Professional Documents
Culture Documents
System Description Bosal
System Description Bosal
© Copyright 2007, Atlas Copco Rock Drills AB, Sweden Any unauthorized use or copying of
the contents or any part thereof is prohibited. This applies in particular to trademarks, model
denominations, part numbers and drawings
ROC L740, ROC L740CR, ROC L830 (with Bosal cabin) system description
PMI NR: 9853 1156 01
Table of contents
Table of contents
Table of contents............................................................................................................................................. 1
Hydraulic system, general............................................................................................................................... 3
General – L740, L740CR ................................................................................................................................ 3
General – L830 .............................................................................................................................................. 4
Hydraulic pumps.......................................................................................................................................... 5
Pump capacities ........................................................................................................................................... 6
Pilot pressure ............................................................................................................................................... 6
Return oil and oil cooler ............................................................................................................................... 6
Electrical system, general ............................................................................................................................... 8
General ........................................................................................................................................................ 8
Battery charging........................................................................................................................................... 8
Main fuse ..................................................................................................................................................... 8
Electrical cabinet.......................................................................................................................................... 8
ECM (Caterpillar) ........................................................................................................................................ 8
Electrical supply........................................................................................................................................... 9
CAN, general................................................................................................................................................. 11
CAN .......................................................................................................................................................... 11
Display D501 ............................................................................................................................................. 11
PLC ........................................................................................................................................................... 11
CAN nodes ................................................................................................................................................ 12
ECM.......................................................................................................................................................... 12
D169/D171/D173 Module .......................................................................................................................... 12
Terminal plug............................................................................................................................................. 12
CAN system overview................................................................................................................................ 13
Sensor/switch monitoring system................................................................................................................ 14
Control panel ................................................................................................................................................ 15
Diesel engine.................................................................................................................................................. 16
Battery switch, OFF ................................................................................................................................... 16
Battery switch, ON..................................................................................................................................... 16
Ignition position ......................................................................................................................................... 16
Start position.............................................................................................................................................. 17
ECM overview........................................................................................................................................... 17
Engine speed.............................................................................................................................................. 18
Control instrumentation.............................................................................................................................. 19
Engine monitoring...................................................................................................................................... 19
Switches and sensors that automatically and manually stop the diesel engine............................................... 20
Switches and sensors that only indicate a fault ............................................................................................ 21
Warning symbol related to the engine ......................................................................................................... 22
Pumps & Pilot Pressure ................................................................................................................................ 23
Pump 1 pressure settings ............................................................................................................................ 25
Pumps 2, 3 and 4........................................................................................................................................ 25
Pumps 5 and 6............................................................................................................................................ 25
Pilot pressure ............................................................................................................................................. 26
Cooling fans .................................................................................................................................................. 27
Tramming ..................................................................................................................................................... 28
Activating the tramming function ............................................................................................................... 29
Reverse warning......................................................................................................................................... 29
Tramming high/low speed .......................................................................................................................... 29
Rear jack (Option)...................................................................................................................................... 29
Positioning..................................................................................................................................................... 30
Boom and feed positioning ......................................................................................................................... 30
Positioning during tramming ...................................................................................................................... 30
Track oscillation......................................................................................................................................... 30
Air System & Compressor ............................................................................................................................ 31
Air System ................................................................................................................................................. 31
Compressor................................................................................................................................................ 33
Instrumentation & fault indication – L740, L740CR ...................................................................................... 35
1
Table of contents
Instrumentation & fault indication – L830 .................................................................................................... 35
Oil pre-heating.............................................................................................................................................. 36
Drilling functions .......................................................................................................................................... 38
Activation of drilling functions – L740, L740CR........................................................................................... 38
Activation of drilling functions – L830 ........................................................................................................ 38
Drill feed.................................................................................................................................................... 39
Drill rotation .............................................................................................................................................. 43
Rapid feed.................................................................................................................................................. 45
Threading................................................................................................................................................... 50
Impact with air flushing – L740, L740CR...................................................................................................... 51
Impact – L830 ............................................................................................................................................. 53
ECL, rock drill lubrication system .............................................................................................................. 56
HECL, DTH hammer lubrication system .................................................................................................... 57
HECL, COPROD head and sections lubrication system............................................................................... 58
Damper & DPC-I system.............................................................................................................................. 59
Damper ...................................................................................................................................................... 59
DPC-I System ............................................................................................................................................ 60
Dust collector, DCT ...................................................................................................................................... 68
DCT hydraulic system ................................................................................................................................ 68
DCT electrical system ................................................................................................................................ 69
DCT air system .......................................................................................................................................... 69
DCT adjustable parameters......................................................................................................................... 69
Protective functions ...................................................................................................................................... 70
RPC-F system – L740 .................................................................................................................................. 70
Anti-Jamming system ................................................................................................................................. 71
Length measurement .................................................................................................................................... 74
Hole depth measurement ............................................................................................................................ 74
Drill stop activation for reached depth ........................................................................................................ 75
Rod Handling System, RHS 102 ................................................................................................................... 76
Rod transfer ............................................................................................................................................... 76
Carousel rotation ........................................................................................................................................ 80
Rod grippers............................................................................................................................................... 80
Sleeve retainer (Option).............................................................................................................................. 81
Drill steel supports & suction hood ............................................................................................................. 81
Service winch (Option)............................................................................................................................... 81
Rod Handling System, RHS 140 ................................................................................................................... 82
Tube transfer.............................................................................................................................................. 82
Carousel rotation ........................................................................................................................................ 88
Rod grippers............................................................................................................................................... 89
Drill steel supports & suction hood ............................................................................................................. 90
Breakout table and rock drill lock ............................................................................................................... 90
Service winch (Option)............................................................................................................................... 90
Extractor unit (Option)................................................................................................................................. 91
Activating the extractor .............................................................................................................................. 91
Pump pressure when using the extractor ..................................................................................................... 92
TED-Extractor unit for COPROD (Option) ................................................................................................ 93
Water mist system (Option).......................................................................................................................... 94
Water-mist system 225 Litres ..................................................................................................................... 94
Water-mist system 400 Litres ..................................................................................................................... 95
ECG, thread lubrication with oil (Option) ................................................................................................... 96
Function..................................................................................................................................................... 96
Adjusting ................................................................................................................................................... 96
Thread lubrication with grease brushes (Option) ........................................................................................ 97
Function..................................................................................................................................................... 97
Operating................................................................................................................................................... 98
Spray greasing system (Option).................................................................................................................... 99
Function..................................................................................................................................................... 99
Laser sensor (Option) ................................................................................................................................. 100
Adjustment/calibration............................................................................................................................... 101
Calibrating of positioning instruments ...................................................................................................... 101
Adjustable drilling parameters .................................................................................................................. 102
2
Hydraulic system, general L740, L740CR
Hydraulic system, general
General – L740, L740CR
The hydraulic system of the ROC L740 and L740CR is an electrical and pilot pressure
controlled system, with 6 hydraulic pumps. Hydraulic pumps 1, 2, 3 and 4 are in-line
assembled and direct driven by the diesel engine over a flexible coupling.
The hydraulic pumps 5 and 6 are combined to a double pump with a common suction line.
They are driven by the diesel engines extra power-take-off.
The pressure on these pumps is regulated with fixed or variable pressure relief valves. Pump 1
is an axial piston pump with variable displacement. During drilling pump 1 is regulated by the
pressure relief valves for high/low percussion. During tramming pump 1 is connected to two
flow sharing compensated directional control valves. The pump pressure is controlled by
whichever load there is on the tramming motors.
Electrical valves:
Drilling
Impact
Pressure
Control
Panel &
Gauges Extra oil only when drilling
1
2 3 4 5 6
3
Hydraulic system, general L830
General – L830
The hydraulic system of the ROC L830 is an electrical and pilot pressure controlled system,
with 6 hydraulic pumps. Hydraulic pumps 1, 2, 3 and 4 are in-line assembled and direct
driven by the diesel engine over a flexible coupling.
The hydraulic pumps 5 and 6 are combined to a double pump with a common suction line.
They are driven by the diesel engines extra power-take-off.
The pressure on these pumps is regulated with fixed or variable pressure relief valves. Pump 1
is an axial piston pump with variable displacement. During drilling pump 1 operates on
constant pressure. During tramming pump 1 is connected to two flow sharing compensated
directional control valves. The pump pressure is controlled by whichever load there is on the
tramming motors.
Electrical valves:
Drilling
Pressure
Control
Panel &
Gauges Extra oil only when drilling
1
2 3 4 5 6
4
Hydraulic system, general
Hydraulic pumps
Pump 1
The main pump 1 in the hydraulic system is an axial piston pump.
The pump supplies hydraulic power to the following functions:
Pump 2, 3 and 4
These gear pumps are combined to a triple pump unit.
Pump 2 supplies oil to the rotation unit, but is also used for pre-heating of hydraulic oil and
rock-drill impact components (only in L740 & L740CR).
Pump 3 supplies oil to the dust collector suction fan motor.
Pump 4 supplies oil to the boom positioning during tramming, also additional oil to the
rotation motor when drilling.
Pump 5 and 6
Pump 5 drives the cooler motor for the combined hydraulic oil/compressor oil cooler,
also used for enabling the floating mode in track oscillation.
Pump 6 drives the cooler motor for engine radiator and intercooler.
5
Hydraulic system, general
Pump capacities
Rig type L740 L740CR L830
Rpm @ 2000 rpm engine speed @ 2000 rpm engine speed @ 1800 rpm engine speed
Flow(l/min) P (bar, max.) Flow(l/min) P (bar, max.) Flow(l/min) P (bar, max.)
Pump 1 275 250 260 250 235 250
Pump 2 115 170 115 170 110 170
Pump 3 65 170 65 170 65 170
Pump 4 35 250 35 250 40 250
Pump 5 30/*45 210/*225 30/*45 190/*225 32/*45 190/*225
Pump 6 30/*45 210/*225 30/*45 190/*225 32/*45 190/*225
*Higher figure refer to the 55 °C ambient temperature option.
Pilot pressure
The pilot pressure signals from the drill lever are transferred to the main valve block and to
the pressure control panel via logic valves. The pressure gauge panel shows the impact
pressure, feed pressure and rotation pressure in the main valve block. The pressure control
panel controls the working pressure of pump 1 (only in L740 & L740CR), feed and the rotation
functions in the main valve block. The gauges & panel are located in the cab for easy use.
The tramming controls are mounted close to the operator’s seat, and control the main
tramming valves proportionally.
The oil cooler cools the hydraulic oil so that the rig can work at full load in ambient
temperatures up to 55°C (optional). The cooling fan is driven by a fan motor that is supplied
with oil by pump 5. The pressure to the fan motor is controlled by a proportional pressure
relief valve. The control system regulates the pressure, and thereby the fan speed depending
on the cooling demands.
T-Return oil is a collection block that collects return oil from the various circuits and leads
this to the thermostats.
D-Drain oil is a collection block that collects oil from the various circuits and leads this to the
return oil filter.
L-Leakage oil is the oil that goes directly to tank for minimum resistance in the circuits.
The filler pump is used to fill the system. There is a check valve that prevents return oil
from leaking out through the filler pump. A level sensor (B143) detects the level of hydraulic
oil in the tank. Should this drop below a certain level, the diesel engine is switched off
automatically. The sensor signal from B143 goes via PLC input X11-8.
6
Hydraulic system, general
The temperature sensor (B362) senses the hydraulic oil temperature and the temperature
will be shown on the display. The engine will shut down automatically if the hydraulic oil
temperature exceeds 90ºC. The sensor signal from B362 goes via PLC input X16-5.
The drain cock is used to remove water of condensation or to empty the hydraulic oil tank.
7
Electrical system, general
Battery charging
Power supply to the electrical system consists of two, serie-connected 12 volt / 185 Ah
batteries. These are charged by a 3-phase A/C alternator. The batteries are connected to the
system by a manually operated battery switch.
Main fuse
The feed to the electrical cabinet is fused by a 63 A main fuse (F100).
