Vigilohm
The IT earthing system to improve electrical network availability
Catalogue
2013
Vigilohm General contents
Presentation 3
Communication interfaces 30
Accessories 31
Commercial references 52
1
2
Presentation
3
Presentation
230 V TT
110 V
110 mA
230 V IT
0.7 V
< 1 mA
4
Insulation monitoring devices
An indispensible solution for implementing an IT earthing network.
Fault location:
On networks with many circuits, the IMD can be associated with a locator (XD301 – XD312) that can
identify the faulty circuit.
Such locators use the 2.5 Hz signal injected by the IMD to determine through which circuit the fault
FXUUHQWLVÀRZLQJ7KHUHLVQROLQNEHWZHHQWKHORFDWRUVDQGWKH,0'
IMD
Manual
IDXOW¿QGLQJ
2.5 Hz current
5
Presentation
IM400
IM10
XD312
Advantage of the
Schneider Electric offer
6
A reliable and effective solution
Per-feeder measurements for highly critical networks.
This feature,
Large networks Improvement which is exclusive to
and/or several buildings of preventive maintenance Schneider Electric,
can meet the following
Easy to manage IT islands are ideal for large Per-feeder measurements enable constant needs.
networks. If this is not possible, then it is monitoring of the insulation change for each
EHQH¿FLDOWRKDYH5DQG&PHDVXUHPHQWV group of critical circuits.
per building or per critical circuit. This gives the maintenance team a better
overview of the entire network and the
capability to anticipate issues.
Supervisor
MT/BT MT/BT
XLI300
XML316 XML308
Per-feeder measurement
In this architecture, the XML products
provide both the IMD function and per-feeder
measurements.
All measurements and time-stamped alarms
are accessed via the supervisor.
The XLI300 provides both a communication
LQWHUIDFHDQG,0'H[FOXVLRQZKHQWKHVHFRQG
circuit breaker is closed (1).
XML316
This solution can also be combined with fault
location by an XD product, thereby enabling fault
location lower down in the network tree.
(1) Exclusion
The IMD injects a low frequency into the network. In a network with several incoming feeders, depending on the circuit breaker
position, there must be no more than one IMD injecting into the network. This injection exclusion is managed by the XLI300 interface.
7
Presentation
XD312
1 2 3
XD312 test
4 5 6
7 8 9
M
10 11 12 reset
PRQLWRULQJGHYLFHVZLWK
XRM
> XD301/XD312 fault detectors to monitor
the different circuits of the installation.
> XRM receivers for mobile fault locating. Automatic fault locating with R & C measurement
per feeder
Fault locating in hospitals Interface Supervisor XML308/316
The safety of the patient and operating XAS
Printer
room staff is critical and standards prohibit défaut
XML316
9
2 3 4 5 6
10 11 12 13 14 15 16
7 8
valeur d'isolement
test
040 K
9
2 3 4 5 6
10 11 12 13 14 15 16
7 8
test
XD312
XRM
1 2 3
XD312 test
4 5 6
7 8 9
M
10 11 12 reset
50536
P50
P12 P100
on
8
Hospital: dedicated modules
To secure power distribution and monitoring solution for operating theatres.
Operating rooms require extremely high availability and quality of electric power
to offer patients maximum safety.
For this reason, the standards lay down very strict rules to ensure the continuity
of service of electrical installations.
IM10-H and HRP (Hospital Remote Panel) for the "Classic" solution
Simple and efficent
> Graphic display. > Audible and visual alarm for an insulation or
electrical fault (transformer overload or circuit
> Bargraph. breaker tripping).
> Smart HMI. > Testing of the insulation monitoring system.
> 8 languages. > Audible alarm stoppage.
> Earth and injection > 24 V DC power supply.
connection monitoring.
> Antibacterial.
> Tested with Anios products (disinfection products).
> Complies with IEC 60601-1 (medical equipment).
IM20-H as a brick of the advanced solution
Hospital version specificities
> Modbus Communication. > Threshold minimum: 50 kOhm.
> Datalog with timestamping of all events.
> Transformer management: > Measurement current < 1 mA.
- secondary load current display, > Measurement voltage < 25 V.
- alarm on threshold (in % of nominal current), > Transformer monitoring (IM20-H).
- alarm on temperature through the sensor (bimetal).
> IM20-H outputs can be connected to the HRP for a
simple solution with transformer management.
9
Presentation
XD301
XD312/XD308C
XLI300 or
Communication
No No No No No XTU300
interfaces
IM400-1700 or
IM20-1700 PHT1000
PHT1000
Accessories (1) Cardews - Limiting impedance (ZX)
Toroids
Mobile fault locating
(1) Except IM9-OL.
(2) Choice between IM10/IM20 and IM400 - see page 12.
(3) 150µF in photovoltaic farms - see page 14.
10
Choosing the best architecture
A variety of possibilities depending on the type of network.
System choice
There are three steps to choosing a system:
7RGH¿QHWKHQHHGQHWZRUNVL]H'&RU
Printer
Supervisor AC, display, automatic fault location,
additional features…
XML308/316 XM300C
Fault
XD301 XD301/312/308C
XD312
XL308/316
Sensors
11
Presentation
+
DC sub-network
_
CPI
PHT 1000
CPI
12
The photovoltaic power system
Photovoltaic is a unique application which introduces the following specifications:
Selecting the IT Power System
In industry, the IT power system is used when availability is required. It’s the only grounding scheme that provides people
VDIHW\RQ¿UVWLQVXODWLRQIDXOWZLWKRXWKDYLQJWRRSHUDWHWKHSURWHFWLRQGHYLFHVDQGLQWHUUXSWLQJWKHSRZHUV\VWHP
,WDOVRDOORZVOLPLWLQJWKHIDXOW\FXUUHQWRQLQVXODWLRQIDXOWLQDUHDWKDWVKRZV¿UHRUH[SORVLRQULVNV
Insulation Monitoring Devices such as Vigilohm provide then an insulation alarm but do not trig the interruption of the power
system.
In photovoltaic applications, the IT power system allows limiting of the faulty current. People
safety against the risk of electric shock is provided by using class II DC power system (double isolation) in combination with
class II PV modules.
Within a grounded photovoltaic installation, an insulation fault may allow the circulation of an important faulty current with
ULVNRI¿UHDQGRUGHVWUXFWLRQRIPDWHULDO
However it is then required to correct the insulation fault reported by the IMD as in case of a second insulation fault the
faulty current would be very important.
,QVRPHFDVHVXSRQGHWHFWLRQRID¿UVWLQVXODWLRQIDXOWWKHIDXOW\SDUWRIWKH39¿HOGDQGRUWKHLQYHUWHUPD\EH
GLVFRQQHFWHGLQVXODWLRQIDXOWFRUUHFWLRQLVWREHH[HFXWHG
The IM400 is designed for the demanding applications including paralleled inverters.
(1) Total power of the PV modules connected to the power system monitored by the IMD
7KH¿OWHULQJYDOXHLVWREHVHWWRV
(3) In case of connection on the AC side of non isolated inverter, the device must be choice taking in account also the DC side voltage and then the
higher value of both AC & DC.
(4) 1000 V DC with IM400-1700 and 1200 V DC with PHT1000
13
The photovoltaic power system
Architectures
6HYHUDODUFKLWHFWXUHVFDQEHIRXQGKHUHDIWHUVRPHFRPPRQRQHV
On installation with non isolated inverter, the IMD can be placed either on AC or on the DC side.
