DIgSILENT Project:

PowerFactory
15.1.2 Date: 5/29/2019

Load Flow Calculation Complete System Report: Substations, Voltage Profiles, Grid Interchange
AC Load Flow, balanced, positive sequence Automatic Model Adaptation for Convergence No
Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for
Consider Reactive Power Limits No Nodes 1.00 kVA
Model Equations 0.10 %

Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 1
rated Active Reactive Power
Voltage Bus-voltage Power Power Factor Current Loading Additional Data
[kV] [p.u.] [kV] [deg] [MW] [Mvar] [-] [kA] [%]
BARRA C 220 Kv
220.00 1.00 220.36 149.37
Cub_1 /Lne Line BC 220 Kv -9.56 -3.75 -0.93 0.03 2.69 Pv: 4.70 kW cLod: 7.29 Mvar L: 50.00 km
Cub_2 /Tr2 T2 220/ 60 kV 9.56 3.75 0.93 0.03 4.10 Tap: 0.00 Min: 0 Max: 0
BARRA A 15.75 kV
15.75 1.00 15.75 0.00
Cub_3 /Sym GENERADOR 1 9.56 -3.42 0.94 0.37 4.84 Typ: PQ
Cub_2 /Tr2 T1 15.75/ 220 Kv 9.56 -3.42 0.94 0.37 4.06 Tap: 0.00 Min: 0 Max: 0
BARRA B 220 kV
220.00 1.00 220.49 149.65
Cub_1 /Lne Line BC 220 Kv 9.56 -3.49 0.94 0.03 2.69 Pv: 4.70 kW cLod: 7.29 Mvar L: 50.00 km
Cub_2 /Tr2 T1 15.75/ 220 Kv -9.56 3.49 -0.94 0.03 4.06 Tap: 0.00 Min: 0 Max: 0
BARRA D 60 kV
60.00 1.00 59.96 -0.98
Cub_1 /Lne LINEA D-E 60 kV 9.56 3.69 0.93 0.10 9.92 Pv: 58.70 kW cLod: 0.14 Mvar L: 20.00 km
Cub_2 /Tr2 T2 220/ 60 kV -9.56 -3.69 -0.93 0.10 4.10 Tap: 0.00 Min: 0 Max: 0
BARRA E 60kV
60.00 0.99 59.27 -1.79
Cub_1 /Lne LINEA D-E 60 kV -9.50 -3.65 -0.93 0.10 9.92 Pv: 58.70 kW cLod: 0.14 Mvar L: 20.00 km
Cub_2 /Tr2 T3 60/ 10 kV 9.50 3.65 0.93 0.10 51.52 Tap: 0.00 Min: 0 Max: 0
BARRA F 10 kV
10.00 0.97 9.70 -4.63
Cub_1 /Lod CARGA 1 9.50 3.12 0.95 0.59 Pl0: 9.50 MW Ql0: 3.12 Mvar
Cub_2 /Tr2 T3 60/ 10 kV -9.50 -3.12 -0.95 0.59 51.52 Tap: 0.00 Min: 0 Max: 0
DIgSILENT Project:
PowerFactory
15.1.2 Date: 5/29/2019

Load Flow Calculation Complete System Report: Substations, Voltage Profiles, Grid Interchange
AC Load Flow, balanced, positive sequence Automatic Model Adaptation for Convergence No
Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for
Consider Reactive Power Limits No Nodes 1.00 kVA
Model Equations 0.10 %

Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 2
rtd.V Bus - voltage Voltage - Deviation [%]
[kV] [p.u.] [kV] [deg] -10 -5 0 +5 +10
BARRA C 220 Kv
220.00 1.002 220.36 149.37
BARRA A 15.75 kV
15.75 1.000 15.75 0.00
BARRA B 220 kV
220.00 1.002 220.49 149.65
BARRA D 60 kV
60.00 0.999 59.96 -0.98
BARRA E 60kV
60.00 0.988 59.27 -1.79
BARRA F 10 kV
10.00 0.970 9.70 -4.63
DIgSILENT Project:
PowerFactory
15.1.2 Date: 5/29/2019

Load Flow Calculation Complete System Report: Substations, Voltage Profiles, Grid Interchange
AC Load Flow, balanced, positive sequence Automatic Model Adaptation for Convergence No
Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for
Consider Reactive Power Limits No Nodes 1.00 kVA
Model Equations 0.10 %

Grid: Grid System Stage: Grid Study Case: Study Case Annex: / 3
Volt. Generation Motor Load Compen- External Power Total Load Noload
Level Load sation Infeed Interchange Interchange Losses Losses Losses
[MW]/ [MW]/ [MW]/ [MW]/ [MW]/ to [MW]/ [MW]/ [MW]/ [MW]/
[kV] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar]
10.00 0.00 0.00 9.50 0.00 0.00 0.00 0.00 0.00
0.00 0.00 3.12 0.00 0.00 0.00 0.00 0.00
60.00 kV -9.50 -0.00 -0.00 0.00
-3.12 0.53 0.53 0.00
15.75 9.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-3.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00
220.00 kV 9.56 0.00 0.00 0.00
-3.42 0.07 0.07 0.00
60.00 0.00 0.00 0.00 0.00 0.00 0.06 0.06 0.00
0.00 0.00 0.00 0.00 0.00 0.03 0.18 -0.14
10.00 kV 9.50 -0.00 -0.00 0.00
3.65 0.53 0.53 0.00
220.00 kV -9.56 -0.00 -0.00 0.00
-3.69 0.07 0.07 0.00
220.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00 -7.24 0.05 -7.29
15.75 kV -9.56 0.00 0.00 0.00
3.49 0.07 0.07 0.00
60.00 kV 9.56 -0.00 -0.00 0.00
3.75 0.07 0.07 0.00
Total: 9.56 0.00 9.50 0.00 0.00 0.00 0.06 0.06 0.00
-3.42 0.00 3.12 0.00 0.00 0.00 -6.54 0.89 -7.43
DIgSILENT Project:
PowerFactory
15.1.2 Date: 5/29/2019

Load Flow Calculation Complete System Report: Substations, Voltage Profiles, Grid Interchange
AC Load Flow, balanced, positive sequence Automatic Model Adaptation for Convergence No
Automatic Tap Adjust of Transformers No Max. Acceptable Load Flow Error for
Consider Reactive Power Limits No Nodes 1.00 kVA
Model Equations 0.10 %

Total System Summary Study Case: Study Case Annex: / 4


Generation Motor Load Compen- External Inter Area Total Load Noload
Load sation Infeed Flow Losses Losses Losses
[MW]/ [MW]/ [MW]/ [MW]/ [MW]/ [MW]/ [MW]/ [MW]/ [MW]/
[Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar] [Mvar]
\hp\SISTEMA ELECTRICO DE POTENCIA 6 BARRAS\Network Model\Network Data\Grid
9.56 0.00 9.50 0.00 0.00 0.00 0.06 0.06 0.00
-3.42 0.00 3.12 0.00 0.00 0.00 -6.54 0.89 -7.43
Total:
9.56 0.00 9.50 0.00 0.00 0.06 0.06 0.00
-3.42 0.00 3.12 0.00 0.00 -6.54 0.89 -7.43