Location : Jembatan Perniagaan = Betapus B-3

Ground water level = 4.00 m


DPT Batu kali Jbt. Betapus Elevasi atas DPT = 8.95 m 4.75
q (t/m ) 2
Elevasi tanah = 4.20 m
Elevasi muka air tanah = 4.20 m
1 + 8.95 Elevasi dasar pondasi = 4.00 m
b
4 Dimension (panjang pias )
H = 4.95 m B = 1.85 m L = 1.00 m
a
b1 = 0.00 m b2 = 0.30 m b3 = 1.55 m
H=h1

h1 = 4.95 m h2 = 0.20 m hw = 0.20 m

+ 4.20 q = 2.00 t/m2 Kh = 0.15


hw gm = 2.20 t/m3 gw = 1.00 t/m3 gc = 2.40 t/m3

h2
0.2 Backfill soil
0.15 g soil = 1.80 t/m3
g sat = 2.30 t/m3 a = 17.39 o
(untuk analisa stabilitas )
0.3 0.25 f = 30.0 o
a = 0.00 o
(untuk analisa struktural)
b1 b2 b3 c = 0.00 t/m2 b = 0.00 o

Tanah Pondasi
B
g s' = 1.37 t/m3 Angka keamanan (normal) (gempa)
18.963 fB = 24.0 o
Guling |e| < B/6=0.82 B/3=0.62
Potongan DPT 2.31 cB = 0.60 t/m2 Geser fs > 2.00 1.25
Koefisien geser Daya dukung tanah
m = 0.50 qmaks > qa=qu/3 qae=qu/2
Koefisien gaya angkat
Um = 1.00

KB Parahyangan C-56 (1-Masukan) 436567865.xls


Page 2 of 13

STABILITAS : DPT Batu kali Jbt. Betapus B-3

Kondisi Normal Kondisi gempa

a) Stabilitas terhadap guling a) Stabilitas terhadap guling

|e| = 1.46 m > B/6 = 0.40 m Check! |e| = 0.83 m > B/3 = 0.80 m Check!
Sf = 0.822 < 3.00 Check! Sf = 1.307 < 2.50 Check!

b) Stabilitas terhadap geser b) Stabilitas terhadap geser

Sf = 0.51 < 2.00 Check! Sf = 0.69 < 1.25 Check!

c) Daya dukung tanah pondasi c) Daya dukung tanah pondasi

q1 = 29.93 t/m2 > qa = 6.75 t/m2 Check! q1 = 0.00 t/m2 < qae = 10.12 t/m2 OK!
Sf = 0.676 < 3.00 Check! Sf = #DIV/0! ### 2.00 #DIV/0!
q2 = -5.55 t/m2 < qa = 6.75 t/m2 OK! q2 = 0.00 t/m2 < qae = 10.12 t/m2 OK!
Sf = -3.651 < 3.00 Check! Sf = #DIV/0! ### 2.00 #DIV/0!
Use Concrete pile = 0.75 m (spacing)

KB Parahyangan C-56 (2-Cek) 436567865.xls


Page 3 of 13

1. Data Perencanaan q (t/m2) B-3


1.1 Dimensi
b
B = 1.85 m H = 4.95 m
L = 1.00 m (panjang pias )

b1 = 0.00 m H=h1
b2 = 0.30 m
b3 = 1.55 m

h1 = 4.95 m hw

h2 = 0.20 m
h2
hw = 0.20 m
0.2
0.15
1.2 Parameter
0.3 0.25
B
q = 2.00 t/m2 (untuk kondisi normal)
= 0.00 t/m2 (untuk kondisi gempa) b1 b2 b3