Electrical cabinet
The electrical cabinet A1 contains 29 ATO fuses that limit the current intensity to the
different sub-circuits, two auxiliary relays (K18, K178) to handle large currents above 4 Amp,
stop relay for the emergency stop circuit (K11), remote shutdown relay (K200), start relay
(K5A), two main fuses and a PLC (CPU1-3).
ECM (Caterpillar)
Electronic Control Module is used for monitoring the engine’s functions and sensors. It
receives analogue and digital information from the engine. The information is processed and
transferred in J1939 protocol. The ECM stops the diesel engine automatically if a specific
fault occurs. A specific fault is for example low oil pressure which could cause major damage
to the engine.
8
Electrical system, general
Electrical supply
Start
engine
M1
starter motor
ECM
One of the
conditions to
activate K5A
K5A
Start
PLC position
50 circuit
outputs &
relays
CAN nodes
9
5
9
2
1
0
0
5
2
1
D550,
551, 552,
553, 554
E-stops
15 circuit K11
Ignition
position
PLC
25 circuit
processor
& sensor Radio, cabin
inputs lights, utility
light
Main
switch ON
Timer, diesel
heater
Alternator
Batteries
9
Electrical system, general
The power source consists of two 12V/185Ah batteries connected in series and an alternator.
Before the main switch is switched on, there is power to the diesel fire heater & timer.
When the main switch is switched on, there is power supply to the radio, cabin lights, utility
lights and ECM (48,52,53) thorough teminals 10 and 25. Power is also supplied to the starter
motor switch, but the switch is triggered by the starter motor relay via PLC.
When the key is in the ignition position power is supplied to the emergency stop circuit, the
display and the PLC processor and its sensor inputs through terminal 15. If the emergency
stops are intact, relay K11 is activated. Power is now supplied to the ECM (70), PLC outputs
and relays, CAN nodes, working lights/wiper, seat heating and the climate system in the cabin
through terminal 50.
When the key is in the start position the diesel engine is started via starter motor M1, and
starter motor is powered by relay K5A. K5A is activated if the conditions for starter motor are
fulfilled.
ECM is supplied with power both before and after ignition. The difference is, before ignition,
ECM is powered to boot its memory, but its monitoring functions are not started at this level.
Only after the key is in the ignition position, ECM starts working properly.
If any of the emergency stops is activated, it will deactivate switch K11, causing all the
functions at the ignition level except the display and CPU processor & sensor inputs to be
without power, since they are connected parallel with the emergency stop circuit. Turn the
key back to 0 position before re-start.
Note: The electrical system’s ground cables are not isolated by the main switch. This means
that the system consumes a small current even when no functions are activated.
10
CAN, general
CAN, general
This is an overview of the CAN communication
network. If communication is down in any of
the units, the unit will show in red, and a
warning for communication breakdown will be
shown on the status bar.
CAN
There are various types of control modules (PLC, ECM, main display, CAN nodes etc.).
Common to all of these is that they each contain a separate processor. The modules
communicate with each other over a CAN bus. The CAN bus uses serial communication. One
piece of data at a time is sent over the bus until all the data has been transmitted. This is a
simple method that requires only 4 conductors and a screen.
Display D501
All CAN data is handled by the display shown graphically or digitally. The program for the
HEC (Hole/Engine Control) system is stored in the display and the software is downloaded
via a PC or a USB-flash drive (see installation instructions in a separate section).
The display shows engine data, angle/hole information and the status of switches/sensors, etc.
CPU2 receives the information sent from ECM in J1939 protocol and translates this to
CANopen protocol, which is then shown on the display. Other information is sent directly
from the CPUs, CAN nodes, D169 module and D171 module to the display by using
CANopen protocol.
PLC
The PLC system consists of three CPU units (CPU1, CPU2, CPU3). They are each
programmed to handle certain inputs and outputs together with inputs from CAN nodes, and
for some functions inputs from the HEC software is required.
There is a led installed on each CPU unit, a green blinking signal at 2 Hz indicates the CPU is
working normally; a green blinking signal at 5 Hz indicates no operating system is loaded; a
green stable signal indicates a PLC stop. If the led appears to be red or yellow, then the CPU
is experiencing error, contact the factory in this case. And if the led does not light at all, check
the power supply.
All the direct PLC input/output signals are connected to the PLC via 9 indication cards
(marked X10-X18), the led on the indication cards will light in red if the corresponding
input/output is being activated.
11
CAN, general
CAN nodes
The CAN nodes (D550, D551, D552, D553, D554) translate all the input signals for all the
switches located on the operating panels; also the output signals for all the leds and magnets
located in the drill lever, so the modules can communicate in CAN “high”/“low” signals
directly. Every input/output on the CAN nodes each has its own led. The led will light in
constant yellow when their corresponding input/output is activated.
There are also two CAN communication leds on every CAN node, one lights in green and the
other one lights in red. A green stable signal indicates the CAN node is in its preoperational
mode; a green blinking signal indicates that the CAN node is in operation, but both signals
can not indicate whether the CAN node is correctly installed to match the CAN Node ID
number shown in the display. The CAN node ID number has to be set manually on the
module when installed. When a communication fault occurs during operation, the red led will
be activated.
ECM
CAT’s engine control module that controls engine operation.
D169/D171/D173 Module
D169 module is a CAN-based aiming device that communicates with the display directly.
D171 module is a CAN-based angle sensor that communicates with the display directly.
D173 module (option) is a CAN-based GPS compass that communicates with the display
directly.
Terminal plug
At the start and end of the CAN network there are terminal plugs installed. A terminal plug
consists of a resistor (120Ω) which terminates the network’s both ends in the correct way so
that the signal does not “bounce back to the system”.
There are 4 terminal plugs installed in the CAN network which is made of CAN 1 and CAN 2
nets (see figure below). One is connected to D171 module, one is connected to CPUs, one is
connected to plug X4 on the display, and the last one is connected internally to plug X2 on the
displayed (non-visible on block diagram).
12
CAN, general
RCS
X2 CAN 2
D501
X1 ESC
CAN 1
X3
K 11
D550 D169
D173
Ignition D551
D171
D552
End plug
D553
CAN +/-
D554
CAN H/L
CPU1
13
CAN, general
The digital (ON/OFF) switches are connected via the CAN nodes, and the digital sensors are
connected via the CPUs, except sensor B379 (operator in chair) and switch S121 (chair in
position) are connected via CAN node.
By selecting a module with the curse on the screen, and press the enter button, status of each
module could be checked (in the event of a red module).
By selecting in/outputs for the CPUs or the CAN nodes modules on the screen, status for all
inputs and outputs could be checked in the system. An actuated function is displayed as “1”
while and un-actuated function is displayed as “0”.
Note that for an input, “0” or “1” is the status that is received by the CPUs; while “0” and “1”
for an output is the signal sent from the CPUs. I.e. there is not any confirmation that the signal
actually is received by the valve, etc. Broken cables are not noticed by the system.
14
Control panel
Control panel
The control panel is comprised of a touch panel user interface and a power
board for function actuation.
Before ignition, the power board is powered with 24 V via fuse F25, the
button for light in engine compartment and the indication lamp for battery
start to blink in green.
After ignition, the power board is powered with 24 V via fuses F4, F5 and
F10, and the power board is lit up in white.
A CAN cable is used as the communication media between the power board
to the touch panel; also used to power up the touch panel. This CAN
network exists as a separate circuit, aside from the CAN network mentioned
in the chapter before.
15
Diesel engine
Diesel engine
The engine on ROC L740, L740CR is a turbocharged, water cooled C13 diesel engine from
Caterpillar. Rated power at 2000 rpm is 328 kW.
The engine on L830 is a turbocharged, water cooled C15 diesel engine from Caterpillar. Rated
power at 2000 rpm is 402 kW.
Battery switch, ON
When the battery switch S300 is switched on there is 24V to:
• Utility lights in engine compartment, cabin lights, instrumental lights, radio and cell phone
outlets via fuse F25, F26 in A1 cabinet.
• ECM is also powered via fuse F25, but the communication between ECM and rest of the
system has not yet started.
ON OFF
S300 ROC
S300
Ignition position
When the ignition key S139 is in the ignition position the contacts 30-15 and 30-75 are
closed. The ignition relay K11 is activated and the relay contacts are closed under the
conditions that the emergency stops are intact.
When the relay contacts are closed the ECM is supplied with voltage via fuse F13, ECM is
now functional. The display and the emergency stop circuit are also supplied with voltage via
fuse F25. PLC processor and sensor inputs are supplied with voltage via fuse F14. PLC
outputs and relays, CAN nodes are supplied with voltage via F15-F23.
The above figures show the display transition during ignition, several symbols for the rig
functions can be lit (only the symbol for communication breakdown is shown here in the
above example) for a few seconds before going off since the ECM has been waiting to be
booted.
16
Diesel engine
Start position
Conditions for activation of starter motor:
• Emergency stops S132A and S132B not activated => PLC input X10-8/ON
• Fuses F100, F3, F13, F14, F15, F23 are intact.
• S130 in tramming mode => D552-CH2 or CH3/ON
• Compressor switch S180 OFF => D552-CH9/OFF
• Ignition key S139 in start position => D550-CH4/ON
• Only for L830: Start preventing pressure sensor B336 OFF => PLC input X13-4/OFF
When all the above conditions are met, this will result in:
• Start relay K5A is activated and the relay contact is closed, hence activating starter motor M1,
i.e. engine is cranking.
When the ignition key S139 is turned to the start position and the engine fails to start, check
which symbol(s) are displayed and rectify the fault. Turn the key back to position 0 before
trying again.
ECM overview
ECM is functional when the battery is
switched (1) and the ignition key is position
(2). To start the diesel engine, K200 has to be PLC Remote shut down
Batteries
Manually switching off the ignition key shuts
down all the above mentioned functions
including the display.
To cut off ECM power supply completely, dis-engage the battery switch S300.
17
Diesel engine
Engine speed
The engine speed can be de- or increased by flicking switch S189
up- or downwards. Digital signal is sent directly into the CAN
node D554, then to CPU2 through CAN open protocol, and at last
sent to the ECM through J1939 protocol. b c
a d
CPU2 can support 7 engine revolutions, and it can store 3 separate
engine speeds, one for tramming, one for rod handling and one for
drilling. CPU2 remembers the engine speeds for rod handing and a
drilling even when the battery switch is turned off. In tramming
mode the system will always start at 1200 rpm. The speeds can all b
be set individually within the range specified below. c
The engine starts on idling speed 1200 rpm, flicking the switch once upwards should increase
the speed to 1500 rpm, then the engine speed increases with 100 rpm per flick upwards until it
reaches the maximum speed of 2000 rpm. It is also possible to hold the switch for several
seconds in order to reach the maximum speed. To decrease the engine speed from the idling
speed, flick the switch once downwards takes down the speed step by step just like upwards.
When changing from tramming position to drilling, the engine speed automatically increases
to engine speed set for drilling and vice versa.
18
Diesel engine
Control instrumentation
The ECM controls and monitors all engine data and diagnostic information from the diesel
engine. This information is sent via CPU2 to the display, where all the necessary engine
information is presented. CPU2 also translates the information from J1939 to CAN open so it
can be presented on the display.
Signals from the rig sensors are sent via the CPUs directly to the display, where information
can be viewed. (See figure)
Engine monitoring
A number of sensors and switches on the engine do not generate warnings on the status bar in
the event of a fault. A direct code system has been introduced, this allows you to go directly
to the CAT fault diagnosis table to interpret the codes. The table will only present information
when a fault arises. The ECM or the engine sensor symbol on the status bars indicates that a
fault has been detected. This can be found in the menu for ECM sensors. The fault is
displayed as a 3 digit SPN code and 2 digit FMI code. (See figure)
Ex:
SPN code 164. According to the CAT manual, 164 is the injection actuator pressure sensor.
The SPN code indicates the faulty component.
FMI code 02. According to the CAT manual, 02 means that the sensor does not have a signal.
The FMI code indicates the nature of the problem.
Note: The CAT fault diagnosis table will only show faults that are related to the motor. That
is to say some faults indicated on the status bar can be found in the table, but not all the faults
show in the table can be found on the status bar.
