Professional Documents
Culture Documents
HVAC Training Material PDF
HVAC Training Material PDF
HVAC Training Material PDF
PRODUCTION / DISTRIBUTION
PLANT
TRAINING PROGRAM
The purpose of this training program is to provide maintenance and project staff with
overall view and broad understanding of cooling energy production and distribution
systems of large capacity specifically located in Asian countries nonetheless
applicable to other tropical areas. It has been designed through ten years of
technical assistance experience over the Asian continent in order to offer the
primordial knowledge required for whoever involved in HVAC engineering field.
This training does not focus on calculation. It has a pragmatic and easy manner of
explanation. We however assume the trainee has all physics fundamental knowledge
and is comfortable with technical environment.
If the trainee is not so familiar with all physics fundamental and wish to learn some
basics in this field, we suggest the following books to be overlooked. These books
cover the field of production and distribution of heating and cooling energy and are
designed for technician level.
For further details of the subjects covered by this training and for very much more
comprehensive information and knowledge concerning the high level engineering
field of production, distribution of heating and cooling energy, we suggest the
following book to be read.
INTRODUCTION ..................................................................................................Page 5
PHYSIOLOGY OF COMFORT.............................................................................Page 12
TEMPERATURE VARIATIONS............................................................................Page 48
TROUBLESHOOTING .........................................................................................Page 71
MEASUREMENT .................................................................................................Page 83
Ventilating and air conditioning systems are mainly designed to create a comfortable
environment. This training is therefore limited to space indoor dry temperature to be
maintained for human comfort. Air contaminants, differential pressurization, air
motion, noise level, systems of small cooling capacity ( window unit, split unit, air
cooled package unit, etc… ) and systems for specified process are not included in
this material but can be discussed with the lecturer.
As a first step required and for a better understanding, we will present an air
conditioning installation not having any automatic control systems ( no regulation
loop ) at the beginning. Then, as the air conditioning process itself will have been
presented, control systems will be discussed.
The term air conditioning engineering is a bit inappropriate for evasive. Air
conditioning engineering itself is actually just one of the engineering fields we must
master in production and distribution of cooling energy. To be familiar with this
discipline requires knowledge of the following in sequence besides all physics
fundamental.
Each of the above mentioned subject is comprehensive engineering field having its
specialists. The ventilating and air conditioning ( called VAC which is more
appropriate a term than air conditioning ) engineer must have the overall view and
understanding of each of them and above all to understand their interacting and
connections ( see flow chart next page ).
A, B, C, D, C.
The
control
systems
and The water distribution
electrical system removes the
power
supply
E C heating load absorbed by
over the the air distribution system
whole
equipment
Each of these systems and interfaces can be compare with links of one chain
Such installation is not actual but to give an idea only. Some operating temperatures
are displayed. Their value, which must not be strictly taken but interpreted ( + / - 1 or
2deg.C ), also depend on the followings:
• This plant sample is running at its maximum capacity and load without
interference of any control systems.
• The design and operating of this plant sample are normal ones.
14°c
Cooling coil
Air supply 14 °c Air return 25°c
25°c
Ambient air 23°c
Fan
Space to be cooled
6°c 12°c
Chilled
Condenser C E water
water O Compressor V
pipe
pipe N A
system
system D P
E. Chiller O.
27°c
Chilled water
Air draft return 12°c
32°c
Cooling
tower
water fall
Cooling tower
fan 27°c
Condenser water
pump
• The cooling capacity actually removes the heating load resulting in a lower
temperature.
• If the heat transfer does not occur, the heating gain cannot be removed.
• If the cooling capacity supplied is more than the heating load, the resulting
temperature will be lower. If the heating load is more than the cooling capacity
supplied, the resulting temperature will be higher.
Cooling capacity
makes the Exchange or heat
temperature transfer between the
decrease heating gain and the Thermal gain or
cooling capacity makes heating
an average temperature load makes the
temperature
increase
The building heating load or thermal gain is the quantity of heating energy
accumulated into the building space and structure by various means during a period
of time.
Outdoor and indoor conditions, building structure and architecture, its material and
insulation, the region climate and local weather undergone by the building… all these
among others are parameters affecting the building heating gain.
Outdoor conditions:
Indoor conditions:
Because of the outdoor conditions, the heating gain is always varying within one day,
from one day to the next and this all year round. Even by night in tropical area the
building is heated up.
PHYSIOLOGY OF COMFORT
People are the one complaining about too cold or too warm indoor conditions so it is
important to know that people perceive a feeling of comfort which is not always seen
through temperature measurement.
A body gets radiation effect not measurable directly whatever the thermometer
probes used. Radiation can be measured by a special instrument. About radiation,
we usually have in mind the sun rays which radiate a huge amount of heat at a very
high rate. However, a hot surface radiates as well some heat that is perceived by
human body.
If someone is near a wall or window having a temperature higher than the ambient
one, this person’s body will feel a higher temperature than the ambient one.
Window surface
Window temperature
measured by
surface probe Wall
displays the
reading 34°c
The body undergoes both ambient temperature and window radiation effect. What
really feels this body can be determined by the following rule of thumb.
Whatever the ambient temperature, the person will always tend to complain about air
conditioning. There is no use in supplying more cooling capacity in this case.
In a room having a very bad diffusion, people’s body will tend to feel cold if there is
an air stream on their back of neck or their heels.
In general:
Outdoor
Indoor corridor
set point at 25°C
Outdoor gate
Indoor room
set point at 24°C
Distribution of thermal energy can be done by air. Air is flowed to deliver cooling
capacity and remove heating load through a supply and return network ( duct system
for air ).
There is a thermal exchange or heat transfer between the cooling capacity supplied
by air and the air heated by the building heating load. The cooling capacity actually
removes the heating load resulting in a lower temperature.
Diffuser Grille
Space to be cooled
1. There is a cool air flow entering the room through supply diffuser ( cooling
capacity supplied ).
2. Through air diffusion, there is a mixing of this supplied cool air with the ambient
air heated by the building heating gain ( heat transfer ).
3. The air flow leaves the room through the return grille ( thermal load removed ).
This potential will be effective if there is a heat transfer between the heating load and
the cooling capacity supplied.
Between the air supply ( entering the room ) and the air return ( leaving the room )
there is a difference of temperature which depends on the cooling capacity potential ,
the heating gain removed and efficiency of the heat transfer.
The difference of temperature between the air entering and leaving the room and the
air flow throughout this room is the effective total cooling capacity operating.
Flow factor:
• If the heating gain is more than the cooling capacity supplied, the indoor
temperature rises.
• If the heating gain is less than the cooling capacity supplied, the indoor
temperature drops.
• If there is no flow, there is no cooling capacity so the heating gain makes the
indoor temperature rise.
• If there is not enough flow, the cooling capacity is less so the indoor temperature
rises if the heating gain is more than the cooling capacity.