gm = 2.20 t/m 3

gw = 1.00 t/m3 Potongan DPT


gc = 2.40 t/m3
Tanah urugan Tanah pondasi Angka keamanan
gs = 1.80 t/m3 gs' = 1.37 t/m3 (=gsat-gw) Guling
gsat = 2.30 t/m3 cB = 0.60 t/m2 normal |e|<B/6=0.31m
c = 0.00 t/m2 fB = 24.00 o
gempa |e|<B/3=0.62m
f = 30.00 o
m = 0.50 (koefisien geser) Geser
Um = 1.00 (koefisien gaya angkat) normal fs > 2.00
b = 0.000 o
gempa fs > 1.25
a = 17.387 o
(untuk analisa stabilitas) Daya dukung pondasi
= 0.000 o
(untuk analisa struktural) normal qmax<qa
d = 0.000 o
(untuk analisa stabilitas pada kondisi normal, d = b) qa=qu/3
= 20.00 o
(for structural analysis in normal condition, d = 2/3 f) gempa qmax<qae
= 21.55 o
(untuk analisa stabilitas pd kondisi gempa, lihat bagian 2.3) qae=qu/2
= 15.00 o
(untuk analisa struktur pada kondisi gempa, d = 1/2 f)
F = 8.531 o
( = Arc tan(Kh) ) Kh = 0.15

2. Perhitungan Stabilitas
2.1 Kasus 1 (Kondisi normal, dengan beban hidup vertikal)

q = 2.00 t/m2 0.30


0.00 1.55

Pa
1 7 5
Pa2
4.95

qa2 qa1
8 6
2
0.20 Pp1 0.20
Pa4 1
Pa3 3
0.20
1
11 0
9 0.15

qa4 O
qa3 qp
1
qu2
qu1
Pu2
Pu
1
0.30 1.85 0.25

Acting Load in Case 1

KB Parahyangan C-56 (3-Stabilitas) 436567865.xls


Page 4 of 13

(1) Beban vertikal

No. Uraian W X WxX


1 0.50 x 4.80 x 0.00 x 2.20 0.000 2.100 0.00
2 4.80 x 0.30 x 2.20 3.168 1.950 6.18
3 0.50 x 4.80 x 1.55 x 2.20 8.184 1.283 10.50
4 0.50 x 4.60 x 0.00 x 1.80 0.000 2.100 0.00
5 4.75 x 0.00 x 1.80 0.000 2.100 0.00
6 0.50 x 0.20 x 0.00 x 2.30 0.000 2.100 0.00
7 4.60 x 0.30 x 1.80 2.484 2.250 5.59
8 0.05 x 0.30 x 2.30 0.035 2.250 0.08
9 0.15 x 1.85 x 2.40 0.666 1.325 0.88
10 0.35 x 0.25 x 2.40 0.210 0.125 0.03
11 0.35 x 0.30 x 2.40 0.252 2.250 0.57
q 2.00 x 0.30 0.600 1.850 1.11
T o t a l (1 s/d q) 15.599 24.94
Pu1 0.20 x 1.85 x 0.50 x -1.00 -0.185 1.233 -0.23
Pu2 0.00 x 2.40 x 0.50 x -1.00 0.000 0.800 0.00
Total ( 1 s/d Pu2) 15.414 24.71

(2) Beban horisontal


Koefisien tekanan tanah aktif

Cos2(f -a)
Ka =
Sin(f+d) x Sin(f-b) 2
Cos2a x Cos(a+d) x 1+
Cos(a+d) x Cos(a-b)

a = 17.387 o
d = 0.000 o
b = 0.00 o

Cos2(f -a) = 0.952 Sin(f+d) = 0.500


Cos2a = 0.911 Sin(f -b) = 0.500
Cos(a+d) = 0.954 Cos(a-b) = 0.954

Ka = 0.472 untuk sisi depan DPT

a = 0.000 o
d = 20.000 o
b = 0.00 o

Cos2(f -a) = 0.750 Sin(f+d) = 0.766


Cos2a = 1.000 Sin(f-b) = 0.500
Cos(a+d) = 0.940 Cos(a-b) = 1.000

Ka' = 0.297 untuk sisi belakang DPT

Koefisien tekanan tanah pasif

Cos2(f+a)
Kp =
Sin(f-d) x Sin(f+b)
2
Cos2a x Cos(a -d) x 1-
Cos(a +d) x Cos(a-b)
a = 17.387 o
d = 0.000 o
b = 0.00 o

