Professional Documents
Culture Documents
Electrical Machines
Electrical Machines
Electrical Machines
10. In a transformer, the leakage flux of (c) any side is short circuited with
each winding is proportional to the preference
current in that winding because (d) none of the above.
(a) Ohm’s law applies to magnetic circuits
(b) leakage paths do not saturate 14. The equivalent resistance of the
(c) the two windings are electrically primary of a transformer having K = 5
isolated and R1 = 0.1 ohm
(d) efficiency of the transformer. (b) only kVA rating is reduced in the same
proportion as the frequency
(c) both voltage and kVA rating are
18. The main purpose of performing
reduced in the same proportion as the
open-circuit test on a transformer is to
frequency
measure its
(d) none of the above.
(a) Cu loss
(b) core loss
22. The voltage applied to the h.v. side of
(c) total loss
a transformer during short-circuit test is
(d) insulation resistance. 2% of its rated voltage. The core loss will
be.......percent of the rated core loss.
19. During short-circuit test, the iron loss (a) 4
of a transformer is negligible because (b) 0.4
(a) the entire input is just sufficient to (c) 0.25
meet Cu losses only
(d) 0.04
(b) flux produced is a small fraction of the
normal flux
23. Transformers are rated in kVA instead
(c) iron core becomes fully saturated
of kW because
(d) supply frequency is held constant.
(a) load power factor is often not known
(b) kVA is fixed whereas kW depends on
20. The iron loss of a transformer at 400 load p.f.
Hz is 10 W. Assuming that eddy current
(c) total transformer loss depends on
and hysteresis losses vary as the square
voltampere
of flux density, the iron loss of the
transformer at rated voltage but at 50 Hz (d) it has become customary.
would be....... watt.
(a) 80 24. When a 400-Hz transformer is
(b) 640 operated at 50 Hz its kVA rating is
(c) 375
(d) 429 32. The marked increase in kVA capacity
produced by connecting a 2 winding
transformer as an autotransfomer is due
28. The ordinary efficiency of a given to
transformer is maximum when
(a) increase in turn ratio
(a) it runs at half full-load
(b) increase in secondary voltage
(b) it runs at full-load
(c) increase in transformer efficiency
(c) its Cu loss equals iron loss
(d) establishment of conductive link
(d) it runs slightly overload. between primary and secondary.
(b) kVA rating
33. The kVA rating of an ordinary 2- (c) voltage ratio
winding transformer is increased when (d) percentage impedance.
connected as an
autotransformer because
37. If the impedance triangles of two
(a) transformation ratio is increased transformers operating in parallel are not
(b) secondary voltage is increased identical in shape and size, the two
(c) energy is transferred both inductively transformers will
and conductivity (a) share the load unequally
(d) secondary current is increased. (b) get heated unequally
(c) have a circulatory secondary current
34. The saving in Cu achieved by even when unloaded
converting a 2-winding transformer into (d) run with different power factors.
an autotransformer
is determined by 38. Two transformers A and B having
(a) voltage transformation ratio equal outputs and voltage ratios but
(b) load on the secondary unequal percentage impedances of 4 and
2 are operating in parallel. Transformer A
(c) magnetic quality of core material
will be running over-load by .......
(d) size of the transformer core. percent.
(a) 50
35. An autotransformer having a (b) 66
transformation ratio of 0.8 supplies a
(c) 33
load of 3 kW. The power transferred
conductively from primary to secondary (d) 25
is.......kW.
(a) 0.6 Answers
(b) 2.4 1. d 2. d 3. d 4. d 5. b 6. a 7. c 8. a 9. c
(c) 1.5 10. b 11. c 12. d 13. b 14. d 15. c 16. a
17. c 18.b 19. b 20. b 21. b 22. d 23. c
(d) 0.27
24. a 25. c 26. b 27. b 28. c 29. a 30. c
31. d 32. d 33. c 34. a 35. b 36. a 37. d
36. The essential condition for parallel 38. c
operation of two 1-φ transformers is that
they should have the same (A) Choose the Correct Answer :
