Download as pdf or txt
Download as pdf or txt
You are on page 1of 105

OFFICE: CENTER OF ELECTRICAL ENERGY SYSTEM (CEES)

FACULTY ELECTRICAL ENGINEERING


UNIVERSITI TEKNOLOGI MALAYSIA
81310 UTM JOHOR BAHRU
JOHOR DARUL TAKZIM

ROOM NO: P07-412


Tel: 07-5536262
WELCOME
• POWER SYSTEM ENGINEERING
• SEE 4423
• LECTURER: ASSOC PROF MD SHAH MAJID
• ROOM NO: P08-409/P07-417(CEES)
• TEL: 07 -5535295/5536262 (CEES)
• E-mail: mdshah@fke.utm.my, mdshah@ieee.org
SEE 4423
POWER SYSTEM ENGINEERING
SEMESTER II SESSION 2009/2010

Assoc Prof MD SHAH MAJID


SEE 4423
POWER SYSTEM ENGINEERING
SEMESTER 1 SESSION 2009/2010

4
CHAPTER 1

INTRODUCTION TO PROTECTION
SYSTEM
Introduction:Need for Protective Systems

• Power system consists of; generators, transformers, transmission and


distribution lines, etc…..etc.
– Sistem kuasa mengandungi: penjana, pengubah, talian penghantaran dan pengagihan dsbnya

• Short circuits and other abnormal conditions often occur on a power system
– Litar pintas dan keadaan tidak normal kerap berlaku pada sistem kuasa

• Heavy current associated with short circuits is likely to cause damage to


equipments
– Arus yg tinggi ketika litar pintas mungkin menyebabkan kerosakan pada peralatan jika geganti
perlindungan dan pemutus litar tidak di bekalkan untuk perlindungan bagi setiap seksyen
sistem kuasa
Need for Protective Systems

• Short circuit is a faults (power engineer)

• Failure of conducting path due to a break in a conductor is a type of fault

• Fault occurs – automatic protective device is needed to isolate the faulty


element as quickly as possible to keep the healthy section of the system in
normal operation

• Fault must be cleared within fraction of a second

• Uncleared short circuits may cause total failure of the system


• A protective scheme includes transducers, protective relays and circuit
breakers to isolate the faulty section of the system from the healthy section

• Protection is needed not only against short circuit but also against any
abnormal condition
– Overspeed of generators and motors
– Overvoltage
– Underfrequency
– Loss of excitation
– Overheating of stator or rotor of an alternator
– Etc…etc…etc

• Protection is a pre-requisite for an effective and reliable system

• A protective relay does not anticipate or prevent the occurrence of fault,


rather it takes action only after a fault has occurred – except Buchholz relay; a
gas actuated relay
Nature and causes of Faults

• Faults are caused either by;

– Insulation failure –
– Conducting path failure
• results in short circuit

• Faults on transmission and distribution lines are caused by


overvoltage
– Lightning and switching surges
– External conducting objects falling on overhead line.

• Birds also may cause faults on overhead line if their bodies touch one
of the phase and earth wire
• If conductors are broken – failure of conducting path and the conductor
becomes open-circuited
– If broken conductor fall to the ground, results in short circuit

• Joint failure on cables and overhead lines also cause a failure of the
conducting path

• Opening of one or two of the three phases makes the system unbalanced
– Set-up harmonics
• Other causes of faults in o/h line
– Direct lightning strokes
– Aircraft
– Snakes
– Ice and snow loading
– Abnormal loading
– Storm
– Earthquakes
– Creepers
– Etc…..etc……etc……etc
• Cables, transformer generators and other equipment:
– Failure of solid insulation due to aging
– Heat
– Moisture
– Overvoltage
– Mechanical damage
– Accidental with earth
– Flashover due to overvoltages
– Etc…etc…..etc
Types of faults

• Symmetrical faults
• Unsymmetrical faults

• Symmetrical faults
– Kerosakan tiga fasa atau tiga fasa ke bumi

• Unsymmetrical faults
– Single line to earth, line-to-line, double line to
earth, open-circuited phases
• Faults can interrupt power system in several ways:

– Heavy current to flow


• Effect : overheating of power system component

– Fault is a short circuit and exist as electrical arc and liquid e.g air
• Effect: equipment faulty and fire
• Fault
– can increase/decrease voltage system outside its acceptable range

– Can cause unstable three phase system, improper operation of three phase
equipments

– Prevent power flow

– Can cause system to be unstable and collapse


• Faults incur MONEY.

