UERL

STUBBCREEK EPF 200 KVA (1300 SERIES) PERKINS EMERGENCY/BLACK

START DIESEL GENERATOR DAILY CHECK LIST/PARAMETER

MONITORING DATA SHEET

DATE: 09-07-2014 (Wednesday).


S/N CHECKS 0800HRS 10.00HRS 12.00HRS 1400HRS 1600HRS 1800HRS REMARKS/COMMENTS
1 RADIATOR AT FULL OK
COOLANT LEVEL MARK
2 ENGINE OIL LEVEL AT FULL OK
(DIP STICK) MARK
3 ENGINE 27 0 C 53 0 C 460 C 55 0 C 54 0 C OK
TEMPERATURE
4 ENGINE OIL 4.9 Bar 4.7 Bar 4.8 Bar 4.7 Bar 4.7 Bar OK
PRESSURE
5 ENGINE RUN 6203.2 6205.4 6205.6 6206.9 6207.8 OK
HOURS
LAST ENGINE 5980 5980 5980 5980 5980
6 SERVICE RUN OK
HOURS
NEXT DUE -27Hrs -27Hrs -27Hrs -27Hrs -27Hrs OK
7 ENGINE SERVICE
RUN HOURS
AVAILABLE RUN 6180 6180 6180 6180 6180
8 HOURS BEFORE OK
NEXT DUE
ENGINE SERVICE
NUMBER OF 1264 1264 1265 1265 1265 OK
9 STARTS
NUMBER OF E- 126 126 126 126 126 OK
10 STOPS
98 98 98 98 98 OK
11 SHUT DOWNS
BATTERY 25.5 Volts. 27.8 Volts. 25.9 Volts. 27.8Volts 27.8 Volts
12 VOLTAGE OK

13 FUEL TANK LEVEL 275 Litres 175 litres


Tank Vol. Tank Vol.
100 litres of Diesel
Oil Used.

14 START TIME 0930 Hrs. 1337 Hrs. OK


15 STOP TIME 1128 Hrs. 1558 Hrs OK

16 50.0 Hz 49.9 Hz 50.0Hz 50.0Hz 50.0Hz OK


FREQUENCY (Hz)
17
LEAKAGE Nil Nil Nil Nil Nil OK

18 VIBRATION N/A N/A N/A N/A N/A OK

19 EXHAUST GAS PARTIAL OK


COLOR WHITE
20 LOAD (KVA) 13KVA 57 KVA 6 KVA 63 KVA 57 KVA OK

21 ALARMS OK

22 NOISE OK

CHECKED BY: STEPHEN, EKEMINI

Date: 09-07-2014

COMMISSIONING TEAM