Daily report

LER HVAC system Siemens BMS Desigo Exwork module, and SYNCO 700 control system
On Saturday (6-7-2019):

-check the system status and wiring connection with field instrument and dampers spatially for Battery
room, simulate closing and opening for Battery supply and inter dampers from the control panel
HMI(PXM20), and they are ok

-check system data, instrument status, debugging data and alarm history from PXM20 HMI and analyze
the result

We noticed that some setting need to be modify, so we modify as our system required

On Sunday (7-7-2019):

A-We tested the system for Battery room when the H₂ detection is on and noticed:

-closing the inter Batter damper to UPS room

-opening the exhaust damper of Battery room

-start the exhaust fan

Also we test by removing the H₂ detection (off) and noticed

-opening the inter Batter damper to UPS room

-closing the exhaust damper of Battery room

-stop the exhaust fan

Every status and action was monitored by the PXM20 HMI

B- We check the wiring connection from the CP1, CP2 and main PLC control panel spatially for the
PACU1 and 2 healthy dampers, we noticed that one wire in main control panel need to fixed again,
check the status through HMI and was ok so we remove the relay 6 forcing and put it in normal state

C- Checking if the PACU1 will operate when CP1 is in off position and CP2 is in manual position after
checking the wiring connection of auto manual switches connection of the two boards (CP1, CP2) and
their interconnection, no problem was found, and the problem was related to HMI previous setting. So
after checking the HMI status for both PACU1, 2 we operate the system PACU2 in manual mode and
stop PACU1 a for about two hours no fault was found so this problem was solved
2- Setting the time schedule for exhaust fan1, 2 change over on Monday for every week, using the HMI
client