Professional Documents
Culture Documents
Gas Turbine Operation
Gas Turbine Operation
Operation 1.2
1.2
Operation
TABLE OF CONTENTS
OPERATION PRINCIPLE
OPERATION SEQUENCES
ALARMS INTERPRETATION
SPECIAL SEQUENCES
Rev. : A
Page : 1/9
OPERATION AND MAINTENANCE MANUAL
OPERATION
OPERATION PRINCIPLE
1. INTRODUCTION..................................................................................................................... 2
2. RECORD OF EVENTS ........................................................................................................... 2
2.1. DATE, TIME AND METERS ................................................................................................ 3
2.2. OPERATION PHASES ........................................................................................................ 3
2.3. ALARMS AND TRIPS .......................................................................................................... 4
2.4. SPECIAL NOTES AND ABNORMALITIES.......................................................................... 4
2.5. INSTRUCTIONS .................................................................................................................. 4
2.6. PARAMETER READOUTS.................................................................................................. 4
3. KEEP ORIGINAL STATE........................................................................................................ 4
3.1. CLEANLINESS OF THE EQUIPMENT................................................................................ 4
3.2. FLUID LEVELS .................................................................................................................... 5
3.3. CONDITION OF FILTERS ................................................................................................... 5
3.4. INSTRUMENTATION .......................................................................................................... 5
3.5. BEHAVIOR CHANGE .......................................................................................................... 5
3.6. LIGHTING AND SIGNALING............................................................................................... 6
4. PARAMETERS READ OUT AND ANALYSIS......................................................................... 6
4.1. PARAMETER READOUTS.................................................................................................. 6
4.2. ANALYSIS OF THE PARAMETERS ................................................................................... 7
4.3. VIBRATION READOUTS..................................................................................................... 9
4.4. ANALYSIS ........................................................................................................................... 9
Rev. : A
Page : 2/9
OPERATION AND MAINTENANCE MANUAL
OPERATION
1. INTRODUCTION
Operating the gas turbine is mainly through the Human-Machine Interface (HMI) using the
command and automatic sequences like :
x Barring or ratcheting
x Cranking
x Normal starting
x Synchronizing
x Loading
x Water injection
x Washing
x Normal shut down
x Etc.
As a supplement of the above, the operating crew shall organize a working structure to :
x Record the events
x Keep the original state
x Monitor the parameters
The experience acquired during daily operation of the installation will enable the operating
staff to further supplement and refine the operation principle described below.
Refer also to GER 3620 : Operation and maintenance consideration.
2. RECORD OF EVENTS
It is important to record all the events from the very first time of operation to built up the
history of operation for the gas turbine. This will facilitate trouble shooting, event analysis
and can be an appreciable support for preventive maintenance scheduling.
The events may be recorded manually or automatically, on paper or on data carrier. The
wealth of information that these records represents for operation and maintenance will
become apparent during their use.
Main events to be recorded are :
x Date, time and meters.
x Operation phases.
x Alarms and trips.
x Special notes.
x Instructions.
x Parameter readouts.
Rev. : A
Page : 3/9
OPERATION AND MAINTENANCE MANUAL
OPERATION
Relevant data :
x Date of the day.
x Time of the operation: start-up, synchronizing, shutdown…
x Daily meter readouts: number of start-ups, number of ignitions, number of
emergency shutdowns…, number of flame hours according to the fuel used…
x Climatic conditions :
- External ambient temperature.
- External atmospheric pressure.
x Weather conditions :
- Wind, rain, storm, snow, frost, humidity...
Rev. : A
Page : 4/9
OPERATION AND MAINTENANCE MANUAL
OPERATION
Any machine behavior that is considered abnormal or unusual: vibrations, noise, defective
instrumentation etc...
2.5. INSTRUCTIONS
x General operating instructions.
x Provisional instructions specific to each unit, with exact date and duration
x Restrictions of use.
x Specific shift-change instructions.
Periodical visit and inspection, while the gas turbine is operating or during short standby
periods, shall be included in the daily task of the operator. Those task are not part of
preventive maintenance activities like combustion inspection, hot gas path inspection or
major inspection.
x Keeping the original state of the installation includes the following :
x Cleanliness of equipment
x Fluid levels
x Condition of filters
x Instrumentation
x Behavior change
x Lighting and signaling
Rev. : A
Page : 5/9
OPERATION AND MAINTENANCE MANUAL
OPERATION
Regular monitoring of the filters for pressure drop allows a schedule to be drawn up for
appropriate replacement of the cartridges. The main filters are located on the following
circuits :
x Lube oil.
x High pressure oil and control oil
x Gas fuel, liquid fuel, atomizing air
x Starting diesel or standby diesel generator lubricating oil and air filter
x Turbine air intake.
3.4. INSTRUMENTATION
Behavior change can be identified by noise level intensity change, vibration increase, due
to : ball bearing, flow inlet condition, output condition, flow rate, etc.
Rev. : A
Page : 6/9
OPERATION AND MAINTENANCE MANUAL
OPERATION
Lighting lamps and signaling devices such as alarms or motor status indicators must be
operational at all times. Rapid replacement of defective bulbs is part of compliance with
the operating regulations.
In order to maintain the performances and the reliability of the gas turbine, the operating
parameters must be read out and analyzed. This information, which is available on the
control screens or on site, can be divided into two families: the operating parameters and
the vibration readouts.
The readouts are performed manually or automatically with a frequency that depends on
the operational requirements. The following frequency is recommended:
x For the operating parameters: 1 to 4 readouts every 24 hours.
x For the vibration readouts: 1 to 4 readouts per month.
One method for reading out the parameters consists in classifying them into the following
categories :
x Performances
Active power, reactive power, generator voltage, generator current, excitation
voltage and current, ambient temperature, atmospheric pressure, pressure drop of
air filter etc…
x Generator temperatures
All generator temperatures: hot air, cold air, stator bars, return oil of bearings etc...
x Compressor temperatures and turbine cooling
Inlet temperature (CTIF), outlet temperature (CTDA), wheel space temperatures
(TTWS), tunnel temperature (TTIB).
x Turbine exhaust temperatures
TTXD, average temperature TTXM.
Rev. : A
Page : 7/9
OPERATION AND MAINTENANCE MANUAL
OPERATION
For gas turbines type 6000B : turbine speed at which the electric starting motor
stops or the diesel motor goes into idling speed.
x External environment
Battery charger current and voltage, main transformer temperature and oil level,
etc…
The parameter readouts taken during the first commissioning period serve as reference.
All subsequent readouts will be compared against the original readouts.
x Performances
The power output of the gas turbine varies with changes in the atmospheric
conditions. The analysis must be based on measurements carried out at full load
with temperature control (base load). The performances of the machine must
therefore be corrected prior to any comparison. A decrease in active power is
generally linked to fouling of the compressor. An ON line or OFF line water wash
allows to recover the largest part of the kilowatts. Air inlet filter pressure drop also
reduces the machine performance. The filter element replacement frequency
primarily depends on the air quality of the site.
x Generator temperatures
Refer to the generator volume.
x Compressor temperatures and turbine cooling
The cooling temperatures must not exceed the limit values and two thermocouples
located in the same zone must have similar temperature values; example: zone
after second wheel: the difference between thermocouples TTWS 2A0-1 and
TTWS 2AO-2 must be less than 75°C.
In the event of a fault, check the measuring loop and implement the appropriate
corrective action.
x Turbine exhaust temperatures
The exhaust temperature is limited by the control system as a function of the
compression ratio of the axial compressor.
Rev. : A
Page : 8/9
OPERATION AND MAINTENANCE MANUAL
OPERATION
Any drift of the measurement system or control system must be analyzed and
corrected as soon as possible.
If the turbine runs on liquid fuel oil, the nozzle pressure of each chamber at the
outlet of the flow divider can be read out. The maximum permissible pressure
difference between these pressures is 10% of the median value. If the difference
exceeds this value, the machine must be shut down and the difference corrected
before it is restarted.
x Turbine and auxiliaries temperatures
Like the pressures, the temperatures reflect the proper functioning of the systems.
Sometimes it is also necessary to monitor temperature differences between inlet
and outlet; example: difference between oil supply and oil drain at bearings.
x Shaft line vibration
The vibration values read out after the first run-ups of the turbo-generator set
represent the vibration signature of the shaft line. This signature is machine-
specific.
Rev. : A
Page : 9/9
OPERATION AND MAINTENANCE MANUAL
OPERATION
- Turbine speed (TNH), control signal (FSR) and exhaust temperature (TTXM) as
a function of the start-up time.
- Start-up time. The start-up time must always be timed with respect to the same
conditions; example: from the start command when the machine is turning until
the 100% speed level.
x Shut down
Measurement of the shutdown time allows to validate the rotating conditions of the
shaft line. The timing must also be performed under the same conditions; example:
from 99% speed level until activation of the turning gear.
x External environment
For analysis of the environmental parameters of the gas turbine, reference shall be
made to the documents of the manufacturers.
The vibration measurements discussed in this chapter are carried out with a portable
device. The measuring schedule may be monthly or bimonthly. It is important to specify
the following:
x The type of value measured: displacement or speed.
x The units : µm or mm/s.
x The amplitude: single or double.
The readouts are related to the following auxiliaries: motor pump units, motor fans,
auxiliary gearbox. Vibration displacement measurements on lifting trunions or on the
bases of the different modules provide information on the strength of the anchorages in
the civil engineering structures.
It is advisable to mark the exact location of the measurements on the equipment to allow
the results to be compared in time (for instance, by applying paint marks).
To characterize the vibration, it is preferable to make 3 measurements in the same plane:
x Along the vertical axis, (V : vertical).
x Along the horizontal axis parallel to the axis of rotation, (A : axial or L :
longitudinal).
x Along the horizontal axis perpendicular to the axis of rotation. (H : horizontal or
T : transverse).
4.4. ANALYSIS
Increased vibrations are often an indication of degradation of the rotating parts of the
machine, of their attachments or of their alignment.
Refer to the supplier documents for the acceptable limits and the corrective actions.
In certain cases the vibration frequency and phase values need to be measured to allow
for a more precise diagnostic.
Rev. : A
Page : 1/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
OPERATION SEQUENCES
1. INTRODUCTION ................................................................................................................. 2
1.1. FOREWORD........................................................................................................................ 2
1.2. OPERATING SEQUENCES ................................................................................................ 2
1.3. SCREEN SHOTS................................................................................................................. 2
2. OPERATOR RESPONSIBILITY.......................................................................................... 3
3. TURNING GEAR OPERATION (COOLDOWN CONTROL) ............................................... 3
3.1. INITIAL CONDITIONS ......................................................................................................... 3
3.2. SEQUENCES ...................................................................................................................... 4
3.3. FINAL CONDITIONS ........................................................................................................... 5
4. NORMAL START-UP .......................................................................................................... 6
4.1. INITIAL CONDITIONS ......................................................................................................... 6
4.2. SEQUENCES ...................................................................................................................... 7
4.3. FINAL CONDITIONS ........................................................................................................... 9
5. SYNCHRONIZING............................................................................................................. 10
5.1. INITIAL CONDITIONS ....................................................................................................... 10
5.2. SEQUENCES .................................................................................................................... 11
5.3. FINAL CONDITIONS ......................................................................................................... 11
6. LOAD PICK UP ................................................................................................................. 12
6.1. INITIAL CONDITIONS ....................................................................................................... 12
6.2. SEQUENCES .................................................................................................................... 13
6.3. FINAL CONDITIONS ......................................................................................................... 13
7. LEAD / LAG MOTORS...................................................................................................... 14
7.1. INITIAL CONDITIONS ....................................................................................................... 14
7.2. SEQUENCES .................................................................................................................... 14
7.3. FINAL CONDITIONS ......................................................................................................... 15
8. NORMAL SHUTDOWN ..................................................................................................... 16
8.1. INITIAL CONDITIONS ....................................................................................................... 16
8.2. SEQUENCES .................................................................................................................... 16
8.3. FINAL CONDITIONS ......................................................................................................... 17
9. EMERGENCY SHUTDOWN.............................................................................................. 17
9.1. INITIAL CONDITIONS ....................................................................................................... 17
9.2. SEQUENCES .................................................................................................................... 17
9.3. FINAL CONDITIONS ......................................................................................................... 17
10. ON-LINE COMPRESSOR WASH ..................................................................................... 18
10.1. INITIAL CONDITIONS ....................................................................................................... 18
10.2. SEQUENCES .................................................................................................................... 18
10.3. FINAL CONDITIONS ......................................................................................................... 19
11. OFF-LINE COMPRESSOR WASH.................................................................................... 20
11.1. INITIAL CONDITIONS ....................................................................................................... 20
11.2. SEQUENCES .................................................................................................................... 21
11.3. FINAL CONDITIONS ......................................................................................................... 22
Rev. : A
Page : 2/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
1. INTRODUCTION
1.1. FOREWORD
After on-site installation, the first commissioning of the gas turbine is carried out with the
participation of General Electric Engineers and according to the specific commissioning
procedures.
