Pow-R-Command Family
22 Pow-R-Command Family Flexibility: Lighting control panel- Labor: Because contactors and relays
boards allow simple and inexpensive are eliminated, the labor associated
Eaton’s Cutler-Hammer brand Pow-R- changes during start-up. Contactor with installing them and the additional
Command family of lighting control and relay panels often require rewiring cables and conduit associated with
23 panelboards is designed to meet the to make changes in the field. them is eliminated.
lighting control needs for buildings of
Choices: The Cutler-Hammer brand of Start-up: Start-up for the Pow-R-
all sizes and complexity. The system
24 incorporates microprocessor-based dis-
lighting control panelboards offers Command panelboards is straightfor-
varying levels of flexibility, from six ward. The PRC25 requires no start-up.
tributed intelligence within a traditional
zones per panel with the Pow-R-Com- It is prewired at the factory. The PRC100
panelboard, simplifying wiring in the
25 field. The panelboard design allows
mand 25 up to 250 zones per panel is provided with factory start-up assis-
with the Pow-R-Command 2000. tance for trouble-free installation. The
the Pow-R-Command lighting control
PRC750, PRC1000 and PRC2000 are
system to meet short circuit ratings, Space: Lighting control panelboards
26 as required by the National Electrical eliminate contactor panels and/or relay
provided with an LCD display and
keypad for on-site programming.
Code (NEC). panels, freeing up valuable wall space.
Pow-R-Command panels are the same Operational Considerations
27 Lighting Control Overview width as standard panelboards. Failure Modes: If a lighting contactor or
Traditional lighting control employs Retrofit Applications: Retrofitting relay fails to operate due to a mechanical
28 lighting contactors or relay panels traditional lighting control methods or control system failure, it is very
to turn groups of lighting on or off. into an existing electrical distribution difficult to control the lights manually.
Input devices are typically time clocks, system often requires extensive rewir- Often, it is necessary to hard-wire
29 photo cells, wall switches, or, in more ing and unwanted downtime. In most around the device on a temporary basis.
sophisticated applications, contact cases, a Pow-R-Command panel inte- With a lighting control panelboard
inputs from a building automation rior can be installed into an existing system, the circuit breaker can be
30 system (BAS). Pow-R-Command is panelboard back box, and the cables manually switched on or off as necessary
a lighting control panelboard with can be re-terminated on the new circuit until the system is back in operation.
remote controllable circuit breakers. breakers, with minimal downtime. Flexibility: In many cases, the lighting
31 These controllable circuit breakers
control scheme may change over the
perform a dual function: Installation Considerations
life of the facility. With traditional light-
1. They provide the overcurrent and Simplicity: Lighting control panelboards ing control methods, changes require
32 overload protection for the circuit. are as easy to install as standard major rewiring and facility downtime.
panelboards. There are no additional Breaker control schemes can be changed
2. They perform the same function components to install. within the lighting control panelboard,
33 as relays and contactors in tradi- often with a simple modification
tional lighting control systems, through software.
opening and closing the circuit
34 in response to a remote signal. Table 23.0-1. Pow-R-Command Product Features
Design Considerations Description PRC2000(B) PRC1000 PRC750 PRC100 PRC25
35 Short Circuit Protection: In the past, Built-in Time Clock Yes Yes Yes Yes No
contactors or relay panels were Data Logging Yes Yes Yes Yes No
mounted close to the lighting load Field Programmable Yes Yes Yes Yes No
36 and short circuit ratings were not a Hand-Held Programmer Optional Optional Optional Optional No
major concern. Today, most of the Number of Lighting Zones 250 250 250 42 6
lighting control devices are located in Remote Access Yes Yes Yes Yes No
37 electrical rooms, often adjacent to the Switch Inputs Yes (16) Yes (16) Yes (16) Yes (12) Yes (6)
panelboards that feed them. These Stand-Alone Capability Yes Yes Yes Yes Yes
Telephone Override Yes Yes Yes Yes No
devices are subjected to short circuit
Yes Yes
38 conditions almost as high as those of
LCD Programming Display Yes No No
Networked Capability Yes Yes No Yes No
the electrical distribution equipment.