On installation with isolated inverter, the IMD must be placed on the DC side. Optionally an IMD can be placed on the AC side
(if in IT power system).
,QVRPHLQVWDOODWLRQWKHLQVXODWLRQDODUPRXWSXWRIWKH,0'FDQEHXVHGWRGLVFRQQHFWWKH39¿HOGIURPWKHLQYHUWHU
Increased value of C
*LYHQWKHODUJHVXUIDFHDUHDRI39PRGXOHVFRQVWLWXWLQJWKHSKRWRYROWDLF¿HOGRUWKHLQVWDOODWLRQFRQGLWLRQLWLVSRVVLEOHWRKDYH
a value of the leakage capacitance (C) much higher than those usually witnessed in industry.
In industry, if the C value is very high, the impedance (Zc) linked to C could drive this network towards a TT network leading to
risk of dangerous contact voltage and high faulty current.
In photovoltaic applications like every DC applications, the high value of C has no consequences on people’s safety nor on the
faulty current.
14
Selecting a communication
interface (for XM300C & XML308/316)
The power of a communicating system.
XL308
Two interfaces
> XLI300 interface, for the transmission of measurements and One set of busbars with supervisor.
measurement parameters from the XM300C and XD308C devices
to a supervisor. This interface is used on single busbar installations.
7KHH[FOXVLRQRIRWKHULQVXODWLRQPRQLWRULQJGHYLFHVIRXQG supervisor
on the same installation is managed automatically. or
PLC
supervision Modbus
15
Insulation Monitoring Vigilohm IM9
Devices
PB106370_47
Vigilohm IM9
Type of installation to be monitored
LV AC IT systems Phase-to-phase voltage
with IM9 connected to neutral 600 V AC max
with IM9 connected to phase 480 V AC max
Frequency 45-440 Hz
Limited in size IT subsystem
Electrical characteristics
Fault signalling Number of thresholds 2 (sealable)
Thresholds Pre-alarm: 2-5-10-20-50-100-200-
Nȍ
Alarm 1-2,5-5-10-25-50-100-
Nȍ
Response time y7s
Device operating test Local and remote
Failsafe feature (1) Option on the front face
Output contact Number 1 (standard or failsafe)
Type of contact Changeover
Breaking AC 250 V 6A
capacity
DC 12 to 24 V 6A
Use Maximum consumption 7 VA
IT systems: Impedance At 50 Hz Nȍ
b LV AC installations up to: Maximum current injected 70 µA
v 415 V ph-ph Auxiliary supply voltage 50/60/400 Hz 115/415 V AC ±15 %
b one device only for each separate installation DC 125/250 V DC ±15 %
b isolated from earth or connected to earth through an
Mechanical characteristics
impedance
Weight < 0.2 kg
b remote test (for machine control).
Thermoplastic case Mounting Horizontal or vertical
Operation Degree of protection Front IP40
b Injection of DC voltage. Case IP20
b An electronic device measures insulation from the Other characteristics
leakage current created in the installation by the Temperature range For operation -25 ºC to +55 ºC
voltage injected between the installation and earth and
For storage -40 ºC to +70 ºC
trips the alarm pre-set by the user.
Climatic conditions (2)
Earth coupling capacitances do not affect insulation
measurement. Standards Product IEC 61557-8
Safety IEC 60664-1
Installation and connection EMC IEC 61326-2-4
b Live part in moulded, insulating, disconnectable, Marine DNV approval
modular case, eight 9 mm modules wide, with Fault locating with other device
transparent sealable cover.
Mobile XGR portable generator and XRM receiver + probes
b Horizontal or vertical mounting on symmetrical rail.
(1) Failsafe: the relay is disactivated either on occurrence of a fault or if the auxiliary supply
b Connection by tunnel terminals for 2.5 mm² wiring.
voltage accidentally fails.
(2) Suitable for use in all climates:
Standards b damp heat, equipment not operating (IEC 60068-2-30)
b Product: IEC 61557-8. b damp heat, equipment operating (IEC 60068-2-56)
b Safety: IEC 60664-1. b salt mist (IEC 60068-2-52).
16
Vigilohm IM9-OL
(Off-Line)
PB106371_47
Vigilohm IM9-OL
Type of installation to be monitored
LV AC IT / TT /TN-S systems Phase-to-phase voltage y 690 V (1)
(de-energised) Frequency 45-440 Hz
DC (de-energised) Voltage between polarities y 690 V (1)
Electrical characteristics
Fault signalling Number of thresholds 2
Thresholds Prealarm 0.5-1-1.5-2-3-5-7.5
0ȍ
Motor no start 0.25-0.5-0.75-1-1.25-
0ȍ
Response time y2s
Device operating test Yes
Standards
b Product: IEC 61557-8.
b Safety: IEC 60664-1.
17
Insulation Monitoring Vigilohm IM10 and IM20
Devices
PB106374_55
18
Vigilohm IM10-H and IM20-H
(For hospitals)
PB106375_55
19
Insulation Monitoring Vigilohm IM400
Devices
????????
The IM400 accurately measures insulation of systems that contain switching power
electronics (speed drives, motor starters, inverters, Thyristors…) and DC
components.
RM 10N
P12
P50
P100
S1
6WDQGDUGVDQGFHUWL¿FDWLRQV
The IM400 complies with standards:
S2
20
Vigilohm IM400
Type of installation to be monitored
AC or mixed Phase-to-phase voltage y 830 V AC (1)(4) or
AC/DC IT systems (1) with IM400 connected to neutral 1700 V AC (5)
With IM400 connected to phase y 480 V AC (1)(4) or
1000 V AC (5)
Frequency 45-440 Hz
'&RUUHFWL¿HGV\VWHPV Line voltage < 480 V DC (1)(4) or
1200 V DC (5)(6)
Electrical characteristics
Range for insulation resistance readings 10 ȍWR0ȍ
Range for capacitance readings 0.1 µF to 500 µF
ȝ)IRU39
applications)
1. Display indicating: Signalling Number of thresholds 2 (protected password)
b the value of the overall insulation resistance R Threshold Insulation Alarm 0.1 kȍ to 500 kȍ
b other information as selected via function keys. settings Preventative Insulation 1 kȍ to 1 Mȍ