19
Diesel engine
Switches and sensors that automatically and manually stop the diesel
engine
Automatically stopping (or shutting down) the diesel engine does not mean that the whole
system also goes off. All functions at the key ignition level are still working. To shut down
the whole system including the display, turn the key back to the 0 position.
Manual:
Automatic:
These are indicated by a red lamp on the status bar and switch the engine off automatically.
20
Diesel engine
• Fuel temperature
The engine fuel temperature sensor is part of the Capterpillar system and connected to the
ECM. Should the fuel temperature reach 80°C, a warning is shown on the status bar.
• Battery voltage
Should the battery voltage fall below 24 V, a warning is shown on the status bar.
21
Diesel engine
22
Pumps & Pilot Pressure L740, L740CR
Pumps & Pilot Pressure
Pump 1 – L740, L740CR
Pump 1 is the main pump in the hydraulic system of ROC L740, L740CR. It is an axial piston
pump with a variable displacement. The pump is pressure compensated, which means that the
pressure is maintained constant irrespective of the flow.
The pump pressure can be controlled by either pressure relief valves connected to the control
panel when impact is started, or by pressure control valve 4d.
23
Pumps & Pilot Pressure L830
Pump 1 – L830
Pump 1 is the main pump in the hydraulic system of ROC L830. It is an axial piston pump
with a variable displacement. The pump is pressure compensated, which means that the
pressure is maintained constant irrespective of the flow.
The pump pressure can be controlled by pressure control valve 4d.
In order to avoid start the diesel engine with pump 1 pressurized, the Drilling/Tramming
switch must be in the Tramming position when starting. In this position, pump 1 runs at
standby pressure, 23 bar. Starting with the switch in Drilling position is also electrically
blocked.
24
Pumps & Pilot Pressure
Pumps 2, 3 and 4
Pumps 2, 3 and 4 are combined to a triple gear pump, mounted on pump 1.
The maximum pressure of pump 2 is set by relief valves 4x and 4y in the drill rotation circuit.
The pressure of pump 3 can be set on a variable relief valve 13a in the DCT valve block.
The pressure of pump 4 is set by a fixed relief valve 4c in the main valve block.
Pump 2 & 3 are running unloaded in different ways when switch S130 is in Tramming
position.
Pumps 5 and 6
Pumps 5 and 6 are gear pumps and driven by an extra power take off on the side of the diesel
engine.
The maximum pressure is set by an electro proportional relief valve mounted in each cooler
fan motor. These pumps are loaded 15 seconds after engine start.
25
Pumps & Pilot Pressure
Pilot pressure
Pilot pressure is supplied by pump 1 and generated in the main valve block by pressure
reducing valve 4b set to 35 bar, and then out to the pilot circuits.
Solenoid valve Y169 control whether the pilot pressure goes to the drilling circuit or to the
tramming circuit. Solenoid valve Y169 is activated when the Drilling/Tramming switch S130
is in tramming position and deactivated when the switch is in drilling position.
26
Cooling fans
Cooling fans
The rig is equipped with two standard fan drives, one for cooling the compressor/hydraulic
oil, and one for cooling the engine water/air inlet. High ambient temperature fan drive for
warmer environment is available as an option.
The signal input to solenoids Y504 and Y501 varies between 50mA – 510mA depending on
the cooling demands.
Revolution
0 mA
50 510
27
Tramming
Tramming
Conditions for tramming function:
Tramming direction and speed is controlled via the tramming S174 S175
paddles (S174/S175 see figure). These controls send a signal to
the electrical pilot valves for tramming forward or backward.
The pilot pressure changes the directional valves’ position
proportionally and pump 1 supplies the tramming motors’
hydraulic circuits with oil.
28
Tramming
Activation of Y121A:
- It allows pump 1 pressure to connect to pressure compensator 4p and 4r in the main
valve block, 4p and 4r also have the functions of dividing the oil flow equally. The
tramming pressure is limited by pressure relief valve 4d set to 230 bar.
Activation of Y121B:
- The oil flow from pump 4 goes through pressure relief valve 4c set to 250 bar. The
pressure is then delivered to positioning functions.
Activation of Y169:
- It allows pilot pressure to come through to the tramming circuit.
The tramming direction and speed are controlled by means of pilot pressure controlling the
proportional directional valves. And these directional valves are controlled by solenoid valves
Y206A, Y206B, Y207A and Y207B.
The valve block included in the tramming motor 66 contains a shuttle valve 66a, a pilot
operated directional valve 66b and a pressure reducing valve 66c for releasing the tramming
brake when the motor is pressurized. To prevent the motors from increasing speed when
tramming down a slope, the over centre valve 66d serves as hydraulic brakes by means of
creating counter pressure in the motor return line when the pressure in the motor pressure line
drops.
Reverse warning
Warning signal/flash H185 is activated when tramming backwards.
29
Positioning
Positioning
The positioning circuit is mainly supplied with oil from pump 1. However, since the
tramming circuit is also supplied from pump 1, it is necessary to use pump 4 for positioning
during tramming. Since pump 1 is bigger and operates at higher pressure than pump 4, it
means that positioning is quicker in Drill mode than it is in Tramming mode.
Track oscillation
The track oscillation solenoid valves Y419 and Y420 are controlled by switch S176 and S177
respectively.
The oscillation cylinders are hydraulically linked by a two positioned solenoid valve, Y473,
controlled by switch S445.
- ON, Floating
When solenoids valve Y473 is activated with switch S445 in
position (a), the valve is open allowing system pressure to open
the over centre valves in the Track Oscillation valve block 68. b c
Both cylinders are inter-connected to enable oil to flow between a d
- OFF, Locked b
When solenoid valve Y473 is de-activated, the connection c
between the two cylinders is blocked. Both cylinders can still be
operated individually by switches S176 and S177.
This valve position should be used all the time except when the
rig is trammed in order to ensure a stable set-up.
30
Air System & Compressor
The volume of flushing air is controlled by the Flush air switch Figure: example, L740 left panel
S100, but activation of flushing air is done with Impact switch S446.
There are two air flushing modes, reduced and full air flushing, activated by their respective
solenoid valves Y116 and Y115. When full air flushing is activated, both the valves are open
and when reduced air flushing is activated only Y116 is open.
When a low flushing air pressure and flow is required, e.g. collaring in fractured rock, the
flushing air can be used in reduced mode by setting switch S100 in position (b). In this
position only Y116 will be activated.
31
Air System & Compressor
32
Air System & Compressor
Extra air-outlet
The rig is equipped with two air outlets where a grinder or tool can be connected. The air
pressure is limited to 7 bar by a pressure reducing valve.
Compressor
General – L830
The on board compressor is a double stage, oil-injected screw compressor. The normal
working pressure has been set to 30 bar, which also is the maximum pressure. The maximum
free air delivery (FAD) is 434.2 l/sec at 30 bar working pressure with 20°C ambient
temperature.
33
Air System & Compressor
Air flow
Intake air is drawn in through the air filter and the inlet valve to the compressor element. The
air is mixed with injected oil and after compression is passed through the check valve into the
air receiver. The check valve prevents back-flow of compressed air when the compressor is
stopped. In the air receiver, most of the oil is removed from the air/oil mixture by the oil
separator. The flow of compressed air then passes through the minimum pressure valve out
into the drill rigs air system. The minimum pressure valve prevents the pressure in the air
receiver to drop below the minimum working pressure of the compressor before the air is
released, in order to ensure proper function of the oil system.
Air/Oil Mixture
Oil
34
Air System & Compressor
Note: A thermostatic valve bypasses the oil cooler when the oil is below 40 °C for L740,
L740CR, and 80 °C for L830.
35
Oil pre-heating L740, L740CR
Oil pre-heating
Oil pre-heating – L740, L740CR
Pump 2 is used for pre-heating the hydraulic oil
and the rock-drill impact components. Normal
operating temperature of the hydraulic oil is
40°C. Before operating the drill rig the oil
should be pre-heated to minimum operating
temperature, 20°C.
36
Oil pre-heating L830
Oil pre-heating – L830
Pump 2 is also used for pre-heating the hydraulic oil. Normal
operating temperature of the hydraulic oil is 40°C. Before
operating the drill rig the oil should be pre-heated to minimum
operating temperature, 20°C.
Note: It’s possible to tram the rig at the same time warming up
the hydraulic oil, solenoid valve Y169 can also be activated
when S130 in pre-heating position.
37
Drilling functions
Drilling functions
Activation of drilling functions – L740, L740CR
When S130 is in drilling position, Y121A and Y121B are not activated, Y169 is deactivated
to let through pilot pressure to the drilling circuits.
De-activation of Y121A:
- It allows pump 1 pressure to connect to LS/pump pressure line directly. If impact is
activated, the pump pressure will be according to the preset values of the
hammer/pump pressure pressure relief valves (47e and 47f) in the logic block. If
impact is not activated, the working pressure is limited by pressure relief valve 4d.
De-activation of Y121B:
- The pump 4 pressure supplied to positioning functions during tramming, is now used
for rotation function together with pump 2. This is simply to assist pump 2 for a better
rotation output.
De-activation of Y169:
- Pilot pressure is now led to the drill lever through logic valve and to the DCT circuit,
PLC output X11-1/OFF.
The Drilling functions such as Drill feed, Rapid feed, Rotation and Threading functions are all
controlled by one drill lever.
De-activation of Y121A:
- It allows pump 1 pressure to connect to LS line directly. The working pressure is
limited by pressure relief valve 4d.
De-activation of Y121B:
- The pump 4 pressure supplied to positioning functions during tramming, is now used
for rotation function together with pump 2. This is simply to assist pump 2 for a better
rotation output.
De-activation of Y169:
- Pilot pressure is now led to the drill lever through logic valve and to the DCT circuit,
PLC output X11-1/OFF.
The Drilling functions such as Drill feed, Rapid feed, Rotation and Threading functions are all
controlled by one drill lever.
38
Drilling functions
Drill feed
The drill feed circuit includes functions for feeding down- and upwards and controlling the
feed pressure during collaring and drilling. The hydraulic power is supplied from pump 1.
The Anti-Jamming circuit is described separately, see chapter “Protective functions”.
F
C 8I
L740
Drill mode: Rapid feed/threading mode:
E: neutral E: neutral
B: rotation anti-clockwise B: Threading
B+A: rotation anti-clockwise and feed B+A: rotation anti-clockwise and rapid feed
forward (magnet function) forward
B+C: rotation anti-clockwise (magnet B+C: rotation anti-clockwise and rapid feed
function) and feed backward. backward
D: Feed forward (magnet function) D: Rapid feed forward
F: Feed backward F: Rapid feed backward
H: rotation clockwise H: Unthreading
H+G: rotation clockwise and feed forward H+G: rotation clockwise and feed forward
H+I: rotation clockwise and feed backward H+I: rotation clockwise and feed backward
Diode H452 is lit in this mode. There is no diode indication in this mode.
39
Drilling functions
L740CR, L830
Drilling mode: Rapid feed/threading mode:
E: neutral E: neutral
B: rotation clockwise B: Threading
B+A: rotation clockwise and feed forward B+A: rotation clockwise and rapid feed
(magnet function) forward
B+C: rotation clockwise (magnet function) and B+C: rotation clockwise and rapid feed
feed backward. backward
D: Feed forward (magnet function) D: Rapid feed forward
F: Feed backward F: Rapid feed backward
H: rotation anti-clockwise H: Unthreading
H+G: rotation anti-clockwise and feed forward H+G: rotation anti-clockwise and feed
H+I: rotation anti-clockwise and feed backward forward
H+I: rotation anti-clockwise and feed
backward
Diode H452 is lit in this mode. There is no diode indication in this mode.
Magnetic holding on rotation during drilling or/and feeding forwards can only be achieved
when the control lever is being pulled to the end position, and when S452 is not activated
(Led H452 = ON). Pulling the lever only half way and then release would result in lever
springed back to the neutral position, which also marks the end of the movement.
To unlock the magnetic lock and get the lever back to the neutral sector, activate switch S453
or shift the lever to Rapid feed position with switch S452.
When switch S453 is pressed once on the drill lever the magnets will be temporarily
deactivated and the drill lever returns to neutral position which results in the actual feed and
rotation being switched off, with impact and air flushing remains on.