• If fault is isolated as quickly as possible and


accurate –less money required

• Cost of protective equipment is 5% of the total


cost of the system
• PROTECTION DOES NOT MEAN
PREVENTION
– A protective relay does not anticipate or prevent the occurrence of fault,
rather it takes action only after a fault has occurred – except Buchholz relay; a
gas actuated relay
Functions of Protective
System
• Fast and automatically opens the faulty section in the power system

• Increase system reliability and security – only affected area will be


isolated and maintain the healthy line
– Ensure consumers receive continuity of supply

• Delay in isolating the fault


– System unstable, loss of synchronism, total failure of the system
– Fire
Requirements of Protective
System
• The basic requirements of a protective
system are as follows:

– Discrimination/selectivity
– Sensitivity
– Reliable
– Stability
– Speed
(Discrimination/Selectivity)

• Ability to select either to operate or not


– Keupayaan untuk memilih sama ada bekerja atau tidak

• Select to isolate the faulty section only (the


rest normal condition)
– Memilih untuk mengasingkan bahagian rosak sahaja (yang lain berkeadaan
normal)

• The nearest circuit breaker will trip


– Pemutus litar yang hampir sahaja terbelantik (trip)
Radial protection system

SD2 SD3
SD1

SD1 SD2 SD3


Sensitivity

• Relay should operate when the magnitude of the current exceeds the
preset value

• This value is called pick up current

• Should not operate when current is below its pick-up value

• Should be sufficiently sensitive to operate when the operatinfg current


just exceeds the pick-up value – relate with minimum operating current
Reliability

• A protective system must operate reliably


when a fault occurs in its zone of protection
• Failure may due to its protective element
system; CT, PT, CB, relay etc….
• Reliability of protective system 95%
Stability
• A protective system should remain stable even
when a large current is flowing through its
protective zone due to an external fault

• Concerned circuit breaker is supposed to clear


the fault
No Yes

SD1 SD2 SD3

Radial system protection


Speed-fast operation

• Isolate fault as quickly as possible (at shortest time possible )

• Isolate disturbances before loss of synchronism and plant stop operation – time
should not exceed critical clearing time

• Speed balanced with economy


– Cost of protective equipment should be relevant to the cost of the protected
zone

• Avoid fire to equipments, interruption of supply to consumer, voltage drop


operating time; 1 cycle, ½ cycle are also available; distribution system > 1 cycle
Operating time

• Total time to accomplish the isolation

• Calculated at the instance of fault until the


given trip signal

• Must be low for the sake of plant and


equipment safety

• Delay time – for discrimination


Protection economy
• Protection system can be designed as:
– Simple and cheap
– Complex and expensive

• Baesd on:
– The cost of fault
– Safety level requirement
Protection economics…
• Cost of fault
– Cost of damage toward the plant
– Cost loss of revenue due to cut-out supply
– Cost of customers confidence

• Higher the cost of fault, more expensive the protection system

• Higher the plant kVA, more complex protection system required


Protection system at customer level

• Simple fuse – protect equipment and certain


circuits

• Fius ringkas melindungi alat-alat dan litar


tertentu

• Miniature circuit breaker- MCB


Protection system at distribution
level

• Fuse and switch fuse

• Automatic reclosing circuit breaker


– For rural area
– Transient fault is corrected by self clearing
Protection system at transmission
level

• Technical consideration outweighs the economy

• 275kV dan 400kV System require a protection system which is:


– very reliable
– Full discrimation
– High speed

• Expensive and complex

• Provide back-up protection


Zone of Protection
GENERATOR
PROTECTION

CIRCUIT BREAKER
• Power system is divided into HV SWITCHGEAR
several zones PROTECTION