2. Red self-test light, indicating internal IM400 fault or Alarm
wiring connection lost or over capacitance. Time delay for signaling 0s to 7200s
3.<HOORZOLJKWÀDVKLQJDFFRUGLQJWRWKH
Dielectric strength 4000 V AC / 5500 V DC
communication. 7.3 kV impulse
4. Green light, indicating a normal insulation value.
Blinking indicates the injection inhibition. Auxiliary supply voltage 50/60/400 Hz 100 to 440 V AC
5. White light, indicating a pre-alarm. DC 100 to 440 V DC
6. Yellow light, indicating an insulation fault. Blinking Auxiliary supply voltage tolerances +/-15 %
indicates a transient fault. Monitored system voltage IM400 directly connected +5%
7. Function key to access the menu. tolerances IM400 used with IM400-1700 +15%
8. Function key to Escape to the previous screen. Maximum device consumption 25 VA / 10W
9. Three contextual keys. Measurement voltage Variable 15 Vp, 33 Vp, 120 Vp
Measurement current Variable 375 ȝAp, 825 ȝAp, 3 mAp
Fault Locating current 3.75 mAp
Extraneous DC voltage Ufg 506 V
50 Hz/DC impedance 40 kȍ(directly connected)
Device test Self-test / manual test
Output contact Quantity 2
Type of contact Changeover
Breaking AC 250 V 3A
Capacity DC 48 V 1 A, 10 mA min. load
Injection inhibition (voltage supllied by the Voltage 24 V DC
IM400) Current 5 mA
Installation Category 300 V/OVC III, degree
of polution 2
600 V/OVC II, degree
of polution 2
Mechanical characteristics
Weight 0.75 kg
Degree of protection Front face IP54
Back case IP20
Other characteristics
Multi-language display 8 languages
Inverter without transformer (1) Tamperproof settings Password
Temperature range Operating -25ºC to +55ºC [65ºC (3)]
Storage -40ºC to +70ºC
Fault locating with other devices and accessories
Automatic Detectors XD301/312/308C
Manual Mobile receiver XRM + probes
HV plate commercial reference IMD-IM400-1700 (for network up to 1.7 kV
without fault location)
50248 (for network up to 1.7 kV with fault location)
(1) When the insulation monitor is linked to a non insulated inverter it is necessary to take into
account the DC voltage limit rather than the AC limit.
(2) Failsafe: a failsafe relay operates in the event of an accidental interruption of auxiliary power or a fault.
(3) With HV subassembly and 230 +15% V AC power supply.
(4) IM400 directly connected to the power system
(5) IM400 used with IM400-1700 or PHT1000 subassemblies
(6) 1000 V DC with IM400-1700 and 1200 V DC with PHT1000
Commercial reference:
b IMD-IM400
21
Insulation Monitoring Vigilohm XM300C
Devices
044148_SE_52
d é f a u t
valeur d'isolement
040 K
TEST MENU
2QLQVWDOODWLRQVZLWKPRQLWRULQJGHYLFHVFRYHULQJYDULDEOHFRQ¿JXUDWLRQVRQO\
P 100
one device at once is allowed to inject a voltage between earth and the installation
Insulation downstream on the incoming circuit breaker. The system must therefore manage the
fault detection and locating exclusion of other monitoring devices and each locator must identify the monitoring
XRM XL308/316 device it is capturing the signal from. This is handled by either:
b by the XTU300 interface for multiple busbar installations
b by the XLI300 inrterface for single busbar installations.
XL316
test
5 6 7 8
1 2 3 4
1 3 1 4 1 5 1 6
9 1 0 1 1 1 2
In both cases, the circuit breaker position indication contacts are wired to the digital
P 5 0
P 1 2
o n
test/ reset
R M 1 0 N
inputs of the XM300C or the XML308/316. If only XD308C detectors are associated
with the XM300C, monitoring device exclusion is handle by the XLI300.
Sensors Standards
The XM300C complies with the following standards:
b IEC 364 parts 4 and 5
b IEC 61557-8.
P O
S2
b +RUL]RQWDOÀXVKPRXQWLQJRQWKHIURQWIDFHRIDFXELFOHRUHQFORVXUH
b Easy mounting in Prisma enclosures using the corresponding mounting plates
and front plates appropriate cutouts.
b The devices are interconnected by shielded cables (double 0.75 mm2
twisted pair).
7KHUHVLVWDQFHEHWZHHQWKHWZRPRVWGLVWDQWSRLQWVPXVWQRWH[FHHGȍ
The coupling capacitance between pairs must not exceed 250 nF.
22
DB127892
Vigilohm XM300C
Type of installation to be monitored
AC or mixed Phase-to-phase voltage y 760 +20%
i AC/DC IT systems (4) with XM300C connected to neutral or 1700 V AC (1)
With XM300C connected to phase y 440 +20%
or 1000 V AC (1)
Frequency 45-440 Hz
'&RUUHFWL¿HGV\VWHPV Line voltage < 500 V DC or 1200 V
DC (1)
1 7 6 2 4 5 3 Electrical characteristics
Ohmmeter Digital
Range for insulation resistance readings 0.1 kȍWRkȍ
1. Display indicating: Range for capacitance readings 0.1 µF to 999 µF
b the value of the overall insulation resistance R Signalling Number of thresholds 2 (sealable settings)
b other information as selected via function keys.
Threshold 1st threshold (prevent) 1 to 299 kȍ
2. Red self-test light, indicating internal XM300C faults. settings
3. Light indicating that a transient fault has occurred. 2nd threshold (fault) 0.2 to 99.9 kȍ
4. Five lights indicating the insulation level. Dielectric strength 2500 V
5. Instruction manual stored in a drawer on the front Auxiliary supply voltage 50/60 Hz 115/127 V AC
face of the device. 220/240 V AC
6. Sealable cover ensuring tamperproof settings. 380/415 V AC
7. Function keys for: Auxiliary supply voltage tolerances -15 % to +10 %
b accessing earth coupling capacitance readings
Maximum device consumption 30 VA
b setting thresholds
Measurement voltage 6 V max
b displaying the value of the last transient insulation
fault Measurement current 5 mA max
b choosing language. 50 Hz/DC impedance 22 kȍ
Commercial references:
b 115/127 V AC: 50540
b 220/240 V AC: 50541
b 380/415 V AC: 50542
23
Insulation Monitoring Vigilohm XML308 and XML316
Devices
044149_SE_60
Interfaces Communication
XLI300C XLI300 and XTU300 interfaces allow monitoring devices, locators, and
communicating detectors to exchange data with a supervisor. The XLI300 and
XTU300 interfaces connect to the Vigilohm System bus and allow timestamping
X L I3 0 0
d é f a u t
test
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 valeur d'isolement
XML308 and XML316 can operate with type A , OA, and XS toroids.
Installation and connection
Sensors
b +RUL]RQWDOÀXVKPRXQWLQJRQWKHIURQWIDFHRIDFXELFOHRUHQFORVXUH
b Easy mounting in Prisma enclosures using the corresponding mounting plates
and front plates appropriate cutouts
P O
b The devices are interconnected by shielded cables (double 0.75 mm2 twisted pair).
7KHUHVLVWDQFHEHWZHHQWKHWZRPRVWGLVWDQWSRLQWVPXVWQRWH[FHHGȍ
S1
S2
The coupling capacitance between pairs must not exceed 250 nF.
24
DB127893
XML316
Vigilohm XML308 and XML316
test
Type of installation to be monitored
1 2 3 4 5 6 7 8
AC or mixed Phase-to-phase voltage y 760 or 1700 V AC (1)
9 10 11 12 13 14 15 16
i AC/DC IT systems with XM308/316 connected to neutral
With XM308/316 connected to phase y 440 or 1000 V AC (1)
Frequency 45-440 Hz
'&RUUHFWL¿HGV\VWHPV Line voltage < 500 or 1200 V DC (1)
Electrical characteristics
Ohmmeter Digital
9 8 10 1 7 2 3 6 4 5
Range for insulation resistance readings 0.1 kȍWRkȍ
1. Display indicating: Range for capacitance readings 0.1 µF to 999 µF
b the value of the overall insulation resistance R Signalling Number of thresholds per installation 2 (sealable settings)
b other information as selected via function keys. Number of thresholds per circuit 1 (sealable settings)
2. Red self-test light, indicating internal device faults. Threshold 1st threshold (prevent) 1 to 299 kȍ
3. Light indicating that a transient fault has occurred. settings 2nd threshold (fault) 0.2 to 99.9 kȍ
4. Five lights indicating the insulation level. Dielectric strength 2500 V
5. Instruction manual stored in drawer on front of
Auxiliary supply voltage 50/60 Hz 115/127 V AC
device.