Magnetic holding can also be switched off once S452 is activated, thus shifting to rapid
feed/threading mode where magnetic holding is not supported. The actual impact and air
flushing at this point will also be switched off.
Note: Magnetic holding will be automatically reactivated after a delay of 0.2 seconds if
switch S453 is deactivated. This means that the next time the drill lever is moved to one of
these sectors (sector for drill feed or drill rotation), magnetic holding will be activated again.
40
Drilling functions
The feed circuit is supplied with oil from pump 1. In drill mode the electrical pilot valves
Y178A-F are not activated. When feed is activated with the drill lever the pilot pressure is
directed first via either directional valves Y178A or B depending on the choice of feed
direction, then via directional valve Y109 which changes the feed direction in case of anti-
jamming and out to the directional valve in the drill feed block. Anti-jamming is described
later.
• Feed pressures
The pressure for forward feeding can be read on pressure gauge 33.
The feed pressure is generated from the system (Feed/Tram) pressure by pump 1, and it is
regulated by pressure relief valve 4d. When feeding forwards, the pressure relief valves 47a
or 47b limits the maximum pressure to the feed cylinder. If these pressure relief valves would
for some reasons fail to work, then the check valve 4n would limit the maximum pressure.
When feeding forwards during drilling, pressure compensator 4e in the main valve block is
controlled by either pressure relief valve 47a or 47b for low and high feed pressure
respectively. The impact switch control S446A and S446B determines which valve controls
the pressure as below:
41
Drilling functions
• Feeding speed
The drill feed speed is set to correspond to a drill feed speed of 15
m/min upwards and 8 m/min downwards.
42
Drilling functions
Drill rotation
Note: When Y179A/B is activated the magnetic holding is obtained when the drill lever is
moved to the sectors for drill rotation or/and drill feed.
When switch S453 is pressed once on the drill lever the magnets will be temporarily
deactivated and the drill lever returns to neutral position which results in feed and rotation
being switched off, with impact and air flushing remains on.
Magnetic holding can also be switched off once S452 is activated, thus shifting to rapid
feed/threading mode where magnetic holding is not supported. The actual impact and air
flushing at this point will also be switched off.
Note: Magnetic holding will be automatically reactivated after a delay of 0.2 seconds if
switch S453 is deactivated. This means that the next time the drill lever is moved to one of
these sectors (sector for drill feed or drill rotation), magnetic holding will be activated again.
When rotation is activated (with the drill lever) the pilot pressure is directed, via electrical
pilot valve Y178C or D depending on the choice of rotation direction, then to the directional
valve 4w in the main valve block. If clockwise rotation (for drilling) is activated the pilot
pressure passes via pilot valve Y178D through a flow regulator (see figure below) which
regulates the rotation speed for drilling. In ROC L740 and L740CR, the pilot pressure also
activates the DPC-I system. (For further information, refer to section “DPC-I” under chapter
“Damper & DPC-I system”.)
43
Drilling functions
• Rotation speed
- L740 Anti-clockwise rotation (drilling); L740CR & L830 Clockwise rotation (drilling)
When the drill lever is in “Drill-rotation” position, the setting of the flow regulator
controls how much the directional valve 4w will open. The flow to the rock drill rotation
motor is proportional to the opening of the directional valve 4w.
- L740 Clockwise rotation; L740CR & L830 Anti-clockwise rotation
The drill lever controls the rotation speed. The main directional valve 4w opens in
correspondence to the lever angel. The flow regulator is not connected.
The adjustment knob for flow regulator can be seen in chapter “Adjustment/calibration”.
• Rotation pressures
The rotation pressure is generated by pump 2 with the assistance of pump 4 when drilling.
Depending on the direction of rotation, the pressure relief valve 4u or 4t is activated to limit
the maximum pressure for clockwise and anti-clockwise rotation respectively.
L740: The maximum pressure for rotation anti-clockwise is limited to 125 bar (valve 4t), and
the maximum pressure of rotation clockwise is limited to 160 (valve 4u) bar.
L740CR & L830: The maximum pressure for rotation clockwise is limited to 125 (valve 4t)
bar, and the maximum pressure of rotation anti-clockwise is limited to 160 (valve 4u) bar.
44
Drilling functions
Rapid feed
When rapid feeding forwards, the logic valve R is activated by the forward pilot pressure. The
return oil from the feed cylinder is being directed to both directional valve 4j for drainage
back to the tank and via the activated Y178F to logic-R for drainage back to the tank. This is
in order not to run all the return flow from the piston side though the directional control valve,
so the cylinder can reach a higher speed.
45
Drilling functions
• Logic valve P
When rapid feeding backwards, logic valve P is activated by the pilot pressure. The activated
logic valve blocks the forward feeding action, which is part of the threading function when
pulling the drill lever to the left in order to achieve some rotation (ex. when cleaning the
drilled hole). In other words, if logic-P is not activated, and rotation (anti-clockwise rotation
only, clockwise rotation would cause the threads to come loose) is needed for rapid feed
backwards. This would result in feed direction valve 4f giving out feed forward pressure and
rapid feed direction valve 4j giving out rapid feed backward pressure, logic-P blocks the pilot
signal to 4f.
M4 M3 M2 M1
Stop forward (M1) – Rapid feed stop forward above the upper drill steel support, so the rock
drill can be threaded into the rod caught in the drill steel support.
Stop lower uncoupling (M2) – Rapid feed stop backward, when the coupling sleeve is in the
upper drill steel support in order to unthread the rods.
Stop upper uncoupling (M3) – Rapid feed stop backward, when the rod is in correct position
to be inserted into the magazine.
Stop backward (M4) – Rapid feed stop backward, at a position above the RHS magazine,
but before mechanical stop. This stop is used prior to adding/removing a rod to/from the drill
centre.
46
Drilling functions
M4 M3 M2 M1
Stop forward (M1) – Rapid feed stop forward above the breakout table, so the rock drill can
be threaded into the tube caught in the lower breakout jaw.
Stop lower uncoupling (M2) – Rapid feed stop backward, when the joint between two tubes
is between the breakout jaws in order to break the tube threads.
Stop upper uncoupling (M3) – Rapid feed stop backward, when the tube is in correct
position to be inserted into the magazine.
Stop backward (M4) – Rapid feed stop backward, at a position above the RHS magazine,
but before mechanical stop. This stop is used prior to adding a new tube into the drill centre.
47
Drilling functions
M4 M3 M2 M 1M 0
Impact stop (M0) – Feed stop forward between M1 and the mechanical stop forward. No
impact is allowed if the rock drill is too near the mechanical stop.
Stop forward (M1) – Rapid feed stop forward just above the breakout table, so the rock drill
can be threaded into the tube caught in the lower breakout jaw.
Stop lower uncoupling (M2) – Rapid feed stop backward, when the joint between two tubes
is between the breakout jaws in order to break the tube threads.
Stop upper uncoupling (M3) – Rapid feed stop backward, when the tube is in correct
position to be inserted into the magazine.
Stop backward (M4) – Rapid feed stop backward, at a position above the RHS magazine,
but before mechanical stop. This stop is used prior to adding a new tube into the drill centre.
48
Drilling functions
Calibrating B172
In order for these build-in software stops to work, calibration sensor B104 is used to calibrate
the depth encoder B172. The depth encoder B172 is an optical encoder which through
sending out pulses defines the position of the cradle on the beam.
The distance to be entered in the display is the cradle travel distance between the rear end
mechanical stop and when the indicator plate actuates sensor B104. This value can be put in
manually or automatically.
Manual input
Operator needs to use a ruler to manually measure the distance between the front of the rock
drill cradle indicator plate and the calibration sensor B104, when the rock drill is in its rear
end stop.
Automatic input
The cradle needs to be moved back to the upper most position at the mechanical stop. To
carry out this movement, the drill lever needs to work in drill mode. Once the cradle has
reached the top end, reset the position of the cradle. Then mark the check-box for “Auto set
sensor position”, now move the drill lever forward slowly so the cradle can pass through the
calibration sensor B104 at a maximum speed of 4m/min. Once B104 is activated, a value is
presented on the display.
Note: It’s recommended that both manual and automatic input is done to ensure a better
precision. This distance is a factory setting, it is not necessary to change the distance unless
sensor B104 has been moved, or if the rock drill’s rear-end mechanical stop has been
changed, i.e. if the feed ropes have been replaced or tensioned.
Calibration is done every time the cradle passes through B104 from above, a distance is then
achieved. This distance (measured by B172) is being compared with the preset value of B104
in the display. If these two distances differ from each other, the B104 value will then over-
write the B172 measured value, so measurement can be carried on correctly from this point.
In other words, B104 can be seen as a control factor in length measuring.
49
Drilling functions
Threading
In threading mode the electrical pilot valves Y178A-F are activated just as in rapid feed
mode. The threading function is a combined activation of both drill feed and rock-drill
rotation by one lever stoke. When threading is activated with the drill lever the pilot pressure
is directed via the activated solenoid Y178C or D depending on the choice of threading
direction, and then to the directional valve in the drill feed and rotation block respectively.
By pulling the lever to the left (threading), logic valve G is activated, which connects the feed
pressure to the pressure relief valve for thread feed forward 47d. And by pulling the lever to
the right (unthreading), logic valve H is activated, which connects the feed pressure to the
pressure relief valve for thread feed backward 47c.
Feed:
As earlier mentioned in Rapid feed, all of the electrical pilot
valves Y178A-F are activated when the switch for switching
to rapid feed/threading S452 is activated. Y178A-D affect the
choice between drill and feed mode, and Y178E-F affect the
drill feed speed since it will be much slower than feed and
rapid feed. The feed speed can be changed by adjusting the
flow regulators 10 located in respective feed direction. They
shall be set to match the pitch of the drill string threads.
50
Drilling functions L740, L740CR
Impact with air flushing – L740, L740CR
Conditions for the impact function:
The impact circuit includes function for activating the rock drill impact mechanism and
controlling the pressure for collaring and drilling (low and high pressure). The circuit also
activates the Impact hour counter (a function of the HEC software in the display).
Activation of Impact
Pressing the impact control switch S446A/B for longer than 0.5 seconds activates low
respective high impact under the condition that high impact is achieved after first using low
impact. Otherwise if starting directly on high impact, the button for high impact activation
S446B must be held in at all time. Logic valves I and J in the DPC-I system sense the rock
drill damper pressure. If the damper pressure is lower than the preset value of logic-I or
higher than the preset value of logic-J, the valves will prevent activation of impact.
When impact is activated, pump 1 system pressure is also led to logic valve B, which allows
any of the two impact pressure relief valves 47e and 47f to take control over the pump 1
pressure. In ROC L740CR, there is also a logic valve O that will stop/prevent impact when
feed pressure is below its preset value.
S446A/B controls the activation of solenoid valves Y115, Y116 in the air system, but it is
S100 that controls the combination of Y115 and Y116. It’s recommended to keep S100
activated to allow full flushing air pressure as soon as S446 is activated. S100 should be
switched off (changing to reduced flushing air) only when drilling through a weaker complex
of the rock layer. S446A/B also control three solenoids valves in the hydraulic system,
Y101A, for activating impact, Y101B, for activating low impact, Y101C, for switching
between high/low feed pressure.
51
Drilling functions L740, L740CR
Air flushing:
Solenoid valve Y116 (or Y116+Y115) is activated to engage reduced (or full) air
pressure depending on the status of Y100, and the air pressure is directed to the
regulating valve for air pressure regulation.
Drill feed:
The drill feed low pressure solenoid valve Y101C is not activated in order to engage
low feed pressure.
Deactivation of impact
Impact can be deactivated by pressing S446A/B for shorter than 0.5 seconds. If the lever is
situated in magnetic holding position, impact will be switched off with the lever returning to
the neutral position, thus also switching off feed, rotation and air flushing.
Impact
hour count Accumulated
since last impact hours
reset.
52
Drilling functions L830
Impact – L830
Conditions for the impact function:
The impact circuit includes function for activating the DTH hammer impact mechanism and
controlling the pressure for collaring and drilling (low and high pressure). The circuit also
activates the Impact hour counter (a function of the HEC software in the display).