Cos2(f+a) = 0.458 Sin(f-d) = 0.500


Cos2a = 0.911 Sin(f+b) = 0.500
Cos(a +d) = 0.954 Cos(a-b) = 0.954

Kp = 2.327

a = 0.000 o
d = 20.000 o
b = 0.00 o

Cos2(f +a) = 0.750 Sin(f-d) = 0.174


Cos2a = 1.000 Sin(f+b) = 0.500
Cos(a+d) = 0.940 Cos(a-b) = 1.000

Kp' = 1.648

qa1 = Ka x q = 0.943 ton/m


qa2 = Ka x (h1- hw1) x gsoil = 4.032 ton/m
qa3 = qa1 + qa2 = 4.975 ton/m
qa4 = Ka x hw1 x gsat = 0.217 ton/m
qp1 = Kp x h4 x gsoil = 0.838 ton/m

KB Parahyangan C-56 (3-Stabilitas) 436567865.xls


Page 5 of 13

No. Uraian H Y HxY


Pa1 0.943 x 4.75 4.480 2.575 11.54
Pa2 4.032 x 4.75 x 0.50 9.576 1.783 17.08
Pa3 4.975 x 0.20 0.995 0.100 0.10
Pa4 0.217 x 0.20 x 0.50 0.022 0.067 0.00
Pp1 -0.838 x 0.20 x 0.50 -0.084 0.067 -0.01
Total 14.988 28.71
(3) Perhitungan Stabilitas

a) Stabilitas terhadap guling


a) -1 Tanpa gaya angkat
B = 2.40 m

SWxX-SHxY 24.94 - 28.71


X = = = -0.242 m
SW 15.599

B 2.95
e = - X = - -0.242 = 1.442 m > B/6 = 0.400 m Check !
2 2
a) -2 Dengan gaya angkat
B = 2.40 m

SWxX-SHxY 24.71 - 28.71


X = = = -0.259 m
SW 15.414

B 2.40
e = - X = - -0.259 = 1.459 m > B/6 = 0.400 m Check !
2 2

b) Stabilitas terhadap geser


b)-1 Tanpa gaya angkat
Gaya geser : SH = 14.988 ton
Gaya penahan : HR = m x S W = 0.50 x 15.599 = 7.800 ton
(koefisien geser : m = 0.50 )

HR 7.800
Fs = = = 0.520 < 2.00 Check !
SH 14.988
b)-2 Dengan gaya angkat
Gaya geser : SH = 14.988 ton
Gaya penahan : HR = m x S W = 0.50 x 15.414 = 7.707 ton
(koefisien geser : m = 0.5 )

HR 7.707
Fs = = = 0.514 < 2.00 Check !
SH 14.988
c) Reaksi tekanan tanah pondasi
SW 6xe
q1,2 = x (1 + )
B B

15.599 6x 1.442
q1 = x (1 + ) = 29.931 t/m2 > qa = 6.749 t/m2 Check !
2.40 2.40

15.599 6x 1.442
q2 = x (1 - ) = -16.931 t/m2 < qa = 6.749 t/m2 OK !
2.40 2.40
Reaksi tekanan tanah pondasi pada kasus 1

-16.931 t/m2 - t/m2


29.931 t/m 2
- t/m 2

bila, e > 0 bila, e < 0


(dipakai) (tidak dipakai)