220/240 V AC
6. Sealable cover ensuring tamperproof settings.
380/415 V AC
7. Function keys for:
Auxiliary supply voltage tolerances -15 % to +10 %
b accessing earth coupling capacitance readings
b setting thresholds Maximum device consumption 30 VA
b displaying three last values of transient insulation Measurement voltage 6 V max
faults Measurement current 5 mA max
b reading measurements made on individual circuits 50 Hz/DC impedance 22 kȍ
by the internal locator Device test Self-test & manual test
b remote access to faults located by XL308 or Failsafe feature (2) As standard
XL316 detectors Output contacts Changeover Quantity 3 (1 failsafe)
b choice of language (English or French). Breaking capacity AC 400 V pf = 0.7 3A
8. Two indicator lights continuously display insulation AC 230 V pf = 0.7 5A
level of the whole installation. DC 220 V L/R = 1 ms 0.45 A
9. 8 or 16 lights indicating faulty circuits. DC 48 V L/R = 1 ms 2.5 A
10. Light indicating transient fault event. DC 24 V L/R = 1 ms 10 A
Auxiliaries Circuit breaker position indication contacts (3) Voltage supplied 24 V
b Cardew surge limiter: page 33. (voltage and current supplied by XLI or XTU Max current supplied 10 mA (short circuit)
b ZX limiting impedance to create an impedance- interfaces)
earthed neutral: page 34. Connection cross-sections Rigid conductors 1 to 1.5 mm2
b PHT1000 subassembly if the device is used on Flexible conductors 0.75 to 1.5 mm2
1000-1700 V installations: page 34. Mechanical characteristics
Weight 4.5 kg
Sheet-metal case Horizontal Disconnectable screw terminal block
Degree of protection Flush mounting IP30
Other characteristics
Types of toroid used A, OA, (XS compliant)
Interfacing possible with supervisor
Multi-language display English/French
Tamperproof settings Behind sealable cover
Temperature range Operating -5 ºC to +55 ºC
Storage -25 ºC to +70 ºC
(1) The upper limit is extended to the second value by adding a PHT1000 subassembly.
(2) Failsafe: a failsafe relay operates in the event of an accidental interruption of auxiliary power
or a fault.
(3) This contact is an auxiliary switch mounted on the circuit breaker and used to indicate its
operating status.
Commercial references:
b XML308:
v 115/127 V AC: 50490
v 220/240 V AC: 50491
v 380/415 V AC: 50492
b XML316:
v 115/127 V AC: 50322
v 220/240 V AC: 50323
v 380/415 V AC: 50324
25
Fault Location Devices Vigilohm XD301 / XD312 / XD312-H
Automatic insulation fault locators
Electrical characteristics
Type of installation to be monitored Low voltage AC 45-400 Hz / Hospital
DC
Operating threshold 2.5 mA at 2.5 Hz .ȍ
Polling time 20 s 20 s per channel
Fault indications 1 12 channel indicator lights
indicator (+ 1 general)
light
Local tests For indicator lights and output relay
Clearing of indications Reset button on device
Latching of transient fault indications On/off via selector
Output relay Number of contacts 1 failsafe
Use Breaking capacity of output AC 400 V pf = 0.7 3A
contacts
XD301 & XD312 insulation fault locators have two functions: AC 230 V pf = 0.7 5A
b fault detection (with respect to the fault threshold) DC 220 V L/R = 1 ms 0.45 A
b automatic locating of the faulty circuit. DC 120 V L/R = 1 ms 0.65 A
DC 48 V L/R = 1 ms 2.5 A
Operation DC 24 V L/R = 1 ms 10 A
b XD301 and XD312 insulation fault detectors are
$X[LOLDU\VXSSO\YROWDJH 50/60 Hz 115/127 V AC -
¿[HGUHFHLYHUVXVHGZLWKEXWQRWFRQQHFWHGWR
XM300C, XML308/316 and IM400 insulation 220/240 V AC
monitoring devices. Via measurement toroids, they 380/415 V AC -
detect and automatically locate insulation faults. $X[LOLDU\VXSSO\YROWDJHWROHUDQFHV -15 % to +10 %
b The XD312-H is compatible with IM10-H and IM20-H. Consumption 6 VA
b The XD312/XD312-H detector, with 12 channels Dielectric strength 2500 V
FRQQHFWHGWRDPD[LPXPRIWRURLGVLQVWDOOHGRQ Connection with insulation monitoring device None
different circuits of the installation, includes the
Mechanical characteristics
following features on its front face:
Weight 0.3 kg 0.6 kg
v 12 fault indicator lights corresponding to 12 channels
v a selector to enable or disable latching of transient Thermoplastic case Horizontal mounting
fault indications until reset. Degree of protection Flush mount IP30
b Detector XD301 is a single-channel version Surface mount IP20
designed for use with one measurement toroid. Other characteristics
Temperature range For operation -5 ºC to +55 ºC
Installation and connection For storage -25 ºC to +70 ºC
b Live part is in an insulated case with a sealable,
Types of toroids to be used A, OA, (N and O compatible) TA30
transparent sealable cover. Width equal to 8 (XD301)
Toroid for direct connection to case 30 & 50 mm None
or 12 (XD312) 9 mm width modules. type A
b +RUL]RQWDOÀXVKRUVXUIDFHPRXQWLQJRQ',1UDLO
Fault locating with other device
b Tunnel terminals for 1.5 mm2 wiring.
Mobile XGR portable generator and XRM receiver + probes
Toroids (1) The operating threshold of the XD301/312 detectors is not adjustable. These devices are
b XD301 and XD312 insulation fault detectors operate GHVLJQHGWRGHWHFWORZLPSHGDQFHIDXOWV7KHGHWHFWLRQWKUHVKROGYDULHVEHWZHHQȍDQG
NȍGHSHQGLQJRQWKHFKDUDFWHULVWLFVRIWKHLQVWDOODWLRQDQGDURXQG.ȍIRUWKH;'+
with type A and OA toroids. They are also compatible Commercial references
with the older type N and O toroids. b XD301:
b The XD312-H must be used with the toroid TA30 v 115/127 V AC: 50506
ZLWKDVSHFL¿FZLULQJ v 220/240 V AC: 50507
v 380/415 V AC: 50508
b XD312:
v 115/127 V AC: 50535
DB127894
4 5 6 test
7 8 9
10 11 12 reset
1 3 2 4 5 6
26
Vigilohm XD308C
Communicating automatic insulation
fault locator
Electrical characteristics
Type of installation to be monitored Low voltage AC 45-400 Hz /DC
Operating threshold 2.5 mA at 2.5 Hz (1)
Polling time 20 s per channel
Fault indications 8 indicator lights
Operating tests Local
Functions tested Indicator lights and electronics
Clearing of memorised faults Local reset on front face
Remote reset from supervisor
$X[LOLDU\VXSSO\YROWDJH 50/60 Hz 115/127 V AC
220/240 V AC
380/415 V AC
$X[LOLDU\VXSSO\YROWDJHWROHUDQFHV -15 % to +10 %
1. Lights indicating faulty Consumption 6 VA
DB127895
XD308C
circuit. Dielectric strength 2500 V
2. General fault indicator Connection with insulation monitoring device Via 4-wire Vigilohm System bus
1 2 3 4 5 6 7 8
light.
