Professional Documents
Culture Documents
Unsymmetrical Fault Analysis
Unsymmetrical Fault Analysis
Unsymmetrical Fault Analysis
Lectures prepared by
Lectures prepared by
Prof. S. Shahnawaz Ahmed
Unsymmetrical Fault analysis:
•Symmetrical components, sequence
networks.
[1]. John J. Grainger, William D. Stevenson, Jr. "Power System Analysis",
M G
McGraw‐Hill, 1994.
Hill 1994
Why symmetrical components?
The occurrence of unsymmetrical faults such as L‐G, L‐L and L‐L‐G faults in a three‐phase system with
balanced impedance elements such as machines,
machines transformers,
transformers transmission lines and Y or Δ connected
loads, causes unbalanced currents and voltages to exist in each phase. Depending upon the system
parameters and network connections, occasionally L‐G fault current can also be higher than that for the
symmetrical (L‐L‐L) fault. Moreover, relay setting needs the knowledge of the minimum fault current
that might occur for any of the unsymmetrical faults.
faults
The unbalanced voltages at any point of a system can be determined by superposing the individual
responses of the system elements to three sets of balanced currents known as symmetrical
components into which the original currents can be resolved.
resolved
This also holds good for vice versa i.e., unbalanced currents from the responses to three sets of
balanced voltages.
For this it is also necessary to determine sequence impedances of each element and to combine them
to form sequence networks.
networks
C.L.Fortescue
C L Fortescue’ss theorem:
A system of n unbalanced phasors (currents or voltages) can be resolved into n sets of balanced phasors
termed symmetrical components such that the phasors belonging to the same set are of equal
magnitudes and the phase angle between adjacent phasors are equal.
As for instance, for a three‐phase system the three unbalanced phasors can be resolved into three
balanced sets termed positive sequence, negative sequence and zero sequence components.
Resolution into S.C.
Combining these relationships
1+a+a2 = 0
1= a3 = 1<360° =1<0°
Synthesis from S.C.
Similarly for currents
The similar set for line to line voltages can
be written by replacing Va, Vb, Vc
Sum is zero for Ia+Ib+Ic and for Vab+Vbc+Vca
If expressed in pu of line and phase
current bases on respective sides then
√3 will disappear from right side of above
relations.
Note: in Y with unconnected neutral, line
current sum is zero while in Δ line voltage Similarly for a Y cct
y starting with
g
sum is zero due to being around a series loop.
If expressed
It can be derived that in pu of
p
respective
However, if both sides expressed in pu on same base bases
then the factor √3 will remain. √3 will
disappear
from right
side.
Power in terms of symmetrical components:
Where S in VA, V in volts and I in amps.
But if pu values are used then the
multiplier 3 disappears from right side.
lti li 3 di f i ht id
Example: Line c is open while a and b currents are as shown. Find symmetrical components.
A l i
Applying the three phase sequence component relationships
h h h l i hi
symmetrical components of line to neutral
Both sides derived in
pu but on respective
but on respective
base (L‐L and L‐N)
Van (0) = 0 as zero sequence current
So that cannot flow in unconnected neutral
Z0 ≈ 2 to 3.5 Z1 or Z2
If Znn and Zan included in zero sequence impedance
Sequence impedances can be derived using similar eqns for
also takes into account the ground wires and the
Vbn, Vcn, and transformation matrix A, and defining
earth return path impedances, then the sequence
voltages shown in Fig. 11.12 are with respect to a
perfectly conducting or ideal ground as the
reference
Sequence circuits for unsymmetrical series impedances or Y loads:
For unbalanced elements it is not possible to decouple the sequence components from
each other so that their sequence impedances are not distinct and the voltage drop of
any one sequence depends upon on the current of all three sequences.
