Professional Documents
Culture Documents
Test Pack Review
Test Pack Review
SIS to be signed
CS flange showing as blind flange at test limit in Inconel line, to be corrected and same material flange
shall be used.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
2. 0130-385-8M-OS-010
SIS to be signed
CS flange showing as blind flange at test limit in Inconel line, to be corrected and same material flange
shall be used.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
3. 0130-385-8M-P-005
SIS to be signed
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
4. 0130-385-8M-P-006
SIS to be signed
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
5. 0130-385-8M-RL-004
SIS to be signed
CS flange showing as blind flange at test limit in Inconel line, to be corrected and same material flange
shall be used.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
6. 0143-385-8M-P-001
SIS to be signed
CS flange showing as blind flange at test limit in Inconel line, to be corrected and same material flange
shall be used.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
7. 0146-385-8M-P-001
SIS to be signed
CS flange showing as blind flange at test limit in Inconel line, to be corrected and same material flange
shall be used.
8. 0148-385-8M-P-001
SIS to be signed
CS flange showing as blind flange at test limit in Inconel line, to be corrected and same material flange
shall be used.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
9. 300-385-8M-OS-001
CS flange showing as blind flange at test limit in Inconel line, to be corrected and same material flange
shall be used.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
10. 410-385-80-SR-001B
The given filling point not comply the SAES-A-004, para 9.1.1 requirement. The test fluid shall be
injected at the lowest point in the system to minimize entrapped air.
Line designation table to be attached
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
11. 410-385-80-SR-001C
The given filling point not comply the SAES-A-004, para 9.1.1 requirement. The test fluid shall be
injected at the lowest point in the system to minimize entrapped air.
Line designation table to be attached
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
12. 2020-385-8M-RL-003
SIS to be signed
CS flange showing as blind flange at test limit in Inconel line, to be corrected and same material flange
shall be used.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
13. 300-385-8M-OS-002
SIS to be signed
CS flange showing as blind flange at test limit in Inconel line, to be corrected and same material flange
shall be used.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
14. 130-385-8M-P-008
SIS to be signed
CS flange showing as blind flange at test limit in Inconel line, to be corrected and same material flange
shall be used.
15. 130-385-8M-P-009
SIS to be signed
CS flange showing as blind flange at test limit in Inconel line, to be corrected and same material flange
shall be used.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
16. 520-385-8M-C-001
SIS to be signed
CS flange showing as blind flange at test limit in Inconel line, to be corrected and same material flange
shall be used.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
17. 2020-385-8M-RL-002
SIS to be signed
CS flange showing as blind flange at test limit in Inconel line, to be corrected and same material flange
shall be used.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
18. 410-385-8O-OWS-008
The given filling point not comply the SAES-A-004, para 9.1.1 requirement. The test fluid shall be
injected at the lowest point in the system to minimize entrapped air.
CS flange showing as blind flange at test limit in SS line, to be corrected and same material
flange shall be used.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
19. 410-385-8O-SR-001
The given filling point not comply the SAES-A-004, para 9.1.1 requirement. The test fluid shall be
injected at the lowest point in the system to minimize entrapped air.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
20. 410-385-8O-OWS-003
The given filling point not comply the SAES-A-004, para 9.1.1 requirement. The test fluid shall be
injected at the lowest point in the system to minimize entrapped air.
CS flange/NPTF Cap showing as test blind at test limit in SS Line, to be corrected and same
material flange shall be used.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
21. 410-385-8O-OWS-004
The given filling point not comply the SAES-A-004, para 9.1.1 requirement. The test fluid shall be
injected at the lowest point in the system to minimize entrapped air.
CS flange/NPTF Cap showing as test blind at test limit in SS Line, to be corrected and same
material flange shall be used.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
22. 410-385-8O-OWS-005
The given filling point not comply the SAES-A-004, para 9.1.1 requirement. The test fluid shall
be injected at the lowest point in the system to minimize entrapped air.
