28 Manufacturer's responsibility
28.2 Certificate
The manufacturer shall prepare, or have prepared, a certificate confirming that the equipment
is in conformity with the requirements of this standard along with its other applicable parts and
additional standards mentioned in Clause 1. The certificate can relate to Ex equipment or an
Ex component.
29 Marking
It is essential that the system of marking indicated below only be applied to electrical
equipment or Ex components which comply with the applicable standards for the types of
protection listed in Clause 1.
29.1 Location
The electrical equipment shall be legibly marked on a main part on the exterior of the
equipment and shall be visible prior to the installation of the equipment.
NOTE 1 The marking should be in a location that is likely to be visible after installation of the equipment.
NOTE 2 Where the marking is located on a removable part of the equipment, a duplicated marking on the interior
of the equipment may be useful during installation and maintenance by helping to avoid confusion with similar
equipment. See 29.10 for additional guidance on extremely small equipment and Ex components.
29.2 General
The marking shall include the following:
a) the name of the manufacturer or his registered trademark;
b) the manufacturer's type identification;
c) a serial number, except for
– connection accessories (cable glands, blanking element, thread adaptor and
bushings);
– very small electrical equipment on which there is limited space;
(The batch number can be considered to be an alternative to the serial number.)
d) the name or mark of the certificate issuer and the certificate reference in the following
form: the last two figures of the year of the certificate followed by a “.” followed by a
unique four-character reference for the certificate in that year;
NOTE 1 For some regional third-party certification, the separating character “.” may be replaced by another
separating designator such as “ATEX”.
e) if it is necessary to indicate specific conditions of use, the symbol “X” shall be placed after
the certificate references. An advisory marking may appear on the equipment as an
alternative to the requirement for the “X” marking;
NOTE 2 The manufacturer should ensure that the requirements of the specific conditions of use are passed
to the purchaser together with any other relevant information.
f) the specific Ex marking for explosive gas atmospheres, see 29.3, or for explosive dust
atmospheres, see 29.4. The Ex marking for explosive gas atmospheres and explosive
dust atmospheres shall be separate and not combined;
g) any additional marking prescribed in the specific standards for the types of protection
concerned, as in Clause 1.
NOTE 3 Additional marking may be required by the applicable industrial safety standards for construction of
the electrical equipment.
For associated apparatus suitable for installation in a hazardous area, and where the energy
limitation is provided inside the apparatus in the hazardous area, the symbols for the type of
protection shall be enclosed within square brackets, for example, Ex d[ia] IIC T4 Gb. When
the equipment group of the associated apparatus differs from that of the apparatus, the
equipment group of the associated apparatus shall be enclosed within the square brackets,
for example, Ex d [ia IIC Ga] IIB T4 Gb.
NOTE 2 A typical example is a shunt diode safety barrier located inside a flameproof enclosure.
For associated apparatus suitable for installation in a hazardous area, and where the energy
limitation is provided from outside the apparatus in hazardous area, the symbols for the type
of protection shall not be enclosed within square brackets, for example, Ex d ia IIC T4 Gb.
NOTE 3 A typical example is a flameproof luminaire with an intrinsically safe photocell connected to a safe area.
For associated apparatus not suitable for installation in a hazardous area, both the symbol Ex
and the symbol for the type of protection shall be enclosed within the same square brackets,
for example, [Ex ia Ga] IIC.
For equipment that includes both associated apparatus and intrinsically safe apparatus with
no connections required to be made to the intrinsically safe part of the apparatus by the user,
the “associated apparatus” marking shall not appear unless the equipment protection levels
differ. For example, Ex d ib IIC T4 Gb and not Ex d ib[ib Gb] IIC T4 Gb, but Ex d ia[ia Ga] IIC
T4 Gb is correct for differing equipment protection levels.
NOTE 4 For associated apparatus not suitable for installation in a hazardous area, a temperature class is not
included.