The present document, which relates to the operation of the gas turbine, only addresses
the normal operating procedures.
Each technical intervention on the gas turbine must be backed up by a work permit.
Strict adherence to the work permit procedures guarantees the safety of the personnel as
well as observance of the initial functional configuration of equipments.
The sequences described in the tables below include initial conditions, sequences and
final conditions. The sequences are represented in four columns:
x The first column, titled Input, lists the manually initiated actions and significant
thresholds in sequences execution
x The second column describes the main events
x The third column, titled Output, lists the principal motors
x The last column, title Status, specifies the status of the relevant component or
sequence:
¾ 0 means that the motor stops
¾ 1 means that the motor runs
¾ 2min means that the sequence lasts 2 minutes
The screen shots included in this document are carried out without equipment of control
connected to the gas turbine. The posted physical values are thus not representative of
operating parameters.
Example: -18°C for the exhaust temperature.
These sights only facilitate the understanding of the text.
Rev. : A
Page : 3/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
2. OPERATOR RESPONSIBILITY
The operator is a person, authorized by his employer, who is familiar with the operation
of a turbo-generator used for electrical power generation.
His role consists in conducting the installation in accordance with the relevant
operational, system and personal safety procedures.
Rev. : A
Page : 4/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
3.2. SEQUENCES
Rev. : A
Page : 5/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
The shaft line rotates at low speed and the gas turbine is available for start-up.
Deselecting the turning gear sequence will stop the shaft line rotation if the turbine is
cold.
Rev. : A
Page : 6/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
4. NORMAL START-UP
If the shaft is already turning, following the start command, the starting frequency
converter starts, the turning motor stops and the sequence proceeds as described below.
When the gas turbine has been at standstill for more than two days without barring, it is
recommended to start the auxiliaries first and keep the machine at turning speed for few
minutes, as described in the above chapter “cool down control”. After few minutes
running, the normal start up sequence may be initiated.
Rev. : A
Page : 7/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
4.2. SEQUENCES
Rev. : A
Page : 8/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev. : A
Page : 9/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
Lubrication of the shaft line is ensured by one of the two AC lube oil pump.
Gas turbine is at nominal speed, generator excited at nominal voltage, turbo-generator
set ready to be synchronized to the grid for electrical power supply.
Rev. : A
Page : 10/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
5. SYNCHRONIZING
RESYNC push button has the same function as automatic synchronizing. It must be used
to allow automatic re-synchronizing.
Rev. : A
Page : 11/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
5.2. SEQUENCES
Rev. : A
Page : 12/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
6. LOAD PICK UP
Preselect: the load reaches a preselected power according to a loading slope defined by
the Speedtronic.
Base: the load increase until the base load is reached according to a loading slope
defined by the Speedtronic.
Action on + / - Speed push buttons cancels Base mode selection.
External Load: The load follows the external load command given by remote operation
according to a loading slope defined by the Speedtronic.
Action on + / - Speed push buttons cancels External mode selection.
Manual: Action on + / - Speed push buttons allows the operator to adjust the load.
Rev. : A
Page : 13/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
6.2. SEQUENCES
Rev. : A
Page : 14/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
Some motors and associated driven components like pumps, fans, boosters, are
redundant and running in a lead/lag philosophy which means that the operating motor is
the “lead” motor, the other been in standby. The operator has the choice to select the
motor to run by #1 Lead or #2 Lead, and to change over to the standby motor at any
time, to balance the running hours. Changeover is manual, or automatic in case of failure
of the active motor.
Auto Rotate : Enable / Disable : if Enable is selected, the automatic change over occurs
at each starting sequence of the gas turbine. If Disable is selected, the lead motor
selected by the operator remain the same at each gas turbine starting up.
Prior to any manual changeover, check that the relevant motor and associated system
are available.
7.2. SEQUENCES
Rev. : A
Page : 15/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
Suppose two redundant motors and associated driven components M1 and M2. M1 is the
lead motor, M2 is the standby motor. If M1 fails, M2 starts automatically, a corresponding
alarm will inform the operator. The speedtronic logic will keep in memory that M1 is “lead”,
the operator must select “M2 lead” to confirm unavailability of M1.
Rev. : A
Page : 16/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
8. NORMAL SHUTDOWN
8.2. SEQUENCES
Rev. : A
Page : 17/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
The shaft line is rotating at turning gear speed to allow the cooling cycle to be carried out.
The compartments fans remain in operation according to the compartments temperature.
The cooling water pump remains in operation according to lube oil temperature.
Deselecting the turning gear sequence is forbidden during the first hours of cooling.
Normal restart is possible at any time.
9. EMERGENCY SHUTDOWN
This action can be initiated with the gas turbine loaded, starting or in normal shutdown
condition:
x Either by pressing an emergency shutdown pushbutton.
x Or through the operation of an electrical or mechanical protection.
9.2. SEQUENCES
Rev. : A
Page : 18/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
10.2. SEQUENCES
Rev. : A
Page : 19/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev. : A
Page : 20/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
A B C D E
Turbine speed
20
10
0
0 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90
Time
Rev. : A
Page : 21/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
11.2. SEQUENCES
Rev. : A
Page : 22/22
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
ALARMS INTERPRETATION
SIGNAL NAME ALARM TEXT POSSIBLES CAUSES ACTIONS TO BE TAKEN
GENERATOR BRG #1 T1 METAL The generator bearing metal temperature (journal #1 ) is Check bearing (journal #1).
BTGJ1_1_ALM
TEMP HIGH high Check lube oil system and drain piping
GENERATOR BRG #1 T1 METAL The generator bearing metal temperature (journal #1 ) is Check bearing (journal #1).
BTGJ1_1H_ALM
TEMP HIGH HIGH very high Check lube oil system and drain piping
GENERATOR BRG #1 T2 METAL The generator bearing metal temperature (journal #1 ) is Check bearing (journal #1).
BTGJ1_2_ALM
TEMP HIGH high Check lube oil system and drain piping
GENERATOR BRG #1 T2 METAL The generator bearing metal temperature (journal #1 ) is Check bearing (journal #1).
BTGJ1_2H_ALM
TEMP HIGH HIGH very high Check lube oil system and drain piping
Check lube oil system
GENERATOR BRG #2 T1 METAL Bearing metal temperature of generator journal #2 high. Check cooling water system.
BTGJ2_1_ALM
TEMP HIGH Thermocouple fault. Check bearings.
Check thermocouples BT_GJ2_1A.
GENERATOR BRG #2 T1 METAL The generator bearing metal temperature (journal #2 ) is Check bearing (journal #2).
BTGJ2_1H_ALM
TEMP HIGH HIGH very high Check lube oil system and drain piping
Check lube oil system
GENERATOR BRG #2 T2 METAL Bearing metal temperature of generator journal #2 high. Check cooling water system.
BTGJ2_2_ALM
TEMP HIGH Thermocouple fault. Check bearings.
Check thermocouples BT_GJ2_2A.
GENERATOR BRG #2 T2 METAL The generator bearing metal temperature (journal #2 ) is Check bearing (journal #2).
BTGJ2_2H_ALM
TEMP HIGH HIGH very high Check lube oil system and drain piping
TURBINE BRG #1 T1 METAL TEMP Check bearing (journal #1).
BTJ1_1_ALM The turbine bearing metal temperature (journal #1 ) is high
HIGH Check lube oil system and drain piping
TURBINE BRG #1 T1 METAL TEMP The turbine bearing metal temperature (journal #1 ) is very Check bearing (journal #1).
BTJ1_1H_ALM
HIGH HIGH high Check lube oil system and drain piping
TURBINE BRG #1 T2 METAL TEMP Check bearing (journal #1).
BTJ1_2_ALM The turbine bearing metal temperature (journal #1 ) is high
HIGH Check lube oil system and drain piping
TURBINE BRG #1 T2 METAL TEMP The turbine bearing metal temperature (journal #1 ) is very Check bearing (journal #1).
BTJ1_2H_ALM
HIGH HIGH high Check lube oil system and drain piping
TURBINE BRG #2 T1 METAL TEMP Check bearing (journal #2).
BTJ2_1_ALM The turbine bearing metal temperature (journal #2 ) is high
HIGH Check lube oil system and drain piping
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
TURBINE BRG #2 T1 METAL TEMP The turbine bearing metal temperature (journal #2 ) is very Check bearing (journal #2).
BTJ2_1H_ALM
HIGH HIGH high Check lube oil system and drain piping
TURBINE BRG #2 T2 METAL TEMP Check bearing (journal #2).
BTJ2_2_ALM The turbine bearing metal temperature (journal #2 ) is high
HIGH Check lube oil system and drain piping
TURBINE BRG #2 T2 METAL TEMP The turbine bearing metal temperature (journal #2 ) is very Check bearing (journal #2).
BTJ2_2H_ALM
HIGH HIGH high Check lube oil system and drain piping
Check bearings and lube oil system.
RED GEAR FWD BULL BRG #1 Red gear bearing or lube oil problem
BTRGB11_ALM Check that lube oil circulate correctly in the load gear.
METAL TC HIGH Load compartment ventilation fault
Check load compartment ventilation.
RED GEAR FWD BULL BRG #1 The turbine bearing metal temperature (journal #1 ) is very Check bearing (journal #1).
BTRGB11H_ALM
METAL TC HIGH HIGH high Check lube oil system and drain piping
RED GEAR FWD BULL BRG #2 The reduction gear forward bull bearing #2metal Check reduction gear forward bull bearing #2metal bearing.
BTRGB12_ALM
METAL TC HIGH temperature is high Check lube oil system and drain piping
RED GEAR FWD BULL BRG #2 The turbine bearing metal temperature (journal #1 ) is very Check bearing (journal #1).
BTRGB12H_ALM
METAL TC HIGH HIGH high Check lube oil system and drain piping
RED GEAR AFT BULL BRG #1 The reduction gear after bull bearing #1 metal temperature Check reduction gear after bull bearing #2metal bearing.
BTRGB21_ALM
METAL TC HIGH is high Check lube oil system and drain piping
RED GEAR AFT BULL BRG #1 The reduction gear after bull bearing #1 metal temperature Check reduction gear after bull bearing #2metal bearing.
BTRGB21H_ALM
METAL TC HIGH HIGH is high Check lube oil system and drain piping
RED GEAR AFT BULL BRG #2 The reduction gear after bull bearing #2metal temperature Check reduction gear after bull bearing #2metal bearing.
BTRGB22_ALM
METAL TC HIGH is high Check lube oil system and drain piping
RED GEAR AFT BULL BRG #2 The turbine bearing metal temperature (journal #2 ) is very Check bearing (journal #2).
BTRGB22H_ALM
METAL TC HIGH HIGH high Check lube oil system and drain piping
Check pinion and lube oil system.
RED GEAR FWD PINION BRG #1 Red gear pinion or lube oil problem.
BTRGP11_ALM Check that lube oil circulate correctly in the load gear.
METAL TC HIGH Load compartment ventilation fault
Check load compartment ventilation.
RED GEAR FWD PINION BRG #1 The turbine bearing metal temperature (journal #1 ) is very Check bearing (journal #1).
BTRGP11H_ALM
METAL TC HIGH HIGH high Check lube oil system and drain piping
RED GEAR FWD PIN BRG #2 The reduction gear forward pinion bearing #2metal Check reduction gear forward pinion bearing #2metal bearing.
BTRGP12_ALM
METAL TC HIGH temperature is high Check lube oil system and drain piping
RED GEAR FWD PIN BRG #2 The turbine bearing metal temperature (journal #1 ) is very Check bearing (journal #1).
BTRGP12H_ALM
METAL TC HIGH HIGH high Check lube oil system and drain piping
Check pinion and lube oil system.
RED GEAR AFT PINION BRG #1 Red gear pinion or lube oil problem.
BTRGP21_ALM Check that lube oil circulate correctly in the load gear.
METAL TC HIGH Load compartment ventilation fault
Check load compartment ventilation.
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
RED GEAR AFT PINION BRG #1 The turbine bearing metal temperature (journal #2 ) is very Check bearing (journal #2).
BTRGP21H_ALM
METAL TC HIGH HIGH high Check lube oil system and drain piping
RED GEAR AFT PIN BRG #2 The reduction gear after pinion bearing #2metal Check reduction gear after pinion bearing #2metal bearing.
BTRGP22_ALM
METAL TC HIGH temperature is high Check lube oil system and drain piping
RED GEAR AFT PIN BRG #2 The turbine bearing metal temperature (journal #2 ) is very Check bearing (journal #2).
BTRGP22H_ALM
METAL TC HIGH HIGH high Check lube oil system and drain piping
BRG METAL TEMP THRUST Check bearing (thrust active).
BTTA1_12_ALM The bearing metal temperature (thrust active ) is high
ACTIVE 12 HIGH Check lube oil system and drain piping
BRG METAL TEMP THRUST Check bearing (thrust active).
BTTA1_12H_A The bearing metal temperature (thrust active ) is very high
ACTIVE 12 HIGH HIGH Check lube oil system and drain piping
BRG METAL TEMP THRUST Check bearing (thrust active).