Mechanical characteristics
3. Power on.
test reset
Weight 0.6 kg
4. Test button for indicator
Metal case with insulated front Vertical mounting
lights.
Degree of protection Flush mount
5. Device internal fault
IP 30
indication (self-test). Other characteristics
6. Self-test fault indicator Temperature range For operation -5 ºC to +55 ºC
1 4 5 3 2 6 light. For storage -25 °C to +70 °C
Types of toroids to be used A, OA, (N and O compatible)
(1) The operating threshold of the XD308C detectors is not adjustable. This device is designed
WRGHWHFWORZLPSHGDQFHIDXOWV7KHGHWHFWLRQWKUHVKROGYDULHVEHWZHHQȍDQGNȍ
depending on the characteristics of the installation.
Use
The XD308C provides 3 functions: Commercial references
b 115/127 V AC: 50723
b detection of insulation faults b 220/240 V AC: 50724
b DXWRPDWLFORFDWLQJRIWKHIDXOW\FLUFXLWLGHQWL¿HG b 380/415 V AC: 50725
by the number of the illuminated indicating light
b communication of this information to an XLI300
DB127887
Operation X L I3 0 0
d é f a u t
channels
v 1 general fault indicator light signalling that a fault
has occurred Insulation
v 1 light indicating the device operating status fault detection and locating
v 2 pushbuttons (self-test and reset). XRM XD308C
XD308c
5 6 7 8
1 2 3 4
on
test reset
P 5 0
P 1 2
R M 1 0 N
250 nF. S1
S2
Toroids
b XD308C insulation fault detectors operate with type
A and OA toroids. They are also compatible with the
older type N and O toroids.
27
Measurement per feeder Vigilohm XL308 & XL316
Insulation fault local measurement
044145_SE_51
d é f a u t
test
valeur d'isolement
040 K
TEST MENU
P 100
Insulation
fault detection and locating
XRM XL308/316
XL316
test
5 6 7 8
1 2 3 4
1 3 1 4 1 5 1 6
9 1 0 1 1 1 2
P 5 0
P 1 2
o n
test/ reset
R M 1 0 N
Sensors
P O
S1
S2
28
Insulation fault locators XL308 XL316
DB127896
XL31
Electrical characteristics
1 2 3 4 5 6 7 8
Ohmmeter Digital
9 10 11 12 13 14 15 16 test/reset
i Range for insulation resistance readings WRNȍ
Range for capacitance readings 0.1 µF to 999 µF
- + F !
Signalling 8 lights (1/channel) 16 lights (1/channel)
Signalling threshold and 1
setting range (per channel) Fault threshold 0.2 to 99.9 kȍ
Polling time 15 seconds per channel
Device test Self-test and manual test
1 2 9 7 8 5 6 4 3 Dielectric strength 2500 V
$X[LOLDU\VXSSO\YROWDJH 50/60 Hz 115/127 V AC
1. Display indicating measured insulation resistance 220/240 V AC
and earth coupling capacitance value. 380/415 V AC
2. Light indicating measurement units for displayed $X[LOLDU\VXSSO\YROWDJHWROHUDQFHV -15 % to +10 %
YDOXHNȍȝ)HWF Consumption 30 V A
3. Red self-test light, indicating device faults Indicator and output relay Local or from insulation monitoring device
4. Yellow light indicating that a transient fault has
Output relays 2 ( 1 failsafe)
occurred.
Breaking capacity of output AC 400 V pf = 0.7 3A
5. 2 lights indicating the insulation level:
contacts AC 230 V pf = 0.7 5A
b green light: normal
b red light: insulation resistance below fault threshold DC 220 V L/R = 1 ms 0.45 A
on one of the circuits. DC 120 V L/R = 1 ms 0.65 A
6. Instruction manual stored in a drawer on the front DC 48 V L/R = 1 ms 2.5 A
face. DC 24 V L/R = 1 ms 10 A
7. Function keys for: Connection with insulation monitoring device Via 4-wire communication bus
b accessing earth leakage capacitance readings Connection cross-sections Rigid conductors 1 to 1.5 mm2
b setting thresholds
)OH[FRQGXFWRUV 0.75 to 1.5 mm2
b accessing three last values of transient insulation
faults. Mechanical characteristics
8. Sealable cover ensuring tamperproof settings. Weight 3.5 kg
9. Lights indicating faulty circuits. Sheet-metal case Horizontal mounting
Disconnectable screw terminal block
Other characteristics
Temperature range For operation -5 °C to +55 °C
For storage -20 °C to +70 °C
Types of toroids to be used A, OA, (N and O compatible)
Commercial references
b XL308:
v 115/127 V AC: 50606
v 220/240 V AC: 50607
v 380/415 V AC: 50608
b XL316:
v 115/127 V AC: 50615
v 220/240 V AC: 50616
v 380/415 V AC: 50617
29
Communication interfaces Vigilohm XLI300, XTU300
Device XLI300 /
044141_SE_30
XTU300
Function
Interface between the Vigilohm System bus and a supervisor or PLC b
Power supply to Vigilohm System bus b
Operates with Monitoring device XM300C b
Mon./locating device XML308/316 b
Locator XL308/316 b
Detector XD301/312 -
XD308C b
Maximum Monitoring device XM300C and/or XML308/316 4
FRQ¿JXUDWLRQ Locator XL308/316 8
Detector XD308C 8
Electrical characteristics
Use Auxiliary supply voltage 50/60 Hz 115/127 V AC
When two or more communicating devices (XM300C, 220/240 V AC
XML308/316, XL308/316 or XD308C) are used or 380/415 V AC
when communication with a supervisor is required, Maximum device consumption 30 VA
it is necessary to connect one (and only one) interface Dielectric strength 2500 V
to the communication bus.
Mechanical characteristics
Functions Weight 1.864 kg
The interface allows communication between the Metal case with insulated front b
Vigilohm System and a supervisor or PLC using Degree of protection IP30
a Modbus type protocol. Degree of protection of front IP40
It transmits the information provided by the Vigilohm Other characteristics
System: Interface possible with supervisor b
b prevention and fault alarms from XM300C
or XML308/316 monitoring devices Modbus connector Sub D 9-pin (not supplied) b
b fault alarms from XML308/316 or XM308/316 Communication with other devices Via 4-wire data bus b
locators Temperature range Operation -5 ºC to +55 ºC
b insulation resistance and capacitance Storage -25 ºC to +70 ºC
measurements
Installation
b threshold settings
Vertical mounting on front plate b
b IDXOWDODUPVDQGIDXOW\FLUFXLWLGHQWL¿FDWLRQ
from XD308C detectors. Connection
The interface also allows the thresholds to be set Vigilohm System bus 1.5 mm2 tunnel terminals b
form the supervisor. External bus RS485 Sub D9 female connector b
Communication
As the IMD injects a low frequency into the network,
Speed (baud) Adjustable 300... 19200
it is necessary to have at least one IMD, but no more
Per fault 9600
than one, per subnetwork.