Activation of Impact
Pressing the impact control switch S446A/B for longer than 0.5 seconds activates low
respective high impact.
The impact control switch S446A/B, positions low and high, control three solenoid valves in
the air system, Y116, low impact, Y115, high impact and Y210B, high/low air pressure
regulation. They also control one solenoid valve in the hydraulic system, Y101C, switching
between high/low feed pressure.
53
Drilling functions L830
Deactivation of impact
Impact can be deactivated by pressing S446A/B for shorter than 0.5 seconds. If the lever is
situated in magnetic holding position, impact will be switched off with the lever returning to
the neutral position, thus also switching off feed, rotation and air flushing.
Impact
hour count Accumulated
since last impact hours
reset. (can not be reset)
54
Drilling functions L740, L740CR
Impact stroke length
The stroke length of the COP 4050, COP 4050CR impact
piston is electrically controlled through switch S400.
Which position to use has to be decided from the rock condition. Drilling in softer formations,
each stroke can contain more energy than can be absorbed by the rock. In such cases it can be
better to use only the short stroke length.
55
Drilling functions L740, L740CR
ECL, rock drill lubrication system
Function
ECL pump Y106 starts to pump as soon as Impact is turned ON. The ECL pump is an
electrical piston pump, controlled by the PLC output X17-9 which sends out pulses to the
pump. Lubrication oil is then fed through a small plastic hose inside the air hose to the rock
drill, where the oil and air are mixed. A pressure reducing valve set to 5.5 bar limits the
amount of air used for the ECL system. The ECL lubrication pressure gauge is located in the
cabin. There are two sensor switches which control the ECL oil collection pressure, B381 for
limiting the low collection pressure and B382 for limiting the high collection pressure. The
ECL oil collection system is optional.
Note: The ECL pump works for an extended time after the percussion is switched off.
This time delay can be adjusted via the HEC3 display.
Adjustable parameters
• Time pulse – length of the pulse, i.e. the signal
time.
• Pulses/minute – how many pulses there is per
minute
• Extended time – total time of the pumping
cycle (after air flushing stop).
56
Drilling functions L830
HECL, DTH hammer lubrication system
Function
The HECL pump Y165 is a hydraulic driven lubrication pump that starts pumping as soon as
the Impact/Flushing air is turned ON. The pump receives pulses from the HECL PLC output
X11-16 (30-40 pulses/min) in the electrical cabinet. Lubrication oil is then led through a ¼”
hose to the rotation unit, where the lubricating oil and air is mixed. The HECL lubrication
pressure gauge is in the cab.
Note: The HECL pump works for an extended time after the percussion is switched off.
This time delay can be adjusted via the HEC3 display.
Adjustable parameters
• Time pulse – length of the pulse, i.e. the signal
time.
• Pulses/minute – how many pulses there is per
minute
• Extended time – total time of the pumping
cycle (after air flushing stop).
57
Drilling functions L740CR
HECL, COPROD head and sections lubrication system
Function
The HECL pump Y165 is a hydraulic driven lubrication pump that starts pumping as soon as
the Flushing air is turned ON. The pump receives pulses from the HECL PLC output X11-16
(30-40 pulses/min) in the electrical cabinet. Lubrication oil is then led through a ¼” hose to
the flushing air connection at the rock drill, where the lubricating oil and air is mixed. There
is no pressure gauge for the HECL lubrication pressure.
Note: The HECL pump works for an extended time after the percussion is switched off.
This time delay can be adjusted via the HEC3 display.
Adjustable parameters
• Time pulse – length of the pulse, i.e. the signal
time.
• Pulses/minute – how many pulses there is per
minute
• Extended time – total time of the pumping
cycle (after air flushing stop).
58
Damper & DPC-I system L740, L740CR
Damper & DPC-I system
Damper
The rock-drill damper circuit is supplied with oil from Pump1 through a constant flow
regulator. The flow regulator is adjusted to correspond to a pressure of 25 bar at the damper
hose connection on the rock-drill.
The damper pressure during drilling shows the actual feed force on the drill bit. The pressure
can be read on the pressure gauge in the cabin. During drilling, the damper pressure controls
certain logic valves, which in turn controls the impact pressure (hammer pressure). This is
described below as the DPC-I system.
Read on the gauge on the damper connection the pressure should be:
COP 4050 & COP 4050CR, 25 bar
The corresponding pressure read on the cabin gauge: (happens to be higher than the one read
on the damper connection because it has a smaller pressure drop)
COP 4050 & COP 4050CR, 30 bar
NOTE! The percussion should stop if the damper pressure exceeds 120 bar of if it is lower
than 45 bar.
Warning! Wronged adjusted damper pressure can cause damage to rock-drill, drill rig and
drill string. Adjustments should only be performed by a qualified Atlas Copco
service technician.
59
Damper & DPC-I system L740, L740CR
DPC-I System
Function
The DPC-I system (Damper Pressure Controlled Impact) controls the impact function by
sensing the damper pressure during drilling. Depending on the damper pressure, impact can
be allowed, stopped or changed between high and low impact pressure. This is done by a
number of logic valves in the rig hydraulic system.
• Logic-I. Prevents activation of impact if the damper pressure is below 45 bar, or stops
impact if the damper pressure drops below 45 bar in case of, e.g., hose rupture, valve
malfunction or drilling into cavity.
• Logic-J. Stops impact if the damper pressure exceeds 120 bar in case of, e.g., excessive
feed pressure or mechanical failure of the damper.
• Logic-A. During normal drilling with high impact pressure, the logic proportional valve A
is activated by the damper pressure through logic valve D. If the damper pressure falls
below the preset value of logic-A, it is deactivated. The Pump 1 pressure provided by the
high impact relief valve 47f is then connected to the low impact relief valve 47e, thus the
low impact relief valve 47e controls the pump pressure.
ROC L740CR:
• Logic-O. Allows activation of impact when the feed pressure has reached 45 bar and stops
impact when feeding backwards or entering a cavity in the rock.
Warning! Wronged adjusted damper pressure can cause damage to rock-drill, drill rig and
drill string. Adjustments should only be performed by a qualified Atlas Copco
service technician.
ROC L740:
Guidelines for setting logic valves. (Optimum setting might be higher).
Logic-I Logic-J Logic-A
45 bar 120 bar 50 bar
ROC L740CR:
Guidelines for setting logic valves. (Optimum setting might be higher).
Logic-I Logic-J Logic-A Logic-O (Feed pressure)
45 bar 120 bar 50 bar 45 bar (or 2-5 bar below low feed pressure).
60
Damper & DPC-I system L740
Setting during drilling – L740
Logic-I, Setting during drilling:
1. Check that the damper pressure is adjusted according to “Adjusting the damper pressure”.
2. Start drilling on low impact pressure and collaring feed pressure.
3. Adjust the feed pressure slowly towards 0 while observing the damper pressure gauge.
4. When the damper pressure drops below 45 bar as a result of the low feed pressure, impact should be
stopped automatically.
5. If needed, adjust logic-I CW to increase the setting or CCW to decrease it.
6. Test the function by starting drilling on low impact pressure and collaring feed pressure. When the drill
cradle comes to a stop against the mechanical end stop, impact should shut of immediately. If not, the
setting of logic-I should be increased.
NOTE! The setting of logic-I should be the highest possible without making it difficult to start impact. This
means that high collaring feed and damper pressures calls for a higher setting of logic-I.
61
Damper & DPC-I system L740
6. Verification: Increase and decrease the damper pressure a few times in order to verify that impact is
stopped when the damper pressure is below 45 bar.
7. De-activate impact and turn off the diesel engine.
8. Tighten the lock nut on logic-I without changing the setting and reconnect the impact pressure hose on
the rock-drill.
9. Adjust the damper pressure according to “Adjusting the damper pressure”. Verify through test drilling
that impact can not be activated unless the drill bit is pressed against the rock.
62
Damper & DPC-I system L740
Related logic-valves
• Logic-D. It is activated by the pilot signal for drill rotation anti-clockwise. This means
that the DPC-I system is only in effect when drill rotation is active. When logic-D is
closed to damper pressure it is open to the Pump 1 system pressure. This means that when
rotation is not active, the impact pressure will be according to the position of the impact
control switch S446A/B, irrespective of the damper pressure.
• Logic-C. It is activated through Y101B (impact low pressure activated) or when feeding
backwards. This excludes logic-E from getting activated. Consequently, in these cases
there can only be low impact pressure. Feeding backwards and activating impact is the
case when back hammer function is switched on. It does not matter which impact button
(high or low) is pushed, the impact pressure will stay low anyway.
Note: Impact pressure has the same pressure as the pump pressure, since impact pressure
comes from pump 1. In the diagram they are being distinguished by two different colours to
identify their own circuits.
When activating button S446B for high impact, solenoid valve Y101A is then activated. The
oil from Y101A activates logic-B, allowing the pump pressure to come through. The adequate
damper pressure activates logic-I, leading the impact pressure to logic-Q and logic-E. The
activated logic-Q ensures the hammer pressure gets delivered. The activated logic-E leads the
pump pressure to pressure relief valve 47f under the condition that logic-A is activated.
The meaning with DPC-I is that the pump 1 pressure is controlled by the damper pressure.
The adequate damper pressure activates logic-A when anti-clockwise rotation is active. But
when the damper pressure falls below the preset valve of logic-A (adjustable), the pump
pressure is then led from pressure relief valve 47f to 47e. (see figure above)
63
Damper & DPC-I system L740CR
Setting during drilling – L740CR
Logic-I, Setting during drilling:
1. Check that the damper pressure is adjusted according to “Adjusting the damper pressure”.
2. Disable logic-O by turning its adjustment screw 3-4 turns CCW. If this is not done, impact will be
stopped due to too low feed pressure during the setting of logic-I.
3. Start drilling on low impact pressure and collaring feed pressure.
4. Adjust the feed pressure slowly towards 0 while observing the damper pressure gauge.
5. When the damper pressure drops below 45 bar as a result of the low feed pressure, impact should be
stopped automatically.
6. If needed, adjust logic-I CW to increase the setting or CCW to decrease it.
7. Verify that impact can not be activated without rock contact, and that impact can be activated when the
bit is pressed against the rock with collaring feed pressure.
8. Readjust logic-O by turning its adjustment screw CW the same number of turns as it was turned CCW
in point 1, or according to instruction.
9. Test the function by going into the display and change the setting for “impact stop” (position M0) by
adding 0.5 m in menu “Rapid feed stop”. This will deactivate the automatic impact stop. Write down
the original setting! Impact should then cease immediately when the rock drill cradle stops against the
mechanical end stop. If not, the setting of logic-I should be increased.
10. Re-enter the parameter setting for “impact stop”.
NOTE! The setting of logic-I should be the highest possible without making it difficult to start impact. This
means that high collaring feed and damper pressures calls for a higher setting of logic-I.
NOTE! Excessive drilling with too low feed pressure can cause damage to COPROD sections and rock
drill.
64
Damper & DPC-I system L740CR
3. Increase the feed pressure towards maximum while observing the damper pressure gauge.
4. When the damper pressure exceeds 120 bar, impact should be stopped automatically.
5. If needed, adjust logic-J CCW to lower the setting or CW to increase it.
NOTE! During this adjustment there is an increased risk of getting stuck in the hole due to the increased
feed pressure.
NOTE! In soft rock conditions it can be difficult to force the damper pressure high enough. In this case the
damper pressure regulator can be adjusted temporarily to 120 bar.
Setting in workshop
Logic-I, Setting in workshop:
1. Disconnect and plug the impact pressure hose on the rock-drill.
2. Start the diesel engine, increase the rpm to 1500 and turn switch S130 to Drilling position.
3. Adjust the damper pressure to 45 bar, read on the damper pressure gauge in the cabin.
4. Activate drill-feed forward. This is required to enable activation of impact on COPROD rigs (logic-O).
When the rock-drill almost reaches its lower end position, impact will be stopped by the impact stop
check. This can be avoided by adding 0.5 m to the parameter for “impact stop”. Write down the
original setting!