BTTA1_6_ALM The bearing metal temperature (thrust active ) is high
ACTIVE 6 HIGH Check lube oil system and drain piping
BRG METAL TEMP THRUST Check bearing (thrust active).
BTTA1_6H_ALM The bearing metal temperature (thrust active ) is very high
ACTIVE 6 HIGH HIGH Check lube oil system and drain piping
BRG METAL TEMP THRUST Check bearing (thrust inactive).
BTTI1_4_ALM The bearing metal temperature (thrust inactive ) is high
INACTIVE 4 HIGH Check lube oil system and drain piping
BRG METAL TEMP THRUST The bearing metal temperature (thrust inactive ) is very Check bearing (thrust inactive).
BTTI1_4H_ALM
INACTIVE 4 HIGH HIGH high Check lube oil system and drain piping
BRG METAL TEMP THRUST Check bearing (thrust inactive).
BTTI1_8_ALM The bearing metal temperature (thrust inactive ) is high
INACTIVE 8 HIGH Check lube oil system and drain piping
BRG METAL TEMP THRUST The bearing metal temperature (thrust inactive ) is very Check bearing (thrust inactive).
BTTI1_8H_ALM
INACTIVE 8 HIGH HIGH high Check lube oil system and drain piping
FUEL GAS STAINER DIFF PRESS Check 4-20mA 96FSDP-11 transmitter (connections, cables.).
FSDPH_ALM 4-20mA 96LFSDP-11 fault
HIGH Replace transmitter if necessary.
GAS STRAINER DIFF PRESS HIGH Check 4-20mA 96FSDP-11 transmitter (connections, cables.).
FSDPHH_ALM 4-20mA 96LFSDP-11 fault
MAIN REQD Replace transmitter if necessary.
The speed control system has not limited turbine speed
PROTECTIVE MODULE Determine and repair before restarting (mechanical, electrical
L12H_ACC_ALM with the trip limits (fault detected by P module).
ACCELERATION TRIP _ HP or fuel or speed control trouble).
The turbine trips during the electrical over speed test
The speed control system has not limited turbine speed
ELECTRICAL OVERSPEED TRIP - Determine and repair before restarting (mechanical, electrical
L12H_ALM within the trip limits.
HP or fuel or speed control trouble).
The turbine trips during the electrical over speed test.
LOSS OF PROTECTIVE HP SPEED
L12H_FLT_ALM VPRO modules fault Check VPRO modules
SIGNALS
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
PROTECTIVE MODULE
Investigate cause of over speed.
L12H_P_ALM OVERSPEED TRIP _ HP (HIGH <P> module HP over speed trip.
Check the module over speed (power supply, short, link, cut).
PRESSURE)
Search the cause of this problem :
Check electronic over speed system.
The trip circuit has been tripped by mechanical over speed Check proper operation and setting of over speed bolt
L12HBLT_ALM OVERSPEED BOLT TRIP _ HP
action. assembly.
Repair before starting and reset manually the mechanical over
speed limit switch on the over speed bolt.
Check wiring to speed pickups.
Machine tripped due to loss of speed signal.
Check speed system.
CONTROL SPEED SIGNAL LOSS _ Control speed signal loss and the unit trips (TNH_OS).
L12HF_ALM Check supply, connections.
HP Power supply fault, ground, short, open.
Check the logic circuit.
Speed magnetic pickups fault (77 HT_1,2,3).
Check speed magnetic pickups.
CONTROL SPEED SIGNAL
L12HFD_C_ALM HP speed pickup voting mismatch in <C> Check and recalibrate HP speed pickups.
TROUBLE _HP
PROTECTIVE SPEED SIGNAL
L12HFD_P_ALM HP speed pickup voting mismatch in<P> Check and recalibrate HP speed pickups.
TROUBLE
Defective speed sensors of speed Check speed sensors (setting value, wiring )
Uncoupling between TG and alternator Check PTUR and PPRO cards
L14CX_FLT TURB PURG SPEED LEVEL FAULT
Trip SFC Check coupling between TG and alternator
rolling-up alternator fault Check SFC fault and reset
Check the valve
WATER INJ PURGE FAIL TO OPEN Water fuel purge fail to open : Check water injection system
L20WP1_ALM
SHUTDOWN Valve fault Refer to specific chapters for more information about the fire
protection.
K25A RELAY HAS NOT BEEN
L25A_ENAB_AL Synchronization permissive disable Check synchronization permissive
ENABLED
Check water supply to the atomizing air pre-cooler, isolating
valve position flow restrictions.
Check for leakage in the cooling water circuit.
Failure of atomizing pre-cooler louvers to open and close
ATOMIZING AIR TEMPERATURE Check the proper operation of the thermocouples
L26AAH_ALM Lack of water in the cooling system.
HIGH Check the temperature control system of the cooling water
Temperature control of the water circuit in faulty.
circuit.
Check the regulating valve and its setting point.
During start-up, check the atomizing air temperature.
All right reserved Copyright – Droits de reproduction réservés
OMMO_5_6FA_E1018_EN_V3 Revision : A Date : 05/2011
Page :4/74
GE Energy
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
88AK1 STATOR TEMPERATURE One of the three sensor is not ok Check sensors
L26STAK1HH_A
VERY HIGH Standby motor running Check motor
88AK2 STATOR TEMPERATURE Check sensors
L26STAK2HALM One of the three sensor is not ok
HIGH Check motor
88AK2 STATOR TEMPERATURE One of the three sensor is not ok Check sensors
L26STAK2HH_A
VERY HIGH Standby motor running Check motor
TURBINE CTRL COMPARTMENT
L26TCCH_ALM The temperature is high in the turbine compartment control. Check the ventilation system
HIGH
TURBINE CTRL COMPARTMENT
L26TCCL_ALM The temperature is low in the turbine compartment control. Check the ventilation system
LOW
FAULT WOBBE INDEX INHIBITION
L26TFWILD_A For information For information
RELEASE LOAD CONTROL
Check water supply to the load gear air pre-cooler, isolating
Failure of load gear pre-cooler louvers to open and close valve position flow restrictions.
HEAT VENT VERY HIGH TEMP. IN Normal shutdown. Check for leakage in the cooling water circuit.
L26VAHH_ALM
LOAD GEAR COMPARTMENT Lack of water in the cooling system. Check the temperature control system of the cooling water
Temperature control of the water circuit in faulty. circuit.
Check the regulating valve VTR2_1 and its setting point.
HEAT VENT VERY LOW TEMP. IN
L26VALL_ALM See alarm : L26VAHH_ALM See alarm : L26VAHH_ALM
LOAD GEAR COMPARTMENT
Check water supply to the DLN air pre-cooler, Isolating valve
Failure of DLN pre-cooler louvers to open and close position flow restrictions.
HEAT VENT VERY HIGH TEMP. IN Normal shutdown. Check for leakage in the cooling water circuit.
L26VLHH_ALM
DLN COMPARTMENT Lack of water in the cooling system. Check the temperature control system of the cooling water
Temperature control of the water circuit in faulty. circuit.
Check the regulating valve VTR2_1 and its setting point.
HEAT VENT VERY LOW TEMP. IN
L26VLLL_ALM See alarm : L26VLHH_ALM See alarm : L26VLHH_ALM
DLN COMPARTMENT
COOLING WATER TEMPERATURE
L26WC_FLT Cooling water Temperature fault Check cooling water system
FAULT
COOLING WATER TEMPERATURE
L26WCHH_ALM Cooling water temperature fault Check cooling water temperature system
VERY HIGH
Check battery charger AC breaker.
BAT CHAR AC UNDERVOLT - T.D. Battery charger AC under voltage.
L27BLN11_ALM Check voltage magnitude.
NORMAL SD Charger faulty.
Check the proper operation of the battery charger.
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Check SRV
SRV position fault
GAS FUEL INTER-VALVE PRESS. Check GCV
L30FPG2L_ALM GCV position fault
(P2) LOW Check gas feeding
Gas feeding fault
Check regulating system
LOSS OF FIRE PROTECTION - GT
L30FTA_ALM Fire Protection System Faulty Check the Fire Protection System
NORMAL SHUTDOWN
L30FTGH_ALM FUEL GAS TEMPERATURE HIGH Fuel gas temperature high Check fuel gas temperature system
Fuel gas temperature high.
L30FTGHH_ALM FTG HIGH-HIGH - HEATER TRIP Check the heater.
Heater fault
FUEL GAS TEMPERATURE HIGH-
L30FTGSD_ALM Fuel gas temperature high Check fuel gas temperature system
HIGH SHUTDOWN
Check the ventilation system of this compartment.
Check fuses, breakers, protections, supplies.
LIQUID FUEL COMP. VENT. The liquid fuel compartment ventilation is faulty. Check the mechanical status of the fan and the motor in
L30FVX_ALM
CHANGE OVER FAULT Motor 88FV_1 or 2 fault trouble.
Check the proper operation of the cooling air fan motor 88FV
Check the position of vent flap.
L30GRD_ALM GAS DETECTION RACK FAULT Gas detection rack fault Check gas detection rack
HEAT VENT LOAD
Check heater
L30HG1X_ALM COMPARTMENT HEATER IN Heater fault
Check fuses, breakers, protections, supplies.
TROUBLE
Check the ventilation system of this compartment..
Check fuses, breakers, protections, supplies.
HEAT VENT WATER INJ COMP The water injection compartment ventilation is faulty. Check the mechanical status of the fan and the motor in
L30JSX_ALM
VENT. . CHANGE OVER Motor 88JS_1 or 2 fault trouble.
Check the proper operation of the cooling air fan motor 88JS
Check the position of vent flap.
LIQ FUEL PURGE DIFF PRESS Liquid fuel purge diff press transmitter value difference
L30LFDP_FLT Check setting of 96PL-1A, 96PL-1B, 96PL-1C
XDUCER FAULT measure >0.5 psi between Higher ad lower value
LIQ FUEL PURGE DIFF PRESS Liquid fuel purge diff press transmitter value difference
L30LFDP_FLT Check setting of 96PL-1A, 96PL-1B, 96PL-1C
XDUCER FAULT measure >0.5 psi between Higher ad lower value
LIQUID FUEL PURGE LOW
L30LFPLA Transmitters 96PL-1A,B, C fault. Check the transmitters 96 PL-1A, B, C.
PRESSURE RATIO
LIQ FUEL PURGE MED DIFF
L30LFPTA Transmitters 96PL-1A,B, C fault. Check the transmitters 96 PL-1A, B, C.
PRESS TRBL
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
VIB BN GEN BRG #2 RADIAL Generator bearing 2 radial shat displacement alert
L39VS10D_ALM Check vibration sensors and wiring.
SHAFT DISPLACEMENT DANGER 2nd step
VIB BN GT BRG #1 RADIAL SHAFT GT bearing 1 radial shat displacement alert
L39VS1A_ALM Check vibration sensors and wiring.
DISPLACEMENT ALERT 1st step
VIB BN GT BRG #1 RADIAL SHAFT GT bearing 2 radial shat displacement alert
L39VS1D_ALM st Check vibration sensors and wiring.
DISPLACEMENT DANGER 1 step
VIB BN GT BRG #2 RADIAL SHAFT GT bearing 1 radial shat displacement alert
L39VS2A_ALM Check vibration sensors and wiring.
DISPLACEMENT ALERT 2nd step
VIB BN GT BRG #2 RADIAL SHAFT GT bearing 2 radial shat displacement danger
L39VS2D_ALM Check vibration sensors and wiring.
DISPLACEMENT DANGER 2nd step
VIB BN LG BRG #1 RADIAL SHAFT
L39VS5A_ALM LG bearing #1 radial shat displacement alert Check vibration sensors and wiring.
DISPLACEMENT ALERT
VIB BN LG BRG #1 RADIAL SHAFT
L39VS5D_ALM Generator bearing 1 radial shat displacement alert Check vibration sensors and wiring.
DISPLACEMENT DANGER
VIB BN LG BRG #2 RADIAL SHAFT
L39VS6A_ALM LG bearing #2 radial shat displacement alert Check vibration sensors and wiring.
DISPLACEMENT ALERT
VIB BN LG BRG #2 RADIAL SHAFT
L39VS6D_ALM Generator bearing 2 radial shat displacement alert Check vibration sensors and wiring.
DISPLACEMENT DANGER
VIB BN LG BRG #3 RADIAL SHAFT
L39VS7A_ALM LG bearing #3 radial shat displacement alert Check vibration sensors and wiring.
DISPLACEMENT ALERT
VIB BN LG BRG #3 RADIAL SHAFT
L39VS7D_ALM Generator bearing 3 radial shat displacement alert Check vibration sensors and wiring.
DISPLACEMENT DANGER
VIB BN LG BRG #4 RADIAL SHAFT
L39VS8A_ALM LG bearing #4 radial shat displacement alert Check vibration sensors and wiring.
DISPLACEMENT ALERT
VIB BN LG BRG #4 RADIAL SHAFT
L39VS8D_ALM Generator bearing 3 radial shat displacement alert Check vibration sensors and wiring.