Built-in Web Server Yes No No No No
The current version of the National
39 Electrical Code now requires that these
With optional hand-held programmer, or through network.
Minor wiring changes required.
lighting control devices carry a short With proper network equipment.
circuit rating (Article 110-10). Although
40 some traditional lighting control com-
Additional switch inputs are available with optional network controllers.
With optional Telephone Override Controller (TOC).
ponents are available with short circuit With optional LCD Programming Display.
ratings, these ratings are limited and
41 may require upstream fusing. A light-
ing control panelboard makes meeting
the requirements of NEC 110-10 as
42 simple as specifying the short circuit
rating of the panelboard.
43
36
37
38
39
40
41
42
43
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
39
40
41
42
43
System Configurations
22
PRC Network Architecture Web Enabled PC
Containing an embedded webserver,
each Pow-R-Command 2000 system is
Webserver
XML/SOAP/BACnet
23
TCP/IP
programmed with a unique IP address
for communication via any standard Ethernet Ethernet
Internet browser. Web access is stan- 24
PRC2000 PRC2000 PRC2000
dard with the PRC2000. Each controller Integrated Integrated Integrated
can support up to three additional Panelboard Panelboard Panelboard
expansion panels and can be connected IP Address: IP Address: IP Address: 25
to a BACnet Client Workstation with an 10.0.0.222 10.0.0.222 10.0.0.222
additional upgrade. RS-485 RS-485 RS-485
Network Network Network 26
27
28
29
Figure 23.1-1. PRC Network Architecture 30
Breaker Control Busses
Every Pow-R-Command Expansion 31
Panelboard can be configured with the
left and/or right breaker control busses
installed. This feature not only permits 32
standard and remote controllable
breakers to be intermixed within the
same panelboard, but also permits for 33
greater flexibility and versatility in
design and control when integrating
with the Pow-R-Command System 34
Controller.
35
36
37
38
39
Figure 23.1-2. Breaker Control Busses
40
41
42
43
5th Floor
27 SLAN
RS-485
28 PRC
EP
1
29
4th Floor
PRCEP PRCEP
30 RS-485
PRC
EP
31 2
3rd Floor
32
RS-485
33 PRC
EP
2
Technical Data Main Lugs Only Table 23.1-1. Main Circuit Breakers
The short circuit rating of the MLO Breaker Frame Interrupting Rating 22
Panelboard Ratings assembled panelboard will be fully Type Ampere (kA Symmetrical)
■ Voltage: rated based upon the lowest rated Rating 240 V 480Y/277 V
❑ 240 Vac branch device or may be series rated 23
EHD 100 18 14
with an approved upstream device.
❑ 480Y/277 Vac FDB 150 18 14
■ Main lugs: ■ Main lugs only ampere ratings: FD 225 65 35 24
100 and 225. HFD 225 100 65
❑ 100 through 225 amperes FDC 225 200 100
■ Main breakers: Main Circuit Breakers ED 225 65 — 25
❑ 100 through 225 amperes The short circuit rating shown is that EDH 225 100 —
EDC 225 200 —
■ Branches: of the main breaker only. The short
❑ 15 through 100 amperes
circuit rating of the assembled panel- JD
HJD
250
250
65
100
35
65
26
board is the rating of the lowest fully JDC 250 200 100
❑ Controllable from 15 through rated main or branch device or the
30 amperes rating of an approved series rating 27
combination.
Interrupting Capacity (Symmetrical)
■ 240 Vac: 65 kA maximum fully rated. Branch Circuit Breakers 28
■ 240 Vac: 100 kA maximum The type GHQRSP and BABRSP are the controllable circuit breakers. Controllable
series rated. breakers are available in 1- and 2-pole styles, from 15 through 30 amperes.