• Each zone of protection is TRANSFORMER

provided with 2 types of


PROTECTION

protection:
EHV SWITCHGEAR
– Primary protection PROTECTION

– Backup protection
TRANSMISSION LINE
PROTECTION

EHV SWITCHGEAR
PROTECTION

ZONE OF
PROTECTION
Protection zone

• Region or area encompass a protection system


Protection zone
CB3
CB3
CB1
CB2

SD1 SD2 SD3

Radial protection system


Main/primary protection

• In general primary protection is provided for


each transmission line segment, major piece
of equipment and switchgear
• If fault occurs, it is the duty of the primary
protective scheme to clear the fault
• First line of defence - Responsible to isolate
fault as quickly as possible
• Fails, back-up protection clears the fault
Backup Protection

• Act when primary protection fails – second


line of defence

• Usually several back up protection scheme will


act to control the power system

• Longer time delay


Radial protection system

SD1 SD2 SD3

Main protection

Back-up protection
Zone of protection
• Zone of protection usually overlap
Fault detection

• Current magnitude
• Current in abnormal path (earth)
• Current balance (current out#current in)
• Voltage balance
• Changes in impedance
• Protective system damage(Buchholz), power flow direction, temeprature
& pressure
Protective system components

1. Circuit breaker
2. Transducer – current transformer (CT), voltage transformer (VT),
potential transformer (PT)
3. Communication links
– Pilot wire
– Radio link
– Overlapping signal, power line carrier (PLC)
Protective system components

4. Relay
– Electromagnetic

– Static – improve reliability,versatile, fast response (1/4 cycle)

– Microprocessor- VLSI teknologi – current interest to power engineers;


adv:attractive flexibility due to programmable approach, can provide
protection at low cost and compete with conventional relays

5. Fuse
Transducer

Serves as a sensor to detect


abnormal system conditions and to
transform the high values of short
circuit current and voltage to a lower
values

43
Protective relays
• Process the signals provided by the
transducers which may be in the form of
current, voltage or a combination of current
and voltage

44
Circuit breaker

• Mechanical device used to energize and


interrupt an electric circuit

45
Ex. Protective system: power
flow balance
2. CT, PT
1. PL 1. P.L

4. Relay

R1 R2

3
Classifications of relay based on its
function

• Overcurrent relay
• Undervoltage relay
• Impedance relay
• Under frequency relay
• Directional relay etc….etc….etc
Classification of protective scheme

• Overcurrent protection
• Distance protection
• Current carrier protection
• Differential protection
Transformer in a protective system

• CT assume ideal
Feeder Ip • Normal rating:
conductor – 1:1, 2:1. 2.5:1, 4:1, 5:1
– 20:1, 40:1, 100:1, 200:1, 300:1,
600:1
Is CT – 1000:1, 2000:1, 4500:1
• Secondary coil is connected to a
Vp “sensitive device” eg voltmeter
Vs
• Low Stray impedance so that voltage
drop small

VT
Current transformer (CT)

• Normal rating
– 1A (Europe)
– 5A (USA)

• Example :
– 50:5, 100:5, 150:5, 200:5, 250:5
– 450:5, 500:5,……1000:5, ……, 6000:

• Secondary coil is connected to a “current sensing device” of zero


impedance

• Shunt impedance high so that I0 low.


(current transformer CT)

• Working principle similar to voltage transformer


• Supply by current source
• Primary winding connected in series with power circuit
– Carries full load current
• Transformer impedance (referred to secondary and can be neglected)
• Secondary coil connected to load (burden)
(current transformer CT)

• Secondary winding feeds the protective system


• Current is reduced but must be almost the same with the power system
current
• Secondary rated current 5 A or 1 A
• Fault current 10 – 20 X rated current. Transformer must be capable to
operate reliably/accurately at this value
• Burden usually usually small – flux do not saturate
Current transformer construction

Bar Type
Core
Power system
current

Primary winding
(1 turn)- from power system

Secondary winding wound


on the core
Current transformer construction

Wound type
design
• CT – similar to a normal transformer emf
equation

• Average induced voltage = product of No. of


turn and rate of change of flux magnet; eaverage
= N(dΦ/dt)