(a) polarity
1. Which of the following does not change 7. In case there are burrs on the edges of
in a transformer? the laminations of the transformer, it is
1. Current likely to result in
2. Voltage 1. vibrations
3. Frequency 2. noise
4. All of the above 3. higher eddy current loss
2. In a transformer the energy is conveyed 4. higher hysteresis loss
from primary to secondary 8. The path of a magnetic flux in a
1. though cooling coil transformer should have
2. through air 1. high resistance
3. by the flux 2. high reluctance
4. none of the above 3. low resistance
3. A transformer core is laminated to 4. low reluctance.
1. reduce hysteresis loss 9. No-load test on a transformer is
2. reduce eddy current losses carried out to determine
3. reduce copper losses 1. copper loss
4. reduce all the above losses 2. magnetising current
4. Which loss is not common between a 3. magnetising current and loss
transformer and rotating machines? 4. efficiency of the transformer
1. Eddy current loss 10. The dielectric strength of transformer
2. Copper loss oil is expected to be
3. Windage loss 1. 1 kV
4. Hysteresis loss. 2. 33 kV
5. The degree of mechanical vibrations 3. 100 kV
produced by the laminations of a 4. 330 kV
transformer depends on 11. Sumpner’s test is conducted on
1. tightness of clamping transformers to determine
2. guage of laminations 1. temperature
3. size of laminations 2. stray losses
4. all of the above. 3. all-day efficiency
6. The no-load current drawn by 4. none of the above
transformer is usually what percent of the 12. The permissible flux density in case
full-load current? of cold rolled grain oriental steel is
1. 0.2 to 0.5 per cent around
2. 2 to 5 per cent 1. 1.7 Wb/m2
3. 12 to 15 per cent 2. 2.7 Wb/m2
4. 20 to 30 per cent 3. 3.7 Wb/m2
4. 4.7 Wb/m2
13. During the short-circuit test on a 3. primary side
small transformer the frequency is 4. secondary side
increased from 50 Hz to 200 Hz. The 19. In a transformer the toppings are
copper losses will increase by a factor of generally provided on
1. 16 1. primary side
2. 4 2. secondary side
3. 4 3. low voltage side
4. ¼ . 4. high voltage side
14. The efficiency of a transformer will be 20. The use of higher flux density in the
maximum when transformer design
1. copper losses = hysteresis losses 1. reduces weight per kVA
2. hysteresis losses = eddy current 2. reduces iron losses
losses 3. reduces copper losses
3. eddy current losses = copper losses 4. increases part load efficiency
4. copper losses = iron losses 21. The chemical used in breather for
15. No-load current in a transformer transformer should have the quality of
1. lags behind the voltage by about 750 1. ionizing air
2. leads the voltage by about 750 2. absorbing moisture
3. lags behind the voltage by about 150 3. cleansing the transformer oil
4. leads the voltage by about 150 4. cooling the transformer oil
16. The purpose of providing the iron 22. The chemical used in breather is
core in a transformer is to 1. asbestos fibre
1. provide support to windings 2. silica sand
2. reduce hysteresis loss 3. sodium chloride
3. decrease the reluctance of the 4. silica gel
magnetic path 23. If a pump motor is run on 2/3rd of its
4. reduce eddy current losses. supply voltage, it will
17. Which of the following is not a part of 1. continue to deliver same power
transformer installation? 2. burn
1. Conservator 3. stall
2. Breather 4. continue to run at lower speed
3. Buchholz relay 24. An ideal transformer has infinite
4. Exciter values of primary and secondary
18. Which conducting short-circuit test inductances. The statement is
on a transformer the following side is 1. true
short-circuited 2. false
1. high voltage side 25. An ideal transformer ratings are
2. low voltage side usually expressed in terms of
1. volts 31. The higher voltage for transmitting
2. amperes electrical power in India is
3. kW 1. 33 kV
4. kVA 2. 66 kV
26. The noise resulting from vibrations of 3. 132 kV
laminations set by magnetic force, is 4. 400 kV
termed as 32. In a transformer the resistance
1. magnetostriction between its primary and secondary is
2. boo 1. zero
3. hum 2. 1 Ω
4. zoom 3. 1000 Ω
27. Hysteresis loss in a transformer varies 4. Infinite
as (Bmax= maximum flux density) 33. A transformer oil must be free from
1. Bmax 1. sludge
2. Bmax1.6 2. odour
3. Bmax2 3. gases
4. Bmax2.4 4. moisture
28. Material used for construction of 34. A Buchholz relay can be installed on
transformer core is usually
1. auto-transformers
1. wood 2. air-cooled transformers
2. copper 3. welding transformers
3. aluminium 4. oil-cooled transformers
4. silicon steel 35. Gas is usually not liberated due to
29. The thickness of laminations used in dissociation of transformer oil unless the
a transformer is usually oil temperature exceeds
1. 0.4 mm to 0.5 mm 1. 500C
2. 4 mm to 5 mm 2. 800C
3. 14 mm to 15 mm 3. 1000C
4. 25 mm to 40 mm 4. 1500C
30. The function of conservator in a 36. The main reason for generation of
transformer is harmonics in a transformer could be
1. to protect against internal fault 1. fluctuating load
2. to reduce copper as well as core 2. poor insulation
losses 3. mechanical vibrations
3. to cool the transformer oil 4. saturation of core
4. to take case of the expansion and 37. Distribution transformers are
contraction of transformer oil due to generally designed for maximum
variation of temperature of efficiency around
surroundings.