DISPLACEMENT DANGER
VIB BN GEN BRG #1 RADIAL GEN bearing 1 radial shat displacement alert
L39VS9A_ALM Check vibration sensors and wiring.
SHAFT DISPLACEMENT ALERT 1st step
VIB BN GEN BRG #1 RADIAL GEN bearing 1 radial shat displacement alert
L39VS9D_ALM Check vibration sensors and wiring.
SHAFT DISPLACEMENT DANGER 2nd step
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
L3PAIC_1A5AR_DIAG <R> PAIC 1A5A DIAGNOSTIC See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1A5AR_FLT <R> PAIC 1A5A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1A5AS_DIAG <S> PAIC 1A5A DIAGNOSTIC See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1A5AS_FLT <S> PAIC 1A5A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1A5AT_DIAG <T> PAIC 1A5A DIAGNOSTIC See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1A5AT_FLT <T> PAIC 1A5A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1B1AS_FLT <S> PAIC 1B1A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1B1AT_FLT <T> PAIC 1B1A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1B2AR_FLT <R> PAIC 1B2A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1B2AS_FLT <S> PAIC 1B2A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1B2AT_FLT <T> PAIC 1B2A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1B3AR_FLT <R> PAIC 1B3A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1B3AS_FLT <S> PAIC 1B3A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1B3AT_FLT <T> PAIC 1B3A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1B4AR_FLT <R> PAIC 1B4A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1B4AS_FLT <S> PAIC 1B4A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1B4AT_FLT <T> PAIC 1B4A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1C1R_FLT <R> PAIC 1C1 LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1C1S_FLT <S> PAIC 1C1 LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1C1T_FLT <T> PAIC 1C1 LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1D2AR_DIAG <R> PAIC 1D2A DIAGNOSTIC See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1D2AR_FLT <R> PAIC 1D2A FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1D2AS_DIAG <S> PAIC 1D2A DIAGNOSTIC See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1D2AS_FLT <S> PAIC 1D2A FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1D2AT_DIAG <T> PAIC 1D2A DIAGNOSTIC See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_1D2AT_FLT <T> PAIC 1D2A FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_2B1AR_FLT <R> PAIC 2B1A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_2B1AS_FLT <S> PAIC 2B1A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_2B1AT_FLT <T> PAIC 2B1A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_2B2AR_FLT <R> PAIC 2B2A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_2B2AS_FLT <S> PAIC 2B2A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_2B2AT_FLT <T> PAIC 2B2A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_2B3AR_FLT <R> PAIC 2B3A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_2B3AS_FLT <S> PAIC 2B3A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
L3PAIC_2B3AT_FLT <T> PAIC 2B3A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_2C1A_FLT PAIC 2C1A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_2C1B_FLT PAIC 2C1B LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_2C2A_FLT PAIC 2C2A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_2C2B_FLT PAIC 2C2B LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_2C3A_FLT PAIC 2C3A LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PAIC_2C3B_FLT PAIC 2C3B LINK FAULT See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PDIA_1E3A_DIAG PDIA 1E3A DIAGNOSTIC See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
L3PDIA_1E3B_DIAG PDIA 1E3A DIAGNOSTIC See alarm : L3PAIC_1A3AR_DIAG See alarm : L3PAIC_1A3AR_DIAG
Check alarm number in GEH-6721 vol II
Check board power supply is correctly connected else connect
it.
Check IO pack Ethernet link or power supply is correctly
connected (Leds on IO pack must be active), else connect it.
Check IR port of the IO pack is protected by its metallic
Wrong barcode in software
plate,else turn the plate until IR port is hidden.
L3PDIA_1E5R_FLT <R> PDIA 1E5 LINK FAULT Wrong firmware loaded in IO pack
Check barcode is identical on board and inside IO hardware
IO pack Ethernet link or power supply disconnected
configuration in the software, else change barcode number,
build and download.
Check Jumper is in the same position than configured in
software else changes the position to match the software.
Check firmware is correct in the IO pack else download again
the firmware with actual ToolbowST release.
L3PDIA_1E5S_FLT <S> PDIA 1E5 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_1E5T_FLT <T> PDIA 1E5 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_1F5R_FLT <R> PDIA 1F5 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_1F5S_FLT <S> PDIA 1F5 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_1F5T_FLT <T> PDIA 1F5 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_1G5R_FLT <R> PDIA 1G5 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_1G5S_FLT <S> PDIA 1G5 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_1G5T_FLT <T> PDIA 1G5 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_1H5_FLT PDIA 1H5 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2E1R_FLT <R> PDIA 2E1 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2E1S_FLT <S> PDIA 2E1 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2E1T_FLT <T> PDIA 2E1 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
All right reserved Copyright – Droits de reproduction réservés
OMMO_5_6FA_E1018_EN_V3 Revision : A Date : 05/2011
Page :33/74
GE Energy
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
L3PDIA_2E2R_FLT <R> PDIA 2E2 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2E2S_FLT <S> PDIA 2E2 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2E2T_FLT <T> PDIA 2E2 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2E3R_FLT <R> PDIA 2E3 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2E3S_FLT <S> PDIA 2E3 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2E3T_FLT <T> PDIA 2E3 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2F1R_FLT <R> PDIA 2F1 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2F1S_FLT <S> PDIA 2F1 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2F1T_FLT <T> PDIA 2F1 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2F2R_FLT <R> PDIA 2F2 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2F2S_FLT <S> PDIA 2F2 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2F2T_FLT <T> PDIA 2F2 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2F3R_FLT <R> PDIA 2F3 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2F3S_FLT <S> PDIA 2F3 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2F3T_FLT <T> PDIA 2F3 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2G1R_FLT <R> PDIA 2G1 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2G1S_FLT <S> PDIA 2G1 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2G1T_FLT <T> PDIA 2G1 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2G2R_FLT <R> PDIA 2G2 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2G2S_FLT <S> PDIA 2G2 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2G2T_FLT <T> PDIA 2G2 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2G3R_FLT <R> PDIA 2G3 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2G3S_FLT <S> PDIA 2G3 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2G3T_FLT <T> PDIA 2G3 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2G4R_FLT <R> PDIA 2G4 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2G4S_FLT <S> PDIA 2G4 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2G4T_FLT <T> PDIA 2G4 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2G5R_FLT <R> PDIA 2G5 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2G5S_FLT <S> PDIA 2G5 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2G5T_FLT <T> PDIA 2G5 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2H1_FLT PDIA 2H1 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2H2_FLT PDIA 2H2 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2H3_FLT PDIA 2H3 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
L3PDIA_2H4_FLT PDIA 2H4 LINK FAULT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
L3PDIA_2H5_FLT PDIA 2H5 LINK FLT See alarm : L3PDIA_1E5R_FLT See alarm : L3PDIA_1E5R_FLT
Check alarm number in GEH-6721 vol II
Check board power supply is correctly connected else connect
it.
Check IO pack Ethernet link or power supply is correctly
connected (Leds on IO pack must be active), else connect it.
Check IR port of the IO pack is protected by its metallic plate
Wrong barcode in software
else turn the plate until IR port is hidden.
L3PDOA_1E1R_FLT <R> PDOA 1E1 LINK FAULT Wrong firmware loaded in IO pack
Check barcode is identical on board and inside IO hardware
IO pack Ethernet link or power supply disconnected
configuration in the software, else change barcode number,
build and download.
Check Jumper is in the same position than configured in
software else changes the position to match the software.
Check firmware is correct in the IO pack else download again
the firmware with actual ToolbowST release.
L3PDOA_1E1S_FLT <S> PDOA 1E1 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1E1T_FLT <T> PDOA 1E1 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1E2R_FLT <R> PDOA 1E2 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1E2S_FLT <S> PDOA 1E2 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1E2T_FLT <T> PDOA 1E2 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1E3R_FLT <R> PDOA 1E3 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1E3S_FLT <S> PDOA 1E3 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1E3T_FLT <T> PDOA 1E3 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1E4R_FLT <R> PDOA 1E4 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1E4S_FLT <S> PDOA 1E4 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1E4T_FLT <T> PDOA 1E4 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1F1R_FLT <R> PDOA 1F1 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1F1S_FLT <S> PDOA 1F1 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1F1T_FLT <T> PDOA 1F1 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1F2R_FLT <R> PDOA 1F2 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1F2S_FLT <S> PDOA 1F2 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1F2T_FLT <T> PDOA 1F2 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1F3R_FLT <R> PDOA 1F3 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1F3S_FLT <S> PDOA 1F3 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1F3T_FLT <T> PDOA 1F3 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
All right reserved Copyright – Droits de reproduction réservés
OMMO_5_6FA_E1018_EN_V3 Revision : A Date : 05/2011
Page :35/74
GE Energy
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
L3PDOA_1F4R_FLT <R> PDOA 1F4 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1F4S_FLT <S> PDOA 1F4 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1F4T_FLT <T> PDOA 1F4 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1G1R_FLT <R> PDOA 1G1 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1G1S_FLT <S> PDOA 1G1 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1G1T_FLT <T> PDOA 1G1 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1G2R_FLT <R> PDOA 1G2 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1G2S_FLT <S> PDOA 1G2 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1G2T_FLT <T> PDOA 1G2 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1G3R_FLT <R> PDOA 1G3 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1G3S_FLT <S> PDOA 1G3 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1G3T_FLT <T> PDOA 1G3 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1G4R_FLT <R> PDOA 1G4 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1G4S_FLT <S> PDOA 1G4 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1G4T_FLT <T> PDOA 1G4 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1H1_FLT PDOA 1H1 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1H2_FLT PDOA 1H2 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1H3_FLT PDOA 1H3 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
L3PDOA_1H4_FLT PDOA 1H4 LINK FAULT See alarm : : L3PDOA_1E1R_FLT See alarm : : L3PDOA_1E1R_FLT
Check alarm number in GEH-6721 vol II
Check board power supply is correctly connected else connect
it.
Check IO pack Ethernet link or power supply is correctly
connected (Leds on IO pack must be active), else connect it.
Check IR port of the IO pack is protected by its metallic plate,
Wrong barcode in software
else turn the plate until IR port is hidden.
L3PPDA_1D6A_FLT PPDA 1D6A LINK FAULT Wrong firmware loaded in IO pack
Check barcode is identical on board and inside IO hardware
IO pack Ethernet link or power supply disconnected
configuration in the software, else change barcode number,
build and download.
Check Jumper is in the same position than configured in
software, else change the position to match the software.
Check firmware is correct in the IO pack, else download again
the firmware with actual ToolbowST release.
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
L3PRTD_1C2B_FLT PRTD 1C2B LINK FAULT See alarm : L3PRTD_1C2A_FLT See alarm : L3PRTD_1C2A_FLT
L3PRTD_1C3A_FLT PRTD 1C3A LINK FAULT See alarm : L3PRTD_1C2A_FLT See alarm : L3PRTD_1C2A_FLT
L3PRTD_1C3B_FLT PRTD 1C3B LINK FAULT See alarm : L3PRTD_1C2A_FLT See alarm : L3PRTD_1C2A_FLT
Check alarm number in GEH-6721 vol II
Check board power supply is correctly connected else connect
it.
Check IO pack Ethernet link or power supply is correctly
connected (Leds on IO pack must be active), else connect it.
Check IR port of the IO pack is protected by its metallic plate
Wrong barcode in software
else turn the plate until IR port is hidden.
L3PSVO_1A5AR_FLT <R> PSVO 1A5A LINK FAULT Wrong firmware loaded in IO pack
Check barcode is identical on board and inside IO hardware
IO pack Ethernet link or power supply disconnected
configuration in the software, else change barcode number,
build and download.
Check Jumper is in the same position than configured in
software else changes the position to match the software.
Check firmware is correct in the IO pack else download again
the firmware with actual ToolbowST release.