■ 480Y/277 Vac Non-controlled circuit breakers can be located within the panelboard chassis. 29
Service Table 23.1-2. Branch Circuit Breakers
■ 3-phase, 4-wire 208Y/120 V, Breaker Ampere Number Interrupting Rating (kA Symmetrical) 30
480Y/277 Vac and 240/120 V Delta. Type Rating of Poles 120 V 120/240 V 240 V 277 V 480 V
■ Single-phase, 3-wire, 120/240 V.
BAB
BAB
15 – 70
15 – 100
1
2
10
—
—
10
—
—
—
—
—
—
31
Mains BAB 15 – 100 2, 3 — — 10 — —
For available mains, refer to BAB-D
Table 23.1-1. BAB-C
15 – 60
15 – 30
1, 2
1, 2
10
10
10
10
—
—
—
—
—
—
32
BABRSP 15 – 30 1, 2 10 10 — — —
Branch Circuits
GHQRSP
For available branch circuit devices,
15 – 20 1, 2 — — 65 14 14
33
QBGF , QBGFEP 15 – 50 1, 2 10 10 — — —
refer to Table 23.1-2.
HID (High Intensity Discharge) rated breaker.
Switching neutral breaker. 1-pole device requires 2-pole space; 2-pole device requires 3-pole space. 34
Controllable breaker.
GFCI for 5 mA personnel protection.
GFP for 30 mA equipment protection. 35
50 ampere devices are available as 2-pole only.
Series Ratings 36
Eaton has tested the GHQRSP and BABRSP controllable circuit breakers for
Series Rated Combinations up to 200 kAIC with breakers or fuses. For a complete
listing of available series ratings, see Section 22 (Panelboards) Series Ratings 37
Tables 22.0-6 through 22.0-16.
38
39
40
41
42
43
ckt ckt 14 in. - 18 Ckt. Chassis PRC2000 Panel Layout Instructions Layout Example
22 1 2 Includes PRC2000
1. Select PRC2000 Panelboard 1. Panel Description:
3 4 Controller
5 6 Chassis from Figure 23.1-5.
20 in. - 30 Ckt. Chassis a. PRC2000, 3-phase 4-wire, 208Y/
23 7
9
8
10
Includes PRC2000 a. Determine required mains 120 Vac, interrupting rating
Controller
11 12 (lugs or breaker) of 10,000 AIC symmetrical:
13 14 26 in. - 42 Ckt. Chassis 225 ampere main lugs only at
24 15 16 Includes PRC2000 b. Select appropriate Main Lug
17 18 Controller
bottom, surface mounted and
c. Select appropriate Main Device the following branch breakers
19 20
21 22 Note: PRC2000 d. Select appropriate branch
25 23 24 Chassis is located at breakers
b. 36 – 20 ampere, 1-pole BABRSP
25 26 the Top of the panel- c. 6 – 20 ampere, 1-pole BABRSP
27 28 board immediately 2. Layout panel as shown in spaces
26 29 30 above the breakers. Figure 23.1-5. Total "in." determine
31 32 box height shown in Table 23.1-3. 2. Layout information from
33 34
(When total "in." units exceeds Figure 23.1-5.
35 36
27 37
39
38
40
the number shown, use next
size box size.
a. PRC2000 with 42-circuit Interior
41 42
26 in.
PRC2000 b. 225 ampere Main Lugs Section
28 Controller
4 in.
c. Total Panelboard Height 30 in.
Main Lug Section 2 in. — 100 Amp MLO
29 4 in. — 225 Amp MLO 3. From Table 23.1-3:
Vertically Mounted 8 in. — 100 Ampere Panel Height: 30 in.
■
Frame EHD, EDB, EDS,
30 ED, EDH, FD, HFD
20 in. wide x 5.75 in. deep
9 in. — 225 Ampere ■ Box Height: 48 in.