5. Activate low impact pressure. Check the pressure on the impact pressure gauge in the cabin.
6. Slowly adjust logic-I in and out to find the activation point where the impact pressure disappears from
the gauge. CW increases the activation point and CCW lowers it. Finally, adjust slowly CCW until the
impact pressure appears on the gauge again.
7. Verification: Increase and decrease the damper pressure a few times in order to verify that impact is
stopped when the damper pressure is below 45 bar.
8. De-activate impact and feed and turn off the diesel engine.
9. Tighten the lock nut on logic-I without changing the setting, re-enter the parameter setting for “impact
stop” and reconnect the impact pressure hose on the rock-drill.
10. Adjust the damper pressure according to “Adjusting the damper pressure”. Verify through test drilling
that impact can not be activated unless the drill bit is pressed against the rock, and that impact can be
activated when the bit is pressed against the rock with collaring feed pressure.
65
Damper & DPC-I system L740CR
8. Verification: In-crease and de-crease the collaring feed pressure in order to verify that impact is
stopped at the set value.
9. De-activate impact and feed and turn off the diesel engine.
10. Tighten the lock nut on logic-O without changing the setting, re-enter the parameter setting for “impact
stop” and reconnect the impact pressure hose on the rock-drill.
11. Adjust the damper pressure according to “Adjusting the damper pressure”. Verify through test drilling
that impact is stopped immediately when drill feed is stopped or reversed.
66
Damper & DPC-I system L740CR
9. Tighten the lock nut on logic-J without changing the setting, re-enter the parameter setting for “impact
stop” and reconnect the impact pressure hose on the rock-drill.
10. Adjust the damper pressure according to “Adjusting the damper pressure”. Verify through test drilling
that impact is stopped when the damper pressure exceeds 120 bar if the feed pressure is increased to
maximum.
Related logic-valves
• Logic-D. It is activated by the pilot signal for drill rotation clockwise. This means that the
DPC-I system is only in effect when drill rotation is active. When logic-D is closed to
damper pressure it is open to the Pump 1 system pressure. This means that when rotation
is not active, the impact pressure will be according to the position of the impact control
switch S446A/B, irrespective of the damper pressure.
• Logic-C. It is activated through Y101B (impact low pressure activated).
Note: Impact pressure has the same pressure as the pump pressure, since impact pressure
comes from pump 1. In the diagram they are being distinguished by two different colours to
identify their own circuits.
When activating button S446B for high impact, solenoid valve Y101A is then activated. The
oil from Y101A activates logic-B, allowing the pump pressure to come through. The adequate
damper pressure activates logic-I, leading the impact pressure to logic-Q and logic-E. The
activated logic-Q ensures the hammer pressure gets delivered. The activated logic-E leads the
pump pressure to pressure relief valve 47f under the condition that logic-A is activated.
The meaning with DPC-I is that the pump 1 pressure is controlled by the damper pressure.
The adequate damper pressure activates logic-A when clockwise rotation is active. But when
the damper pressure falls below the preset valve of logic-A (adjustable), the pump pressure is
then led from pressure relief valve 47f to 47e. (see figure above)
67
Dust collector, DCT
The DCT system includes functions for starting the fan, controlling suction ON/OFF and
cleaning the filters. The hydraulic power is supplied from pump 3.
When the fan motor is stopped by turning switch S130 away from drilling position, the pilot
operated relief valve 13b acts as a brake. It creates counter pressure in the return line when it
is no longer pilot opened by the pump pressure and is set to stop the fan wheel in 8 seconds.
The stop time can be changed by adjusting the screw on pressure relief valve 13b.
The fan motor drain connection is fitted with restrictor 15 to keep a sufficient amount of oil
inside the housing for cooling purposes.
68
Dust collector, DCT
When the DCT switch S181 is OFF or when impact is shut off by S446, the control system
activates valves Y251A-D simultaneously to clean the DCT filters. The cleaning time can be
adjusted in the “Extended time” data entry field in the display.
69
Protective functions L740
Protective functions
RPC-F system – L740
RPC-F, Rotation Pressure Controlled Feed.
When drilling, the drill string must have a certain rotation torque in order to keep all the rod
couplings tightened. Loosened joints increases the loss of impact energy transmitted to the
drill bit and leads to damage of the threads with drill steel breakage as a possible result.
However, too high rotation torque also has disadvantages:
The working relation between RPC-F and anti-jamming is that, RPC-F tries to prevent the
activation of anti-jamming. But once RPC-F can not bear it anymore, i.e. the drill-bit gets
stuck, anti-jamming takes over the control over feed and rotation pressure while maintaining
the required rotation torque.
70
Protective functions
Anti-Jamming system
Devices
The drill rig is equipped with two types of anti-jamming device.
• Flushing air flow switch – L740, L740CR
• Rotation pressure switch – All types
Both changes the direction of feed from forward to backward, if activated by insufficient
flushing air or too high rotation pressure, in order to avoid getting stuck.
71
Protective functions
L740 L740CR
a S100
S100
a
b
72
Protective functions
Adjusting B134
Setting of the activation pressure of the anti-jamming is done on the pressure switch B134
itself. The activation pressure can be difficult to adjust during drilling because it is usually
difficult to force the rotation pressure high enough. In stead, a simulation can be done.
Warning! During the setting, the rock-drill will reverse automatically.
1. Turn the knob for adjustment of the drill rotation speed anti-clockwise until the spring
pressure is released. The rotation speed will now be 0 rpm.
2. For CR and DTH: Feed the rock drill down until the coupling sleeve of the drill steel is in
the upper break out table. Close the upper break out table to lock the sleeve.
For TH: Feed the rock drill down until the drill bit is in the upper drill steel support. Close
the upper drill steel support to lock the drill bit.
3. Activate drill rotation.
4. Activate drill feed.
5. Slowly turn the rotation speed control
clockwise while observing the drill rotation
pressure gauge. When the pressure exceeds the
preset value of the pressure switch B134, the
feed direction will change. This can be seen as
the feed pressure turns to 0 and the rock drill
tries to pull out of the drill steel support.
6. Turn the rotation speed control anti-clockwise
to lower the rotation pressure and allow the feed
to change back to downwards.
7. If the setting needs to be changed this can be
done by turning the adjustment screw on B134
clockwise to increase the activation pressure or
anti-clockwise to decrease it.
8. Repeat point 1 – 6 to verify the new setting.
9. Re-adjust the rotation speed to normal.
73
Length measurement
Length measurement
Hole depth measurement
Data from pulse sensor B172 is handled for measuring
hole length, with stop signal for drilling when set length
is reached. A choice can be made between hole depth
and hole length which stops the drilling.
The last row displays the total number of drilled metres. This parameter can be reset.
The hole length measurement system works in close relation with sensor B104. Every time
the cradle passes through sensor B104 from above, the cradle position is being calibrated, so
the cradle always finds itself at the correct position on the beam. Refer to section “Rapid
feed”, paragraph “Calibrating B172” for more information.
74
Length measurement
During rod handling, the HEC system pause the drill length/depth measuring. This means that
negative distance created when backing up to add a new rod is not taken into consideration by
the system.
The start of the pause is defined by a signal coming from a pressure switch B128 along with
other conditions (see below). B128 is activated when unthreading the rock drill from the rod.
To exit standby and re-enter measuring mode after adding a drill steel, the following
conditions must be fulfilled.
75
Rod Handling System, RHS 102 L740
Rod Handling System, RHS 102
Conditions common for all RHS functions:
The hydraulic power is supplied from Pump 1 and is limited to 200 bar by pressure reducing
valve 91. Some functions have individual pressure reducers to further limit the pressure.
Rod transfer
Since moving to/from the carousel/drill centre applies to different set of conditions, the
movement sequences will be described at different stages.
CLAIM: The carousel loaded, the grippers are in the carousel holding on to the rod which is
going to moved, the initial holding state should be hard grip.
76
Rod Handling System, RHS 102 L740
Control lever S111 is mechanically latched during this movement, that is to say one push on
the lever and the lever stays there, instead of a spring return to centre position. With the lever
in position it will carry out the whole movement until the rod is moved into the drill centre.
The function has been introduced to prevent grippers to automatically switch to loose grip
moved into the drill centre.
Loose grip can be achieved by pulling the lever back to the neutral position, when the arm
reached its end position (drill centre).
NOTE! Always put the rod grippers in loose grip before the threads meet in order to let the
rod in the rod gripper rotate. The threads will otherwise be easily damaged.
Additional conditions:
- Sensor B118 activated, PLC input X10-5/ON. (Arm in carousel.)
- The rod grippers should be in hard grip during this movement as the PLC output X12-
8 and X12-3 are OFF. This is also the normal condition of the grippers.
- RHS control lever S111 to position (b), input D551-CH3/ON.
When all the conditions are met, these two functions will take place in its order:
• Solenoid valve Y301B will be activated by PLC output X12-5. The cylinder speed is
limited by restrictors 82. (Rod transfer towards dill centre starts.)
When the rod transfer arm have reached position drill centre, sensor B120 will be
activated, PLC input X10-3/ON. This results in:
• PLC output X12-5/ON, Y301B activated. (Rod transfer towards drill centre
stops mechanically.)
SEQUENCE COMPLETE
77
Rod Handling System, RHS 102 L740
To carousel without a rod
CLAIM: The carousel could still have rods in it or not, arm has to move back to carousel in
order to get the next rod to drill; also to allow drilling.
Additional conditions:
- Sensor B120 activated, PLC input X10-3/ON. (Arm in drill centre.)
- RHS control lever S111 top button pushed, input D551-CH6/ON. The rod grippers
should be in open grip during this movement.
- RHS control lever S111 to position (a), input D551-CH2/ON.
When all the conditions are met, this function will take place:
• Solenoid valve Y300 will be activated by PLC output X12-3. (Rod grippers are open.)
• Solenoid valve Y301A will be activated by PLC output X12-4. The cylinder speed is
limited by restrictors 82. (Arm transfer towards carousel starts.)
When the rod transfer arm have reached position carousel, sensor B118 will be activated,
PLC input X10-5/ON. This results in:
• PLC output X12-4/ON, Y301A activated. (Arm transfer towards carousel stops
mechanically.)
SEQUENCE COMPLETE
CLAIM: The carousel empty or not, rods are supposed to be put back to the carousel.
Additional conditions:
- Sensor B120 activated, PLC input X10-3/ON. (Arm in drill centre.)
- The rod grippers should be in hard grip during this movement as the PLC output X12-
8 and X12-3 are OFF. This is also the normal condition of the grippers.
- RHS control lever S111 to position (a), input D551-CH2/ON.
When all the conditions are met, these two functions will take place in its order:
• Solenoid valve Y301A will be activated by PLC output X12-4. The cylinder speed is
limited by restrictors 82. (Rod transfer towards carousel starts.)
When the rod transfer arm have reached position carousel, sensor B118 will be activated,
PLC input X10-5/ON. This results in:
• PLC output X12-4/ON, Y301A activated. (Rod transfer towards carousel stops
mechanically.)
SEQUENCE COMPLETE
78
Rod Handling System, RHS 102 L740
To drill centre without a rod
CLAIM: The carousel could be empty or not, the grippers are in hard grip state in carousel.
This is the case when drilling has been done, rods are being pulled out and need to
be picked up from the drill centre.
Loose grip is needed first when the grippers have been moved into the drill centre, because
only loose grip can allow the upper rod to rotate out of the lower rod/drill bit which is being
held in the drill steel support. Loose grip can be achieved by pulling the lever to the neutral
position. Manual switching is needed here since the lever is latched in this position.
Once the upper rod has been unthreaded, hard grip needs to be activated in order to allow the
rock drill to be unthreaded. Hard grip can be achieved by pulling the lever backwards to the
“arm to drill centre” position, thus breaking the conditions for loose grip.
Loose grip stage S111 to arm to drill centre Hard grip stage
Additional conditions:
- Sensor B118 activated, PLC input X10-5/ON. (Arm in carousel.)
- RHS control lever S111 top button pushed, input D551-CH6/ON. The rod grippers
should be in open grip during this movement.
- RHS control lever S111 to position (b), input D551-CH3/ON.