• If there is too much flow, the cooling capacity is more, so the indoor temperature
drops if the heating gain is less than the cooling capacity supplied.
• If the room entering air temperature is higher, the cooling capacity potential is
less, so the indoor temperature rises if the heating gain is more than the cooling
capacity operating.
• If the room entering air temperature is lower, the cooling capacity potential is
more, so the indoor temperature drops if the heating gain is less than the cooling
capacity operating.
• If the room leaving air temperature is the same as the room entering air
temperature, it means that there is no heat transfer or no heating gain at all in the
room.
• Both air temperatures entering the room through the diffuser and the air flow
throughout the room are the potential of cooling capacity. If there is not enough
air flow throughout the room or a high air temperature on the diffuser, this
potential is lower so could be the cooling capacity operating.
• If this potential is high enough, the thermal exchange efficiency ( between the air
cooling capacity and the heating gain of the room ) and the room heating gain
itself determine the indoor temperature and the difference of air temperatures
between leaving and entering which combined with the air flow rate is
representative of the cooling capacity operating.
Temperatures:
The indoor room temperature, the room entering air temperature, the room leaving
air temperature and the room air difference of temperature depends on:
• The air cooling capacity potential ( air flow throughout the room and the air
temperature entering the room ).
• The room heating gain ( outdoor and indoor conditions plus building civil
engineering characteristics itself ).
Air flows throughout the space to be cooled down, a return and supply duct system,
a cooling coil, a fan ( and actually other components ) and supplies the cooling
capacity required to overcome the heating gain of the space and to remove it. The
air is cooled down as it passes through the cooling coil of the air handling unit called
AHU.
Cooling
il Fan
Air duct supply ( lower temp.
)
Space to be cooled down
AHU
Several areas can be supplied by the same AHU. In that case the different areas
have ( more or less ) the same supply air temperature at their diffusers.
If only one of the areas is too hot or too cold and since the air temperature supply is
the same for all the areas, we can only adjust the potential of cooling capacity
required in this area by varying the air flow rate throughout this area.
Duct system
Air flow
supply Area one Area two Area three
and
return
14°c X°c
Fan
Cooling coil
AHU
Beware
Changing the air flow to one diffuser in order to adjust the potential of cooling
capacity in one area makes the air flows change on the other diffusers so through
each of the other areas. The cooling capacity supply therefore changes into each
area and so does the indoor and return air temperatures.
A B C
If you close the damper A, the flow will decrease on the diffuser A, the flows will
increase on the diffusers B and C. We consider at this step of the training that the air
flow through the fan will keep operating at a constant rate.
AIR DISTRIBUTION
We repeat that for a better understanding we consider the air systems of our
following demonstration not having any automatic control systems ( no regulation
loop ).
Each room has a different heating gain so needs a different cooling capacity supply.
Since the cooling coil of the air unit system supplies a common air temperature for
each room, the only way to adjust each room cooling capacity to match each room
heating gain is by adjusting each room air flow rate.
The duct system is therefore balanced through return and supply dampers to provide
each room with a correct air flow so a correct indoor air temperature is roughly
maintained in each room.
This variation can be quite acceptable and even not perceived by people working in
the area.
Duct system
Return
and
supply
dampers
25°c 14°c 25°c 14°c 25°c 14°c
Air flow
supply Room one Room two Room three
and
return
Cooling coil
14°c 25°c
Fan
The balancing of the air duct system offers the total cooling capacity of the AHU to
be divided into several areas so that each of these areas can be supplied by its own
cooling capacity required to maintain a comfortable indoor temperature.
PHYSICS OF FLUID
Here this subject is in a first time covered to give understanding of duct systems
balancing. Physics fundamental discussed in this training is very simplified. To
understand fluid physics characteristics is important. The principle of fluid is the
same for air or water ( actually different mathematically but our demonstration is to
give an idea ) we will first discussed about air physics characteristics.
Fluid physics laws have the same effect ( but not in the same proportion ) as
electrical ones so we can understand fluid network parameter variations by referring
to electrical formulas.
The voltage can be compare with the pressure drop, the current with the fluid flow
rate.
As the current passing through the resistance increases from 2A to 5A, since the
resistance has a constant value ( 10 ohms ), the voltage will increase from 20 volts to
50 volts.
Like in electricity, any component of fluid ( air or water ) network has a resistance, for
instance, a valve of a pipework or a damper of a duct connection.
Pressure ∆p
Curve of a fluid network
component having a
constant resistance
2
Flow m3/h
10 15
B
B The
resistance
decreases
Flow m3/h
A generator supplies electrical power ( voltage and current ). A fan or pump supplies
aerodynamic or hydraulic power ( difference of pressure and water flow ).
Each fan and each pump has a performance curve given by the manufacturer on
which is crossed the network curve displaying the flow rate throughout the network
and the pressure drop overcome by the fan or the pump. The fan or pump curve is
representative of the available power.
Note: The difference of pressure given on the manufacturer chart is a total pressure.
We do not in this training discuss the subject of static, dynamic and total pressures.
20 Mm.w
Flow m3/h
10 m3/h
The available fan power is displayed by both fan and air duct resistance curves.
According to the fan curve performance, as the air duct resistance increases, so as
the difference of pressure of the fan ( called also pressure drop ) increases, the air
flow rate decreases.
Balancing is required to match the cooling capacity to each room heating gain. The
air flow rate conveys a quantity of energy so each room must have a proper air flow
rate to overcome its heating gain.
Ar Return dampers Br Cr
As Supply dampers Bs Cs
Fan Cooling
coil
• By closing anyone of the dampers Ar, Br, Cr, As, Bs or Cs, the resistance of the
whole duct system increases so the fan flow rate decreases.
• By opening anyone of the dampers Ar, Br, Cr, As, Bs or Cs, the resistance of the
whole duct system decreases so the fan flow rate increases.
• By closing one of the dampers Ar, Br, Cr, As, Bs or Cs, the air flow decreases
through its duct connection whereas the air flow increases through the other duct
connections meanwhile the total air flow through the fan actually decreases.
We remember the effect of any flow variation on the cooling capacity. A lower flow
rate means a lower potential of cooling capacity. A higher flow means a higher
potential of cooling capacity. By changing the damper position of one duct
connection, it affects air flow throughout the whole duct system and each of its
connections hence affecting each respective cooling capacity.
Ar As Br Bs Cr Cs
Air flow
supply
and
return
For example:
The room one is too cold, the cooling capacity is therefore more than the room
heating gain. To rise the indoor temperature, we can decrease the cooling capacity
supply by closing the dampers.
• The air flow rate decreases through the room one ( this is what we want ).
• The air flow rate through the rooms two and three will increase ( this is what we
do not want ) and so will do the cooling capacity.
Changing the air flow on one diffuser to adjust the cooling capacity required in one
room makes the cooling capacity supply change into the other rooms. The fan air
flow changes and the fan motor operating condition changes as well.