•For transposed transmission lines mutual coupling is considered inherently in calculating self
inductance and the three phase series impedances become equal (Za = Zb
inductance and the three phase series impedances become equal (Za = Zb = Zc= Z) so that the
= Zc= Z) so that the
sequence voltage drops are produced only by respective sequence currents. Moreover, then
the sequence impedances become Z1 = Z2 = Z and Z0 = Z + 3 Znn if any impedance Znn in the
ground path.
Sequence circuits for synchronous machines when supplying an unbalanced load or
subjected to an unbalanced fault:
Then as usual transforming the set of Van, Vbn, Vcn
and the currents on right side into symmetrical
components , it can be derived eventually that
‐
so that the resultant sequence circuits for the generator are
as in the next slide
Source is only in positive sequence network
y p q
Reference is neutral and same as ground
Reference is ground.
For zero sequence current the cct for any element of a
power system is always analogous to a single phase circuit
as the zero sequence components of phases a,b,c do not
have phase shift.
But positive and negative sequence ccts represent per
phase equivalents.
Z1 = Z2 =Xd’’
Zg0 =0.1 to 0.7 Xd’’
Zn = 0
equal
for L G Note:
for L‐G Note:
fault Vab =Va‐Vb will always be obtained in pu of the base
used on RHS. So if L‐N voltage base is used on RHS then
Vab will be in pu of L‐N voltage base.
Sequence ccts. for three phase transformers: Z
Positive and negative sequence ccts (for Y‐Y, Δ‐Δ) are as usual
For a transformer , impedances in pu
For a transformer impedances in pu are Zare Z1 = Z
= Z2 =Z (i.e. X
=Z (i e Xleakage)
No phase shift
and Z0 = Z + 3ZN +3 Zn if both side Y connected and ZN, Zn ≠ 0
For Y‐Δ or Δ‐Y (step up) these are
as follows: (in pu √3 N1/N2 omitted)
Compliant with following
ANSI labeling
However, in the following case
VA(1) = ‐j Va(1)
VA(2) = +j Va(2)
Note:
Vab =Va‐Vb will always be obtained in pu of the base
used on RHS. So if L‐N voltage base is used on RHS then
Vab will be in pu of L‐N voltage base.
Salient points about sequence circuits:
Example on combining sequence circuits for a power system
ΔY
Δ‐Y or Y‐Δ
Y Δ transformer phase shifts neglected in above sequence circuits.
t f h hift l t di b i it
Given the parameters shown in the zero sequence
cct.:
Generator and motor X0 = 0.05 pu on respective
rating
Current limiting reactors in gen. and motor neutrals
each 0.4 ohms
Transmission line X0 = 1.5 ohms/km
These are then converted on specified base
Δ
A brief note on three phase transformer connection and grounding
•Y‐Y with both sides grounded (i.e. Yg‐Yg) is good for detection of L‐G faults by relays
because then zero sequence current can flow. Also this provides (i)a path for the third
harmonic component of excitation current and hence a distortion free voltage (however, if Y
is grounded only on primary side then also this 3rd harmonic component can flow but not
the zero sequence current due to unbalanced load or fault), (ii)stable set of phase to neutral
voltages in case of unbalanced loads or unsymmetrical fault conditions. However, such a
connection does not provide isolation of the primary side (generator side) from transient
disturbances of the secondary side (transmission side).
•Y –Δ or Δ‐Y with neutral grounded on Y side is better than Yg‐Yg in the sense that Δ
provides a circulating path for zero sequence currents of faults, third harmonic component
of excitation current, and partially redistributes the imbalance conditions in line voltages
and currents due to unbalanced loads. Moreover , the zero sequence impedance by such a
connection is a higher than that due to Yg‐Yg connection so that the L‐G fault current can
be limited to a lower level but still detectable by the relays. Also the isolation of one side
from transient disturbance of the other side is also achieved.
•If no path is provided for flow of the zero sequence current (e.g. Y‐Y with ungrounded
neutral, Y‐Δ with ungrounded Y and Δ‐Δ ) then in case of a L‐G fault the current being
abnormally low (termed HIF—high impedance fault) is not detected by the conventional
relays, which poses a danger if the fault is of permanent nature. Also in such situations the
resulting small fault current returns back through the charging capacitors of a transmission
line and gives rise to arcing ground due to alternate charging and discharging of the
distributed line to ground capacitors producing distortions and imbalance in the voltage.