Frame EDB, EDS, ED, ■ Box Catalog Number:
31 EDH, FD, HFD, FDC YS2048 or EZB2048R
Figure 23.1-5. Pow-R-Command PRC2000 Layout ■ Trim Catalog Number:
LT2048S or EZT2048S
32 Table 23.1-3. Box Selection — Dimensions in Inches (mm)
Maximum Box Height, Catalog Number
33 Panel Height Inches YS Box LT Trim EZ Box EZ Trim
20-Inch Wide x 5.75-Inch Deep Boxes
0 – 22.00 36.00 YS2036 LT2036S or F EZB2036R EZT2036S or F
34 23.00 – 28.00 42.00 YS2042 LT2042S or F EZB2042R EZT2042S or F
29.00 – 34.00 48.00 YS2048 LT2048S or F EZB2048R EZT2048S or F
35.00 – 46.00 60.00 YS2060 LT2060S or F EZB2060R EZT2060S or F
35 47.00 – 58.00 72.00 YS2072 LT2072S or F EZB2072R EZT2072S or F
38
39
40
41
42
43
37
38
39
40
41
42
43
42
43
System Configurations
Protocol Interfaces 22
System Architecture ■ BACnet/IP
Network up to 120 Pow-R-Command ■ SOAP/XML
1000 Panelboards together to a central ■ OPC 23
workstation or computer to control
your building’s lighting. Each Pow-R-
Command 1000 Integrated Panelboard 24
can support up to three additional
expansion panels (EP).
25
26
27
PRC1000 PRCEP
Sub LAN — RS-485 Modbus
28
Figure 23.2-1. System Architecture 29
Typical Applications
Eaton’s Cutler-Hammer Pow-R-Command HVAC System 30
1000 System can be enabled for inte- Fire/Emergency
gration into Modbus native networks System
that are common today in building Security/Access Control System
31
automation to perfectly satisfy any Other Mechanical Control System
lighting control need.
32
34
35
Maximum Network Length 4,000 Feet
(1.2 Kilometers) Using Twisted Shielded Pair 36
37
40
41
42
43
Technical Data Main Lugs Only Table 23.2-1. Main Circuit Breakers
22 The short circuit rating of the MLO Breaker Frame Interrupting Rating
Panelboard Ratings assembled panelboard will be fully Type Ampere (kA Symmetrical)
■ Voltage: rated based upon the lowest rated Rating 240 V 480Y/277 V
23 ❑ 240 Vac branch device or may be series rated
EHD 100 18 14
with an approved upstream device.
❑ 480Y/277 Vac FDB 150 18 14
24 ■ Main lugs: ■ Main lugs only ampere ratings: FD 225 65 35
100 and 225. HFD 225 100 65
❑ 100 through 225 amperes FDC 225 200 100
25 ■ Main breakers: Main Circuit Breakers ED 225 65 —
❑ 100 through 225 amperes The short circuit rating shown is that EDH 225 100 —
EDC 225 200 —
■ Branches: of the main breaker only. The short
26 ❑ 15 through 100 amperes
circuit rating of the assembled panel- JD
HJD
250
250
65
100
35
65
board is the rating of the lowest fully JDC 250 200 100
❑ Controllable from 15 through rated main or branch device or the
27 30 amperes rating of an approved series rating
combination.
Interrupting Capacity (Symmetrical)
28 ■ 240 Vac: 65 kA maximum fully rated. Branch Circuit Breakers
■ 240 Vac: 100 kA maximum The type GHQRSP and BABRSP are the controllable circuit breakers. Controllable
series rated. breakers are available in 1- and 2-pole styles, from 15 through 30 amperes.
29 ■ 480Y/277 Vac Non-controlled circuit breakers can be located within the panelboard chassis.