For instance, by varying the resistance of the air duct system, so by varying the
pressure drop and the air flow of the fan, the resistance curve can be at the limits of
the fan normal running condition.
Pressure ∆p Mm.w
Flow m3/h
If the network curve intersects the fan curve in the zone A, the fan has not enough
flow and too much pressure drop, the inlet current will tend to decrease, the power
factor will be very low and the electrical coils of the motor will overheat due to both
magnetic effect and not enough air flow rate which is also used to cool down the
motor.
This is the worst case that can occur and the only proper protection is a thermal
switch ( if any, since inserted in the motor by the manufacturer ) correctly connected
and tested during testing and commissioning.
Without this protection, the electrical coil will overheat till the motor electrical coil
resins melt to finally short-circuit the motor.
If the network curve intersects the fan curve in the zone B, the fan has too much flow
and less pressure drop, the inlet current will tend to increase, the motor will overload.
As for this case, motors are usually protected with overload relay. It is important to
check the motor protection system and its fan running performance before carrying
out any modification and balancing on the air duct system.
FAN TECHNOLOGY
The above mentioned effects will be different according to the fan technology. It is
enough to remember the two kinds of centrifugal fans we usually come across. The
backward and the forward curved impeller.
Backward blades:
This fan has a few but large blades. We come across such fan for AHU or any
ventilation system with high pressure drop to overcome. Its fan curve performance is
a “curved” one which means that the air flow rate does not vary so much with the
pressure drop. For this kind of fan, the motor running amperes does not obviously
decrease with an air flow rate decreasing.
Pressure ∆p Mm.w
Flow m3/h
In general, this type of fan is the most efficient and most stable.
This fan has many but small blades. We come across such fan for FCU or any
ventilation with little pressure drop. Its fan curve performance is a “flat” one which
means that the air flow rate does vary a lot with the pressure drop. For this kind of
fan, the motor running amperes decrease with an air flow rate decreasing.
Pressure ∆p Mm.w
Flow m3/h
During this training we do not discussed about the following which is however very
usefull to know:
The air duct system and ventilation running condition has a bit been overlooked
because except for specified application the above explained is enough for the
purpose of this training program. We consider that air duct balancing may be
required to achieve more comfortable indoor conditions only. Energy saving can be
more easily achieved by rebalancing a chilled water pipe system since the water
specific heat ( 4.18 Kj / Kg / Deg. ) is four times more than the air one ( 1 Kj / Kg /
Deg. ). Therefore the very difficult task of balancing a network for the purpose of
achieving better comfort and energy saving is worth being carried out more on chilled
water pipe system than on air duct system.
We remember the thermal relation between air system and the room to be cooled
down. A room is a “heat transfer system” between the air distribution cooling capacity
potential and the room heating gain.
1. Cooling capacity potential of air entering the room ( or potential of any fluid
entering a heat transfer system ).
2. Heat transfer between the room heating gain and the air cooling capacity
potential.
3. The removed heating gain leaving the room ( thermal load leaving a heat transfer
system ).
Cooling
il Fan
Air duct supply ( lower temp.
)
Space to be cooled down
AHU
The air thermal load coming from the room heating gain is conveyed throughout the
duct system and afterwards removed by the cooling coil.
There is exchange from the cooling capacity supplied by the water flowing inside the
tubes of the cooling coil to the air passing through this cooling coil. The heat transfer
through the tube wall cools down the air passing through and warms up the water
leaving the cooling coil.
Cooling coil
The possible variation of each of these parameters ( air flow, inlet and outlet air
temperature, water flow, entering and leaving water temperature ) is a bit
complicated to master.
1. The potential of cooling capacity of the heat transfer system which is the air /
water thermal exchanger named cooling coil is both the chilled water flow rate
throughout the inside cooling coil tubes and the cooling coil entering chilled water
temperature.
2. The heating gain of the cooling coil is both the inlet air temperature and the air
flow rate through the cooling coil.
3. The heat transfer operating depends on the cooling coil thermal exchange
efficiency between air and water.
4. Whatever the heat transfer efficiency, the air distribution system heating gain (
which is the difference of temperatures between the coil air inlet and the coil air
outlet by the air flow rate through the coil ) matches the water distribution cooling
capacity ( which is the difference of temperatures between the water entering the
coil and the water leaving the coil by the chilled water flow rate throughout the
coil ).
Air factor:
• For a constant cooling coil capacity potential ( correct chilled water flow rate and
chilled water entering temperature ), if the air flow rate decreases or the inlet air
temperature is lower, the air thermal load or cooling coil heating gain decreases
so does the cooling coil chilled water leaving temperature.
• For a constant air flow and inlet air temperature of the cooling coil, if its cooling
capacity potential is lower ( lower chilled water flow rate or higher chilled water
entering temperature ) or if the cooling coil heat transfer efficiency decreases, the
cooling coil outlet air temperature increases and the cooling capacity potential of
the air system delivering the space to be cooled down decreases.
Remember:
So it must be noted that if the medium flow rate decreases at a fixed time during
which the cooling capacity is constant, the first an immediate effect will be a
difference of temperature increasing but the final cooling capacity will be less since a
medium flow rate decreasing makes the cooling capacity decrease.
Note:
Temperature measurement is practically the only way to diagnose the good running
condition of the installation, it is therefore very important to understand the
temperature variations with the many parameters involved.
The water thermal load coming from the cooling coil heating gain ( which comes from
the air system and which comes from the building ) is conveyed throughout the
chilled water pipe system and afterwards removed by the chiller. The water is cooled
down as it passes through the chiller evaporator.
The chilled water flow passes throughout the cooling coil, the pipework, the pump
and the chiller evaporator ( and other components ).
The water flow supplies the cooling capacity to the AHU cooling coils and returns the
heating load to the chiller.
Chiller
evaporator Cooling
coil of AHU
Since there are many AHUs in the building, each supplying a different cooling
capacity to the building areas, the chilled water pipe system has many AHU cooling
coils to supply. Each cooling coil requires a different cooling capacity.
The only way to adjust each AHU cooling coil capacity is by adjusting each AHU
cooling coil chilled water flow rate since the chilled water temperature supply is the
same for all the AHUs.
The chilled water pipe system flow rate is provided by the pump. The chilled water
pipe system supply temperature is provided by the chiller.
AHU
cooling
coils
PHYSICS OF LIQUID
The principle of fluid has already been seen above. We know that hydraulic physics
laws have the same effect ( but not in the same proportion ) as electrical ones and
so we can understand hydraulic network parameter variation tendencies by referring
to electrical formulas.
The voltage can be compare with the pressure drop, the current with the water flow
rate. If a current pass through a resistance, there is a voltage.