KB Parahyangan C-56 (3-Stabilitas) 436567865.xls


Page 6 of 13

2.2 Kasus 2 ( Kondisi normal, tanpa beban hidup vertikal)

0.30
0.00 1.55

Pa
1 7 5
Pa2
4.95

qa2 qa1
8 6
2
0.20 Pp1 0.20
Pa4 1
Pa3 3
1 0.20
11 0
9 0.15

qa4 O
qa3 qp
1
qu2
qu1
Pu2
Pu
1
0.30 1.85 0.25

Gaya yang bekerja pada kasus 2


(1) Beban vertikal

No. Rincian W X WxX


1 0.50 x 4.80 x 0.00 x 2.20 0.000 2.100 0.00
2 4.80 x 0.30 x 2.20 3.168 1.950 6.18
3 0.50 x 4.80 x 1.55 x 2.20 8.184 1.283 10.50
4 0.50 x 4.60 x 0.00 x 1.80 0.000 2.100 0.00
5 4.75 x 0.00 x 1.80 0.000 2.100 0.00
6 0.50 x 0.20 x 0.00 x 2.30 0.000 2.100 0.00
7 4.60 x 0.30 x 1.80 2.484 2.250 5.59
8 0.05 x 0.30 x 2.30 0.035 2.250 0.08
9 0.15 x 1.85 x 2.40 0.666 1.325 0.88
10 0.35 x 0.25 x 2.40 0.210 0.125 0.03
11 0.35 x 0.30 x 2.40 0.252 2.250 0.57
T o t a l (1 s/d 9) 14.999 23.830
Pu1 0.20 x 1.85 x 0.50 x -1.00 -0.185 1.233 -0.23
Pu2 0.00 x 1.85 x 0.50 x -1.00 0.000 0.617 0.00
Total ( 1 s/d Pu2) 14.814 23.60

(2) Beban Horisontal

Koefisien tekanan tanah aktif

Ka = 0.472 (untuk analisa stabilitas)


Ka ' = 0.297 (untuk analisa struktural)

Koefisien tekanan tanah pasif

Kp = 2.327
qa1 = Ka x q = 0.000 ton/m
qa2 = Ka x (h1- hw1) x gsoil = 4.032 ton/m
qa3 = qa1 + qa2 = 4.032 ton/m
qa4 = Ka x hw1 x gsat = 0.217 ton/m
qp1 = Kp x h4 x gsoil = 0.838 ton/m

No. Rincian H Y HxY


Pa1 0.000 x 4.75 0.000 2.575 0.00
Pa2 4.032 x 4.75 x 0.50 9.576 1.783 17.08
Pa3 4.032 x 0.20 0.806 0.100 0.08
Pa4 0.217 x 0.20 x 0.50 0.022 0.067 0.00
Pp1 -0.838 x 0.20 x 0.50 -0.084 0.067 -0.01
Total 10.320 17.15

KB Parahyangan C-56 (3-Stabilitas) 436567865.xls


Page 7 of 13

(3) Perhitungan Stabilitas

a) Stabilitas terhadap guling


a) -1 Tanpa gaya angkat
B = 2.40 m

SWxX-SHxY 23.83 - 17.15


X = = = 0.445 m
SW 14.999
B 2.40
e = - X = - 0.445 = 0.755 m > B/6 = 0.400 m Check !
2 2
a) -2 Dengan gaya angkat
B = 2.40 m

SWxX-SHxY 23.60 - 17.15


X = = = 0.435 m
SW 14.814
B 2.40
e = - X = - 0.435 = 0.765 m > B/6 = 0.400 m Check !
2 2

b) Stabilitas terhadap geser


b)-1 Tanpa gaya angkat
Gaya geser : SH = 10.320 ton
Gaya penahan : HR = m x S W = 0.50 x 14.999 = 7.499 ton
(koefisien geser : m = 0.5 )

HR 7.499
Fs = = = 0.73 < 2.00 Check !
SH 10.320
b)-2 Dengan gaya angkat
Gaya geser : SH = 10.320 ton
Gaya penahan : HR = m x S W = 0.50 x 14.814 = 7.407 ton
(koefisien geser : m = 0.5 )

HR 7.407
Fs = = = 0.72 < 2.00 Check !
SH 10.320

c) Reaksi tekanan tanah pondasi

SW 6xe
q1,2 = x (1 + )
B B
14.999 6x 0.755
q1 = x (1 + ) = 18.045 t/m2 > qa = 6.749 t/m2 Check !
2.40 2.40
14.999 6x 0.755
q2 = x (1 - ) = -5.546 t/m2 < qa = 6.749 t/m2 OK !
2.40 2.40

-5.546 t/m2 - t/m2


18.045 t/m2 - t/m2

bila, e > 0 bila, e < 0


(dipakai) (tidak dipakai)

