DIgSILENT Project:

PowerFactory
15.1.2 Date: 5/29/2019

Fault Locations with Feeders


Short-Circuit Calculation / Method : complete 2-Phase to Ground / Max. Short-Circuit Currents
Short-Circuit Duration Fault Impedance
Break Time 0.10 s Resistance, Rf 0.00 Ohm
Fault Clearing Time (Ith) 1.00 s Reactance, Xf 0.00 Ohm

Grid: Grid System Stage: Grid Annex: / 1


rtd.V. Voltage c- Sk" Ik" Ik' ip Ib ib EFF
[kV] [kV] [deg] Factor [MVA/MVA] [kA/kA] [deg] [kA] [kA/kA] [kA] [kA] [-]
BARRA D 60 A 60.00 17.23 0.55 1.00 0.00 MVA 0.00 kA 0.0 0.00 0.00 kA 0.00 0.00 0.47
B 0.00 -120.00 160.36 MVA 4.63 kA 128.0 3.92 13.09 kA 3.97 9.64 0.00
C 0.00 120.00 163.95 MVA 4.73 kA 54.0 4.00 13.39 kA 4.06 9.85 0.00
LINEA D-E BARRA E A 1.13 MVA 0.03 kA -20.5 0.03 0.09 kA
B 0.57 MVA 0.02 kA 159.5 0.01 0.05 kA
C 0.57 MVA 0.02 kA 159.5 0.01 0.05 kA
T2 220/ BARRA C 22 A 1.13 MVA 0.03 kA 159.5 0.03 0.09 kA
B 160.84 MVA 4.64 kA -51.9 3.93 13.13 kA
C 163.80 MVA 4.73 kA -125.8 4.00 13.37 kA