As the current passing through the resistance increases from 2A to 5A, since the
resistance has a constant value (10 ohm), the voltage will increase from 20 volts to
50 volts. So for a constant resistance, the voltage varies with a current increasing or
decreasing. Like in electricity, any component of hydraulic network like a valve has a
resistance. As the valve is in a constant position, the resistance of the valve is
constant. if the water flow increases, the pressure drop or difference of pressure
between the valve inlet and outlet will increase.
Pressure ∆p Bar
Curve of a hydraulic
component having a
constant resistance
2.25 Bar
1 Bar
Flow m3/h
10m3/ 15m3/
h h
Any hydraulic network has a resistance, the pipe line itself has a resistance plus
every component connected throughout the network. So a resistance curve can be
the equivalent resistance of all the hydraulic components installed.
B
B The
resistance
decreases
Flow m3/h
• A pump ( like a generator ) does not supply a constant hydraulic power, this
hydraulic power varies according to running condition.
Each pump has a performance curve given by the manufacturer on which is crossed
the hydraulic network curve displaying the water flow rate throughout the network
and the pressure drop overcome by the pump. The pump curve is representative of
the hydraulic power.
By reading the pressure drop at the gauges connected at the inlet and outlet of the
pump, we can know what is the flow, provided that we have the pump performance
curve given by the manufacturer.
2 Bars
Flow m3/h
10 m3/h
The available pump power ( headpump running ) is displayed by both pump and
hydraulic resistance curves. According to the pump curve performance, as the
hydraulic resistance increases, so as the difference of pressure of the pump ( called
also pressure drop ) increases, the water flow rate decreases.
Inlet pressure gauge 0.5 bar Outlet pressure gauge 2.5 bar
Since the chilled water pipe system can be considered as the core of the cooling
distribution whole system and is of such importance in term of energy saving and
chiller running good condition so life span, more understanding to physics of liquid is
required.
F3/RX
A B F2/RY F1/RZ
F3/RX
One pressure drop represented by A, which is the common pipe F3 / RX in serie with
the connection F1 / RZ. Another one pressure drop represented by B, which is the
common pipe F3 / RX in serie with the connection F2 / RY.
F3 is the total flow in the main pipe divided into the connections F2 and F1 that have
their respective flow. The flow 3 = flow 2 + flow 1
Whatever the resistance of each connection, the ∆P of the pump is the same for
each connection in parallel. So if the resistance varies in one connection, the ∆P
varies through all the other connections in parallel and so do all the connection flow
rates, since they have their resistance remaining constant, till reaching a common ∆P
for every connection.
Like the duct system, if you decrease the flow of one hydraulic connection by
increasing the resistance of this connection, this will make the water flow rates
increase through the other connections in parallel and the water flow rate decreases
through the pump itself.
The water thermal load coming from each cooling coil heating gain is conveyed
throughout the chilled water pipe system and afterwards removed by the chiller. The
water is cooled down as it passes through the chiller evaporator. The water flow
supplies the cooling capacity to the AHU cooling coils and returns the heating load to
the chiller.
Each chilled water pipe connection supplies a specified cooling capacity through its
own chilled water flow rate which is adjusted during the testing and commissioning of
the project.
All these adjustments required for each AHU cooling coil chilled water flow rate is
called balancing of the chilled water pipe system. For each adjustment carried out at
a time, which means for each variation of flow in one connection due to the
adjustment, the chilled water flow rate of all the other connections varies and so does
the chilled water flow rate through the pump.
Pressure ∆p Bar
Flow m3/h
If the network curve intersects the pump curve in the zone A, the pump has not
enough flow and too much pressure drop, the inlet current will tend to decrease, the
power factor will be very low and the electrical coils of the motor will overheat due to
magnetic effect.
In that case, the only proper protection is a thermal switch ( if any, since inserted in
the motor by the manufacturer ) correctly connected and tested during testing and
commissioning.
Without this protection, the electrical coil will overheat till the motor electrical coil
resins melt to finally short-circuit the motor.
If the network curve intersects the pump curve in the zone B, the pump has too much
flow and less pressure drop, the inlet current will tend to increase, the motor will
overload.
As for this case, motors are usually protected with overload relay. It is important to
check the motor protection system and its pump running performance before
carrying out any modification and balancing on the chilled water pipe system.
In large buildings, the plant of condenser and chilled water pipe systems can be
complicated because some pumps are associated in series or in parallel.
Since we know the flow variation interactings and effects on capacities and
temperatures, the number of pumps running and the chilled water pipe system
design is important to be mastered.
The flow of the two pumps add themselves and the pressure drop tend to match.
Network curve
Pressure ∆p Bar
Resulting pump
curve of two pumps
mounted in parallel
Flow m3/h
Beware:
To switch on two pumps mounted in parallel does not mean that the water flow will
increase two fold afterwards. Actually to switch over one to two pumps in paralell
makes the total flow rate increase of 30% to 60% around. Not more.
The flows tend to match and the pressure drops add themselves. ( Pumps in series
are seldom installed unless for retrofitting ).
Resulting pump
curve of two pumps
mounted in series
Pressure ∆p Bar
Network curve
Flow m3/h
Association of pumps can be both in serie and in parallel that is the case for primary
and secondary pumps installed at some chilled water pipe system. This particular
design will subsequently be studied in the next chapter.
As for operating of pump associated in parallel ( which is the most usual application
come across ), to change over two pumps running in parallel to one pump can make
this one works out of these limits and trip.
1
1
2
2
1 2
The pump operating effect on the pump motor running amperes. The effects on the
temperatures is herewith studied.
Reading taken as chiller one and its pump are running with the chiller one gate valve
opened and the chiller two gate valve closed. The chilled water pipe system is
running under the following conditions:
The network curve B, the pump curve D, the pressure drop F, the water flow H.
Reading taken as two chillers and their pumps are running with the two chiller gate
valves opened. Now the chilled water pipe system is running under the following
conditions:
The network curve A, the association of the two pumps curve C, the pressure
difference E, the water flow I at the common header, the water flow G through each
pump and each chiller.
B
∆P A
F
D C
m3/h
G H I
The network curve resistance has decreased since there are connections in parallel (
from B to A ).
The pressure difference read at the pump one has increased ( form F to E ). The
pressure difference is the same for each of the two pumps ( E ).
The water flow in the chiller has decreased ( from H to G ). The total water flow ( I )
is divided into the two chillers.
The water flow at the common header has increased ( from H to I ). This water flow
supplies to and returns from the AHUs.
Each chilled water pipe system is different therefore sketches should be done on site
before studying the system. Do never trust schematics and check by yourself.
You may come across many different designed chilled water pipe systems, you must
be able to understand each of them. A chilled water pipe system can have primary
and secondary pumps associated both in parallel and in series.
The project schematics and other drawings are presented in a way that must be
simplified for a better understanding and interpretation of the pipework operating.
Chiller two
Bypass pipe
Secondary
pumps
Depending on each pump hydraulic power or how many pumps running in the
secondary and primary network, the direction of the flow through the bypass pipe
changes.