• Knee point voltage(rms) = 4.44 BAfN


Burden
• Defined as the load connected across its
secondary CT
– express in VA (VA taken as nominal secondary
current of CT) or
– Impedance (at the rated secondary current at a
given power factor usually 07. lagging

• Increase in impedance – increase burden


• CT unloaded if secondary winding is short
circuited
Example
• 5VA burden at 1A transformer, gives 5 Ohms
impedance.
• 5VA/1A = 5V
• impedance = 5V/1A = 5Ω

• or

• At 5A CT
• 5VA/5A
• impedance = 1V/5A = 0.2 Ω
Example
• CT ratio 300/1, core area 40x30 mm
• Voltage at knee point?

• V = 4.44 x 0.0018 x 300 x 50 = 120 V


• 1.5 x 40 x 30 x10-6 = 0.0018 Wb ( B for sheet
steel, 1.5 tesla at knee point)
CT open circuit

• If burden high, Es high– exceed Vkp (knee point voltage)


• Io high ; I2 less

• Limited value when the secondary CT open circuit; I2 = 0;


• Then N1I1 = N2 (I2+Io) = N2Io

• This will drive the CT to saturation level


• dΦ/dt = 100 x Vkp (induced = 100 Vkp )
• Cause insulation failure and overheated
Current transformer equivalent circuit

Ip’ x r Is

I0’
Ic ’ Load (burden)
Es Im’ Vs
R

Ip = primary current
(nominal ratio) Kn
I0 = primary excitation
current (no load)

I 'p = I p / Kn I 0' = I0 / Kn
Current transformer equivalent circuit
Ip’ x r Is

I0’

Im’ Ic ’ Load (burden)


Es Vs
R

Es
Ip’
I 'p = Is + I 0'
Is
θ
Is = I 'p − I 0'
I0’
Ic ’ φ
Im’
relationship Es and φ (flux)

N=no of turn in secondary



es = N
dt π
es = Nωφm sin(ωt + )
2
φ = φ m sin ωt
Nωφ m
es = Nωφm cos ωt Es = ∠90°
2
(Nominal Turn Ratio)
• Determine from the given current ratio
– Eg.1000/5 (bar type)

Ip
200
K n = nominal ratio = =
Is 1
Actual Ratio
• Actual ratio value Ip and Is


Ip
actual ratio = winding ratio ×
Is

Ip
= Kt ×
Is
• Winding ratio= secondary coil turn if transformer is of bar type l
– Kt = N2/1

• Ideally ′
Ip
=1
Is
• Practically

Ip
〉1
Is
Actual turn≥ nominal ratio
CT error
• Current error or ratio error
• Phase error
• Composite error
Ratio error or current error

nominal ratio -actual ration


ratio error = × 100%
actual ratio

Nominal ratio= Kn ′
Ip
actual ratio = K t ×
Turn ratio= Kt Is
No compensation Kn=Kt
Cont’d

I p'
K n − Kt
Is
ratio error =
I p' Kn=Kt
Kt
Is
(no compensation)
K n I s − Kt I '

=
p

K t I p'
difference in
I s − I 'p magnitude between
ratio error = × 100% Ip’ and Is
I 'p
Phase Error
Difference in angle between Ip’ and Is

Phase error= θ
Es

Ip’
Is
α θ
I0’

φ
Im’
Compensating winding

• Secondary coil winding is reduced (1 or 2 turn)


to compensate current error due by I0’.

