DIgSILENT Project:

PowerFactory
15.1.2 Date: 5/29/2019

Fault Locations with Feeders


Short-Circuit Calculation / Method : IEC 60909 2-Phase to Ground / Max. Short-Circuit Currents
Asynchronous Motors Grid Identification Short-Circuit Duration
Always Considered Automatic Break Time 0.10 s
Fault Clearing Time (Ith) 1.00 s
Conductor Temperature c-Voltage Factor
User Defined No User Defined No

Grid: Grid System Stage: Grid Annex: / 1


rtd.V. Voltage c- Sk" Ik" ip Ib Sb EFF
[kV] [kV] [deg] Factor [MVA/MVA] [kA/kA] [deg] [kA/kA] [kA] [MVA] [-]

BARRA D 60 kV A 60.00 19.32 1.36 1.10 0.00 MVA 0.00 kA 0.00 0.00 kA 0.00 0.00 0.48
B 0.00 -120.00 188.99 MVA 5.46 kA 128.41 14.66 kA 5.46 188.99 0.00
C 0.00 120.00 191.42 MVA 5.53 kA 54.85 14.84 kA 5.53 191.42 0.00
LINEA D-E 60 BARRA E A 0.00 MVA 0.00 kA 0.00 0.00 kA
B 0.00 MVA 0.00 kA 0.00 0.00 kA
C 0.00 MVA 0.00 kA 0.00 0.00 kA
T2 220/ 60 k BARRA C 22 A 0.00 MVA 0.00 kA 0.00 0.00 kA
B 188.99 MVA 5.46 kA -51.59 14.66 kA
C 191.42 MVA 5.53 kA -125.15 14.84 kA