If the secondary network hydraulic pump power is higher than the primary one, the
direction of the bypass flow will be as indicated B. In this case, the secondary
network water supply temperature will be a mixing of the chiller leaving temperature
with the secondary network return water temperature. So the AHU supply
temperature will be higher than the chiller leaving temperature.
If the primary network hydraulic pump power is more important than the secondary
one, the direction of the bypass flow will be as indicated A. In this case, the chiller
entering temperature will be a mixing of the chiller leaving temperature with the
secondary network return water temperature. So the chiller entering temperature will
be lower and the chiller water temperature difference will decrease.
Readings can be taken while the system is running under different conditions so that
you can know the temperature variations. With this temperature readings, the flow
direction of the bypass pipe and the flow variation through the chiller(s) can be
understood.
Big variation of flow is mainly seen through pump motor running amperes. Variation
of the thermal load or cooling capacity and variation of water flow are practically seen
through temperature measurements.
In the building, each room maximum heating gain is actually calculated at the design
stage of the project and the air conditioning installation is sized according to this
design calculation.
Cooling
coil
( Specific heat: Water 4.18 kj/kg/°c Air 1 kj/kg/°c ) Fan
( Air temperature difference taken around 10°c )
( Water temperature difference 5°c )
Each room has a different maximum heating gain. The balancing is done for the
cooling capacity to match this maximum heating gain.
For each room, this heating gain is not permanently maximum and is actually varying
within one day and from one day to the next. Sunny or cloudy weather, day or night
period, building indoor activity, installation just started up or running for a while, all
these make important difference of thermal variation.
Heating gain in rooms and areas in the building loads the whole air conditioning
installation ( air systems, water systems, chillers and cooling towers ) so the whole
installation has thermal loads always varying.
TEMPERATURE VARIATIONS
In sequence:
and so on...
What must be noticed is that for a constant flow rate as the entering temperature of
a heat transfer system drops, the leaving temperature of this system drops but the
difference of temperature between leaving and entering also decreases at a different
rate that finally decreases the cooling capacity.
1. For a constant flow, if the thermal load varies then the temperatures vary.
2. For a constant thermal load, if the flow rate varies then the temperatures vary.
The cooling capacity will also vary in both cases. This variation will however be more
important through temperature change than through flow rate change.
It must not be neglected that the cooling capacity supplied by the systems can more
or less naturally adjust itself to the varying heating load. However, if we relied only on
this fact, this auto control would be done through a lower thermal exchange
efficiency of the interfaces and in counterpart of the equipment operating condition
so life span. Temperatures will not be maintained anyway.
Whatever equipment and systems; air, water or other fluid like refrigerant for the
chillers, the cooling capacity must be more or less adjusted to match the thermal
load. Since the potential of cooling capacity depends on the entering temperature of
the system and the flow rate of this system, one way to match the cooling capacity to
the heating gain is by varying either entering temperature or flow rate of the system.
There are many ways to do it.
Control systems have function to adjust the cooling capacity to the heating gain by
varying either entering temperature or flow rate of one heat transfer system through
a regulation loop. When many heat transfer systems are interconnected through a
common system or plant ( air ducting, chilled water pipe system ), variation of one of
these systems due to regulation loop operating must not affect the other systems
connected.
Control systems have to maintain the whole plant having many heat transfer systems
interconnected operate under stable conditions and deliver the cooling capacity
required. It must be noticed that any control system regulation loop is always a
compromise between accuracy of the variable and stability of its process operating.
Regulation loop:
We will not discussed about proportional plus integral, proportional plus derivative,
proportional plus integral plus derivative, floating control, time proportioning control
systems and installation parameter time lags during this training. We will focus on
proportional and two positions on / off systems only demonstrated with simple
applications.
Proportional control:
A proportional controller has a linear relationship between the value of the incoming
sensor signal and the controller output. This parameter is adjustable and called
proportional band. This proportional band is a range within the output signal varies
from its minimum to its maximum value.
The input is the measurement of the variable which must be representative of the
heating gain to be overcome in case of temperature control, the output must be
representative of the cooling capacity to be supplied.
Depend on the proportional band adjustment, the output can cover less than this
difference ( not enough cooling capacity supply for the thermal load ), which means
that we cannot reach back the set point, or the output can cover more than this
difference ( too much cooling capacity for the thermal load ) and therefore reach
back and go beyond the initial set point.
There is therefore a very important relation between the control system parameters
and the plant design and operating parameters. The plant design and equipment
installed must be compatible with the control system and vice versa.
Water tap
water make up system
Water
Water supply level
system to be
maintained
Floating
Water ball
The water level in the tank is what we want Temperature to be maintained in a room.
to maintain.
The water filling the tank is the supply The cooling capacity supply.
The water make up system ( tap water and The regulation loop or control system.
floating ball system ).
Whatever the water make up system adjustment ( whatever the regulation loop
proportional band adjustment ), the water supply system capacity must be limited
and adjusted to match the water flowing out rate or water lost ( if air or water system,
balancing must be done to match the maximum heating gain and not to be more ).
The air conditioning installation process and its cooling capacity potential is therefore
very important and we can now understand the function of balancing. The potential
must be limited and the regulation loop will be working below this limit.
The stroke of the floating ball over the stroke of the water tap is representative of the
regulation loop proportional band adjustment. According to this adjustment, the
whole system ( process itself and the regulation loop ) will respond very differently.
Figure A: The stroke of the floating ball is longer than the stroke of the tap. It means
that for a big difference of water level, the tap will open a bit.
Floating
water tap ball
Water
Water supply level
system to be
maintained
Water
The proportional band is a large one. For a big difference, the output is small.
Floating
water tap ball
Water
Water supply level
system to be
maintained
Water
The proportional band is a short one. For a small difference, the output is big.
The tank water make up system can be compare with a room which indoor
temperature is maintained by a regulation loop controlling an air conditioning system
whatever technology installed ( Split unit, Window unit, AHU VAV box, FCU... ).
If the potential of cooling capacity is too much, we can limit it by balancing or if not
possible by adjusting a large proportional band. In this case the indoor temperature
will be fluctuating within the range of this large proportional.
P. B. of 1°C
100%
0%
The output is not from a minimum to a maximum but minimum or maximum. For this
technology, the proportional band is called differential. One typical application is the
thermostat.
This on / off control system is applicable to equipment whom process has a potential
of cooling capacity that is minimum or maximum. As the demand due to the thermal
load is half the cooling capacity available, the differential or set point adjustment will
make the output “on” therefore overpassing the set point or “off’ therefore not
reaching the set point.
Unless the cooling capacity supply does permanently match the thermal load, this
system is inaccurate and unstable. It is commonly come across however and can be
perfectly suitable for some applications.
Each room in the building has a different thermal load so needs a different cooling
capacity supply limited by balancing and then permanently adjusted by controlling.