L3PSVO_1A5AS_FLT <S> PSVO 1A5A LINK FAULT See alarm : L3PSVO_1A5AR_FLT See alarm : L3PSVO_1A5AR_FLT
L3PSVO_1A5AT_FLT <T> PSVO 1A5A LINK FAULT See alarm : L3PSVO_1A5AR_FLT See alarm : L3PSVO_1A5AR_FLT
L3PSVO_1B5AR_FLT <R> PSVO 1B5A LINK FAULT See alarm : L3PSVO_1A5AR_FLT See alarm : L3PSVO_1A5AR_FLT
L3PSVO_1B5AS_FLT <S> PSVO 1B5A LINK FAULT See alarm : L3PSVO_1A5AR_FLT See alarm : L3PSVO_1A5AR_FLT
L3PSVO_1B5AT_FLT <T> PSVO 1B5A LINK FAULT See alarm : L3PSVO_1A5AR_FLT See alarm : L3PSVO_1A5AR_FLT
L3PSVO_1C4AR_FLT <R> PSVO 1C4A LINK FAULT See alarm : L3PSVO_1A5AR_FLT See alarm : L3PSVO_1A5AR_FLT
L3PSVO_1C4AS_FLT <S> PSVO 1C4A LINK FAULT See alarm : L3PSVO_1A5AR_FLT See alarm : L3PSVO_1A5AR_FLT
L3PSVO_1C4AT_FLT <T> PSVO 1C4A LINK FAULT See alarm : L3PSVO_1A5AR_FLT See alarm : L3PSVO_1A5AR_FLT
L3PSVO_1C5AR_FLT <R> PSVO 1C5A LINK FAULT See alarm : L3PSVO_1A5AR_FLT See alarm : L3PSVO_1A5AR_FLT
L3PSVO_1C5AS_FLT <S> PSVO 1C5A LINK FAULT See alarm : L3PSVO_1A5AR_FLT See alarm : L3PSVO_1A5AR_FLT
L3PSVO_1C5AT_FLT <T> PSVO 1C5A LINK FAULT See alarm : L3PSVO_1A5AR_FLT See alarm : L3PSVO_1A5AR_FLT
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
HZD GAS DETEC GAS CAB A leak of gas is detected in the DLN/auxiliaries
L45HA5HH_ALM See alarm : L45HA4_ALM
COMPT#5 HIGH HIGH LEVEL compartment.#5
HZD GAS DETEC GAS
L45HA6_ALM A leak of gas is detected in the DLN compartment. See alarm : L45HA4_ALM
COMPCARD FLT - WAY #6
HZD GAS DETEC GAS CAB A leak of gas is detected in the DLN/auxiliaries
L45HA6HH_ALM See alarm : L45HA4_ALM
COMPT#6 HIGH HIGH LEVEL compartment.#6
HZD GAS DETEC HIGH HIGH
L45HGDHH_ALM A leak of gas is detected in the ventilation compartment See alarm : L45HA4_ALM
LEVEL INFORMATION
HZD GAS DETEC FAILURE - SHUT
L45HGDSD_ALM A leak of gas is detected in the ventilation compartment See alarm : L45HA4_ALM
DOWN
Gas leak detection alarm may be generated either by gas
detection loop fault or by a real gas leak.
Refer to Gas detection control system cabinet and relevant
component literature for detailed fault analysis.
Gas leak detection alarm must be considered as high priority.
Continued operation of the turbine is not recommended.
Proceed to normal shutdown to avoid later trip by higher
detection level.
For dual fuel machine, do not transfer to liquid fuel. This will not
eliminate the leak. The leak shall remain at the same place with
other fluid (e.g. purging air).
Do not open the door of the enclosure, keep the area around
HZD GAS DETEC TURB COMP
L45HT1_ALM Gas level high detected in the turbine compartment. free of people.
CARD FLT - WAY #1
Access to enclosure is only permitted when the unit is stopped,
on cooling sequence by ratchet system (Frame 6000B) or by
barring system (Other Frame) with issuing of the relevant
access permit or permit to work.
Visual check the flanges (Refer to Residual risks
summary/Maintenance phase) and the flexible metal hoses
(Refer to GEK 111694).
Pressurise the length/section of pipe according to End User
procedure and appropriate precautions. It may be worth using
portable gas detectors and/or leak detection liquids or spray to
find what caused the alarm.
Repair the leak and reset the alarm after investigation.
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
The second mist eliminator motor starts (88 QV_1A or 1B). Check the mechanical status of the fan.
MIST ELIMINATOR MOTOR Mechanical fault of fan. Check that the vent is not clogged.
L49QV_ALM
OVERLOAD Fan outlet clogged. Check the motor supply (fuses, breaker, connection)
Motor supply fault. Check the overload 49 QV_1 or 2.
Transfer to the second fan.
Check the mechanical status of the motor and the fan.
TURB SHELL & EXH FRAME MTR Electrical motor fault.
L49TK_ALM Check the motor supply (fuses, breaker, connection).
OVERLOAD Motor supply fault.
Check the overload relay
Mechanical fault of the motor and the fan.
Check the mechanical status of the motor and the fan.
Transfer to the second fan.
LOAD COMPARTMENT COOLING Check the motor supply (fuses, breaker, connections, short
L49VG_ALM Motor or fan fault (88VG).
FAN MOTOR OVERLOAD circuit).
Motor supply fault.
Check the overload relay 49VG_1 or 2.
Electrical motor fault. Check the mechanical status of the motor and the fan.
DLN COMPARTMENT VENT FANS
L49VL_ALM Motor supply fault. Check the motor supply (fuses, breaker, connection).
OVERLOAD
Mechanical fault of the motor and the fan. Check the overload relay
Check auxiliary motors to determine which motor is overloaded
and the cause of the overloading.
L49X_ALM AUXILIARY MOTOR OVERLOAD One of the auxiliary motors is overloaded. On the defective motor, check the overload relay, the fuses ,
the motor with the cables.
Check the set point of the overload relay.
L4AAT ATOMIZING AIR SYSTEM TRIP Problem with atomizing air system Investigate atomizing air system
L4BOILT_ALM GT TRIP ORDER FROM BOILER GT trip from boiler Refer to specific volume.
GT TRIP ORDER #2 FROM
L4BOILT2_ALM GT trip order #2 from boiler Check boiler
BOILER
Customer trips input to the L4CT logic have caused an Determine which of the customer trip devices caused the trip
L4CT_ALM CUSTOMER TRIP
automatic trip of the unit. and correct.
L4DLNT DRY LOW NOX SYSTEM TRIP DLN system fault, trip is required. Check DLN system trips and all other annunciated alarms.
REGULATION FAN BLOCK
L4FCBRUN_ALM Regulation block – fan starts For information
STARTS
GENERATOR PROTECTION
L4GP_ALM Refer to specific volume. Refer to specific volume.
GROUPED ALARM
GENERATOR PROTECTION
L4GP_T_ALM Refer to specific volume. Refer to specific volume.
GROUPED TRIP
GAS PURGE FAULT PRE-IGNITION
L4GPF_PIT Gas purge skid fault Check gas purge skid
TRIP
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Transfer to the second fan. Check the mechanical status of the motor and the fan.
HEAT VENT TURBINE Electrical motor fault (88 BT_1 or 2). Check the motor supply (fuses, breaker, connection).
L52BT_ALM
COMPARTMENT VENT. FAULT Motor supply fault. Check the overload relay 49 BT
Mechanical fault of the motor and the fan. Check the temperature switch 26BT.
CSF BREAKER CLOSURE Breaker closing system fault Check the breaker closing system
L52CSF_ALM
TROUBLE Something is blocking the breaker closing Check that nothing is blocking the breaker closing
Determine the breaker, which is open, and find the reason of its
Breaker opened by operator or tripped by high motor position (overload, fuses fault, defected motor, mechanical
L52FC1_2_ALM COOLING WATER FANS#1
temperature. problem of the motor or the fan, supply, etc.).
Correct cause of problem and close breaker.
L52FC11_12_A COOLING WTER FANS#11 See alarm : L52FC1_2_ALM See alarm : L52FC1_2_ALM
L52FC13_14_A COOLING WTER FANS#13 See alarm : L52FC1_2_ALM See alarm : L52FC1_2_ALM
L52FC15_16_A COOLING WTER FANS#15 See alarm : L52FC1_2_ALM See alarm : L52FC1_2_ALM
L52FC3_4_ALM COOLING WATER FANS#3 See alarm : L52FC1_2_ALM See alarm : L52FC1_2_ALM
L52FC5_6_ALM COOLING WATER FANS#5 See alarm : L52FC1_2_ALM See alarm : L52FC1_2_ALM
L52FC7_8_ALM COOLING WATER FANS#7 See alarm : L52FC1_2_ALM See alarm : L52FC1_2_ALM
L52FC9_10_AL COOLING WTER FANS#9 See alarm : L52FC1_2_ALM See alarm : L52FC1_2_ALM
LIQUID FUEL COMPARTMENT
L52FS_ALM Liquid fuel compartment heater feedback fault Check liquid fuel compartment heater feedback
HEATER FEEDBACK FAULT
Transfer to the second fan. Check the mechanical status of the motor and the fan.
Electrical motor fault (88 FV_1 or 2). Check the motor supply (fuses, breaker, connection).
L52FV_ALM LIQUID FUEL COMP. VENT. FAULT
Motor supply fault. Check the overload relay
Mechanical fault of the motor and the fan. Check the temperature switch.
Determine device that tripped the breaker.
The problem should be corrected before coupling again.
Generator breaker has been tripped by an automatic
L52G_ALM GENERATOR BREAKER TRIPPED NOTE :
protective device or manually.
For a new coupling, one must give a new start order for
proper operation of synchronizing sequence.
GENERATOR COMPT FAN
L52GV_ALM Generator compartment fan breaker fault Check generator compartment fan breaker
BREAKER FAULT
AIR INLET DUCT HEATER 23BL-1
L52HBL1_ALM Heater 23BL-1 activation requested, but not running Refer to L52HL_ALM
FEEDBACK FAULT
AIR INLET DUCT HEATER 23BL-1
L52HBL1_ALM Heater 23BL-1 activation requested, but not running Refer to L52HL_ALM
FEEDBACK FAULT
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
COOLDOWN SEQUENCE The cool down sequence has been interrupted before the Continue cool down sequence except in the case of major
L62CD_ALM
RUNNING end of normal cycle. problem.
WARNING : VENTIL AFTER OFF
L62WWY_ALM Ventilation system fault Check ventilation system
LINE INTERRUPTED
Check atomizing air system.
Check the valves .are correctly positioned.
Atomizing air compressor not providing adequate pressure. Check for leakage.
Normal shutdown. Check the status (mechanical and electrical) of the
ATOMIZING AIR DIFFERENTIAL Lack of air at the upstream of the compressor. compressors and the step up gears.
L63ADL_ALM
PRESSURE LOW Compressor fault (CA1_1 or 2). Check motor.
Step up gear fault. Check the check valves before step up gears.
Motor fault (88 AK_1 or 2). Check the proper operation of the pressure switches 63 AD_1,
2 and their setting point.
Check the proper operation of the transmitter 96AD_1.
Check the differential pressure switches 63 AD_1 and 3
ATOMIZING AIR DIFF. PRESS.
L63ADL_SENSR Pressure switches fault. (operation and setting point).
SWITCH TROUBLE
Check the proper operation of the transmitter 96AD_1
ATOMIZING AIR FILTER DIFF The atomizing air filter is dirty FA5_1. Clean or change the air filter if necessary.
L63AF1H_ALM
PRESS HIGH Transmitter fault 96AF_1. Check the transmitter.
LO COMP INLET FILTER
L63BLH_ALM The by pass of LO Comp inlet filter is clogged Clean inlet air filter
CLOGGED - BY PASS OPEN
TURB COMP INLET FILTER The by pass of the turbine compartment inlet filter is
L63BTH_ALM Clean heat vent aux compartment inlet air filter
CLOGGED - BY PASS OPEN clogged
L63CPDL_ALM CPD PRESSURE LOW ALARM CPD pressure low alarm Check GT compressor system
Check the filter status. Change it, if necessary.
Check the differential pressure switch 63 CS (operation and
TURB AIR INLET DIFF PRESS Inlet filter dirty.
L63CS1H_ALM setting point).
HIGH Pressure switch fault.
NOTE:
Refer to specific volumes for Air filter maintenance.
Check the filter status. Change it, if necessary.
Check the differential pressure switch 63 CS (operation and
COMPRESSOR INLET DIFF Inlet filter dirty.
L63CS2CH_ALM setting point).
PRESSURE HIGH ALARM Pressure switch fault.
NOTE:
Refer to specific volumes for Air filter maintenance.
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
The oil demister filter of the tank is dirty. Change the oil demister filter, if necessary.
L63QV_ALM LUBE OIL TANK - LOW VACUUM
Pressure switch fault. Check the pressure switch 63QV-1.
Check the pressure drop.
If the pressure is excessive, change the air filters.
If the pressure is correct, check the pressure switch 63 TF and
TURBINE AIR INLET DIFF. PRESS. Inlet filter excessive pressure drop.
L63TF1H_ALM its setting point.
ALARM Filter is dirty.
NOTE :
Refer to Manufacturer’s recommendations for air filters
maintenance in specific volumes.
LOAD COMP INLET FILTER
L63VGH_ALM The by pass of the DLN compartment inlet filter is clogged Clean DLN- compt inlet air filter
CLOGGED - BY PASS OPEN
DLN COMP INLET FILTER
L63VLH_ALM The by pass of the DLN compartment inlet filter is clogged Clean DLN- compt inlet air filter
CLOGGED - BY PASS OPEN
Check the pumps and motor.
COOLING WATER PUMP DISCH
L63WC1L_ALM The pressure of cooling water pump is low. Check leakage.
PRESS LOW
Check the status of the filters.