When all the conditions are met, this function will take place:
• Solenoid valve Y300 will be activated by PLC output X12-3. (Rod grippers are open.)
• Solenoid valve Y301B will be activated by PLC output X12-5. The cylinder speed is
limited by restrictors 82. (Arm transfer towards dill centre starts.)
When the rod transfer arm have reached position drill centre, sensor B120 will be
activated, PLC input X10-3/ON. This results in:
• PLC output X12-5/ON, Y301B activated. (Arm transfer towards drill centre
stops mechanically.)
SEQUENCE COMPLETE
79
Rod Handling System, RHS 102 L740
Carousel rotation
Additional conditions:
• The rod gipper arms must be in carousel position, sensor switch B118 ON, PLC input
X10-5/ON.
• RHS control lever S111, top button pushed, input X550-CH6/ON.
• RHS control lever S111, to position (c) or (d), input X550-CH4 or CH5/ON.
The carousel stop positions are determined by the two sensors B182 (CCW) and B183 (CW).
The carousel rotation motor solenoid valve Y303A/B is activated by PLC output X15-2
(CWW) and X15-1 (CW).
When rotation is activated it will continue until the corresponding sensor is activated, giving
input to PLC X14-8 and X13-1 respectively. The rotation speed is limited by restrictors 84.
To facilitate the rotation of the carousel, the rod grippers must be the rod grippers must be at
the carousel position to allow rotation, i.e. B118 activated.
Rod grippers
There are three rod gripper positions, which are controlled by
solenoid valves Y300 and Y306.
o Hard grip
Additional conditions:
None. Hard grip is the normal state of the grippers. None of the
solenoid valves are activated with the result that system pressure,
200 bar, is acting to keep the gripper closed.
o Open grippers
Additional conditions:
• RHS control lever S111, top button pushed, input X550-
CH6/ON.
Solenoid valve Y300 is activated by PLC output X12-3.
o Guide grip (loose grip)
Additional conditions:
• RHS control lever S111 must be in middle position, no signal
from the RHS switch to the PLC.
• Sensor B120 activated, PLC input X10-3/ON.
Guide grip can only be achieved when the rod grippers are in the
drill-centre position and when there is no signal from RHS switch
to the PLC.
Solenoid valve Y306 in the guide grip valve block 80, is activated
by PLC output X12-8. In this case, the gripper pressure is set by
the pressure relief valve 80a set to 10 bar (adjustable, see figure right and below). The 0.6 mm
restrictor 80b limits the amount of oil passing over the relief valve.
The pressure to the cylinders would be just enough to support the weight of the drill rod
without obstructing the rod from rotating in the grippers.
80
Rod Handling System, RHS 102 L740
Sleeve retainer (Option)
Additional conditions:
• Sleeve retainer switch S182 ON, input D551-CH13/ON.
Solenoid valve Y309 is activated by PLC output X15-3. The cylinder speed is limited by
restrictors 83. The sleeve retainer can only be folded out when the rod grippers are in drill
centre position and in hard grip mode. The rod transfer movements which include “arm to
carousel” function are electrically blocked as long as the sleeve retainer is activated.
81
Rod Handling System, RHS 140 L830, L740CR
Rod Handling System, RHS 140
Conditions common for all RHS functions:
The hydraulic power is supplied from Pump 1 and is limited to 200 bar by pressure reducing
valve 97. Some functions have individual pressure reducers to further limit the pressure.
Tube transfer
The pressure to the tube transfer cylinders is limited to 100 bars by the pressure reducing
valve 83.
The carousel gates (lower and upper) need to be opened at the same time to let in and let out
drill rods, and this action has to take place before drill rod has been delivered into the carousel
and taken out to the drill centre. The function is activated in connection with the tube transfer
activation.
Since moving to/from the carousel/drill centre applies to different set of conditions, the
movement sequences will be described at different stages.
82
Rod Handling System, RHS 140 L830, L740CR
To drill centre with a tube
CLAIM: The carousel loaded, the grippers are in the carousel holding on to the tube which is
going to moved, the initial holding state should be hard grip.
Control lever S111 is mechanically latched during this movement, that is to say one push on
the lever and the lever stays there, instead of a spring return to centre position. With the lever
in position it will carry out the whole sequence until the tube is moved into the drill centre.
The function has been introduced to prevent grippers to automatically switch to loose grip
when moved into the drill centre.
Loose grip can be achieved by pulling the lever back to the neutral position, when the arm
reached its end position (drill centre).
NOTE! Always put the rod grippers in loose grip before the threads meet in order to let the
tube in the rod gripper rotate. The threads will otherwise be easily damaged.
83
Rod Handling System, RHS 140 L830, L740CR
Additional conditions:
- Sensor B118 activated, PLC input X10-5/ON. (Arm in carousel.)
- The rod grippers should be in hard grip during this movement as the PLC output X12-
8 and X12-3 are OFF. This is also the normal condition of the grippers.
- RHS control lever S111 to position (b), input D551-CH3/ON.
When all the conditions are met, these two functions will take place in its order:
• Solenoid valve Y310 will be activated by PLC output X15-4. The cylinder speed is
limited by restrictors 86. (Carousel door opens.)
• Solenoid valve Y301B will be activated by PLC output X12-5. The cylinder speed is
limited by restrictors 82. (Tube transfer towards dill centre starts.)
When the tube transfer arm has reached the position between the carousel and drill centre,
sensor B119 will be activated, PLC input X10-2/ON. This results in:
• PLC output X12-5/OFF, Y301B deactivated. (Tube transfer towards drill
centre stops.)
• PLC output X16-12/ON, Y311B activated. (This will rotate the rod grippers
from facing the carousel to facing the drill centre.)
The gripper rotation sequence will continue for 3 seconds, after that:
• PLC output 16-12/ON, Y311B activated. (Even though Y311B is activated,
but the gripper rotation has stopped mechanically.)
• PLC output X15-4/OFF, Y310 deactivated. (Carousel door closes.)
• PLC output X12-5/ON, Y301B activated again. (Tube transfer towards
drill centre continues.)
When the tube transfer arm have reached position drill centre, sensor B120 will
be activated, PLC input X10-3/ON. This results in:
• PLC output X12-5/ON, Y301B activated. (Tube transfer towards drill
centre stops mechanically.)
• PLC output X16-12/ON, Y311B activated. (Gripper rotation has stopped
mechanically.)
• PLC output X12-8/OFF and X12-3/OFF, Y306 and Y300 deactivated.
(Hard grip)
SEQUENCE COMPLETE
84
Rod Handling System, RHS 140 L830, L740CR
To carousel without a tube
CLAIM: The carousel could still have tubes in it or not, arm has to move back to carousel in
order to get the next tube to drill; and/or moving back to carousel to allow drilling.
Additional conditions:
- Sensor B120 activated, PLC input X10-3/ON. (Arm in drill centre.)
- RHS control lever S111 top button pushed, input D551-CH6/ON. The rod grippers
should be in open grip during this movement.
- RHS control lever S111 to position (a), input D551-CH2/ON.
When all the conditions are met, this function will take place:
• Solenoid valve Y310 will be deactivated by PLC output X15-4. (Carousel door is
closed.)
• Solenoid valve Y300 will be activated by PLC output X12-3. (Rod grippers are open.)
• Solenoid valve Y301A will be activated by PLC output X12-4. The cylinder speed is
limited by restrictors 82. (Arm transfer towards carousel starts.)
When the tube transfer arm has reached the position between the carousel and drill centre,
sensor B119 will be activated, PLC input X10-2/ON. This results in:
• PLC output X12-4/OFF, Y301A deactivated. (Arm transfer towards carousel
stops.)
• PLC output X18-1/ON, Y311A activated. (This will rotate the rod grippers
from facing the drill centre to facing the carousel.)
The gripper rotation sequence will continue for 3 seconds, after that:
• PLC output 18-1/ON, Y311A activated. (Even though Y311A is activated,
but the gripper rotation has stopped mechanically.)
• PLC output X12-4/ON, Y301A activated again. (Arm transfer towards
carousel continues.)
When the tube transfer arm have reached position carousel, sensor B118 will be
activated, PLC input X10-5/ON. This results in:
• PLC output X12-4/ON, Y301A activated. (Arm transfer towards
carousel stops mechanically.)
• PLC output X18-1/ON, Y311A activated. (Gripper rotation has stopped
mechanically.)
SEQUENCE COMPLETE
85
Rod Handling System, RHS 140 L830, L740CR
To carousel with a tube
CLAIM: The carousel empty or not, tubes are supposed to be put back to the carousel.
Additional conditions:
- Sensor B120 activated, PLC input X10-3/ON. (Arm in drill centre.)
- Sensor B178 deactivated, PLC input X16-1/OFF. (No tube in carousel outlet.)
- The rod grippers should be in hard grip during this movement as the PLC output X12-
8 and X12-3 are OFF. This is also the normal condition of the grippers.
- RHS control lever S111 to position (a), input D551-CH2/ON.
When all the conditions are met, these two functions will take place in its order:
• Solenoid valve Y310 will be activated by PLC output X15-4. The cylinder speed is
limited by restrictors 86. (Carousel door opens.)
• Solenoid valve Y301A will be activated by PLC output X12-4. The cylinder speed is
limited by restrictors 82. (Tube transfer towards carousel starts.)
When the tube transfer arm has reached the position between the carousel and drill centre,
sensor B119 will be activated, PLC input X10-2/ON. This results in:
• PLC output X12-4/OFF, Y301A deactivated. (Tube transfer stops.)
• PLC output X18-1/ON, Y311A activated. (This will rotate the rod grippers
from facing the drill centre to facing the carousel.)
The gripper rotation sequence will continue for 3 seconds, after that:
• PLC output 18-1/ON, Y311A activated. (Even though Y311A is activated,
but the gripper rotation has stopped mechanically.)
• PLC output X12-4/ON, Y301A activated again. (Tube transfer towards
carousel continues.)
When the tube transfer arm have reached position carousel, sensor B118 will be
activated, PLC input X10-5/ON. This results in:
• PLC output X12-4/ON, Y301A activated. (Tube transfer towards
carousel stops mechanically.)
• PLC output X18-1/ON, Y311A activated. (Gripper rotation has stopped
mechanically.)
• PLC output X15-4/OFF, Y310 activated. (Carousel door closes.)
SEQUENCE COMPLETE
86
Rod Handling System, RHS 140 L830, L740CR
To drill centre without a tube
CLAIM: The carousel could be empty or not, the grippers are in hard grip state in carousel.
This is the case when drilling has been done, tubes are being pulled out and need to
be picked up from the drill centre.
Loose grip is needed first when the grippers have been moved into the drill centre, because
only loose grip can allow the breakout table to take place and then allow the upper tube to
rotate out of the lower tube/drill bit which is being held in the lower breakout table. Loose
grip can be achieved by pulling the lever to the neutral position. Manual switching is needed
here since the lever is latched in this position.
Once the upper rod has been unthreaded, hard grip needs to be activated in order to allow the
rotation unit to be unthreaded. Hard grip can be achieved by pulling the lever backwards to
the “arm to drill centre” position, thus breaking the conditions for loose grip.
Loose grip stage S111 to arm to drill centre Hard grip stage
87
Rod Handling System, RHS 140 L830, L740CR
Additional conditions:
- Sensor B118 activated, PLC input X10-5/ON. (Arm in carousel.)
- RHS control lever S111 top button pushed, input D551-CH6/ON. The rod grippers
should be in open grip during this movement.
- RHS control lever S111 to position (b), input D551-CH3/ON.
When all the conditions are met, this function will take place:
• Solenoid valve Y310 will be deactivated by PLC output X15-4. (Carousel door is
closed.)
• Solenoid valve Y300 will be activated by PLC output X12-3. (Rod grippers are open.)
• Solenoid valve Y301B will be activated by PLC output X12-5. The cylinder speed is
limited by restrictors 82. (Arm transfer towards dill centre starts.)
When the tube transfer arm has reached the position between the carousel and drill centre,
sensor B119 will be activated, PLC input X10-2/ON. This results in:
• PLC output X12-5/OFF, Y301B deactivated. (Arm transfer towards dill centre
stops.)
