SEISMIC QUALIFIED

TEST CERTIFICATE OF SEISMIC WITHSTAND CAPABILITY


Eaton’s Cutler-Hammer姞 equipment identified below was tested for seismic withstand capability and tested in accordance
with the combined requirements specified in the International Building Code, California Building Code and the Uniform
Building Code. As required by the codes, the equipment demonstrated its ability to function after the seismic tests.
The seismic capability of the equipment exceeds the worst-case required levels, as illustrated in the figure below.

Transfer Switch Equipment

Period (seconds)
.31 .25 .20 .16 .13 .10 .08 .06 .05 .04 .03 0
3.0

The frequency sweep


2.5
Damping = 5%
tests revealed that the
lowest equipment natural
2.0 frequency is:

Response
Acceleration
(g)
1.5 >3.2 Hz
Zero Period Acceleration

1.0
(DWRQҋV&XWOHU+DPPHU(TXLSPHQW&DSDELOLW\
,%&&%&

.5 8%&=RQH5HTXLUHPHQW

0
3.2 4 5 6.4 8 10 13 17 20 26 32
Frequency (Hz)

3RD PARTY TEST ENGINEER IN CHARGE

TESTED BY For interpretation of testing data


Wyle Laboratories refer to Eaton
December, 1999 – 43617-1 Publication SA12501SE
Drawing Number 69A1002H01