HIGH ON LINE WATER WASH
L63WW1H_ALM On line water wash manifold transmitter fault Checks 96WW-1 transmitters
MANIFOLD PRESSURE
VERY HIGH ON LINE WW
L63WW1HH_ALM On line water wash manifold transmitter fault Checks 96WW-1 transmitters
MANIFOLD PRESS - TRIP WW
LOW ON LINE WATER WASH
L63WW1L_ALM On line water wash manifold transmitter fault Checks 96WW-1 transmitters
MANIFOLD PRESSURE
VERY LOW ON LINE WW
L63WW1LL_ALM On line water wash manifold transmitter fault Checks 96WW-1 transmitters
MANIFOLD PRESS - TRIP WW
Immediate action should be taken to locate ground and to
repair, because if a second ground occurs, this can result in
severe damage to the wiring and to the battery. As soon as
possible, shut down the unit and check the 125 VDC power.
Insulation failure has resulted in a ground on the 125 VDC
L64D_ALM BATTERY 125VDC GROUND Isolate ground and remove from system.
system.
Check the DC motors and all circuits supplied with dc voltage.
CAUTION :
During this repair, the generator and the starting engine
breakers must be opened for safety.
HEAT SOAK PERIOD - LOWER
L70HTS_ALM Heat soak period - lower load For information
LOAD
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
FIRE PROTECTION ZONE 1 CO2 No more CO2 in the bottles Check if CO2 bottles are full. If empty, change them
L71CT1L_1_A
BOTTLE WEIGHT REDUCTION Leaks Check for leaks
FIRE PROTECTION ZONE 2 CO2 No more CO2 in the bottles Check if CO2 bottles are full. If empty, change them
L71CT1L_2_A
BOTTLE WEIGHT REDUCTION Leaks Check for leaks
FIRE PROTECTION ZONE 3 CO2 No more CO2 in the bottles Check if CO2 bottles are full. If empty, change them
L71CT1L_3_A
BOTTLE WEIGHT REDUCTION Leaks Check for leaks
FIRE PROTECTION ZONE 4 CO2 No more CO2 in the bottles Check if CO2 bottles are full. If empty, change them
L71CT1L_4_A
BOTTLE WEIGHT REDUCTION Leaks Check for leaks
FIRE PROTECTION ZONE 1 CO2 No more CO2 in the bottles Check if CO2 bottles are full. If empty, change them
L71CT1L_5_A
BOTTLE WEIGHT REDUCTION Leaks Check for leaks
Gas scrubber high
SCRUBBER LVL HIGH- TRANSFER Purge gas scrubber
L71GS_XFER_A Liquid fuel system not ready
LIQUID FAULT TRIP Check liquid fuel system
Trip
Check the liquid level in the gas filter separator and purge if
GAS FUEL SCRUBBER 101FI-2A
L71GS12A_ALM The liquid level is high in the gas filter separator. necessary.
LEVEL HIGH
Check the level indicator 71 GS_12.
Check the liquid level in the gas filter separator and purge if
GAS FUEL SCRUBBER 101FI-2B
L71GS12B_ALM The liquid level is high in the gas filter separator. necessary.
LEVEL HIGH
Check the level indicator 71 GS_12.
Check the liquid level in the gas filter separator and purge if
GAS FUEL SCRUBBER 101FI-3
L71GS13_ALM The liquid level is high in the gas filter separator. necessary.
LEVEL HIGH
Check the level indicator 71 GS_13.
GAS FUEL COALESC FILTER #1
L71GS1H_ALM Gas fuel coalesc filter #1 level high Change gas fuel coalesc
LEVEL HIGH
GAS FUEL #1 COALESC FILTER
L71GS1HT_SNS Gas fuel #1 coalesc filter level sensor trouble Change gas fuel coalesc
LEVEL SENSOR TROUBLE
GAS FUEL SCRUBBER 121FI-2A
L71GS22A_ALM Gas fuel scrubber 121fi-2a level high Change gas fuel scrubber
LEVEL HIGH
GAS FUEL SCRUBBER 121FI-2B
L71GS22B_ALM Gas fuel scrubber 121fi-2b level high Change gas fuel scrubber
LEVEL HIGH
GAS FUEL SCRUBBER 121FI-3
L71GS23_ALM Gas fuel scrubber 121fi-3 level high Change gas fuel scrubber
LEVEL HIGH
GAS FUEL COALESC FILTER #2
L71GS2H_ALM Gas fuel coalesc filter #2 level high Change gas fuel coalesc
LEVEL HIGH
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
COMPRESSOR INLET Bad thermocouple signal. Thermocouples in the inlet have Check thermocouples and wiring and replace faulty
L86TCI
THERMOCOUPLES DISAGREE failed shorted or open thermocouple(s) (CT_IF_1 and 2).
Check and reconnect thermocouples.
EXHAUST THERMOCOUPLES Excessive number thermocouples fault.
L86TFB_ALM Check the connection and the position.
OPEN TRIP Position, connection, short circuit, cut off fault.
Check for short circuit and cut off.
For information For information For information For information
TURBINE EMERGENCY STOP Electrical trouble with emergency shutdown. Relay 86G The unit should not be operated until the cause of the problem
L86TGT1_ALM
CHANNEL 1 indicates a generator differential. has been determined and corrected.
TURBINE EMERGENCY STOP Electrical trouble with emergency shutdown. Relay 86G The unit should not be operated until the cause of the problem
L86TGT2_ALM
CHANNEL 2 indicates a generator differential. has been determined and corrected.
TURB SHELL & EXH FRAME LAG
L86TK_ALM Turbine shell & exhaust frame lag fan running For information
FAN RUNNING
The temperature control system has not limited exhaust
temperature within the trip limits. Check the temperature control loop and the fuel control
EXHAUST OVER TEMPERATURE
L86TXT_ALM Temperature control system fault. system.
TRIP
Fuel control system fault. Check the cooling and ventilation system.
Ventilation system fault.
Check the load compartment cooling ventilation system
Air fan fault
LOAD COMPARTMENT VENT LAG Check the supply of motors 88VG
L86VG_ALM Motor fault
FAN RUNNING Check fuses, breakers and protections
Power supply fault
Check the mechanical status of the fans and the motors
Check the ventilation system of this compartment.
Check fuses, breakers, protections, supplies.
HEAT VENT LOSS OF LOAD The turbine ventilation is faulty. Check the mechanical status of the fan and the motor in
L86VGX_ALM
COMPARTMENT VENTILATION Motor 88VG_1 and 2 fault trouble.
Check the proper operation of each cooling air fan motor 88VG
Check the position of vent flap.
HEAT VENT DLN COMPARTMENT
L86VLTEST_AL Heat vent DLN compartment test aborted For information
TEST ABORTED
Check the ventilation system of this compartment.
Check fuses, breakers, protections, supplies.
HEAT VENT LOSS OF DLN The turbine ventilation is faulty. Check the mechanical status of the fan and the motor in
L86VLX_ALM
COMPARTMENT VENTILATION Motor 88VL_1 and 2 fault trouble.
Check the proper operation of each cooling air fan motor 88VL
Check the position of vent flap.
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev : A
OPERATION AND MAINTENANCE MANUAL
OPERATION
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency
to be met during installation, operation, and maintenance. The information is supplied for informational purposes only, and
GE makes no warranty as to the accuracy of the information included herein. Changes, modifications, and/or improvements to
equipment and specifications are made periodically and these changes may or may not be reflected herein. It is understood
that GE may make changes, modifications, or improvements to the equipment referenced herein or to the document itself at
any time. This document is intended for trained personnel familiar with the GE products referenced herein.
GE may have patents or pending patent applications covering subject matter in this document. The furnishing of this document
does not provide any license whatsoever to any of these patents.
This document contains proprietary information of General Electric Company, USA and is furnished to its customer solely to
assist that customer in the installation, testing, operation, and/or maintenance of the equipment described. This document
shall not be reproduced in whole or in part nor shall its contents be disclosed to any third party without the written approval of
GE Energy.
GE provides the following document and the information included therein as is and without warranty of any kind, expressed or
implied, including but not limited to any implied statutory warranty of merchantability or fitness for particular purpose.
If further assistance or technical information is desired, contact the nearest GE Sales or Service Office, or an authorized
GE Sales Representative.
Alarm and event information displays by using advanced filtering and sorting capabilities,
as well as functions such as Acknowledging, Locking, and Silencing Alarm and Events.
• Alarms
• Events
• Holds
• Sequence of Events (SOE)
• Diagnostics
The Alarm Server connects to and receives alarm and event data from one or more
controllers listed as consumed devices in a WorkstationST component configured in the
ToolboxST* application. An Alarm Server configuration connected to four controllers is
displayed in the following figure. The Alarm Viewer then connects to the Alarm Server
to display and manage the alarm and event data from the configured controllers and the
Alarm Server.
Note The Alarm Viewer can connect to any single Alarm Server in the system.
For assistance, contact the nearest GE Sales or Service office, or an authorized GE sales
representative.
Multi-language Support
Refer to the section Alarm Starting with the ControlST software suite V04.03, the Alarm Viewer can be displayed in
Viewer Settings, the option the local Windows language as selected in the Control Panel - Region and Language -
Enable Non-translated Content Keyboards and Languages, on the tab Display Language.
for additional information.
To enable the Alarm Viewer to display in the selected language the following is required:
• The Windows Language Pack is installed on the computer for the desired language.
Or
And
• The Alarm Viewer resource DLLs are installed that match the selected Windows
display language.
Refer to GEI-100793, Resource The resource DLLs can be created or modified by using the Resource Translation Manager
Translation Manager for the utility application and exporting the strings to a dictionary text file for translation. This
procedure to use the application is installed automatically when the ControlST software suite, Configuration
Translation Manager utility Tools Package or the WorkstationST application is installed. This utility can be found in
application for creating these the following directory:
resource DLLs. (The document
can be found at \GE Energy\ \Program Files\GE Energy\Resource Translation Manager.
Documentation\GEI-100793.pdf)
Note The Alarm Viewer does not support right-to-left languages.
Starting with the ControlST software suite V04.03, the WorkstationST Alarm Viewer
supports displaying text in the native language of the operating system. When enabled, the
Alarm Viewer displays the application help in the native display language of the operating
system. The help file must reside in the language subdirectory under the installation
directory for the WorkstationST Alarm Viewer.
The Alarm Viewer user’s capabilities are determined by the Alarm Privilege assigned to
the user’s role. The Alarm Privilege is defined as True or False for each role.
Alarm Privilege, when set to True, allows the user to interact completely with the alarm
system. This includes performing tasks such as acknowledging, locking, silencing, and
reset of alarms, defining or saving views, and defining or saving filters.
Go To Definition From HMI Graphics Privilege, when set to True, allows the user
to open the ToolboxST application to display the logic writing the current alarm. When set
to False, this feature is disabled.
If the User Logon dialog box displays when the Alarm Viewer is started, select the User
from the drop down list (as defined in the ToolboxST system component User Names and
Roles feature), and enter the Windows account Password.
Note The < > brackets are displayed to demonstrate usage, not to be included with
the value.
/Host:<HostName>
Where:
Usage: /Host:LocalHost
/IPAddress:<QuadIPAddress>
Where:
Usage: /IPAddress:127.0.0.1
Where:
View file name is the name of the AvView file to be used. The file can be fully qualified
or be the name of the file without the path.
Note If just the file name is specified, the Alarm Viewer uses the Alarm Configuration
Root Path option, and then checks in the Views subdirectory.
Note The View file name must be enclosed in double quotes if there are spaces in the
path or file name.
/View: “C:\WorkstationST\AlarmViewerConfiguration\Views\SpecialView.AvView”
Note For the view file name, the file extension AvView is registered for use by the
Alarm Viewer during installation. When you double-click on a file with that extension,
the Alarm Viewer opens and uses that file to define the display.
/NoSplashScreen indicates to suppress the startup splash screen when the Alarm
Viewer is started.
Screen Overview
Tabs control the information that displays. The initial Alarm Viewer screen displays the
Short Term Historical Alarms and Filter Definitions tabs. Additional tabs display when
items are selected from the View menu.
Managing Columns
Note Rest the cursor on the sort arrow to display a ToolTip describing the sort
direction.
Any column can be used to sort data. Re-selecting the same column toggles the sort
direction. Single-column sorting is the default.
2. Click OK.
Note The special filter <Unfiltered> is available even if no filter collection is loaded.
Collection is the name of the filter collection currently loaded for use. This name is
user-defined and can be set in the filter collection editor.
Filters Available is a list, displayed in a drop down box, of all defined filters in the test
filter collection that can be selected. Selecting a filter applies it to the alarm data being
displayed. The filters available are all user-defined and named.
Priority Filter displays the highest priority alarms that are active and not acknowledged.
Selecting this filter causes the drop-down list of filters to be unavailable. Clicking the
When a filter is selected from the drop-down list, the live alarm display automatically
updates using the selected filter. The column headers also update if the alarm data in a
particular column is used in the filter.
Note The filter equation applied displays when the cursor is positioned over the
drop-down arrow of the filter list.
Clicking the Filter icon for the Type column allows you to edit the filter term for that
column. Changing the selection changes the display based on the new evaluation.
Changes made are reflected back into the current filter. All columns that have the Filter
icon displayed can be edited.