The control and air conditioning systems must through their operating match the
cooling capacity to the heating load. There are many ways to do it. Room by room,
average of many rooms, by areas... with different systems, split unit, window unit, air
handling unit with or without variable air volume system, fan coil unit...
Room by room:
The capacity of a cooling coil supplying a room can be modulated by controlling the
chilled water flow rate through it. The sensor measures air temperature and the
controller output adjusts the water flow through a regulating valve. The sensor
location depends on the application of the system.
Chilled Cooling
water pipe coil
system
B
C
Space to be cooled
down
A Sensor
B Controller
C Three way valve ( in this case )
The above sketch is practically what we usually come across in the area ( except
that for the regulating three way valves that are not often installed and there is
seldom duct system connected at the return ).
The thermostat is the control system regulation loop which has both sensor and set
point device in the same apparatus fixed on the wall. It outputs a signal to the
regulating valve and can also output a manual or automatic control of the fan having
one or several speeds.
BV
GV
FCU F RV GV
AR
AS
Thermostat
Space to be cooled down
Since the cooling coil of the air unit system supplies a common air temperature for
each room, the only way to adjust each room cooling capacity to match each room
heating gain is by adjusting each room air flow rate.
23°c 23°c
Air flow
supply Area one Area two
and
return
R
Cooling coil
Variable speed system
Fan
Air filter
R 12°c
Three way
regulating Balancing valve
valve
This system supplies a cooling capacity to each room through air flow variation.
When this flow variation is required at one duct connection, this must not change the
air flow rate through the other rooms. This providing the control and the air duct
systems are correctly designed, installed, tested, adjusted and balanced.
The duct system has been balanced through return and supply dampers to provide
each room with a maximum air flow. Balancing provides therefore the system with a
limited cooling capacity below which the regulation loop will work adjusting the
cooling capacity to the heating gain.
We remember the fluid network characteristics, if the flow rate decreases through a
connection this will disbalance the other flow rate connections. The air flow control
system must therefore offer variation of air flow rate where the cooling capacity is
varying but no variation at all where it is not required. For the VAV AHU, there is an
air pressure regulation loop at the air supply duct system to meet this function.
The supply air pressure at the AHU fan outlet is controlled by a regulation loop that
adjusts the fan speed ( therefore affecting the pressure drop ) in order to deliver the
air flow required in the whole duct system.
By controlling and maintaining the air static pressure in the supply duct system the
required air flow is supplied whatever the terminal damper position of the VAV boxes
and the duct system connections are kept balanced.
Practically the regulation loop pressure sensor controlling the fan speed does not
measure the difference of pressure of the fan but the fan outlet static pressure.
There are many little but important details to be mastered about sensor location and
real measurement of control systems. We repeat again that the training is to give
you an idea and broad understanding since each of the subjects covered is a
comprehensive engineering field that could required months of training.
Pressure ∆p Mm. W.
I
A
G
C
D
Flow m3/h
F J E
1. The duct system has a resistance curve A running at full load which means that
the air flow E is maximum for the design. All the VAV box dampers are fully
opened. The fan is running at full speed on the curve C. The pressure drop is G.
2. As one of the VAV box dampers closes itself ( which means that less cooling
capacity is required in one room since the indoor temperature regulation loop
outputs to decrease its air flow rate ), the duct system resistance increases to B,
the difference of pressure increases to I and the air flow rate decreases to J
through the fan but increases at the connection where the VAV box dampers
have remained at the same position.
3. The regulation loop controlling the fan speed measures the pressure rise at the
fan outlet and decreases the fan speed till reaching the set point representative
of the difference of pressure to be maintained G. The fan air flow rate decreases
to F.
4. From E to F, the air flow rate has decreased and the pressure drop has been
maintained. The air flow rate has been decreased on the VAV box damper which
closed itself due to less demand in its room and since less flow rate though the
fan, the others VAV boxes did not get more air flow rate.
If the fan speed regulation loop is wrongly adjusted, all the VAV box air flow rates will
be affected as just one VAV box has its air flow rate changed by its indoor
temperature regulation loop.
The VAV AHU system requires a flexible control system so that the testing and
commissioning engineer can do the adjustment easily. By the way, it must be noticed
that the BAS offers easy access to each regulation loop parameter. BAS is therefore
a useful tool for the project or maintenance helping ensure it was properly designed,
installed and commissioned.
Room average.
The regulation loop controls the average temperature of each room therefore each
room has a different ambient temperature due to the heating gain that is different for
each room.
The regulation loop has the same function and effect for every area. It measures the
average temperature of the different spaces to be cooled down
Duct system
Air flow
supply Area one Area two Area three
and
return
Cooling coil
R
Fan
Air filter
12°c
Three way
regulating Balancing valve
valve
6°c
For this kind of installation ( called Constant Air Volume system ), the return duct
system should have a return fan with an exhaust duct system. Often this kind of
installation has even not return duct system and there is no duct dampers for
balancing but diffuser dampers only.
This air conditioning design and system can be acceptable if the areas are in
communication through doors maintained opened or if the heating gain is not so
different from one area to the next.
It must be noticed that if many AHUs are installed in the same manner at the same
storey of a building, the air return can be the mixing of other AHU air returns so the
heating gain of one AHU controlled by its regulation loop may not be the real one.
In term of capacity, the difference between air and water distribution system is in the
specific heat. Air one is of 1 Kj / Kg / Deg.C. whereas water one is of 4.18 Kj / Kg /
Deg.C. so the variation of chilled water flow rate involves very much more cooling
capacity variation.
Moreover, every chiller running must have a constant flow rate especially for the one
which control system is at the outlet of the chiller. For a centrifugal chiller ( for
instance ), any variation of flow will input the chiller regulation loop a temperature
change that will be followed by outputting a load variation. Stability of chilled water
flow rate determine the life span of the chiller.
Water flow control system and stability of the chilled water flow rate:
Pump
Valve
The pipework resistance varies with the valve position. From 100% opened the valve
can be closed to 50%.
B
B Valve
100 % opened
Flow m3/h
The two way valve system does not maintain a constant flow rate through the pump
with the valve position varying.
Part A
Part B
PartC
Whatever the three way valve position, the flow will be constant in the part A of the
network providing the resistance is the same in the part B and C.
B/A
B Valve
100 % opened
Flow m3/h
Actually, the flow rate will have a slight variation especially as the valve is 50 %
opened.
At this position, the part B and C of the network are in parallel, so their resistance are
in parallel, so the equivalent resistance of the whole network decreases. The rate of
this variation occuring as the three way valve is reaching its 50% position depends
on the resistance of the network variable flow part B and C in comparison with the
resistance of the network stable flow part A. The more important the resistance of
the former, the more variation.
As a rule of thumb, the resistance of the network variable flow part must be at least
four times less than the resistance of the network stable flow part.