Data length (bits) 8
Exclusion Parity None
This injection exclusion is managed by the interface. Start bits 1
With two or several set of busbars with bus coupling, Stop bits 1
the exclusion becomes more complex and is managed
by a PLC inside the XTU300. Commercial references
b XLI300 115/127 V AC: 50515
;78 ;/,3/&IXQFWLRQ7KHFRQ¿JXDWLRQ b XLI300 220/240 V AC: 50516
b XLI300 380/415 V AC: 50517
is made by Schneider Electric according to the wiring
b XTU300 220/240 V AC: 50546 (1)
diagram. b XTU300 380/415 V AC: 50547 (1)
(1)3OHDVHFRQVXOW6FKQHLGHU(OHFWULFIRUFRQ¿JXUDWLRQ
30
Accessories XRM mobile fault locating
Receiver & current probes
051350_SE_25
It can be placed at various points along a faulty circuit, capturing the signal emitted
by an XM300C, XML308/316 or IM400 insulation monitoring device to determine
the exact location of the fault.
Three current probes are available, the XP15, XP50 and XP100. The set of live
conductors to be tested must have a maximum diameter of 12, 50 and 100 mm
respectively.
level:
b 0: no fault
b 19: solid fault (no insulation).
Note: the photographs are for information purposes only. There are two types of probes that
function in the same way but are different in shape and colour.
DB100471_SE_50
Insulation monitoring
Insulation fault
detection and
locating
XD301 XD312 XRM
P50
P12 P100
on
RM 10N
Sensors
P O
S1
S2
31
Accessories Vigilohm mobile fault locating
Kit XGR + XRM + probes
053130_SE_63
insulation impedance.
b The XRM mobile receiver is associated with one
of the three tong-type probes, XP15, XP50 or XP100,
and detects this leakage current at 2.5 Hz. It displays
a value between 1 and 19 according to the current
passing through the probe, thus detecting the leakage
current.
DB100471_SE_36
051350_SE_19
32
Vigilohm toroids
Earth leakage current detectors
051352_SE_60
Toroids
Use
The toroids are used to detect the earth leakage currents. They are used with the
Vigilohm System for the detection, locating and measurement of earth fault currents
on IT systems.
Closed toroids (type A) are suitable for new installations and extensions.
Split toroids (type OA) are suitable for renovated installations and extensions.
Functions
These toroids detect leakage current and transmit a proportional signal to the
Closed toroids (type A). associated receiver.
Compatibility
042589_SE_46
All type A and OA toroids are compatible with the various devices of the Vigilohm
System range: XD301, XD312, XD308C, XL308, XL316, XML308 and XML316.
DB127911
Figure 1. Figure 2. For severe operating conditions, use of a mild steel sleeve placed around the cable,
in the toroid, considerably increases immunity.
Recommended characteristics
b Mild steel foil, 1/10 mm thick, to be wound several times around the cable in the
toroid (at least 1 mm thick).
b ,QWHUQDOGLDPHWHURIWRURLG![H[WHUQDOGLDPHWHURIWKHFDEOHEXQGOH¿JXUH
b Toroid-detector link:
v resistance yȍ
v cross-sectional area of wires: 0.75 mm² to 1.5 mm².
b Maximum length: 100 m (see the toroid user manual for details).
33
Accessories Vigilohm toroids
Type A closed toroid, Type OA split toroid
DB127915
DB127916
General characteristics
Type of installation to be monitored LV 50/60/400 Hz & DC LV 50/60/400 Hz & DC
Insulation voltage Ui 1000 V 1000 V
Closed sensor b -
Split sensor - b
Operating temperature -35 ºC to +70 ºC -35 ºC to +70 ºC
Storage temperature -55 ºC to +85 ºC -55 ºC to +85 ºC
Degree of protection IP30 (IP20 connections) IP30 (IP20 connections)
Electrical characteristics
Transformation ratio 1/1000 1/1000
3-phase short-circuit withstand current lcw of 100 kA/0.5 s b b
Differential short-circuit withstand current l$w of 85 kA/0.5 s b b
(as per IEC60947-2 in kA rms)
Overvoltage category 4 4
Rated impulse withstand voltage Uimp (kV) 12 12
Sensor characteristics TA30 PA50 IA80 MA120 SA200 GA300 POA GOA
Max cross-section area of conductors per phase (mm2 of copper) 25 50 95 240 2 x 185 2 x 240 50 240
Mechanical characteristics
Type of sensor Diameter (mm) Weight (kg) Diameter (mm) Weight (kg)
Toroid TA30 Ø 30 0.120 - -
Toroid PA50 Ø 50 0.200 - -
Toroid IA80 Ø 80 0.420 - -
Toroid MA120 Ø 120 0.590 - -
Toroid SA200 Ø 200 1.320 - -
Toroid GA300 Ø 300 2.230 - -
Toroid POA - - 46 1.300
Toroid GOA - - 110 3.200
Mounting
Horizontal or vertically on symmetrical DIN rail TA30, PA50, IA80, MA120 -
2QSODLQRUVORWWHGEDFNSODWHRUSUR¿OHGVKHHWPHWDO TA30, PA50, IA80, MA120, SA200 POA, GOA
On cable IA80, MA120, SA200, GA300 -
Environment (1)
Damp heat, equipment not operating (IEC 60068-2-30) 28 cycles +25 °C/+55 °C / HR 95 % 28 cycles +25 °C/+55 °C / HR 95 %
Damp heat, equipment operating (IEC 60068-2-56) 48 hours, environment category C2 48 hours, environment category C2
Salt mist (IEC 60068-2-52) KB test, severity 2 KB test, severity 2
Degree of pollution (IEC 60664-1) 3 3
&DORUL¿FYDOXH0- 0.98 1.42 3.19 3.89 7.05 - 8.02 16.35
(1) Allows use in all climates.
Commercial references:
b TA30: 50437
b PA50: 50438
b IA80: 50439
b SA200: 50441
b MA120: 50440
b GA300: 50442
b Open POA: 50485
b Open GOA: 50486
b 100 m cable (shielded): 50136
34
Vigilohm auxiliaries
Accessories for various installations
(Cardew)
041857_SE_20
Connection
Characteristics
b Non-arcing voltage at 50 Hz y 1.6 x nominal U.
b Certain arcing voltage at 50 Hz >2.5 x nominal U (3 x nominal U for 220 V).
b Maximum current after arcing: 40 kA/0.2 sec.
b Insulation resistance > 1010 7.
b Cartridge not reusable.
b Temperature range:
v operating: -5 °C to +40 °C
DB127912
DB127913
DB127914
MV/LV L3
L2
L1
Connecting conductor size
b Cable or bar with a size adapted to the transformer rating.
N
b The connecting conductor should be considered to be a protective conductor (PE)
and the calculation of its crosssectional area must satisfy applicable installation
cardew C
standards, considering that this part of the installation is protected by protective
devices located upstream of the MV/LV transformer.
b According to standard IEC 364, the formula for the calculation of the of the size of
WKH3(FRQGXFWRULV6 ¥,WNZKHUH6LVWKHFURVVVHFWLRQDODUHDRIWKH3(
conductor in mm2, I is the fault current, t is the operating time of the protective device
DQGNLVDFRHI¿FLHQWWKDWGHSHQGVRQWKHPHWDODQGLQVXODWLRQPDWHULDOXVHGIRUWKH
conductor.
b Recommendation: if insulation monitoring is provided using the Vigilohm
System, install a type A toroid on the Cardew earthing circuit in order to monitor
operation of the Cardew. The toroid can be connected to an XD301/312 detector or
an XL308/316 or XML308/316 locating device.