If no Filter icon is displayed in the column header, you can add the filter term for the
column. Right-click over the column header and select Edit Column Filter Equation
from the shortcut menu.
Note If the Edit Column Filter Equation item is unavailable, there is no filter allowed
for that column.
The Column Filter dialog box (obtained by clicking the Filter icon in the Type column)
allows you to change the alarm event types being filtered. Selecting the Events check box
displays both alarms and events.
In the following example, there are 27 active, unacknowledged alarms that are currently
not being displayed by the Alarm Viewer. This is due to the filter currently being applied
(keeping them in the background). The notification is removed when:
The information in the ToolTip updates if the status of these alarms changes.
Note The notification does NOT display if the Dynamic Priority filter is applied.
Note Items that are unavailable are due to the current alarm conditions at the
instant that this menu displays (for example, if a selected alarm has already been
acknowledged).
When an alarm set is selected, the row(s) display(s) in blue. The selected alarm set may be
larger than can be displayed at one time. These actions are system-wide.
Action Result
Ctrl-A Selects all alarms visible on screen. Does not include alarms that
must be scrolled into view. All connected clients see this action.
Alarm selections are not required.
Left Mouse Selects the alarm under the cursor and deselects all other selected
alarms
Ctrl-Left Mouse Toggles the selected alarm under the cursor
If the User Defined item is unavailable, from the Options menu, select Viewer
Options, then in the User Defined Alarm Status History Filter Name field, enter a
name for the filter.
Note The selection made on the screen overwrites the variable(s) defined in the filter.
Refer to the section Filters.
Refer to the section Historical The results of the filter are displayed in the Short Term Historical Alarms display tab.
Alarms for more details on
displaying and managing this
Sound Options
information.
The Alarm Viewer can play sounds defined as part of the Alarm Class definition in the
ToolboxST configuration. Sound options include Tone, Wave File, and Voice. Once
defined, they are assigned to an alarm class for variables.
The Alarm Viewer updates the displayed alarm data approximately once a second.
During the update, the Alarm Viewer detects the highest-priority alarm that is active,
unacknowledged and not silenced, and plays the sound for that alarm.
If the sound is defined as Voice, the Alarm Viewer states the phrase Priority <Value>
<Alarm Type> <Description>, where
• Alarm
• Event
• Hold
• SOE
• Diagnostic
Priority 1 Process Alarm, Gas Auxiliary Stop Position Filter Pre-Ignition Trip
Refer to the section, Live Ø To set the sound options: from the Alarm Viewer toolbar, click Options and
Alarms, for options relating to Settings. The Settings dialog box that displays allows you to configure sound
sound. options.
The Alarm Viewer displays the primary and secondary names of the hosts running the
redundant Alarm Servers in the status bar connection pane. The following are samples of
the Alarm Viewer status bar displaying the primary and secondary Alarm Servers:
Clicking the Find button displays the Find dialog box, used to find specific information in
the alarm data displayed.
Alarm data from one or more alarm data files displays in table form based on the filter
selected from the drop-down list. Summary information in table or plotted form can
also be displayed.
• The number of rows returned is clamped at 50,000 unless a filter is defined and the
Maximum Alarm Rows To Return option in the filter definition is non-zero.
• The text in the selected tab is Short Term Historical Alarms – Unfiltered.
• Historical displays as the Alarm Source in the status bar.
Note To restore viewing of all Alarm Data, the Alarm Data Display must be closed
by selecting Close Alarm Data File from the File menu.
Note To update the initial historical data display, select a filter from the drop-down
list. Selecting a different filter always applies the new filter to the current alarm data file
selected.
When the Charts button is clicked, the alarm data displays in table form (the default).
Note When the selection is changed to an item in the Device Summary, the
corresponding alarm summary displays and a new chart button is added to the toolbar.
No alarm summary information is displayed, and the chart button is removed from the
toolbar if the Time Range Summary item is selected.
• Transitions Pareto – A Pareto chart that is scaled to display the data scaled as
percent of the total frequency found. A cumulative percent line from highest to
lowest frequency displays.
Right-click anywhere in the chart area to display the Settings dialog box.
Filter Collections
A filter collection consists of one or more filters. Only one collection can be opened at one
time. Individual filters can be added, modified or deleted within this collection.
Ø To create a new filter collection: from the File menu, select New Filter
Collection. A new filter collection is created with a default filter named Filter1.
Note Alarm Class displays all alarm classes defined in the ToolboxST configuration
for the current system.
Alarm Class displays a list of Alarm Classes. These Alarm Classes are read from the
current system configuration if the option Use Local Workstation Alarm Configuration is
set to True. You can right-click to add or delete Alarm Classes. Select the Alarm Class
to include it in the filter.
Alarm State filters on the condition of the alarm. The choices are All, Active, or Normal.
For event and SOE alarm types, the condition is always Normal.
Alarm Type filters on the type of alarm to display. The choices are Display Alarms,
Display Events, Display Diagnostics, Display SOEs, or Display Holds. Any combination
may be selected.
Description filters on the description of the alarm or event. Wildcard characters ? and *
are supported.
Device Name displays the devices that are the source of the alarm/events. These devices
are read from the current system configuration if the option Use Local Workstation Alarm
Configuration is set to True. You can right-click to add or delete devices. Select the
device to include it in the filter.
Device Time specifies a number of time-filtering options for filtering on the time of the
alarm or event. The options are:
Time entry units must be specified when entering a time for filtering. Time is managed
and stored in Universal Time Coordinated (UTC) in the system. If using Local Time units,
the time value must be expressed in local time. The application converts the time to
UTC to perform any calculations or filtering.
Note It is recommended that the option Time Type for Display be set to the same
units as the units defined here.
Plant Area filters on a logical area of the plant. The Plant Area is configured in tree form
in the ToolboxST application and is associated with each alarm/event. The Plant Area
cannot be edited. All or any portion of the tree may be used in the filter.
Priority filters on the priority value associated with the alarm/event. The operators
defined are <=, =, or >=.
Quality filters on Good or Bad. Good indicates the alarm information is current, Bad
indicates the information is stale and is not updating on the Live alarm display.
Recorded Time specifies the same time-filtering options as in Device Time. This can
filter on the received time of the alarm/event. The received time is the time that the Alarm
Server received the alarm or event. This is used to troubleshoot time-sync problems.
Variable Alias filters on the alias name of the alarm or event. The definition can be a
single variable or a list of variables. Wildcard characters ? and * are supported.
Variable Name filters on the alarm or event name. The definition can be a single variable
or a list of variables. Wildcard characters ? and * are supported.
or
Ø Right-click any tab and select Settings from the shortcut menu.
Alarm Help
Master Workstation Host Name is the host name that is the source of
the Process Alarm/Diagnostics Help.
Communications
Add Default Filters, if set to True, opens the file DefaultFilters.xml (if
found) and adds all contents to the new filter collection being created.
The DefaultFilters.xml file is generated by creating and editing a set of filters
and then saving them to the file named DefaultFilters.xml.
The DefaultFilters.xml file must be located in the Filters folder of the
Alarm Configuration Root Path.
Load Last Used Filter, if set to True, loads the last filter file. The filters can
then be selected and applied.
User Defined Alarm Status History Filter Name is the name of the
filter to locate and apply when selecting the Historical Status.
Language
Display Language allows the selection of the default language for displaying
live alarm data and alarm/event help based upon the languages selected as
primary and secondary in the ToolboxST System Editor. These can also be
selected using the WorkstationST or ControlST icon in the taskbar
notification area.
Local Settings
Alarm Configuration Root Path sets the path to the Alarm Viewer root
configuration directory. All views, filters, and sound filters are located under
this directory.
Alarm Export Path is the path used when the current alarm display is
exported to a .csv file.
Export CSV data with headers, if set to True, writes the headers when the
alarm data is exported to a .csv file. If set to False, no headers are written. Only
the visible columns are written.
Startup Settings
Display Style selects either a resizable, movable form or a fixed sized and
fixed position form.
Show Main Menu, when set to True, displays the main menu. When set to
False, the main menu is hidden.
Show Startup Splash Screen, when set to True, displays the startup splash
screen. When set to False, the startup splash screen is suppressed when the
WorkstationST Alarm Viewer is started.
Show Status Bar, when set to True, displays the status bar at the bottom
of the screen. When set to False, the status bar is hidden.
Show Toolbar, when set to True, displays the toolbar. When set to False, the
toolbar is hidden.
Note This option is hidden when the Operating System is set to run in English.
Alarm ID in Hex, when set to True, displays the alarm ID in hex. When set to
False, the value is displayed as a decimal.
Always On Top, when set to True, keeps the Alarm Viewer on top of all other
windows.
Image Size, sets the size of the images displayed on the Live and Historical
toolbars.
Main Font changes the font used for all items displayed.
Show Text With Toolbar Buttons, when set to True, displays the text
for each toolbar button displayed.
Time Type for Display defines the time type that displays. The selections
are UTC Time, Site Time, or Local. Local and site settings use the local
time zone to calculate the time for display.
Setting this option to 'True' will enable access to features and documentation
that may not be translated into the current Windows display language.
Note When displaying English, this option is hidden and set to True, allowing access
to all features and documentation.
Show Filter Collection Name hides or displays the filter collection name
on the toolbar.
Show Filters Available Label hides or displays the "Filters Available" label
on the toolbar.
Show Page Down Button hides or displays the Page Down button
on the toolbar.
Show Page Up Button hides or displays the Page Up button on the toolbar.
Show Reset All Button hides or displays the Reset All button on this
toolbar.
Show Zoom In Button hides or displays the Zoom In Button on the toolbar.
Show Zoom Out Button hides or displays the Zoom Out Button on the
toolbar.
Show Alarm Help hides or displays the Alarm help button on this toolbar.
Show Lock/Unlock Button Set hides or displays both the Lock and Unlock
buttons in this toolbar.
Show Reset Button hides or displays the Reset button in this toolbar.
Display
Disable Blinking overrides the configured blink value in the Alarm Class
definition for the system. Alarm Class configuration is defined in the
ToolboxST System Editor.
Show Only Priority One Alarms in Balloon ToolTip, when set to True,
displays priority one alarms only in the balloon ToolTip. The Show
Background Alarm Balloon ToolTips must also be set to True.
Sound Configuration
Play Sound Continuously, when set to True, causes the sound configured
for the highest-priority alarm to play repeatedly until the operator takes action
to silence the alarm.
Time To Disable Mute Sound Button is the time delay, in minutes, before
resetting the button when the Mute Sound Button is clicked. While the mute
button is active, all sound is suspended. When this time expires, sound is
played again. A value of 0 mutes the sound indefinitely.
Show Alarm Horn Button displays or hides the Alarm Horn button on the
Sound toolbar.
Show Mute Sound Button displays or hides the Mute Sound button on this
toolbar.
Show Silence All Button displays or hides the Silence All button on this
toolbar.
Voice Options
Use Second Language Description Text, when set to False, uses the text
description. When set to True, uses the second language description text as the
phrase spoken when Voice is the sound type configured.
Active Transitions Bar Color allows the choice of colors used for the bar
when a chart is displayed.
Center Color for Active Transitions Bar Color is the color for the
center of the Active Transition state.
Edge Color for Active Transitions Bar Color is the color for the edge
of the Active Transition state.
Bottom Gradient Color is the gradient color at the bottom of the chart
displayed.
Top Gradient Background Color is the gradient color at the top of the
chart displayed.
Alarm Type Center Color is the color for the center of the Alarm Type
displayed.
Alarm Type Edge Color is the color for the edge of the Alarm Type
displayed.
Diagnostic Type Center Color is the color for the center of the
Diagnostic Type displayed.
Diagnostic Type Edge Color is the color for the edge of the Diagnostic
Type displayed.
Event Type Center Color is the color for the center of the Event Type
displayed.
Event Type Edge Color is the color for the edge of the Event Type
displayed.
Hold Type Center Color is the color for the center of the Hold Type
displayed.
Hold Type Edge Color is the color for the edge of the Hold Type displayed.
Increasing Time Table Sort Direction Set to True to sort the time labels
in increasing order (from oldest time to newest time). Set to False to sort in
decreasing order (from newest time to oldest time). The time display format
is Month-Day Hour:Minute:Second.
Show Time Label Sort Direction Set to True to display the hour time
label on the x axis for data that is not defined for that hour. Set to False to skip
displaying time for no data.
SOE Type Center Color is the color for the center of the SOE Type displayed.
SOE Type Edge Color is the color for the edge of the SOE Type displayed.
Chart Options
Horizontal Grid, when set to True, draws the horizontal grid lines.
Show Alarm/Event states for each variable displays the alarm state
appended on the alarm/event name (variable).
Show Alias Names, when set to True, the Alias name displays in the chart.
When the option is set to False, the standard variable name display behavior is
provided. The variable names are displayed on the bars and also displayed
in the ToolTip.
Note If the alias name to be displayed is blank, the variable name displays instead.
Depending on the configuration, there can be a mixed display of alias and variable
names on the same chart.
Show Bar Text, when set to True, displays the text inside or above the bar
as necessary. When set to False, no bar text is displayed.
