4 5 8 A15 A19 Manual and
anti-trip
A24
Remote
YHJ controlled
switch-on
ZK
1 3 A22
Remote
control
opening
YTJ
A23
Trip circuit
DL
ZK KK TQ Manual and
6 8 6 7 A17 A18 trip output
Tn1
Protection
2LP
Jn
Tn2
HWJ On position
A13
A20 DL
TWJ
A14 Off position
HWJ Closed position
A11 A12 output
TWJ
A09 A10 Trip position
output
HWJ TWJ
A07 A08 Operation circuit
disconnected
42
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
43
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line
WLD[K]-JY-222-2010
Small bus
Fuse
Closing circuit
Tn1 Reclosing
TBJ2
ZK KK1 TBJ Manual and
2 4 5 8 A15 A19
anti-trip
A24
YHJ Remote
controlled
switch-on
ZK
A21 1 3 A22
Remote
control
YTJ opening
A23 DL
Trip circuit
ZK KK2 TQ
Manual and
6 8 6 7 A17 A18 trip output
Tn1
2LP
Jn Protection
Tn2
HWJ On position
A13
A20 DL
TWJ
A14 Off position
HWJ
A11 A12 Closed position
output
TWJ
A09 A10 Trip position
output
HWJ TWJ
A07 A08 Operation circuit
disconnected
In the diagram, KK1, KK2 and ZK are on the panel, in which KK1 and KK2 are manual
closing and manual trip buttons (the manual closing and manual trip contacts are already
connected to manual close in and manual trip in internally), ZK is a changeover switch for
switching between the local/remote positions, completely replacing the changeover and
operating switches on the board/cabinet panel.
Note: The dotted line outlines the internal circuit of the prote ction device. When a
control button on the panel is used, Terminal +KM A21 on the panel must be connected to
+KM.