Reaksi tekanan tanah pondasi pada kasus 2

KB Parahyangan C-56 (3-Stabilitas) 436567865.xls


Page 8 of 13

2.3 Kasus 3 (kondisi gempa)


0.30
0.00 1.55

Pa
1 7 5
Pa2
4.95

qa2 qa1
8 6
2
0.20 Pp1
Pa4 1 0.20
Pa3 3
1 0.20
11 0
9 0.15

qa4 O
qa3 qp
1
qu2
qu1
Pu2
Pu
1
0.3 1.85 0.25

Gaya yang bekerja pada kasus 3


(1) Beban vertikal = Sama dengan kasus 2
(2) Gaya horisontal

f = 30.00 o a = 17.387 o (untuk analisa stabilitas) F = 8.531 o


b = 0.00 o
a = 0.000 o (untuk analisa struktural) (F = Arc tan(Kh) )
q = 0.00 t/m (untuk kondisi gempa)
2
Kh = 0.15
Koefisien tekanan tanah pasif

Cos2(f-F-a)
Kae =
2
Sin(f+d) x Sin(f-b-F)
CosF x Cos2a x Cos(a+d+F) x 1+
Cos(a+d+F) x Cos(a-b)
(untuk analisa stabilitas)
a = 0.000 o
d = 21.55 o

tan d = Sin f Sin ( F + D - b )


1 - Sin f Cos ( F + D - b )
sin D= Sin ( F + b )
Sin f

Sin (F+ b ) == 0.148 Sin f = 0.500


Sin D = 0.296 then D = 17.22
Sin(F+D-b) = 0.434 Cos(F+D-b)= 0.901
tan d = 0.395

Cos2(f-F-a)= 0.866 Sin(f+d) = 0.783


CosF = 0.989 Sin(f-b-F) = 0.366
Cos2a = 1.000 Cos(a-b) = 1.000
Cos(a+d+F) = 0.865

Kae = 0.408 (untuk analis stabilitas)

(untuk analisa struktural)

a = 0.000 o
d = 15.00 o

Cos2(f-F-a)= 0.866 Sin(f+d) = 0.707


CosF = 0.989 Sin(f-b-F) = 0.366
Cos2a = 1.000 Cos(a-b) = 1.000
Cos(a+d+F)= 0.917

KB Parahyangan C-56 (3-Stabilitas) 436567865.xls


Page 9 of 13

Kae = 0.407 (untuk analisa struktural)

Koefisien tekanan tanah pasif

Cos2(f-F+a)
Kpe =
2
Sin(f-d) x Sin(f+b-F)
CosF x Cos2a x Cos(a+d+F) x 1-
Cos(a+d-F) x Cos(a-b)

a = 0.000 o
d = 21.55 o

Cos (f-F+a)=
2
0.866 Sin(f-d) = 0.147
CosF = 0.989 Sin(f+b-F) = 0.366
Cos2a = 1.000 Cos(a-b) = 1.000
Cos(a+d+F)= 0.865

Kpe = 1.797

qa1 = Kae x ( h1 - hw1) x gsoil = 3.488 ton/m


qa2 = qa2 = 3.488 ton/m
qa3 = Kae x hw1 x gsat = 0.188 ton/m
qp1 = Kpe x h4 x gsoil = 0.647 ton/m

No. Description H Y HxY


1 0.150 x 0.000 0.000 1.650 0.000
2 0.150 x 3.168 0.475 2.475 1.176
3 0.150 x 8.184 1.228 1.650 2.026
9 0.150 x 0.666 0.100 0.075 0.007
10 0.150 x 0.210 0.032 0.175 0.006
11 0.150 x 0.252 0.038 0.175 0.007
Pa1 0.500 x 3.488 x 4.750 8.285 1.783 14.775
Pa2 3.488 x 0.200 0.698 0.100 0.070
Pa3 0.500 x 0.188 x 0.200 0.019 0.067 0.001
Pp1 -0.647 x 0.200 x 0.500 -0.065 0.067 -0.004
Total 10.809 18.063