Service Table 23.2-2. Branch Circuit Breakers
30 ■ 3-phase, 4-wire 208Y/120 V, Breaker Ampere Number Interrupting Rating (kA Symmetrical)
480Y/277 Vac and 240/120 V Delta. Type Rating of Poles 120 V 120/240 V 240 V 277 V 480 V
■ Single-phase, 3-wire, 120/240 V.
31 BAB
BAB
15 – 70
15 – 100
1
2
10
—
—
10
—
—
—
—
—
—
Mains BAB 15 – 100 2, 3 — — 10 — —
For available mains, refer to BAB-D
32 Table 23.2-1. BAB-C
15 – 60
15 – 30
1, 2
1, 2
10
10
10
10
—
—
—
—
—
—
BABRSP 15 – 30 1, 2 10 10 — — —
Branch Circuits
GHQRSP
33 For available branch circuit devices,
15 – 20 1, 2 — — 65 14 14
QBGF , QBGFEP 15 – 50 1, 2 10 10 — — —
refer to Table 23.2-2.
HID (High Intensity Discharge) rated breaker.
34
Switching neutral breaker. 1-pole device requires 2-pole space; 2-pole device requires 3-pole space.
Controllable breaker.
GFCI for 5 mA personnel protection.
35
GFP for 30 mA equipment protection.
50 ampere devices are available as 2-pole only.
36 Series Ratings
Eaton has tested the GHQRSP and BABRSP controllable circuit breakers for
Series Rated Combinations up to 200 kAIC with breakers or fuses. For a complete
37 listing of available series ratings, see Section 22 (Panelboards) Series Ratings
Tables 22.0-6 through 22.0-16.
38
39
40
41
42
43
ckt ckt 14 in. - 18 Ckt. Chassis PRC1000 Panel Layout Instructions Layout Example
1 2 Includes PRC1000
1. Select PRC1000 Panelboard 1. Panel Description:
22
3 4 Controller
5 6 Chassis from Figure 23.2-3.
20 in. - 30 Ckt. Chassis a. PRC1000, 3-phase 4-wire, 208Y/
7
9
8
10
Includes PRC1000 a. Determine required mains 120 Vac, interrupting rating 23
Controller
11 12 (lugs or breaker) of 10,000 AIC symmetrical:
13 14 26 in. - 42 Ckt. Chassis 225 ampere main lugs only at
15 16 Includes PRC1000 b. Select appropriate Main Lug 24
17 18 Controller
bottom, surface mounted and
c. Select appropriate Main Device the following branch breakers
19 20
21 22 Note: PRC1000 d. Select appropriate branch b. 36 – 20 ampere, 1-pole BABRSP
23 24 Chassis is located at breakers 25
25 26 the Top of the panel- c. 6 – 20 ampere, 1-pole BABRSP
27 28 board immediately 2. Layout panel as shown in spaces
29 30 above the breakers. Figure 23.2-3. Total "in." determine 26
31 32 box height shown in Table 23.2-3. 2. Layout information from
33 34
(When total "in." units exceeds Figure 23.2-3.
35 36
37 38 the number shown, use next a. PRC1000 with 42-circuit Interior 27
39 40 size box size. 26 in.
41 42
PRC1000 b. 225 ampere Main Lugs Section
Controller
4 in. 28
c. Total Panelboard Height 30 in.
Main Lug Section 2 in. — 100 Amp MLO
4 in. — 225 Amp MLO 3. From Table 23.2-3: 29
Vertically Mounted 8 in. — 100 Ampere Panel Height: 30 in.
■
Frame EHD, EDB, EDS,
ED, EDH, FD, HFD
20 in. wide x 5.75 in. deep 30
9 in. — 225 Ampere ■ Box Height: 48 in.