35
Accessories Vigilohm auxiliaries
Accessories for various installations
019303_SE_20
DB127951
L3
MV/LV
variation of potential so is useful if there is L2
sensitive low-power equipment placed L1
close to the MV/LV transformer, e.g. modem N
power supplies.
1
ZX IMD
Connection
b Creates an installation with an 2
impedance earthed neutral.
b Remains connected during fault locating
at 2.5 Hz:
v ȍDW+]
v 0ȍDW+]
b U y 500 V AC.
Dimension, mounting
Weight: 3.500 kg
DB127917
190
1 2 170
360 185
380 4 Ø8.2 15
Connection DB127952
MV/LV
b For use with Vigilohm System XM300C
and XML308/316 on the following
installations:
v 440 V AC y U y 1000 V AC neutral not 3 2
PHT
accessible 1
v 760 V AC y U y 1700 V AC neutral, 13 14
XM
accessible 22
v 500 V DC y U y 1200 V DC: installation.
Connection
b For use with Vigilohm IM400 and fault
location on the following installations:
v 480 V AC y U y 1000 V AC neutral
not accessible
v 830 V AC y U y 1700 V AC neutral
accessible
v 480 V DC y U y 1200 V DC
Dimension, mounting
Weight: 2 kg
DB127918
110 4 holes Ø7
200
220
184
26
150 80
36
Vigilohm auxiliaries
PB106376_32
Selection table
Cardew C
37
Accessories HRP
Hospital Remote Panel
PB105943_58
Presentation
This accessory provides the interface for an electrical installation monitoring system
in hospitals.
Installed in the operating theatre, the Vigilohm HRP informs hospital personnel,
in real time, of correct operation or the presence of a fault:
b faulty insulation of operating theatre equipment
b electrical fault following a circuit breaker trip or transformer overload.
Use
b Insulation fault signal light (orange).
b Electrical fault signal light (red).
b Correct operation signal light (green).
b Push button to test installation insulation.
b Push button to stop alarm buzzer.
Vigilohm HRP
Mechanical characteristics
Weight 0.5 kg
Case Plastic Vertical mounting
Degree of protection IP54
IK08
Dimensions Height 170 mm
Width 170 mm
Depth 20 mm
Buzzer Factory setting 80 db
Electrical characteristics
Auxiliary supply voltage 24 V DC 65 mA
Environment
Operating temperature 0 °C to 40 °C
Storage temperature -25 °C to +70 °C
Maximum relative humidity 90 %
Altitude 2000 m
Standards
Complies with IEC 60364-7-710 Medical locations
IEC 61557-8 Electrical safety
IEC 60601-1 Medical electrical
equipment
Tested with Anios products (disinfection, antiseptis and detergency products).
)XQFWLRQVLGHQWL¿FDWLRQ
PB105945
est button of the insulation monitoring system (daily test in compliance with
T
IEC 60364-7-710 standard)
Audible alarm stoppage, in case of insulation fault or electrical fault. The alarm
volume setting is made at the mounting phase (available in the rear)
38
DB127897
HRP and IM10-H or IM20-H
2 wires (+24 V 0 V)
ABL8MEM24003
([LVWLQJRUVSHFL¿FSRZHUVXSSO\
Ex: ABL8MEM24003
IM20-H Supervision
4 wires Modbus
ABL8MEM24003
Existing or specfic power supply
Ex: ABL8MEM24003
39
Dimensions Installation and connection
and connections
Product dimensions
IM9, IM9-OL
Mounting on symmetrical DIN rail Cutout
DB127905
2 Ø3.85
66±0.3
45 90 85 46.5±0.3
71 = 61±0.3 =
44
72.5±0.4
67.5
110 96
45 92.4±0.4
93.7
96
46.3
92.4±0.4
59
IM400
Flush mounting Cutout
90
DB127938
73 159
??????
4-RS
112
123
110
101
143.4
129 112
153
9.5 12
192
XD301, XD312
Flush mounting Cutout Surface mounting
DB127936
DB127937
66 66
45 46 46
81 81
6.5 10 66 66
37.5 XD301 5 57 7 93
49.5 XD312 73 110 1 7.5
73.5 57 93
4.5 72 6.5 106
40
XLI300, XTU300
Flush mounting Cutout
DB127900
DB127939
129 112
76
9.5 192 8
71.5
XD308C
Flush mounting Cutout
DB127901
DB127939
129
112
76
9.5 192 8
71.5
XML308, XML316
Flush mounting Cutout
DB127902
DB127940
129
229
9.5 12
192
XRM + probes
XRM manual receiver
DB127903
DB127941
Inside dimensions:
XP15: 12 mm
145 XP50: 50 mm
XP100: 100 mm
37 80
41
Dimensions Installation and connection
and connections
Product dimensions
XGR
DB127904
59
189 108
HRP
Flush mounting
DB127907
DB127908
130
40 min.
H
Test
D W
Ø50 min.
Ø80 max. 2
H W D Weight
170 mm 170 mm 20 mm 0.5 kg
2
(1)
(1)6XSSRUWLQQRQÀDPPDEOHPDWHULDOFRQFUHWHSODVWHUERDUGVWDLQOHVVVWHHO
42
Toroids (type A and OA)
Flush mounting
Type A Ø30 and Ø50 Types A Ø80 to Ø300
DB127919
DB127920
Ø Ø5
2 Ø4.5
16
123
F F H G K B
E
D
8
J C
E D
L
5 B 4
Ø 21
C 29
Type Ø B C D E F Type Ø B C D E F G H J K L
TA30 30 31 60 53 82 50 IA80 80 122 26.5 35 150 80 55 40 126 65 44
PA50 50 45 88 66 108 60
MA120 120 164 26.5 35 190 80 55 40 166 65 44
Ø5
B H
Ø
L
Type Ø H L B
POA 46 38 148 57
GOA 110 44 224 76
042593_SE_45
042591_SE_45
43
Dimensions Installation and connection
and connections
Product connection
IM9
U y 600 V a L-N
PB106370_32
DB127954
P+N
L1
A
3P U y 480 V a L-L
L1
L2
L3
A
3P+N U y 600 V a L-L 10
L1 6A
L2
L3 110...415 Va
N A
6A
IM9-OL
U y 690 VaL-L U y 690 V a L-L
PB106371_32
DB127955
2P/3P 3P
KM1 12...24 Vc 6 A 12...24 Vc 6 A
y 250 Va 6 A KM1 y 250 Va 6 A
6A 6A 6A 6A
- KM3
6A 110...415 Va
6A
110...415 Va
L1 U1
L2 V1 M - F1 - KM2
L3 W1 3a L1 - KM1 U1 U2
L2 V1 M1 V2
- KM1 - F1 W1 3a W2
L3
U1
M
1a Ry 10 k
V1
3xR - KM4
IM10, IM20
P+N U y 480 V a max. 3P U y 480 V L-L a max. 3P+N U y 600 V L-L a max. — max.