(3) Perhitungan Stabilitas

a) Stabilitas terhadap guling


a) -1 Tanpa gaya angkat
B = 2.40 m
SWxX-SHxY 23.830 - 18.063
X = = = 0.385 m
SW 14.999
B 2.40
e = - X = - 0.385 = 0.815 m > B/3 = 0.800 m Check !
2 2
a) -2 Dengan gaya angkat
B = 2.40 m
SWxX-SHxY 23.602 - 18.063
X = = = 0.374 m
SW 14.814
B 2.40
e = - X = - 0.374 = 0.826 m > B/3 = 0.800 m Check !
2 2

KB Parahyangan C-56 (3-Stabilitas) 436567865.xls


Page 10 of 13

b) Stabilitas terhadap geser


b)-1 Tanpa gaya angkat
Gaya geser : SH = 10.809 ton
Gaya penahan : HR = m x S W = 0.50 x 14.999 = 7.499 ton
(koefisien geser : m = 0.50 )
HR 7.499
Fs = = = 0.69 < 1.25 Check !
SH 10.809
b)-2 Dengan gaya angkat
Gaya geser : SH = 10.809 ton
Gaya penahan : HR = m x S W = 0.50 x 14.814 = 7.407 ton
(koefisien geser : m = 0.50 )
HR 7.407
Fs = = = 0.69 < 1.25 Check !
SH 10.809
c) Reaksi tekanan tanah pondasi

c-1) bila, |e| < B/6 (tidak dipakai)


SW 6xe
q1,2 = x (1 + )
B B

q1 = x ) = - t/m2 qae = - t/m2

q2 = x ) = - t/m2 qae = - t/m2

c-2) bila, B/6 < |e| < B/3 Ubah dimensi

2xSW
q1' = = = - t/m2 qae = - t/m2
3 x (B/2-|e|)

- t/m2

- t/m2 - t/m2
in case, e > 0 and e < B/6 in case, e > 0 and B/6 < e < B/3
(tidak dipakai) (tidak dipakai)

- t/m2

- t/m2 - t/m2
in case, e < 0 and |e| < B/6 in case, e < 0 and B/6 < |e| < B/3
(tidak dipakai) (tidak dipakai)

Reaksi tekanan tanah pondasi pada kasus 3

KB Parahyangan C-56 (3-Stabilitas) 436567865.xls


Page 11 of 13

2.4 Daya dukung tanah

(1) Data Perencanaan


fB = 24.00 o cB = 0.60 t/m2 gs' = 1.37 t/m3 (=gsat-gw)

B = 2.40 m z = 0.20 m L = 1.00 m (panjang pias )


f
(2) Daya dukung ultimate , (qu) ###
###
Perhitungan daya dukung ultimate menggunakan metode perhitungan dibawah ini : ###
Rumus Terzaghi : ###
###
qu = (a x c x Nc) + (gsoil' x z x Nq) + (b x gsoil x B x Ng) ###
###
Shape factor (Table 2.5 of KP-06) ###
a = 1.18 b = 0.40
Bentuk pondasi : 3 (segi empat , B x L)
Shape of footing a b
1 lajur 1.00 0.50
2 persegi 1.30 0.40
3 segi empat , B x L 1.18 0.40
(B < L) (= 1.09 + 0.21 B/L)
(B > L) (= 1.09 + 0.21 L/B)
4 lingkaran, diameter = B 1.30 0.30

Bearing capacity factor (Figure 2.3 of KP-06, by Capper)


Nc = 17.0 Nq = 7.5 Ng = 4.7
f Nc Nq Ng
0 5.7 0.0 0.0
5 7.0 1.4 0.0
10 9.0 2.7 0.2
15 12.0 4.5 2.3
20 17.0 7.5 4.7
25 24.0 13.0 9.5
30 36.0 23.0 20.0
35 57.0 44.0 41.0
37 70.0 50.0 55.0
39 > 82.0 50.0 73.0

(a x c x Nc) = 12.011

(gsoil x z x Nq) = 2.055


(b x gsoil x B x Ng) = 6.181

qu = 20.247 t/m2

(3) Daya dukung ijin tanah, (qa)

qa = qu / 3 = 6.749 t/m2 (angka keamanan = 3 , konsiai normal)

qae = qu / 2 = 10.123 t/m2 (anka keamanan = 2 , kondisi gempa)