Frame EDB, EDS, ED, ■ Box Catalog Number:
EDH, FD, HFD, FDC YS2048 or EZB2048R 31
Figure 23.2-3. Pow-R-Command PRC1000 Layout ■ Trim Catalog Number:
LT2048S or EZT2048S
Table 23.2-3. Box Selection — Dimensions in Inches (mm)
32
Maximum Box Height, Catalog Number
Panel Height Inches YS Box LT Trim EZ Box EZ Trim 33
20-Inch Wide x 5.75-Inch Deep Boxes
0 – 22.00 36.00 YS2036 LT2036S or F EZB2036R EZT2036S or F
23.00 – 28.00 42.00 YS2042 LT2042S or F EZB2042R EZT2042S or F 34
29.00 – 34.00 48.00 YS2048 LT2048S or F EZB2048R EZT2048S or F
35.00 – 46.00 60.00 YS2060 LT2060S or F EZB2060R EZT2060S or F
47.00 – 58.00 72.00 YS2072 LT2072S or F EZB2072R EZT2072S or F 35
Cabinets Top and Bottom Gutters
Trims are code gauge steel, ANSI 61 6.38 in. 36
light gray painted finish. Boxes are
code gauge galvanized steel without Minimum Side Gutters
knockout. Standard size is 20 in. wide x 4 in. (minimum) on 20 in. wide box 37
5.75 in. deep. size.
38
39
40
41
42
43
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
37
38
39
40
41
42
43
Technical Data Main Lugs Only Table 23.3-1. Main Circuit Breakers
The short circuit rating of the MLO Breaker Frame Interrupting Rating 22
Panelboard Ratings assembled panelboard will be fully Type Ampere (kA Symmetrical)
■ Voltage: rated based upon the lowest rated Rating 240 V 480Y/277 V
❑ 240 Vac branch device or may be series rated 23
EHD 100 18 14
with an approved upstream device.
❑ 480Y/277 Vac FDB 150 18 14
■ Main lugs: ■ Main lugs only ampere ratings: FD 225 65 35 24
100 and 225. HFD 225 100 65
❑ 100 through 225 amperes FDC 225 200 100
■ Main breakers: Main Circuit Breakers ED 225 65 — 25
❑ 100 through 225 amperes The short circuit rating shown is that EDH 225 100 —
EDC 225 200 —
■ Branches: of the main breaker only. The short
❑ 15 through 100 amperes
circuit rating of the assembled panel- JD
HJD
250
250
65
100
35
65
26
board is the rating of the lowest fully JDC 250 200 100
❑ Controllable from 15 through rated main or branch device or the
30 amperes rating of an approved series rating 27
combination.
Interrupting Capacity (Symmetrical)
■ 240 Vac: 65 kA maximum fully rated. Branch Circuit Breakers 28
■ 240 Vac: 100 kA maximum The type GHQRSP and BABRSP are the controllable circuit breakers. Controllable
series rated. breakers are available in 1- and 2-pole styles, from 15 through 30 amperes.
■ 480Y/277 Vac. Non-controlled circuit breakers can be located within the panelboard chassis. 29
Service Table 23.3-2. Branch Circuit Breakers
■ 3-phase, 4-wire 208Y/120 V, Breaker Ampere Number Interrupting Rating (kA Symmetrical) 30
480Y/277 Vac and 240/120 V Delta. Type Rating of Poles 120 V 120/240 V 240 V 277 V 480 V
■ Single-phase, 3-wire, 120/240 V.
BAB
BAB
15 – 70
15 – 100
1
2
10
—
—
10
—
—
—
—
—
—
31
Mains BAB 15 – 100 2, 3 — — 10 — —
For available mains, refer to BAB-D
Table 23.3-1. BAB-C
15 – 60
15 – 30
1, 2
1, 2
10
10
10
10
—
—
—
—
—
—
32
BABRSP 15 – 30 1, 2 10 10 — — —
Branch Circuits
GHQRSP
For available branch circuit devices,
15 – 20 1, 2 — — 65 14 14
33
QBGF , QBGFEP 15 – 50 1, 2 10 10 — — —
refer to Table 23.3-2.