Unsymmetrical Fault Calculation
Negative seq same as positive one
but with emf source shorted.
Ifa = Ifa(0)+Ifa(1)+Ifa(2)=3Ifa(0)
which is satisfied if the three sequence networks are connected as shown
Derivation of fault current for L‐L fault (assumed on phases b and c)
The following relationship to be satisfied
if prefault current neglected:
if prefault current neglected:
To satisfy the requirements that
and (It may be verified that
Vkb‐Vkc = IfbZf leads to Vka(1)‐ Vka(2)=Ifa(1)Zf )
the Thevenin’s equivalents of positive and negative
sequence networks need to be connected in parallel
as shown
h
Eqn. 12.23
Fault current components from this Fig.
By current division of Ifa(1) ,
Ifa(0) and Ifa(2) are obtained
Then Ifb and Ifc are synthesized from respective symmetrical components
derivable from those for Ifa. The current into the fault is then Ifb + Ifc.
Note: For any ground involved fault (L‐G) or (L‐L‐G) the current into the fault , If =3 Ifa(0)
i.e. three times the respective zero sequence current
Proof:
F L‐L‐G
For L L G fault
f lt as in
i Fig.
Fi If = Ifb + Ifc
For L‐G fault as in Fig. If = Ifa =(Ifa +Ifb +Ifc ) ‐ Ifa
=(Ifa +Ifb +Ifc ) ‐ Ifb ‐ Ifc =3 Ifa(0) ‐0
=3 Ifa(0) ‐0 ‐0 =3 Ifa(0)
=3 Ifa((0)) [i
[since f lt is
fault i on phases
h b and
d c]]
[since fault is on phase a]
Comparison of fault currents
For 3‐phase balanced fault (L‐L‐L), Ifa = Ifa(1)=Vf/(Zkk(1) + Zf)
In general , for the same location magnitudes of current into various bolted faults (i.e. Zf =0 )compare as
follows: Hints:
If L‐L‐L > If L‐G>If L‐L‐G>IfL‐L If L‐L‐L = Ifa(1) If L‐G = 3 Ifa(0) If L‐L‐G = 3 Ifa(0) =‐3
where respective sequence current expressions to be used.
Positive seq. (sources omitted in negative seq.)
Zero seq.
‐j1.373 ‐j0.25
So |I
So |Ic |= 0.25 x Base Amps in machine 2 cct
|= 0 25 x Base Amps in machine 2 cct
= 0.25x(100000/√3x20) = 0.25x2886.751 =721 Amps
EEx. 12.3 for L‐L fault at bus 3 and
12 3 f L L f lt t b 3 d
EX.12.4, Ex 12.5 for L‐L‐G fault at machine 2 terminal (bus 4) of the following Fig. (used also in
Ex. 12.1)
•In these examples phase shift considered for the other side after
completing calculations for sequence currents/voltages on one side of Y‐Δ transformers.
Note:
Vab =Va‐Vb will always be obtained in pu of the base
used on RHS. So if L‐N voltage base is used on RHS
then Vab will be in pu of L‐N voltage base.
Examples 12.6 and 12.7 focus on the physical paths for flow of various sequence
currents for a L‐G fault in a small power system, though these currents are computed
using
i mathematical
h i l interconnections
i i off the
h sequence networks.
k
Also bus impedance matrices have not been used in these examples since the
systems are very small systems. Instead Thevenin’s method is applied to compute the
required
q impedances.
p
Phase shift in
positive and
negative seq.
networks will
be considered
later
(at LV side)
Considering phase shift between HV and LV sides of Y‐Δ transformer
at HV side i.e. between bus 2 and transformer
Line currents (LV side) of transformer
=3Ifa(0) =3x2.564