DC U y 345 V ---
PB106374_32
DB127956
L1
L1 L1 L2
L2 L3
N L3
N
A B C D
A B C D
6A 110...415 Va
6A
1 2 3 4 5
6 7 8 11 12 13 14 15 16
u 5 mA 0V
24 V c
Failsafe wiring Standard wiring
D0 = A’ / Rx-, A / Tx-
6 7 8 6 7 8 D1 = B’ / Rx+, B / Tx+
44
IM10-H
PB106375_32
DB127957
L
U 110....230 Va
N
6A 6A
1 2 3 4 5
6 7 8
Vigilohm Vigilohm
HRP HRP
IM20-H
DB127957
L
044147_SE_32
U 110....230 Va
N
24 VDC
5mA
IT transformer 6A 6A
bimetal contact
1 2 3 4 5
Shorting
block
6 7 8 9 10 1112 13141516
45
Dimensions Installation and connection
and connections
Product connection
IM400
044147_SE_32
46
Dimensions Installation and connection
and connections
Product connection
XM300C
044148_SE_32
DB400264
XM300C
12 fault
11 (failsafe 1
ut 10 feature) adress
9
1
8 fault
7
6 4
ut 5 prevention
Tunnel terminals for 1.5 mm² wiring 4
Legend 21
aa:$&DX[LOLDU\VXSSO\a 15 %, +10 %, 50-60 Hz I1
ut:DSSOLFDWLRQ 23 20
r:LQVWDOODWLRQ
terminal 13: HDUWKFRQQHFWLRQE\URXQGOXJPPGLDPHWHU I2
24 19
WREHFULPSHG
FRQQHFWLRQVXSSOLHGZLWK3+7 18 V-
2 17 B
13
aa 14 16 V+
1
22 15 S
3
DB127926
DB127925
12 MT/BT
2
fault (failsafe
11 1
feature)
N
10
9
ut 14
8 fault cardew C XM300C
7 13
6
5
MT/BT 3
4
2
1
14
cardew C XM300C
13
-
14
XM300C
13
DB127961
XM300C PHT1000
23
* 24
18 V-
2 13
17 B
aa 1 14 16 V+
22 15 S
1 2 3
47
XML308, XML316
044149_SE_60
DB400265
XML308
XML316
12 fault (failsafe
11 1 t9 t16 t1 t8
ut feature) 1 21 2 1 21 2
10 address
9
1
8 fault 9-1 1-1
7 9-2 1-2
6 4 10-1 2-1
ut 5 prevention 10-2 2-2
4 11-1 3-1
11-2 3-2
21
12-1 4-1
I1 12-2 4-2
23 20
13-1 5-1
Tunnel terminals for 1.5 mm² wiring
I2 13-2 5-2
24 19
14-1 6-1
Legend 14-2 6-2
18 V-
aa:$&DX[LOLDU\VXSSO\a 15 %, +10 %, 50-60 Hz 15-1 7-1
17 B
ut:DSSOLFDWLRQ 2 13 15-2 7-2
aa 14 16 V+
r:LQVWDOODWLRQ 1 16-1 8-1
22 15 S
terminal 13: HDUWKFRQQHFWLRQE\URXQGOXJPPGLDPHWHU 16-2 8-2
WREHFULPSHG
FRQQHFWLRQVXSSOLHGZLWK3+7
3
DB127926
DB127927
12 MV/LV
2
fault (failsafe
11 1
feature)
N
10
9
ut 14
8 fault cardew C XML316
7 13
6
5
MV/LV 3
4
2
1
14
cardew C XML316
13
-
14
XML316
13
48
Dimensions Installation and connection
and connections
Product connection
XD301
044144_SE_32
DB127928
t
XD301 5 6
7 8 9 10 11
aa ut
Legend
aa:$&DX[LOLDU\VXSSO\a 15 %, +10 %, 50-60 Hz
ut:DSSOLFDWLRQ
t: toroid A or OA
XD312
044144_SE_32
DB127929
n° 1
n° 2
n° 12
1 2 3 4 5 6 7 8 9 1011 12
XD312
aa ut
Legend
aa:$&DX[LOLDU\VXSSO\a 15 %, +10 %, 50-60 Hz
ut:DSSOLFDWLRQ
t: toroid A or OA
XD308C
044143_SE_32
DB127930
XD308c
1 t1 t8
aa 2
V
B
V+
S
3 1
4 adress
Tunnel terminals for 1.5 mm² wiring 5 4
6
7
8 8
9
10
11
Legend
aa:$&DX[LOLDU\VXSSO\a 15 %, +10 %, 50-60 Hz
t: toroid A or OA
49
XL308, XL316
044145_SE_60
DB126931
XL308
12 fault XL316
11 (failsafe t9 t16 t1 t8 1
ut 10 feature) 1 2 1 2 1 21 2 address
9
3
8 fault 9-1 1-1
7 9-2 1-2
6 10-1 2-1 8
5 10-2 2-2
4 11-1 3-1
11-2 3-2
12-1 4-1
12-2 4-2
13-1 5-1
13-2 5-2
14-1 6-1
14-2 6-2 V-
18
15-1 7-1
2 13 17 B
aa 15-2 7-2
1 16 V+
16-1 8-1
15 S
16-2 8-2
Legend
DB127926
XGR
DB126933
a.a MV/LV
DB127890
DB126932
3
2
1
N
CPI XGR
XGR
Legend +
DB127934
aaDX[LOLDU\VXSSO\
r:LQVWDOODWLRQ
-
CPI XGR
50
Dimensions Installation and connection
and connections
Product connection
XLI300, XTU300
DB127949
b Never connect more than one interface to the Vigilohm System bus.
18 V- b To connect devices to the communication bus (shielded, double twisted pair)
it is recommended to interconnect their respective terminals S, B, V+ and V-.
17 B
16 V+ XLI300 Sub D9
1 6 RS485
not 15 S
used 1 signal ground
5 9
4 received data -
RS482 5 transmitted data -
8 received data +
1 : GND 9 transmitted data +
1 6 4 : B'(RD-)
5 : B(TD-) 2
aa
5 9 8 : A'(RD+) 1
9 : A(TD+)
RS485
13
V- V- V- V- V-
B XL308 B B B XLI300 B
XM300c XL316 XD308c XML308
V+ V+ V+ V+ XTU300 V+
XML316
XAS
S S S S S
HRP
PB105943_42
DB127909
34 V c 14.5 mA
1 Electrical fault
2 Common
34 V c 14.5 mA
3 Insulation fault
+24 V c 65 mA
4
Auxiliary power supply
0V c
5
7
N
51
Commercial references Vigilohm insulation monitoring
52
Commercial references Vigilohm insulation monitoring
TA30 50437
PA50 50438
IA80 50439
MA120 50440
042589_SE_20
SA200 50441
GA300 50442
Open POA 50485
Open GOA 50486
100 m cable (shielded) 50136
Auxiliaries (2) Accessories for various installations
041857_SE_10
(1) 3OHDVHFRQVXOW6FKQHLGHU(OHFWULFIRUFRQ¿JXUDWLRQ
(2)6HHFKRLFHRI&DUGHZRQSDJHDQGDX[LOLDU\VHOHFWLRQWDEOHRQSDJH
53
54
ART838019 © 2013 - Schneider Electric - All rights reserved
PLSED310020EN 01-2013