HID (High Intensity Discharge) rated breaker.
Switching neutral breaker. 1-pole device requires 2-pole space; 2-pole device requires 3-pole space. 34
Controllable breaker.
GFCI for 5 mA personnel protection.
GFP for 30 mA equipment protection. 35
50 ampere devices are available as 2-pole only.
Series Ratings 36
Eaton has tested the GHQRSP and BABRSP controllable circuit breakers for
Series Rated Combinations up to 200 kAIC with breakers or fuses. For a complete
listing of available series ratings, see Section 22 (Panelboards) Series Ratings 37
Tables 22.0-6 through 22.0-16.
38
39
40
41
42
43
39
40
41
42
43
41
42
43
22 System Configurations
26
29
USC
30 USC
Optional TSP RS-485
Network
SOC Switch
31 Inputs
38
39
40
41
42
43
Standard Analog 31
Modem
RS-232
36
Cable
Keyboard
37
Central PC/DDE Server
38
Figure 23.4-2. Typical Building Lighting Control System — Networked
Typical New Lighting Control System As shown, the central personal Legend 39
Eaton’s Cutler-Hammer Pow-R- computer (PC) is optional since each PRC100 = Standard Pow-R-
Command 100 Panelboards shown panelboard is a stand-alone operating Command 100 Panel
above each have a System Controller lighting control system with basic
PRC100-EC = Pow-R-Command 100 40
for the basic lighting control functions. lighting control functions. The PC
may be used for programming with Expansion Chassis
The Pow-R-Command EC Panelboards changes; downloading software; USC = Universal System 41
shown contain additional chassis scheduling, viewing system status Controller Board
space for a switch override controller. and configuration, etc. PC = Personal Computer
NIB = Network Interface Box
42
SOC = Switch Override
Controller 43
23 Feeder
Circuit Feeder
Circuit
From Control Cabinet
From Control
24 (12 Circuits)
Cabinet
N S (12 Circuits)
N
12 Branch Circuits S
S (Controllable)
25 12 Branch
Circuits
30 Branch Circuits S
G (Controllable)
G (Non-controlled)
26 Phase
Phase A, B, C
A, B, C
Standard
27 Standard PRL 1a, 2a Panelboard
or 3a Panelboard, Area 2
42 Circuit Maximum
28 Area 1
29 No Branch Breakers
in Control Cabinet
Control
Power
30 To other USC
Up to 48 Control Points
Control Optional Network Cable
Cabinets
31
24 Branch Circuits
36 G (Non-controlled)
R
Phase
37 A, B, C
Standard PRL 1a, 2a Relay Cabinet
or 3a Panelboard, 48-1P, 20 A Latching Maximum
38 42 Circuit Maximum Area 4
Area 3
39
Figure 23.4-3. Typical Retrofit System — Optional Network
40 The use of a centrally located Control This configuration is used regularly Legend
Cabinet with its own power supply, when encountering retrofit applications, USC = Universal System Controller
System Controller (USC) and SOCs where only select branch circuits need Board
41 allow for the control of up to 48 controlling and the lighting system
remotely controlled points. Each con- components must be minimized. The CC = Control Cabinet
trollable breaker must be connected selection of this approach must weigh SOC = Switch Override
with a harness to the central System the hardware and installation cost of Controller
42 Controller. Multiple configurations, as the harnesses. Relays may be used in
shown above, may be repeated and addition to controllable breakers, but
43 optionally networked together if desired. not in the same cabinet.
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
29
30
31
32
Pow-R-Command 25 Panel 33
General Description
34
Eaton’s Cutler-Hammer Pow-R-
Command 25 is designed to replace
lighting control systems involving 35
multi-pole lighting contactors and
Figure 23.5-1. Typical Electrically Held Contactor Control System
relay panels. The Pow-R-Command 25
utilizes controllable circuit breakers in 36
a panelboard which are grouped into
zones and switched by a dry or control
signal contact from an external source. 37
The controllable breakers are
pre-wired at the factory in up to
six customer-designated zones 38
with up to 16 breakers per zone.
