Professional Documents
Culture Documents
13b.power Swing Detection1-2007
13b.power Swing Detection1-2007
13b.power Swing Detection1-2007
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Power swing due to;
¾ Power system faults (System more affected on 3-ph
fault, so power gain is very less)
¾ Sudden changes to electrical power due to rejection of
load or generators
¾ These type of disturbances causes oscillation in
machine rotor angles (Load Angle = 900 or 1200) & can
result in sever power flow swings. Power swings are
variations in power flow that occur when the internal
voltages of generators at different network locations of
the power system slip relative to each other.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Vector diagram: two machines
Two Machine Problem
E1 E2
ZS1 ZL ΙL ⋅ ZS1 Ι L ⋅ ZL ΙL ⋅ ZS2
ZS2
E1 E2 = E'2
UA UB UA UB
U'B
U'A
E'1
ϑ' ϑ
Ι 'L ΙL
Pmax = {(E1*E2)/X}*SIN(theta)
If the Load angle becomes too large, the system stability can be lost
Knowledge Is Power
Apparatus Maintenance and Power Management
SM
Figure:-1
for Energy Delivery
Power diagram:
Power Diagram
300
250
Pmax = {(E1*E2)/X}*SIN(theta)
200
Critical Angle
Power
150
Stability region
100
Stability limit
50
0
0 50 100 150 200
Rotor Angle
Angle in Degree
If the Load angle becomes too large, the system stability can be lost
Knowledge Is Power SM
Apparatus Maintenance and Power Management Figure:-1A
for Energy Delivery
Power swing detection methods:
¾ Conventional “Rate of Change of Impedance”
(Dz/Dt) Methods:
¾ Concentric characteristic schemes.
¾ Continuous Impedance calculation schemes.
¾ Blinder Schemes:
1) Single Blinder
2) Double Blinder
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Conventional PSB detection methods:
¾ It measures the Positive sequence impedance
¾ During a system swing, the measured impedance
moves slowly on the impedance plane, and the rate of
impedance change is determined by the slip frequency
of an equivalent two-source system
¾ Travel Time (Delta-t) from one point to next point is to
differentiate between fault & swing.
¾ Travel time is more than set value then, distance relay
sense as swing.
¾ Travel time less than set value then, it sense as fault
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Conventional PSB detection methods:
¾ Concentric circle characteristic schemes:
¾ It is simplest method to detect “rate of change of
impedance”
¾ Two impedance zones. Inner zone & outer zone
¾ Figure-3 shows, Relay indicates PSB when transition
time of impedance from outer zone to inner zone is
more than set value (impedance locus move slowly).
¾ PSB: Blocks the zones when swing is stable (Figure:-3)
¾ OST: Trip zones when swing is un stable (Figure-4)
¾ Major drawback of this characteristic is load
encroachment.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Concentric characteristic scheme: MHO Circle
∆t
Set “Zin” & “Zout” on line angle Swing Locus
Stable Swing
Knowledge Is Power SM
Apparatus Maintenance and Power Management Figure:-3
for Energy Delivery
Conventional PSB detection methods:
¾ Example:
¾ Zout = 45 Ohms@75 degree
¾ Zin = 35 Ohms@75 degree
¾ Transition Time = 50ms
¾ Dz/Dt = (45 – 35) / 0.05 = 200 Ohms/second
¾ Relay Operates if Dz/Dt rate of fall is less than
set value
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Concentric characteristic scheme: MHO Circle
∆t Un stable Swing
Knowledge Is Power SM
Apparatus Maintenance and Power Management Figure:-4
for Energy Delivery
Concentric characteristic scheme: MHO Circle
•Difficult to set on
Load Encroachment
Load
Knowledge Is Power SM
Apparatus Maintenance and Power Management Figure:-5
for Energy Delivery
Concentric characteristic scheme: Lens
Load
Knowledge Is Power SM
Apparatus Maintenance and Power Management Figure:-6
for Energy Delivery
Conventional PSB detection methods:
¾ Concentric characteristic schemes:
¾ Polygon Characteristic concept is much more better
than concentric circle characteristic.
¾ Rset & Xset for out zone can able to set independently.
