Professional Documents
Culture Documents
BRU13778 T20 Data Sheet - 04
BRU13778 T20 Data Sheet - 04
Power System
Stabiliser
Power system studies and
many utility regulations require
additional excitation system
control functionality to ensure
that generators contribute to
power system stability.
VST MAX
N
f sTW1 sTW2 1 + 1+sT8 + 1+sT1 1+sT3 1+sT10
1+sTW1 1+sTW2 1+sT6 Σ (1+sT9)M Σ KS1
1+sT2 1+sT4 1+sT11
+ – VST
VST MIN
Range of settings
KS3
TW1 = 2.0 to 20.0s KS1 = 0.00 to 100.0
TW2 = 0.0 to 20.0s KS2 = 0.00 to 10.00
P sTW3 sTW4 KS2 TW3 = 2.0 to 20.0s KS3 = 0.00 to 10.00
1+sTW3 1+sTW4 1+sT7 TW4 = 0.0 to 20.0s
BRUSH
Head Office: Falcon Works, Nottingham Road, Loughborough,
Leicestershire LE11 1EX United Kingdom