• PLC output X16-12/ON, Y311B activated. (This will rotate the rod grippers
from facing the carousel to facing the drill centre.)
The gripper rotation sequence will continue for 3 seconds, after that:
• PLC output X16-12/ON, Y311B activated. (Even though Y311B is
activated, but the gripper rotation has stopped mechanically.)
• PLC output X12-5/ON, Y301B activated again. (Arm transfer towards drill
centre continues.)
When the tube transfer arm have reached position drill centre, sensor B120 will
be activated, PLC input X10-3/ON. This results in:
• PLC output X12-5/ON, Y301B activated. (Arm transfer towards drill
centre stops mechanically.)
• PLC output X16-12/ON, Y311B activated. (Gripper rotation has stopped
mechanically.)
SEQUENCE COMPLETE
Carousel rotation
Additional conditions:
• The rod gipper arms must be in drill centre position or in the middle position, sensor
switch B120 or B119 ON, PLC input X10-3 or X10-2/ON.
• RHS control lever S111, to position (c) or (d), input X550-CH4 or CH5/ON.
The carousel stop positions are determined by the two sensors B182 (CCW) and B183 (CW).
The carousel rotation motor solenoid valve Y303A/B is activated by PLC output X15-2
(CWW) AND X15-1 (CW).
When rotation is activated it will continue until the corresponding sensor is activated, giving
input to PLC X14-8 and X13-1 respectively. The rotation speed is limited by restrictors 85.
To facilitate the rotation of the carousel, the rod grippers must be at the drill centre or at the
middle position, i.e. B120 or B119 activated.
88
Rod Handling System, RHS 140 L830, L740CR
Rod grippers
There are three rod gripper positions, which are controlled by solenoid valves Y300 and
Y306.
o Hard grip
Additional conditions:
None. Hard grip is the normal state of the grippers. None of the
solenoid valves are activated with the result that system pressure,
200 bar, is acting to keep the gripper closed.
o Open grippers
Additional conditions:
• RHS control lever S111, top button pushed, input X550-
CH6/ON.
Solenoid valve Y300 is activated by PLC output X12-3.
o Guide grip (loose grip)
Additional conditions:
• RHS control lever S111 must be in middle position, no signal
from the RHS switch to the PLC.
• Sensor B120 activated, PLC input X10-3/ON.
Guide grip can only be achieved when the rod grippers are in the
drill-centre position and when there is no signal from RHS switch
to the PLC.
Solenoid valve Y306 in the guide grip valve block 80, is activated
by PLC output X12-8. In this case, the gripper pressure is set by
the pressure relief valve 80a set to 10 bar (adjustable, see figure
right and below). The 0.6 mm restrictor 80b limits the amount of
oil passing over the relief valve.
The pressure to the cylinders would be just enough to support the
weight of the drill rod without obstructing the rod from rotating in the grippers.
89
Rod Handling System, RHS 140 L830, L740CR
Drill steel supports & suction hood
Conditions for these functions:
• The Drilling/Tramming switch S130 must be in drilling position
o Drill steel supports, upper and lower – L830
The drill steel supports are controlled by switches S119 (upper) and S187 (lower), which
operates solenoid valves Y361A-B and Y350A-B respectively. The cylinder speed is
limited by restrictors 91 and 92.
o Drill steel support, upper and lower – L740CR
Both the upper and lower drill steel supports are controlled by one switch S187, which
operates solenoid valves Y361A-B. The cylinder speed is limited by restrictor 91.
o Suction hood
The suction hood is controlled by switch S167, which operates solenoid valve Y357. The
hydraulic pressure downwards is limited by pressure reducing valve 94 set to 40 bar, and
the cylinder speed is limited by restrictor 93.
90
Extractor unit (Option) L740
Extractor unit (Option)
The extractor function of the rock-drill consists of a hydraulic piston in the front part of the
rock-drill and a logic valve for the activation of it, the unit is also known as the back hammer.
The hydraulic power is supplied from Pump 1.
The extractor unit is used when the rock conditions vary a lot and there is a large risk of
jamming. The function of the extractor unit is to provide reverse percussion to the shank
adapter and thus the drill string and drill bit. The shank adapter for rock-drills equipped with
an extractor unit has a special flange that receives the reverse percussion force. Since the
shank adapter is pressed into the rock-drill by the feed force during normal drilling, it works
without the flange meeting the extractor piston.
The extractor piston lifts the shank-adapter to enable the impact piston to reach it when
feeding backwards in a jam situation (see picture below).
extractor
piston
impact piston
shank
adapter
In case of a sudden loss of damper pressure, e.g. drilling into weak formations or cavity,
logic-L opens. This allows the extractor piston to move forward to avoid being hit by the
flange on the shank adapter. At the same time, the oil trapped in front of the extractor piston
serves as a cushion to prevent from mechanical contact between piston and front. When the
damper pressure drops, the impact pressure will be reduced or cut off by the DPC-I system.
When feeding backwards, the feed force works in the other direction as the shank adapter
extends out of the rock-drill since it is stuck, logic-L opens due to the loss of damper pressure
and the extractor system is pressurized since the extractor piston is pulled by the shank
adapter to close the outlet ducts in the extractor housing. When pressurized, the extractor
piston lifts the shank adapter high enough to be struck by the impact piston. Once the impact
piston hits the shank adapter, backward shock wave would be generated from the extractor
piston thus causing the reverse percussion.
91
Extractor unit (Option) L740
When feeding backwards, the damper pressure
is below the minimum limit to allow impact,
set by the DPC-I system. To make it possible
to activate impact when using the extractor it
is necessary to override the DPC-I system.
This is done by push-button S451, which
activates solenoid valve Y176, which by-
passes logic valves I and J. Consequently,
impact can be activated at any damper
pressure.
92
TED-Extractor unit for COPROD (Option) L740CR
TED-Extractor unit for COPROD (Option)
The Rock drill can be equipped with a separate, air-powered extractor unit. The function of
the extractor unit is to generate and transmit reverse percussion into the housing and thereby
to the drill string and bit.
The extractor unit, which is fitted in front of the rock drill, is powered by the flushing air.
93
Water mist system (Option)
b
The water-mist system is primarily used for hole stabilization and dust
c
control by adding water into the flush air. Generally a small amount of
water is used in order to make the drill dust moist and bind into larger
particles, for dust control, or to bind to the hole wall, for hole
stabilization. In this case switch S448 should be in position AUTO (b).
The amount of injected water should be adjusted by the needle valve to
match the dust characteristics. Different settings may be necessary on
different sites and different applications.
94
Water mist system (Option)
95
ECG, thread lubrication with oil (Option) L740
ECG, thread lubrication with oil (Option)
Function
The ECG pump Y107 starts pumping as soon as Flushing air is turned ON. The ECG pump is
an electrical piston pump, controlled by the PLC output X11-16 which sends out pulses to the
pump. ECG injects a small amount of lubricating oil into the flushing air. The oil creeps along
the walls of the flushing hole and out into the threaded joints. Atlas Copco recommends the
use of COP OIL for all ECG and ECL lubrication.
Adjusting
• Time pulse – length of the pulse, i.e. the
signal time.
• Pulses/minute – how many pulses there is
per minute
96
Thread lubrication with grease brushes (Option) L740
Thread lubrication with grease brushes (Option)
Function
Lubrication of the drill steel threads is done by two brushes (A) mounted on the lower RHS
carousel bracket.
The grease is supplied by a pump placed in the front of the wagon frame. The pump is
powered by compressed air from the rig compressor and controlled through solenoid valve
Y552.
Activation of Y552 can be done either automatically or manually and is controlled by the
switch S449 on the drilling control panel.
When S449 is put in manual mode, no input from S111 is needed to cause the activation of
Y552.
97
Thread lubrication with grease brushes (Option) L740
Operating
• In normal operation, the system works in automatic mode. The grease pump is activated
when the rod handling lever S111 is in position to transfer a rod to drill centre. The result
is that each time a rod is removed from the carousel, a quantity of lubricant is pumped into
the brushes that the threads of the drill rod pass through.
• If there is a need to additional grease, the system can be run manually. In this case the
grease pump is activated as long as switch S449 is kept in position (a).
• If there is no need for thread greasing the system can be turned off by putting switch S449
in position (c).
b c
a d
The maximum pressure to the pump is adjusted to 7 bars by the pressure regulator 21 which is
displayed by the pressure gauge 22. The system can be switched off by blocking the air
supply with ball cock valve 8 or by the electrical switch in the cabin.
We recommend the use of “Atlas Copco Secoroc thread lubricant A” for the lubrication of
drill steel threads.
98
Spray greasing system (Option) L830, L740CR
Spray greasing system (Option)
Function
Lubrication of the drill steel threads is done
by an air spray and a grease injector
mounted on the lower RHS carousel
bracket.
The grease is injected by a pump placed in
the front of the wagon frame. The grease
pump is powered by compressed air from
the rig compressor and controlled through
solenoid valve Y552A. Compressed air is
also used for the spraying, and it’s
controlled by solenoid valve Y552B. When
functioning, solenoid valve Y552B for air
spray is set to start first before solenoid
valve Y552A for grease pump. The air then
sprays grease onto the thread. When
shutting off the function, Y552A is set to be
turned off first before Y552B.
Activation of Y552 is done manually and is
controlled by the switch S449 on the
drilling control panel.
The maximum pressure to the pump is adjusted to 7 bars by the pressure regulator 21 which is
displayed by the pressure gauge 22. The system can be switched off by blocking the air
supply with ball cock valve 8 or by the electrical switch in the cabin.
We recommend the use of “Atlas Copco Secoroc thread lubricant A” for the lubrication of
drill steel threads.
99
Laser sensor (Option)
The laser sensor is most often used in undulating terrain to maintain as level a hole bottom as
possible for blasting.
Laser level
4m
Hole bottom
Ex:
A rotary laser is placed at the highest point in the area. From here, the depth to hole bottom is
measured (in this case 10 m). When the rotary laser hits the sensor B316 on the rock drill
cradle, the length between the sensor and drill bit (in this case 4 m) is automatically shown on
the display, irrespective of how many metres that has been drilled. This is done every time the
hole depth is reset. In this case, we know that there are 6 metres left to hole bottom (10-4=6
m).
If it takes one meter for B316 to be hit by the rotary sensor in the above example, the
following describes the transaction which will take place on the display.
Before hitting the sensor (i.e. before reaching Hitting The preset value for sensor to drill bit distance
one meter), the display shows the drilling moment, over-writes the measured distance. The lamp for
information like usual. 1 meter laser sensor turns green. And depth measuring
reached. carries on from 4 m.
100
Adjustment/calibration
Adjustment/calibration
Calibrating of positioning instruments
101
Adjustment/calibration
Threading pressure
102
40
68
L7
Bosal
64
63
65
13
14
13a
13b
15
40
L7
45
Bosal
30
31
66f
Bosal
5b
66e
66d
66a
66b
66c
10
4c
4b
4t 4k 4l
4w
4a
4i 4p
4u 4e 4r
4x 4m 4n
4q 4s
4d
4f 4j
4y
34
33
40
L7
Bosal
89
80
90
82
80b
83 84 85 86
80a 87
91
88
40
L7 CR 68
Bosal
64
63
65
13
14
13a
13b
15
40
L7 CR
45
Bosal
31
66e
66d
66a
66b
66c
10
4c
4b
4t 4k 4l
4w
4a
4i 4p
4u 4e 4r
4x 4m 4n
4q 4s
4d 4f
4j
4y
34
33
40
L7 CR
Bosal
93
90
95
80
96
86
80b
80a
87 91 97
84 85
83 98 88
94
89
82
30
68
L8
Bosal
64
63
65
13
14
13a
13b 15
30
L8
Bosal
45
66f
Bosal
5b
66e
66d
66a
66b
66c
10
4c
4b
4t 4k 4l
4w
4a
4i 4p
4u 4e 4n 4r
4x 4m
4q 4s
4d 4f 4j
4y
34 33
30
L8
Bosal
90
95
80
96
87
86
80b
91 92
93
80a
97
84 85
83 98 88
94
89
82