• Secondary coil current will be high, but the


value will be minimised by the excitation
current component

• This can minimised the current error


Example T1

• A current transformer 50 Hz has a secondary current of 3A,Sebuah


• Secondary impedance circuit (0.6+j0.45),
• Maximum flux 0.253 weber
• Magnetisation current and core loss current (primary circuit) at this load
are 0.2 and 0.15 A respectively
• Turn ratio1:10, assume no compensation
• Determine no of turn, ratio error and phase error of transformer
CT equivalent circuit
r
Ip’ Is=3 ∠ αº
I0’

Im’ Ic ’ Load (burden)


Es Vs
= 0.6+j0.45

Es

Ip’ I 'p = I p / Kn I 0' = I0 / Kn


Is
θ I 'p = Is + I 0'
I0’
Ic ’ φ
Is = I 'p − I 0'
Im’
α
N1:N2 = 1:10 Kt = 10 = Kn
Is=3 ∠ αº Im = 0.2 A
Es = I s Z
Ic = 0.15 A
= 3∠α ° × 0.75∠36.87°
N s × φm × ω = 2.25∠(α + 36.87)°
Es = ∠90°
2
Es
(α + 36.87)° = 90°
Ip’ α = 90 − 36.87
α Is = 53.13°
θ

I0’
Ic’
Im’ φ
N s × φm × ω
= 2.25
2
2.25 × 2
Ns =
0.253 × 2π × 50
= 40

∴ N1:N2 = 4:40
I 0 = 0.20 + j 0.15
Is=3 ∠ αº
′ 1
I0 = (0.20 + j 0.15) ×
Im = 0.2 A 10
Ic = 0.15 A = 0.02 + j 0.015

′ ′
I p = I0 + Is
Es
= 0.020 + j 0.015 + 3∠53.13°
Ip’
= 3.024∠52.9975°
Is
θ

I0’
Ic’ φ
Im’

Is + I p 3 − 3.024
ratio error = = × 100%
′ 3.024
Ip
= −0.794 %

phase error = 53.13 − 52.9975


= 0.1325
Ex 1

• A current transformer has 15 turn on the primary and 75 turn on the


secondary. The relay burden is (1.2+j2.6)Ω and secondary winding
impedance of the transformer is (3.6+j0.4)Ω. If the magnitude of the
secondary voltage is 26 volt and magnetization current referred to
secondary is 0.24∠-45o amp. Determine the ratio error and phase error.
Ex 2

• A new non compensated CT with a cross sectional area of 40 cm2 has a nominal
ratio of 2000/5. When 5A is supplied to a relay, the combination of load relay and
secondary winding impedance is (10+j5.77) Ω. If the magnetisation amp-turn is
100 and core loss amp-turn is 50, determine the ratio error and phase error. Using
the same data, calculate also the compensating turn to reduce the ratio error to a
minimum.
Ex. 3

• A CT, 50 Hz has a primary winding of 10 turn and its cross sectional area is 8 cm2.
Secondary current is 5A. The total load and secondary impedance is 0.8+j0.5 Ω.
The excitation current required at the primary winding to establish a working flux
with the secondary open is 0.6∠45o amp. If the flux density is 0.1878
wb/m2,determine the nominal ratio of the transformer. Determine also the ratio
error and phase error of the transformer.
Composite error
• BS 3938:1973
– (r.m.s.) value; difference between ideal secondary
current (i.e CT is ideal ; no excitation component)
with actual secondary current.
• Encompass (current error, phase error and
harmonic effect)
Accuracy limit current of a
protection system CT

• Accuracy limit current (saturation current)


– The maximum current a CT can sustain before
exceed its accuracy
– Specify either in term of primary current or
secondary current
• Accuracy limit factor (saturation factor)
– Ratio of accuracy limit primary current and
rated primary current
– Standard values are 5, 10, 15, 20 and 30
CT specification

• Expressed in
– VA at rated current /class accuracy/accuracy limit factor
– Burden standard rated values
• 2.5,5,7.5,10,15 and 30 VA
– 2 accuracy class: 5P and 10P – gives composite error at rated accuracy limit 5%
and 10% respectively
– Standard accuracy limit factor:
• 5, 10, 15, 20 and 30
Rating of CT

• Method to explain CT

– 10VA/5P/25

Accuracy limit current is 25 x rated


current
Transformer works in good
condition/reliably until 25 x its
Rated burden Class – error rated curent
do not exceed
5%
Ex 1

• CT 10VA/5P/15
• Calculate the accuracy limit factor when the
burden is half of its initial value.
• Secondary resistance of CT 0.15 ohm
Solution
Burden impedance 10VA at rated
current 5A

