NCR - 05042019 (Spalling at The Roof)
NCR - 05042019 (Spalling at The Roof)
KS HSM #2 Project
Ref.No. : KS-NCR-
1. Almost all roof in reheating furnace have cracks or spallings on refractory works (unfired zone until soaking zone).
2. Cracks or Spallings not only occur in refractory zone which exposed to water, but also in zones that are not exposed to water.
3. Severe cracks have gaps that range around 8-15mm, there are even some cracks or spalling that penetrate to the outer layer of the reheating furnace
1. SMS shall provide repairing procedure for all refractory which has small spalling. For severe spalling, Contractor have to dismantle the refractory and replace it with a
new one.
2. QC from PTKE should proactive to monitor and check refractory quality on furnace!
Contractor
Consultant
Contractor
Consultant
Owner
4. Completion Notice
Contractor
Consultant
Owner
NCR
Attachment :
Fig. 1. Actual condition regarding roof refractory on reheating furnace which are not exposed
to the water (Soaking Zone)
Outer layer
Inner Layer
Fig. 2. Actual condition regarding roof refractory on reheating furnace which are not exposed
to the water (Unfired Zone) Severe area
Inner Layer
Penetrate Penetrate
Penetrate Penetrate
Penetrate
Penetrate
Outer layer