D.

6 Energy Cost

Energy cost computations shall take the base load into consideration. Utility
usage and rates shall be provided by the NIH. Backup computations for
items listed in the operating cost shall be included.

Computation shall be made on a monthly basis taking into account variations


in the heating and cooling loads. Energy usage and cost shall be developed
by computer programs using weather bureau tapes or by using Air Force
Manual AFM-88-8, Engineering Weather Data and the bin method
procedure referenced in the latest Fundamentals volume of the ASHRAE
Handbook.

Energy cost computations shall take into consideration the energy used by
fans, and cooling and heating coils in the system as well as refrigeration plant
energy costs that are brought about as a result of the type of air-conditioning
system in the building.

Steam cost shall be as provided by the NIH.