Es
VA V ×I
= Burden (R)

= I × R× I V

= I 2R

10
R =
2
= 0.4 ohm
5
Solution
Total impedance referred to r
secondary winding
= 0.15 + 0.4 = 0.55 ohm
Es

V
Burden (R)
Accuracy limit factor= ratio accuracy
limit current and rated current

Accuracy limit current= Accuracy limit factor × Rated current

accuracy limit current = 15 × 5


= 75 A
secondary emf = 0.55 × 75 V
= 41.25 V

Es
Burden
(R=0.4)
When burden is half
R = 0.2 ohm

Total secondary impedance= 0.15 + 0.2 = 0.35 ohm


new accuracy limit current = 41.25 / 0.35
= 117.8 A

new accuracy limit factor = 117.8 / 5


= 23.56
Smaller the burden, the higher the accuracy
Therefore :
burden has to be low possible
CT Class X

• BS 3938 – CT for special application is known as Class “X’

• Expressed in turn ratio, knee point voltage, excitation current at the specified voltage and
secondary winding resistance

– Application – scheme where the phase fault stability and/or accurate time grading required

• Transformer rating specify in term of e.m.f maximum that can be use by the transformer

• knee point
– Point where an increase of 10% in secondary e.m.f require an addition of 50% excitation current
Definition of knee point

Excitation
voltage

+10%

Knee
point
+50%

Excitation current
Voltage transformer/potential transformer(VT/PT)

• Supply voltage lower than the sistem voltage

• Nominal sekunder voltage110V

• 2 types
– Wound ( electromagnetic) type(> 132 kV non economical)
– Capacitor type- CVT

• Element X and C consist of tuning circuit – to reduce the ratio and phase
angle error secondary voltage
1/ωC2 = ωL pd 50 Hz; V2 = V’
Talian

C1

L
Vp

Rb
V’
Vs
C2 V2
Xb

V’ = 12 kV, C1 = 2000pF

L
C2
V2 110 V
V’
Protection techniques

• Protection scheme:
– Arrangements of CT, VT, pilot wire and relay so
that the required operating characteristics can be
obtained

• Each section of the power system network is monitored by several


protection scheme.
Main/primary scheme usually consists of:

Unit Scheme

Backup scheme consists of:

Non Unit Scheme


Unit scheme

• ZONE OF PROTECTION IS WELL DEFINED


Unit protection scheme
CT CT

Protected zone

P
Pilot wire
R
relay

Q
Difference current scheme: circulating current

FAULT:
Non similar current flow in the relay
CB will trip
R
CT

Healthy and fault


e1 Protected zon e2 external zone (through
fault):
No current in relay,
e1=e2

R R
FAULT:
Current flow in circuit, result e1≠e2

Differencec current scheme: voltage balance


Balance power direction
CT, PT
PL P.L

Relay

R1 R2
Trip
Trip
Restrain

Restrain
CB1 CB2

A
B
R1 R2
Trip
Trip
Restrain

Restrain

Power flow entering the feeder (from point A) will cause relay (R1)
close trip contact CB1
Power flow exit fron the feeder (at point B) will cause relay R2 rotate
and close restrain contact of the further circuit breaker (remote) (CB1)
(relay R2 send restrain signal CB1)
CB1 CB2

A
B
R1 R2
Trip
Trip
Restrain

Restrain

Power enter at A and exit at B, block trip will prevent the CB from
opening.
CB1 CB2

A
B
R1 R2
Trip
Trip
Restrain

Restrain

Power enter at A and at B (fault occurs), both CB open


CB1 CB2

A B
R1 R2
Trip
Trip
Restrain

Restrain

Power enter at A and no power at B, circuit breaker A, CB1 will open


NON UNIT SCHEME

 supervise/monitor one or several points in the power system

 signal will be detected at the points

 this signal is the input to the relay

 section monitored/supervised is not clearly defined


ZONE OF PROTECTION IS NOT WELL DEFINED
2 examples of non unit scheme
(1.) Over Current Protection

(2.) Distance Protection


‘click here to add title

•Q & A

You might also like