Since a chilled water pipe system supplies many AHU cooling coils that have their
own regulation loop so their own chilled water flow rate variation; the problem is that
some parts of the chilled water pipe system must have from time to time variable
flow rate and this without affecting the flow rate of some other parts, meanwhile the
chiller must have a constant flow rate maintained. We know cooling capacity is a flow
by a difference of temperatures and if any flow change, the temperatures vary as
well. It is therefore very important that the chilled water pipe system offers through its
design and installation a chilled water flow rate stable as much as possible through
the chiller whatever variation of flow through the AHU cooling coils.
C
H
I
L
L
E
R
To install a chilled water pipe system with three way valves is more expensive than
installing one with two way valves with regulating bypass valve.
Chilled water pipe system mounted with two way valves and regulating bypass valve:
C
H
I
L
L
E
R
Regulating
Bypass
valve
This system is acceptable for very large building where diversity factor has influence
however this system is almost impossible to be correctly balanced without BAS.
The regulation loop sensor measures the differential pressure of the pump head.
The controller outputs a signal to position the regulating bypass valve thus
maintaining a constant chilled water flow rate though the chiller and the pump.
Regulating
bypass valve
∆P
Controller
As the two way valves of the AHU are closed by their own regulation loop, the chilled
water pipe system total resistance increases and so does the differential pressure (
or pressure drop ) that is immediately measured by the regulating bypass valve
regulation loop and makes the regulating bypass valve open till the original
differential pressure is reached back.
Flow m3/h
Whatever the two way valve positions, The flow rate will be always constant through
the pump and the chiller. It will also supply the cooling capacity required in each AHU
connection.
For any change of the chilled water flow rate, the regulation loop of the chiller, having
at this time its cooling capacity on, will input a chilled water temperature changing
because of the flow variation, it will then unload or load its capacity. This especially
for the chiller regulation loop controlling the leaving temperature of the chiller.
A constant flow rate must be maintained through the chiller. The chiller
manufacturers allow a flow rate variation of 10%.
The chilled water pipe system must be properly balanced whatever two or three way
valve system. This is done by adjusting the balancing valves during the testing and
commissioning of the project. Regulating valves do not have this function. Regulating
valves and balancing valves must be both installed on the chilled water pipe system.
Regulating valves are different with balancing valves. They have different technology
and function.
TROUBLESHOOTING
By overcooling some areas so wasting energy, some air conditioning equipment and
system problems may be hidden. As the energy saving program is implemented,
these problems can suddenly appear and troubleshooting be required. In this case,
the cause of the problem is not the energy saving program but a specified problem
which has to be identified and overcome.
The following is a procedure that will help you to identify and overcome any minor
trouble about which people complaint however. Too hot or too cold are the common
complaint. Solution is at 90% solved through a proper servicing. However, there is
10% left in which very much more important problems can be.
These problems can be beyond the person in charge knowledge. In this case, the
correct procedure and approach required will make the maintenance team save time
and money.
When you attend to a complaint in a area, you must first have a view and idea of all
the following things in a wink - outdoor condition - indoor condition and activity -
people complaining - Then, check the air conditioning system itself. Some
complaints may not be due to the air conditioning system itself.
air supply temperature < air ambient temperature < air return temperature
• Be sure that the air flow is correct throughout the room or area.
• Check if there are supply and return grilles in the same room or area.
• Even if the flow is correct, be sure that the diffusion in the room is good enough
to make an efficient exchange.
Beware:
If you think the air flow supply is too low, do not open the diffuser dampers without
being sure that this is the only reason there is not enough flow.
The dampers were adjusted during the commissioning, they may have been closed
since then inadvertently during the routine servicing. Anyway, be aware of changing
the damper position will affect the whole duct system by causing unbalanced effect.
Changing the air flow on each diffuser makes the cooling capacity supplied change
into each room.
If the air flow and diffusion are correct throughout the room, if the air supply
temperature is constant, the air return temperature will vary with the heating gain, the
more the heating gain, the higher the air return temperature, the higher the
difference of temperature.
If there is no heating gain, there will be no difference of temperature since the air
supply temperature will match the air return temperature.
However, if the air return temperature tends to match air supply temperature while a
heating gain occurs, it means that there is a by-pass effect between air supply and
air return due to a bad diffusion.
Do not forget
So we must have both correct flow and difference of temperatures throughout the air
supply diffusers and air return grilles of the room.
On the air diffuser, if supply air temperature is too high, it may be due to not enough
air flow.
Since there could be a regulation loop that may control the air flow rate or the air
supply temperature, it may be normal that there is not so much air flow rate or a high
air supply temperature. However, if the heating load seems to be maximum in the
space and if the regulation loop properly works, both air flow and air supply
temperature should be as expected.
SUMMARIZE OF PROCEDURE
If there is not enough air flow on the diffuser, do not open the damper diffuser, check
the duct and AHU systems which will be explained at the next chapter.
If the temperature is too high on the diffuser, check the duct and AHU systems.
On air diffuser, if there is any problem of flow or temperature, check the duct system
into the ceiling.
Be sure that the supply and return flows are connected to the same unit supplying
the same area.
Be sure that the diffusers are really connected to the AHU duct system concerned.
The duct system connection may be wrong. The duct system can have some
leakage.
Insulation of the air supply duct system may be depreciated. An extra heating gain
can occur in the ceiling and so raises the supply air temperature through the duct
system wall by heat transfer.
If the duct system is correct, the AHU outlet air temperature must match the air
temperatures on the diffusers ( 1°C of difference is acceptable, depends on the duct
length for no insulation is perfect ).
So for either/both temperature or/and air flow problems on diffusers or return grilles
and if the duct system is correct, check the AHU.
Like on diffusers, be aware that dampers are installed to be adjusted during testing
and commissioning, so avoid touching them unless you are sure they have been
adjusted to the wrong position.
In general, check everything that could increase the resistance of the air passing
though the AHU.
If any electrical modifications were previously done in the control panel, be sure that
the fan direction of rotation is correct, be sure the motor starter system is correct, for
instance, with a delta star system, be sure that the delta stage was reached.
For an air flow too low at the fan air outlet, the air temperature can be correct.
If the air flow is correct but the fan outlet air temperature too high.
Check the entering temperature of the system ( for most AHUs , it is a mixing of
return and fresh air ).
The AHU air inlet temperature may be too high for the designed cooling coil capacity.
So the AHU, even running at its full capacity, cannot maintain a correct air outlet
temperature. ( For an AHU having only a cooling coil, the leaving temperature is
measured at the fan air outlet, the entering temperature is measured before the
cooling coil ).
Check why there is an extra heating gain, it can come from the air return system (
especially if this is one has no duct system ) or it can come from too much fresh air.
The thermal exchange between the air flow and the chilled water through the cooling
coil is not efficient. ( If the cooling coil fins are not clean, this will affect both air flow
rate and efficiency of the heat transfer ).