¾ Rset of outer zone can not reach in to Load region
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Concentric characteristic scheme: Polygon
Characteristic in relay type REL511
Polygon Characteristic for Power swing detection: Set R & X reach independently
ZS1 R
Zload
Angle = 45o
∆Z
Knowledge Is Power SM
Apparatus Maintenance and Power Management Figure:-8
for Energy Delivery
Concentric characteristic scheme: Polygon
Characteristic in relay type 7SA610
E1 > E2 X
ZS2
E1 = E2 B
ZL
ϑ' ϑ load point
A R
E1 < E2 ZLoad
ZS1
Knowledge Is Power SM
Apparatus Maintenance and Power Management Figure:-9
for Energy Delivery
Concentric characteristic scheme: Quadrilateral
Line Angle
Load
Knowledge Is Power SM
Apparatus Maintenance and Power Management Figure:-10
for Energy Delivery
Concentric characteristic scheme: Polygon
Characteristic in relay type RELZ 100
Z3(t3)
Z1(t1)
Z2(t2)
Unstable Swing
Zone 3 limit
Zout boundary
• Timer unit count to starts travel time when Power swing locus crosses Zout boundary
• Travel time (Delta T) more than set time, relay detect as a Power swing
Line Angle
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Continuous Impedance calculation for PSB
detection methods:
Knowledge Is Power SM
Apparatus Maintenance and Power Management Figure:-13
for Energy Delivery
Continuous Power calculation for PSB detection
methods: Polygon characteristic in relay type P437
X
Stable Swing
Setting Parameters:
•Rset
Zpos(t) •Xset
•Line Angle
Unstable Swing
-R R
Let,
SPOS1 = Positive sequence Apparent Power at time (t1)
SPOS2 = Positive sequence Apparent Power at time (t1 + 40 ms)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole Slipping:
¾ The loaded machine with normal excitation
runs out of synchronism with grid network.
During this condition, the generator stator as
well as field current varies heavily as the rotor
angle of machine varies cyclic with respect to
the EMF behind the source impedance of
network as seen from the generator terminal.
¾ If the slip freq. approaches natural shaft freq., torque
produced can break the shaft
¾ High stator iron flux can over heat the generator
stator core
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole Slipping:
¾ Following conditions may cause a generator to
pull out of step;
Operating in an under excited condition (e.g. machine
operates at high load with leading P.F. with relatively
week field)
System switching
AVR & speed controller response time sluggish (e.g.
direct connected machines are run in parallel with
strong grid & sudden outage of grid supplies draws
high inductive load or sudden thrown of dynamic
loads) during sudden system load variations
Faults
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole Slipping:
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole Slipping:
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole Slipping:
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole Slipping:
¾Impedance locus analysis;
XT + Xsys G
Xsys
X”d XT
90o
X”d
X”d > (XT + Xsys) -------Æ Electrical centre below X-axis which
means locus moves from forth quad. To second quad.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole Slipping:
¾ Impedance locus analysis for direct connected
machine; G
ZLoad
X”d
Xsys
Xsys
90o
90o
X”d
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole Slipping:
¾Impedance locus analysis;
XT + Xsys G
Xsys
X’d XT
90o
X’d
X’d > (XT + Zsys) -------Æ Electrical centre below X-axis which
means locus moves from forth quad. To second quad.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Blinder Schemes: Single Blinder
¾ Blinder schemes:
¾ Single Blinder (one pair) scheme (Figure:-17):
¾ One sets of blinders: Resistive reach inner (RRI) & Resistive
reach outer (RRO)
¾ It can be used to restrict tripping of the distance relay for loads
outside of the blinders.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Blinder Schemes: Single Blinder
¾ DR/DT schemes:
¾ Single Blinder scheme (Figure:-17):
¾ One sets of blinders:
¾ It can be used to restrict tripping of the distance relay for loads
outside of the blinders.
¾ If travel time is more than set time & it crosses blinder-1, a
power swing situation is detected further it crosses blinder-2
then it gives a tripping.
¾ Scheme is more suitable for out of step protection for
generators.
¾ Correct settings of blinder-2 & RRR are very difficult to set,
again it’s require high skilled expert to do grid analysis &
effect on machines.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Blinder Schemes: Single Blinder
¾ DR/DT scheme:
¾ How to set timer?