CS flange/NPTF Cap showing as test blind at test limit in SS Line, to be corrected and same
material flange shall be used.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
23. 410-385-8O-OWS-006
The given filling point not comply the SAES-A-004, para 9.1.1 requirement. The test fluid shall be
injected at the lowest point in the system to minimize entrapped air.
CS flange/NPTF Cap showing as test blind at test limit in SS Line, to be corrected and same
material flange shall be used.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
24. 410-385-8O-SR-001A
The given filling point not comply the SAES-A-004, para 9.1.1 requirement. The test fluid shall be
injected at the lowest point in the system to minimize entrapped air.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
25. 430-385-8O-OWS-001
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
26. 520-385-8O-C-001
SIS to be signed
CS flange showing as blind flange at test limit in SS line, to be corrected and same material
flange shall be used.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
27. 430-385-8O-OWS-003
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
28. 300-385-8O-OS-007
SIS to be signed
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
T-4420
1. 420-310-26-AS-001
The given filling point not comply the SAES-A-004, para 9.1.1 requirement. The test fluid shall
be injected at the lowest point in the system to minimize entrapped air.
CS flange/NPTF Cap showing as test blind at test limit in Nickel Alloy Line, to be corrected and
same material flange shall be used.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
2. 430-310-26-OWS-002
The given filling point not comply the SAES-A-004, para 9.1.1 requirement. The test fluid shall
be injected at the lowest point in the system to minimize entrapped air.
CS flange/NPTF Cap showing as test blind at test limit in Inconnel Line, to be corrected and
same material flange shall be used.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
3. 520-310-26-C-001
CS flange/NPTF Cap showing as test blind at test limit in SS Line, to be corrected and same
material flange shall be used.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
4. 520-310-26-C-003
CS flange/NPTF Cap showing as test blind at test limit in SS Line, to be corrected and same
material flange shall be used.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
5. 730-31026-OWS-001
Temporary blind shall be the same as line material.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
6. 410-310-26-SR-001C
The given filling point not comply the SAES-A-004, para 9.1.1 requirement. The test fluid shall
be injected at the lowest point in the system to minimize entrapped air.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
7. 410-310-26-SR-001B
The given filling point not comply the SAES-A-004, para 9.1.1 requirement. The test fluid shall
be injected at the lowest point in the system to minimize entrapped air.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
8. 410-310-26-SR-001A
The given filling point not comply the SAES-A-004, para 9.1.1 requirement. The test fluid shall
be injected at the lowest point in the system to minimize entrapped air.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
9. 410-310-26-SR-001
The given filling point not comply the SAES-A-004, para 9.1.1 requirement. The test fluid shall be
injected at the lowest point in the system to minimize entrapped air.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
10. 410-310-26-OWS-006
Temporary blind shall be the same as line material.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
11. 410-310-26-OWS-005
Temporary blind shall be the same as line material.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
12. 730-310-26-OWS-002
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
13. 730-310-26-P-001
Temporary blind shall be the same as line material.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
14. 740-310-26-SPO-002
Temporary blind shall be the same as line material.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
15. 2020-310-26-RL-001A
Temporary blind shall be the same as line material.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
16. 2020-310-26-RL-001B
Temporary blind shall be the same as line material.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
17. 2020-310-26-RL-001C
Temporary blind shall be the same as line material.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
18. 2020-310-26-RL-001D
Temporary blind shall be the same as line material.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
19. 2020-310-26-RL-002
Temporary blind shall be the same as line material.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
20. 2020-310-26-RL-004
Temporary blind shall be the same as line material.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
21. 120-385-8M-P-003
SIS to be signed
Temporary blind shall be the same as line material.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.
22. 120-385-8M-P-002
SIS to be signed
Temporary blind shall be the same as line material.
Line designation table to be attached
Approved lay-up method procedure sheet to be attached.
Verification of Testing Media for Hydrostatic Testing (Water Quality) SAIC-A-2008 not attached
Re-Instatement Inspection checklist SAIC-L-2022 not attached
Pre-Test Punch Listing check list SAIC-A-2010 to be attached.