1. 90% load 3. primary side
2. zero load 4. secondary side
3. 25% load 43. A substance is placed in strong
4. 50% load magnetic field. Which of the following will
38. Which of the following properties is have maximum influence on the capacity
not necessarily desirable in the material of the substance to get magnetized?
for transformer core? 44. Harmonics in transformer result in
1. Mechanical strength 1. Increase core losses
2. Low hysteresis loss 2. Increase I2R losses
3. High thermal conductivity 3. Magnetic interference with
4. High permeability communication circuits
39. Helical coils can be used on 4. all of the above
1. low voltage side of high kVA 45. Tertiary winding is provided in
transformers transformers having
2. high frequency transformers 1. mesh/star winding
3. high voltage side of small capacity 2. mesh/mesh winding
transformers 3. star/star winding
4. high voltage side of high kVA rating 4. any of the above
transformers 46. The core used in high frequency
40. High frequency transformers transformer is usually
sometimes make use of ferrite cores
1. copper core
because it has
2. cost iron core
1. high specific gravity 3. air core
2. high resistance 4. mild steel core
3. high hysteresis 47. The full-load copper loss of a
4. low permeability transformer is 1600 W. At half load the
41. Cross over windings are used on copper loss will be
1. low voltage side of high kVA rating 1. 6400 W
transformers 2. 1600 W
2. current transformers 3. 800 W
3. high voltage side of high kVA rating 4. 400 W
transformers 48. The value of flux involved in the
4. high voltage side of low kVA rating e.m.f. equation of a transformer is
transformers
1. average value
42. While conducting short-circuit test on
2. r.m.s. value
a transformer the following side is short-
3. maximum value
circuited
4. instantaneous value
1. h.v.side
2. l.v.side
49. Silicon steel used in laminations equal percentage impedance. This is
mainly reduces likely to result in.
1. hysteresis loss 1. short-circuiting of the secondaries
2. eddy current losses 2. power factor of one of the
3. copper losses transformers is leading while that of
4. all the the above the other lagging.
50. Which winding of the transformer has 3. transformers having higher copper
less cross-sectional area? losses will have negligible core losses
1. Primary winding 4. loading of the transformers not in
2. Secondary winding proportion to their kVA ratings
3. Low voltage winding 55. The changes in volume of
4. High voltage winding transformers cooling oil due to variation
51. Power transformers are generally of atmospheric temperature during day
designed to have maximum efficiency and night is taken care of by which part
around of transformer?
1. Conservator
1. no-load
2. Breather
2. half-load
3. Bushings
3. near full-load
4. Buchholz relay
4. 10% overload
56.The transformer laminations are
52. Which of the following is the main
insulated from each other by
advantage of an auto-transformer over a
1. mica strip
two winding transformer?
2. thin coat of varnish
1. Hysteresis losses are reduced 3. paper
2. Saving in winding material 4. any of the above
3. Copper losses are negligible 57.Which type of winding is used in 3-
4. Eddy losses are totally eliminated phase shell-type transformer?
53. During short-circuit test iron losses 1. Circular type
are negligible because 2. Sandwich type
1. the current on secondary side is 3. Cylindrical type
negligible 4. Rectangular type
2. the voltage on secondary side does 58. During open circuit test of a
not vary transformer
3. the voltage applied on primary side is 1. primary is supplied rated voltage
low 2. primary is supplied full-load current
4. full-load current is not supplied to 3. primary is supplied current at
the transformer reduced voltage
54. Two transformers are connected in 4. primary is supplied rated kVA
parallel. These transformers do not have
59.Open circuit test on transformers is 4. Current transformer
conducted to determine 65. The size of a transformer core will
1. hysteresis losses depend on
2. copper losses 1. frequency
3. core losses 2. area of the core
4. eddy current losses 3. flux density of the core material
60. Short circuit test on transformers is 4. (a) and (b) both
conducted to determine 66. Natural air cooling is generally
1. hysteresis losses restricted for transformers up to
2. copper losses
1. 1.5 MVA
3. core losses
2. 5 MVA
4. eddy current losses
3. 15 MVA
61. For the parallel operation of single-
4. 50 MVA
phase transformers it is necessary that
67. A shell-type transformer has
they should have
1. same efficiency 1. high eddy current losses
2. same polarity 2. reduced magnetic leakage
3. same kVA rating 3. negligible hysteresis losses
4. same number of turns on the 4. none of the above.