Show cumulative percent line plot, when set to True, draws the line
connecting the first series of bars representing total percent of the data
displayed.
This option only works if the Chart Type selected is Pareto.
Text Angle is the alarm/event display angle on the screen, and has a range of
0 - 90 degrees.
Vertical Grid, when set to True, draws the vertical grid lines.
Note The following three alarm states (Hi, HiHi, and HiHiHi) designate increasing
levels of severity, or concern, for an alarm in this category. (The higher it gets, the
more critical it is.)
Note The following three alarm states (Lo, LoLo, and LoLoLo) designate increasing
levels of severity, or concern, for an alarm in this category. (The lower it gets, the
more critical it is.)
Create a View
To create a view, you must first set the parameters to display in that view.
Ø To create a view
1. From the View menu, select Local Mode or Remote Mode, Show Live Alarms,
and Show Historical Alarms as appropriate. Refer to the Live Alarms section.
2. Select the Live Alarm Data tab and organize the columns as they need to be
displayed. Refer to the Live Alarms, Organizing and Displaying Columns section.
3. Sort the alarm data as required. Refer to the Live Alarms, Sorting Alarm Data section.
4. Create and name the necessary Filter Collection. Refer to the Filters, Filter
Collections section.
Note If you have filters defined from previous versions of Alarm Viewer, you can
manually copy them to the Filters subdirectory.
Note At this point, the Alarm Viewer should be configured to display all the necessary
parameters. Once you ensure this, proceed with the final step.
7. From the File menu, select Save View As. The file browser defaults to the View
subdirectory. Save the view using a name that describes the view state.
Or
8. Right-click any tab and select Save View As from the shortcut menu.
Or
1. Right-click any tab and select Open View from the shortcut menu.
2. Select the desired view, then click Open. The selected view displays.
Note The Short Term Historical Alarms tab does not automatically apply and display
the filter selected. You must apply the filter to update the Short Term Historical Alarms
display.
Ø To apply a filter to the Short Term Historical Alarms display: with the
Alarm Viewer, open to the correct view, select the Short Term Historical
Alarms tab.
Or
Right-click any tab and select Recent Views from the shortcut menu.
Default View
When the Alarm Viewer is started, it searches for the AlarmViewerDefault.AvView view
file. This is the saved default view and must be created and saved in the same manner as
all other view files.
This view file is also used to animate the alarm button on the navigation bar in CimView.
The animation is controlled by an alarm status client running in the background when
CimView is running. This client reads the CimplicityAlarmStatusHistory.AvView file to
perform the connection to the designated alarm servers. A filter named AlarmStatusFilter
is created to allow only process alarms to be received by the alarm status client. Refer to
GEI-100697, WorkstationST CIMPLICITY Advanced Viewer Integration for additional
information.
The language in use is displayed in a white icon in the left corner. (En indicating English)
Connection indicates the source of the alarm data (local or remote computer). The IP
address or host name of a remote computer also displays. A green icon indicates that the
connection status is good, a red icon indicates a connection problem. The following are
examples of connection options:
Alarm Source indicates whether the data displayed is from a live connection or is
historical, and if the data is filtered.
Filter Applied indicates the name of the filter applied or <Unfiltered> or No Filter. If
a single alarm file displays, File Contents also displays.
Alarm Data indicates the number of rows used for live or historical alarm data. If live data
is displayed, an icon indicates the update status of the screen. If the update is interrupted,
the icon displays in red. The icon turns green when the connection is reestablished.
Directory Structure
Alarm Help uses the existing Master Location defined in the Property Editor in the
ToolboxST System Editor. It adds the Help subdirectory to the directory structure used
by the Alarm Viewer. Two additional subdirectories required are ProcessAlarms and
Diagnostics.
The directory structure created uses the defined component names to contain the help
for that component. The diagnostics Help is configured by device type. The following
is an example of the directory structure:
Help is the subdirectory that defines the start of the help file collection. This subdirectory
is required, and must be named as displayed.
Diagnostics is the subdirectory that defines the start of the diagnostics section. This
subdirectory is required, and must be named as displays. Subdirectories such as AEPA are
specific Distributed I/O packs used in the system.
ProcessAlarms is the subdirectory that defines the start of the process alarms section.
This subdirectory is required, and must be named as displayed.
Diagnostics
The file must use the format <Type>Diags.<language>.chm where:
<Type> is the component type, usually distributed I/O packs (PDOA, PAIC, and
Diags is the required string appended to the Type (for example PAICDiags)
chm is the required file extension. Diagnostics help files must be defined as chm
files.
A properly named file is PAICDiags.en.chm, which indicates the file is for a PAIC pack
type, is authored in English, and is a standard chm file.
Note For information on how MarkV Diagnostic alarms are defined, refer to
GHT-200040, How to Convert a Mark V Component for Use in ControlST Applications.
<Variable> is the variable name as defined in the ToolboxST application without the
device prefix.
<Language> language identifier in the Name column of the Language Naming table
<Extension> is the required file extension (for example, .txt, .htm, and so on).
A properly named file is L63QTX.en.txt, which indicates the file is for the variable
L63QTX, is authored in English, and is a standard text file.
Note Process alarm help files can have the extension.txt, rtf, htm, or chm. If a set of
files is located in this directory, the order txt, htm, rtf, chm is used to display the file.
The first one found is displayed. The name of the file is not case-sensitive.
User Comments
A comment file uses the following formats:
Variable is the name of the process alarm as defined in the ToolboxST application.
<Language> language identifier in the Name column of the Language Naming table
<Type> is the component type, usually distributed I/O packs (PDOA, PAIC, and
PAICComments).
<Language> language identifier in the Name column of the Language Naming table
and
Process Alarms
Process alarm Help is managed on a per instance basis. This requires a file for each
component and each variable, with the correct suffix, to display Help in Alarm Viewer.
Help for a variable that is identical for G1 and G2 must also be copied into both G1
and G2 folders. An example of the process alarm help directory with a help file defined
is as follows:
Diagnostic Alarms
Diagnostic alarm Help is managed on a per type basis. An example of the directory used
for Diagnostics is as follows:
chm identifies the type of file to be viewed. The compiled html file type (CHM)
The Alarm Viewer allows you to determine which language to use when detecting the
correct file for display.
Alarm Viewer
The Alarm Viewer allows you to browse available help files.
You must enter the Master Workstation Host in the Settings dialog box.
Ø To set the Master Workstation Host Name: from the Options menu, select
Settings.
After the Master Host and Path are validated, the Alarm Help Browser button is enabled.
Click the browser button to display a dialog box that allows you to navigate all defined
alarm and diagnostic help files.
Note If the Master Workstation host name is not set, an error displays in the status
bar, and only the root names display in the Tree View.
Use the drop-down list in the Alarm Help Viewer dialog box to change the Help
language.
If a document is not defined in Spanish (the signal name language), the document icon is
missing and the Help tab is blank. The following screen displays:
Examples:
The selection of a single Process Alarm or Diagnostic (row is highlighted in blue) enables
the Alarm Help button and the Alarm Help shortcut menu item. When the mouse pointer
is held over the Alarm Help button, a ToolTip displays.
The toolbar on the Comments tab (displayed below) is used to control editing, and manage
the display.
changes the sort direction of the date/time items in the Tree View (Oldest to Newest or
Newest to Oldest)
to indicate the comment file is locked by the current user for editing.
displays the computer and the user who has the file locked
for editing. This is blank if the file is read-only.
The icons on the Comments tab and the icons in the Tree View change to:
when one or more comment sections have been edited and not yet saved.
The language component used in the file name can now contain the subculture for that
country. The language component of the file can be defined as:
<culture>-<subculture>
or
<culture>
Example:
A file name can be defined using the culture and subculture for Spanish - Spain (Spanish
for Spain) as
L63QTX.es-SP.txt
The alarm help subsystem detects the use of the subculture in the language component of
the file name. If the culture-subculture form is detected it displays, otherwise the culture
form displays.
Bind/Build - To bind the configuration for each consumed exchange and create/update
the configuration for any produced exchange.
EGD - A mechanism that provides access to global data between nodes supporting the
EGD protocol.
Exchange - An EGD data message consisting of a header and a body of data. The header
contains the producer ID and the exchange ID that uniquely identifies the message. The
body of data is a block of bytes in a format agreed upon by the producer and all consumers.
OPC (OLE for Process Control) - A standard for data exchange in the industrial
environment (OLE is Microsoft’s® Object Language Embedding). The OPC foundation
provides specifications for various OPC standards such as OPC DA (Data Access) and
OPC AE (Alarm and Event).
Producer - The EGD node configured to send data messages. The source of the data
samples for an exchange.
Refresh - To bind the configuration for each consumed exchange for a particular
consumed device.
Runtime - Software stored in the controller’s Flash memory that converts application
code (pcode) to executable code.
Unbound Variables - Variables required by a consumer that were not found in the
producer configuration during the bind.
Rev. : A
Page : 1/6
OPERATION AND MAINTENANCE MANUAL
OPERATION
SPECIAL SEQUENCES
1. GENERAL............................................................................................................................... 2
2. STARTING MODE .................................................................................................................. 2
3. FAULTY IGNITION ................................................................................................................. 2
3.1. NORMAL IGNITION............................................................................................................. 2
3.2. FAULTY IGNITION .............................................................................................................. 3
4. INLINE FILTER CHANGEOVER ............................................................................................ 3
5. OVERSPEED TEST................................................................................................................ 4
5.1. INITIAL CONDITIONS ......................................................................................................... 4
5.2. SEQUENCE......................................................................................................................... 4
5.3. FINAL CONDITIONS ........................................................................................................... 4
6. OIL PUMP RESTART TEST................................................................................................... 5
6.1. INITIAL CONDITIONS ......................................................................................................... 5
6.2. SEQUENCE......................................................................................................................... 5
6.3. FINAL CONDITIONS ........................................................................................................... 5
7. PROLONGED SHUTDOWN................................................................................................... 6
Rev. : A
Page : 2/6
OPERATION AND MAINTENANCE MANUAL
OPERATION
1. GENERAL
This document completes the normal operation sequences and contains specific
instructions for special sequences.
The following standard text applies to all gas turbines type 6FA (60 -80MW). Optional
equipment is often identified by the symbol () in the text.
The text is intended as a guide for the operator. The experience acquired during the day-
to-day operation of the plant will enable the operating staff to further supplement and
refine the recommendations contained in this document.
2. STARTING MODE
The operator usually starts the gas turbine in automatic mode by selecting “Auto“ on the
main screen, or “Remote” for remote operation. Mode Select “Crank” and “Fire” are
available for specific sequence test.
“Crank” allows normal starting sequence of the gas turbine up to firing speed but without
firing. This mode is used to test the starting means system.
“Fire” allows normal starting sequence of the gas turbine including firing, but without
accelerating the shaft line. This mode is used to test the firing sequence.
Both “Crank” and “Fire” mode select may be used to demonstrate or to test manually
cranking and/or firing after main maintenance activity on the gas turbine and are not used
during normal operation.
3. FAULTY IGNITION
Rev. : A
Page : 3/6
OPERATION AND MAINTENANCE MANUAL
OPERATION
Rev. : A
Page : 4/6
OPERATION AND MAINTENANCE MANUAL
OPERATION
5. OVERSPEED TEST
The overspeed protection circuit must be inspected once a year by simulation and with the
turbine in standstill position.
Real testing of the protection is not necessary if the simulation yields satisfactory results,
including the turbine trip circuits.
If a real test is scheduled, the following conditions must be fulfilled.
5.2. SEQUENCE
Choose the overspeed test control screen
Select the protection module
Increase the speed until a trip occurs. The speed increase must be maintained without
interruption until the trip occurs.
Rev. : A
Page : 5/6
OPERATION AND MAINTENANCE MANUAL
OPERATION
6.2. SEQUENCE
Input Description Output State
Close the plunger valve and slowly open the test valve.
Main pump test 88QA 1
The main oil pump starts.
Slowly close the test valve and then open the plunger
Main pump test valve. Select again the lead pump on the speedtronic 88QA 0
screen. The main standby pump stops.
Main pump test Acknowledge the alarms on the control cabinets.
Rev. : A
Page : 6/6
OPERATION AND MAINTENANCE MANUAL
OPERATION
7. PROLONGED SHUTDOWN
For particular operating reasons, the turbo-generator set may be shut down for a relatively
long period of time, more than one week, provided it can be started up, at short notice, to
generate power for the grid.
In this standby situation, the following instructions must be observed:
x Keep the electric auxiliaries and the control cabinets energized.
x Keep the heating systems (cabinet, compartments, generator…) and the air
conditioning system in automatic mode.
x The lube oil heating system automatically starts, with the oil pump, to keep the viscosity
at a value that is compatible with the turbine start-up.
x Keep the pipe tracing systems in automatic mode.
x Start up the gas turbine two to four times a month with few minutes at turning gear
before starting, fire and synchronize to the grid at low load to validate all sequences.
Shut down the turbine and observe the 24-hour turning sequence.