The cooling coil fins can be depreciated by corrosion or dented for instance.
SUMMARIZE OF PROCEDURE
1. Check the air diffuser temperatures matching the AHU air outlet temperature.
2. Check the duct system connections into the ceiling from the area to the AHU.
Correct water flow and correct water temperatures on the cooling coil:
Practically we can know if there is a correct chilled water flow rate by measuring the
entering and leaving chilled water temperature of the cooling coil. The water
pressure gauges installed are seldom accurate and we often do not know the cooling
coil pressure drop curve given by the manufacturer.
Whether there is a flow or not throughout a pipe can be heard by closing a gate
valve and as the valve is about 95 % closed, a sound heard can give you an idea of
the flow rate.
Whether the flow rate is correct or not throughout the cooling coil can be known by
measuring the chilled water pipe temperatures.
If the entering water temperature of the cooling coil does not match the leaving water
temperature of the chiller ( be sure that the chilled water pipe system insulation is in
good condition ). It means that there is no flow at all in this connection of the
network. If there is no flow at all in the whole chilled water pipe system, the chiller
must have tripped already.
Air locked.
Dirty pocket.
A valve closed ( balancing valve, gate valve, regulating valve ). Like the dampers of
the duct system, AHU or diffusers, avoid touching a balancing valve since it has
been adjusted during the testing and commissioning.
Beware:
You must interpret this measurement since you must have an idea of the heating
gain ( thermal load ) passing through the cooling coil as you are doing the
measurement.
If the AHU is running with a correct air flow, with a correct chilled water flow rate, at
its maximum cooling capacity matching its designed heating load, the cooling coil
chilled water difference of temperature must be around 4 to 6 deg. C. ( 7 deg. C can
be acceptable ).
Even if the chilled flow throughout the cooling coil is very low, the entering chilled
water temperature of the cooling coil will match the chiller leaving water temperature
but the leaving chilled water temperature of the cooling coil can be very high.
• Strainer choked.
• Air entrapped
• Network disbalanced.
For the latter possibility, it is possible that the balancing of the chilled water pipe
system made during the commissioning does not respond to the real requirement of
the building.
To know if the chilled water pipe system is disbalanced, check the other AHUs
connected to the same network.
SUMMARIZE OF PROCEDURE
2. Check the cooling coil entering temperature matching the chiller leaving
temperature.
4. If not enough flow, check the valves but do not touch the balancing valve.
For the technician, it is important to check the leaving and entering chiller
temperatures of both condenser and evaporator and to know what is the chiller load
by checking its inlet current.
The chiller evaporator difference of temperature must not be more than 7°C. and
must not be less than 2°C. The leaving temperature should be from 6°C. to 8°C.
around.
The chiller condenser difference of temperature must not be more than 6°C. and less
than 2°C. The entering temperature must not be more than 29°C.
The cooling tower water level and cleanliness must be checked. The water
cleanliness to be sure that the chiller condenser will be properly running. The water
level to avoid overflowing or air suction. Too high water level may overflow leading to
a high water consumption. Too low water level can make air be sucked by vortex
effect into the suction pipe of the cooling tower. This air then being entrapped in the
condenser will make the chiller trip and high pressure alarm display.
As many cooling towers are connected in parallel with a common header, despite the
common balancing pipe connecting all cooling towers and an adjustment of the water
make up float system, the water level may vary when the number of cooling towers
running changes. Even if both suction and discharge pipe gate valves are closed.
CONTROL SYSTEMS
As you check from the area to the chiller plant room, you will come across control
system regulation loops.
Usually AHU control systems are more complicated than the FCU ones, most FCU
control systems are by thermostat that is seldom the case for the AHU.
We must note that if many AHUs are installed in the same manner in the storey of a
building, the air return can be the mixing of other AHU air returns so the heating gain
of one AHU controlled by its regulation loop is not the real one.
For instance, in shopping centers, some split unit condensers are mounted in the
ceiling plenum adding heating load to the AHU.
The terminal regulation loop controls the air flow supply through damper installed in
the VAV box to maintain the area ambient temperature. In the area, the difference
between the set point and the ambient temperature outputs the signal varying the
damper position in the VAV box. The air flow on the diffuser varies accordingly. So
the VAV box regulation can be easily checked by changing the set point and noticed
the air flow rate variation at the diffuser.
As for the supply air temperature at the AHU fan outlet, which is controlled by a
regulation loop that controls the chilled water regulating valve position, and the
supply air pressure at the AHU fan outlet, which is controlled by a regulation loop
that controls the fan speed in order to deliver the air flow required in the whole duct
system, to check or adjust this kind of regulation loop should be done by a testing
and commissioning engineer only.
As you do the following, fill up some forms or at least take some notes.
4. Check if the air diffusion is correct ( effective supply and return in the same
area )
9. Check into the ceiling what kind of unit and if air return has a duct system.
10. Check the air diffuser temperatures matching the unit fan outlet air
temperature.
11. Check the duct system connections into the ceiling from the diffusers and
grilles of the area to the unit.
17. Check the unit cooling coil efficiency ( by seeing if there is condensation on it
).
19. Check the cooling coil entering temperature matching the chiller leaving
temperature.
21. Check the leaving and entering temperature of the chiller condenser and
evaporator.
22. Check the cooling tower running condition if any abnormal temperature.
25. Check the other unit cooling coil water flow if doubt of disbalancing.
DO NOT TOUCH:
MEASUREMENT
Most pressure gauges are inaccurate and not reliable. To measure any air or water
flow is practically more or less inaccurate whatever the system used. So the only
means to identify flow rate is by measuring temperatures.
- Dynamic probe:
Probe Handle
Digital thermometer
- Static probe:
Digital thermometer
- Surface probe:
Probe
Handle
Digital thermometer
• Surface of the pipe of a refrigeration circuit to know the superheat and undercool
of the refrigeration cycle.
You can check yourself accuracy of the thermometer easily for the sensors that can
be immersed in liquid by putting it into melting ice. The reading must be 0 Deg.C.
Thermometers are always connected but seldom working. They moreover have a
time lag.
One way is to measure the pipe surface that is representative of the water
temperature flowing inside the pipe. As measuring the return and the supply with the
same probe and method, any error remains the same so the reading is accurate for
a difference of temperature.
As measuring the supply pipe surface temperature, the cooling coil chilled water
entering temperature should match ( one degree above is considered normal
depends on insulation and length of the pipe ) the chiller chilled water leaving
temperature. In case of large pipe with a little flow however, stratification effect will
make the surface pipe temperature 1 or 2 deg. C different with the water
temperature inside the pipe.
The above mentioned is for most cooling application whom the chilled water pipe
system design offers cooling capacity of the air unit cooling coil varying with the
water flow rate. In that case only, it is true that the cooling coil water entering
temperature ( we speak about the water flowing inside the pipe ) matches the chiller
water leaving temperature whatever the flow rate.