Note: Refer to factory for zoning restrictions.
39
Components
■ Intelligent power switching 40
equipment.
■ Maintained-to-momentary board
(MTM). 41
42
43
Technical Data Main Lugs Only Table 23.5-1. Main Circuit Breakers
22 The short circuit rating of the MLO Breaker Frame Interrupting Rating
Panelboard Ratings assembled panelboard will be fully Type Ampere (kA Symmetrical)
■ Voltage: rated based upon the lowest rated Rating 240 V 480Y/277 V
23 ❑ 240 Vac branch device or may be series rated
EHD 100 18 14
with an approved upstream device.
❑ 480Y/277 Vac FDB 150 18 14
24 ■ Main lugs: ■ Main lugs only ampere ratings: FD 225 65 35
100, 225 and 400. HFD 225 100 65
❑ 100 through 400 amperes FDC 225 200 100
25 ■ Main breakers: Main Circuit Breakers ED 225 65 —
❑ 100 through 400 amperes The short circuit rating shown is that EDH 225 100 —
EDC 225 200 —
■ Branches: of the main breaker only. The short
26 ❑ 15 through 100 amperes
circuit rating of the assembled panel- JD
HJD
250
250
65
100
35
65
board is the rating of the lowest fully JDC 250 200 100
❑ Controllable from 15 through rated main or branch device or the
27 30 amperes rating of an approved series rating DK
KD
400
400
65
65
—
35
combination. HKD 400 100 65
Interrupting Capacity (Symmetrical)
KDC 400 200 100
28 ■ 240 Vac: 65 kA maximum fully rated.
■ 240 Vac: 100 kA maximum Branch Circuit Breakers
series rated. The type GHQRSP and BABRSP are the controllable circuit breakers. Controllable
29 ■ 480Y/277 Vac breakers are available in 1- and 2-pole styles, from 15 through 30 amperes.
Non-controlled circuit breakers can be located within the panelboard chassis.
Service
30 ■ 3-phase, 4-wire 208Y/120 V, Table 23.5-2. Branch Circuit Breakers
480Y/277 Vac and 240/120 V Delta. Breaker Ampere Number Interrupting Rating (kA Symmetrical)
■ Single-phase, 3-wire, 120/240 V. Type Rating of Poles 120 V 120/240 V 240 V 277 V 480 V
31
Mains BAB 15 – 70 1 10 — — — —
BAB 15 – 100 2 — 10 — — —
For available mains refer to
32 Table 23.5-1.
BAB 15 – 100 2, 3 — — 10 — —
BAB-D 15 – 60 1, 2 10 10 — — —
Branch Circuits BAB-C 15 – 30 1, 2 10 10 — — —
BABRP
33 For available branch circuit devices
15 – 30 1, 2 10 10 — — —
GHBS 15 – 30 1, 2 65 65 65 14 14
refer to Table 23.5-2. GHQRSP 15 – 20 1, 2 — — 65 14 14
34 QBGF , QBGFEP 15 – 50 1, 2 10 10 — — —
HID (High Intensity Discharge) rated breaker.
Switching neutral breaker. 1-pole device requires 2-pole space; 2-pole device requires 3-pole space.
35
Controllable breaker.
GFCI for 5 mA personnel protection.
GFP for 30 mA equipment protection.
36 50 ampere devices are available as 2-pole only.
Series Ratings
37 Eaton has tested the GHBS,GHQRSP and BABRSP controllable circuit breakers for
Series Rated Combinations up to 200 kAIC with breakers or fuses. For a complete
listing of available series ratings, see Section 22 (Panelboards) Series Ratings
38 Tables 22.0-6 through 22.0-16.
42
43