KB Parahyangan C-56 (3-Stabilitas) 436567865.xls


3. Tiang pancang beton

3.1 Daya dukung tiang

(1) Data perencanaan

Diameter tiang pancang D = 20.0 cm


Panjang tiang pancang L = 6.00 m
Luas penampang tiang pancang A = 1/4 x p x D2 = 0.031 m2
Keliling tiang pancang W = pxD = 0.628 m
Nilai N-SPT = 3

Ni : Rata-rata nilai N pada lapisan tanah = 3


fi : hambatan lekat tanah = 0.20 x Ni = 0.60 t/m2

(2) Daya dukung vertikal ultimate, (qu)

qu = (40 x N x A) + (W x fi x li)
= ( 40 x 3.0 x 0.031 )+( 0.628 x 0.60 x 6.0 )
= 3.770 + 2.262 = 6.032 ton/tiang

(3) Daya dukung tiang ijin, (qa)

qa = qu/n = 6.032 / 3 = 2.011 ton/tiang

(angka keamanan : n = 3)

3.2 Daya dukung horisontal

Daya dukung horisontal tergantung besarnya pergeseran dari tiang pancang

(1) Data perencanaan

Mutu beton tiang : K350


E = 305,206 kg/cm 2
(modulus Young )
d = Pergeseran arah horisontal yang diijinkan = 0.01 m
N = Nilai N-SPT diasumsikan sebesar = 3

p x D4
I = = 7,854.0 cm4 (I : Moment Inertia dari tiang pancang)
64

(2) Daya dukung horisontal ijin tiang pancang (Ha)

a = 0.20 E = 28 x N
Kh = a x E x D-3/4
= 0.20 x( 28 x 3.0 )x( 20.0 )-3/4 = 1.776 kg/cm3

4 Kh x D 4 1.776 x 20.0
b = = = 0.008 cm
4 EI 4 x 305,206 x 7,854.0

Kh x D 1.776 x 20.0
Ha = x d = x 1 = 4,553.66 kg
b 0.008
= 4.554 ton
(3) Daya dukung horisontal berdasarkan tegangan pada tiang pancang

Ha = 2 x b x Ma

s = Tegangan ijin kayu kelas III = 75.00 kg/cm2

p x D3
W = = 785.40 cm3 ; (W : modulus penampang tiang pancang)
32

Ma = s x W = 75.00 x 785.40 = 58,904.9 kg cm

Ha = 2 x b x Ma
= 2 x 0.008 x 58,904.9 = 919.15 kg/tiang = 0.919 ton/tiang

Allowable horizontal bearing capacity acting on the pile top depend upon the allowable
stress of pile itself.

3.3 Jarak antar tiang pancang

(1) Untuk beban horisontal

Ha = 0.919 ton/tiang ; (Ha : Beban horisontal yang ditahan oleh tiang pancang)

Hr = H - Hf = H - V x tan(2f/3) = 14.988 - 5.678 = 9.311 ton/m

Ha 0.919
Jarak antar tiang = = = 0.10 m
Hr 9.311

Jarak antar tiang = 0.10 m (as ke as) oleh gaya horisontal

(2) Untuk beban vertikal

V = 15.599 ton/m : Beban vertikal yang ditahan oleh tiang pancang

qa = 2.011 ton/tiang : Daya dukung vertikal tiap tiang pancang

qa 2.011
Jarak antar tiang = = = 0.13 m
V 15.599

dipakai = 0.75 m

Jarak antar tiang dapat ditentukan sebesar 0.75 m untuk tiang ( f 20, L = 6.00 m ),

Vp = 12.082 ton/m : Beban vertikal yang ditahan oleh tiang

qa = 2.011 ton/pile : Daya dukung tiang ijin

qa 2.011
Jarak antar tiang = = = 0.17 m
Vp 12.082

dipakai = 0.75 m

Jarak antar tiang dapat ditentukan 1.5 m untuk tiang ( f 20, L = 6.00 m ),