Harmonics Estimator Report

Industrial Edition

Date: 25/7/2018 Page: 1

To: MR DANNY Prepared by:


CEO
NEXUSKL

Project: NEXUS
Linear: 0 HP

Non-Linear: 200 HP

Utility: PT EVANS
Source Data I
Source Frequency (Hz) Rating (kVA) Impedance Z (%) Sec. Voltage (V) Isc (A)
Utility XFMR 50 50,000 8.00 13,800 26,148
User XFMR 50 250 4.00 415 8,695
Source Data II
Source Rated Amps, rms (A) Amps Fundamental (A) Amps Harmonics (A) Total Amps (A)
Utility XFMR 2,092 7.4 0.2 7.4
User XFMR 348 247.5 7.3 247.6
Harmonic Summary
Location Current TDD (%) Voltage TDD (%) Isc/Load Transformer Load (%)
PCC2 3.0 1.3 35.1 71.9

IEEE-519 (2014) limits at PCC2 for specified system based on Isc/IL: Voltage THD: 8.0 %, Current TDD: 8.0 %
Project Compliance
Location IEEE-519 (2014) IEC
PCC2 Yes Yes

The results of this estimation may not represent the actual installed system due to insufficient system data and / or limits of the estimating software.
Yaskawa America, Inc. assumes no responsibility for the accuracy of the supplied data or of this report.

Yaskawa Harmonics Estimator (Industrial Edition) Page 1 of 4


Total System Graphs at PCC2
Chart(s)

The results of this estimation may not represent the actual installed system due to insufficient system data and / or limits of the estimating software.
Yaskawa America, Inc. assumes no responsibility for the accuracy of the supplied data or of this report.

Yaskawa Harmonics Estimator (Industrial Edition) Page 2 of 4


PUMP 1
System Data
System Identification:
Type: Matrix System
Total Motor Power: 200.0HP
Motor Efficiency: 0.91
Model/Catalog #: CIMR-UU4E0124***

Source Data
Source Rated Amps, rms (A) Amps Fundamental (A) Amps Harmonics (A) Total Amps (A)
Utility XFMR 2,092 7.4 0.2 7.4
User XFMR 348 247.5 7.3 247.6

Harmonic Summary (With all other systems removed)


Location Current TDD (%) Voltage THD (%) Isc/Load
PCC2 3.0 1.3 35.1

Indvidual System Compliance


Location IEEE-519 (2014) IEC
PCC2 Yes Yes

The results of this estimation may not represent the actual installed system due to insufficient system data and / or limits of the estimating software.
Yaskawa America, Inc. assumes no responsibility for the accuracy of the supplied data or of this report.

Yaskawa Harmonics Estimator (Industrial Edition) Page 3 of 4


Chart(s)

The results of this estimation may not represent the actual installed system due to insufficient system data and / or limits of the estimating software.
Yaskawa America, Inc. assumes no responsibility for the accuracy of the supplied data or of this report.

Yaskawa Harmonics Estimator (Industrial Edition) Page 4 of 4