¾ T = {(Critical load angle – Rotor angle)*Fn}/{(360)*(slip frequency)}
Where;
Critical load angle = 150 degree
Rotor angle = 90 degree
Fn = 50Hz
slip freq. = 4Hz
T = {(150 – 90)*(50)} / {(360)*(4)}
= 2.0833 Cycles
T = 2.0833 * 20 = 41.66ms
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Blinder Schemes: Single Blinder
Single Blinder Relay Type: ZTO 11
OST-REGION
Un stable swing
Stable swing
RRR
Blinder-2 Blinder-1
78 trip 78 pick up
Knowledge Is Power SM
Apparatus Maintenance and Power Management Figure:-17
for Energy Delivery
Blinder Schemes: Single Blinder
Single Blinder Rset is not adjustable in forward
direction
Un stable swing
Stable swing
Swing Locus
Blinder 1
XT+XS
Line Angle
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Blinder Schemes: Double Blinder
Double Blinders
Blinder-2 Blinder-1
Blinder-2 Blinder-1
Knowledge Is Power SM
Apparatus Maintenance and Power Management Figure:-20
for Energy Delivery
Blinder Schemes: Double Blinder
Double Blinders
SEL300G Relay
Blinder-2 Blinder-1
Blinder-1 Blinder-2
Knowledge Is Power SM
Apparatus Maintenance and Power Management Figure:-20
for Energy Delivery
Pole Slipping:
¾ Example to set Basic guide line for Pole slip
function;
Generator rating: 210MW, 9050A, 247MVA, 15.75KV,
Transient reactance (X’d) is 30.5% & Sub-Transient
reactance (X”d) is 21.5%
Generator transformer rating: 250MVA, 15.75/240KV,
%Z = 14%
System fault level = 10000MVA
CT ratio = 10000/5A
PT ratio = 15.75/0.110kV
Rate of Slip = 1600 degree/sec
System impedance angle = 75 degree
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole Slipping:
¾ Example to set Basic guide line for Pole slip
function;
Convert to all X value in to secondary ohms
% PU Primary Ohms Sec Ohms
X”dPU = 21.5%
X”dPrimary = (BaseKV2*X”dPU) / MVAbase
X”dPrimary 2
= (15.75 *0.215) / 247
X”dPrimary = 0.2159 Ohms
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole Slipping:
¾Example to set Basic guide line for Pole
slip function;
Convert to all X value in to secondary
ohms
X’dPU = 30.5%
X’dPrimary = (BaseKV2*X”dPU) / MVAbase
X”dPrimary = (15.752*0.305) / 247 = 0.3063 Ohms
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole Slipping:
¾Example to set Basic guide line for Pole
slip function;
Convert to all X value in to secondary
ohms
XT = 14%
X”dPrimary = (BaseKV2*X”dPU) / MVAbase
X”dPrimary = (15.752*0.14) / 247
X”dPrimary = 0.1406 Ohms
X”dsecondary = (0.1406)*(2000/143.1) = 1.96 Ohms
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole Slipping:
¾Example to set Basic guide line for Pole
slip function;
Convert to all X value in to secondary
ohms
Base KV = 15.75kV
System fault MVA = 10000MVA
Xsys-Primary = (BaseKV2) / Fault MVA
Xsys-Primary = (15.752) / 10000
Xsys-Primary = 0.0248 Ohms
Xsys-Secondary = (0.0248)*(2000/143.1) = 0.3466 Ohms
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole Slipping:
¾Blinder setting;
XT + Xsys
Xsys
X”d XT
270o
75o
X”d
Xsys
X’d XT
270o
75o
X’d
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole Slipping:
¾Mho unit setting;
XT + Xsys
Xsys
X’d XT
270o
75o
X’d
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole Slipping:
¾Example to set Basic guide line for Pole
slip function;
Recommendation:
In-depth Transient stability study required
if observe the mal operation of relay during
normal condition. But, the study require
detail information of inter-connected
system & accurate system models which
are expensive.
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pole slip detection method: Relay type REM54
-R X R
X’d / 2
1
Counter Reset
2
XS Counter
Offset mho
characteristic
-X
Operating Region
Pole-Slip Characteristic
TripÎ When Load angle is
7 More than Trip Angle
Tripping Angle
3
ZA
Warning Angle
1
X in Ohm
-7 -5 -3 -1 1 3 5 7
-1
ZC
-3
-5
ZB
-7
Knowledge Is Power SM Figure:-16
R in Ohm
Apparatus Maintenance and Power Management
for Energy Delivery
Pole slip detection method: Relay type REG 316
¾ System Load angle is more than set value with calculated slip
freq., relay will detect pole slip (Power swing)
¾ Relay calculating Freq slip based on T-Slip time (say 55 ms)
¾ Tripping Angle setting should be based on critical angle of
machine & it can be decided after transient stability study of
system
¾ Without system study, recommended angle setting is 120o
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
DOBLE ENGINEERING PVT. LTD
305-SAKAR, OLD PADRA ROAD,
VADODARA-390 015, INDIA.
Cell: +91 94267 47545
PH: (+91)(265) 655 77 15 & Fax: (+91)(265) 235 62 85
E-MAIL: kdave@doble.com
Website: www.doble.com
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery