PG 0261 Hk09 Int Unitronic Li2ycy TP

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Data communication systems

Data cables low frequency


Low capacitance

UNITRONIC Li2YCY (TP)

UNITRONIC Li2YCY (TP) fine wire

UNITRONIC Li2YCYv (TP)

■ Application range ■ Technical data


▯ The UNITRONIC Li2YCY (TP) model with Core identification code Cable attenuation / attenuation
reinforced black outer sheath (Yv) is suitable DIN 47100, see Table T9 UNITRONIC Li2YCY (TP)
for inside and outside use as well as burial in Mutual capacitance UNITRONIC Li2YCYv (TP)
the ground. UNITRONIC Li2YCY (TP) (recommended values):0.22mm²:
▯ UNITRONIC Li2YCY (TP) is particularly suit- At 800 Hz: max. 60 nF/km (valid starting at 100 kHz 9.0 dB/km
able for wiring from data systems at transmis- 4 pair) 1 MHz 25.0 dB/km
sion rates up tp 10 Megabit per second. Peak working voltage (recommended values):0.34mm²:
UNITRONIC Li2YCY (TP) 100 kHz 6.6 dB/km
▯ Cables of this kind are designed for fixed (not for power applications) 1 MHz 20.0 dB/km
installation in dry and damp interiors and for 250 V (recommended values): 0.5mm²
conditional flexible use. Based on 100 kHz 6.0 dB/km
UNITRONIC Li2YCY (TP) 1 MHz 18.0 dB/km
VDE 0812 UNITRONIC Li2YCY (TP) fine wire
■ Product features Insulation resistance (guideline values): 0.25mm²
▯ Flame-retardant acc. to IEC 60332-1-2 > 5 GOhm x km 100 kHz max. 8.8 dB/km
Inductivity 1 MHz max. 24.0 dB/km
UNITRONIC Li2YCY (TP) Minimum bending radius
■ Product Make-up approx. 0.65 mH/km fixed installation:
UNITRONIC Li2YCY (TP) Conductor stranding 7.5 x cable diameter
UNITRONIC Li2YCY (TP) Short-range crosstalk attenuation
▯ Stranded conductor, 7-wire, bare UNITRONIC LI2YCYv (TP) Up to 1 MHz min. 50 dB
▯ PE core insulation Stranded copper conductor, based on VDE Up to 10 MHz min. 40 dB
▯ Screen braiding made from copper wire 0881, Test voltage
▯ PVC outer sheath 7-wire UNITRONIC Li2YCY (TP)
UNITRONIC LI2YCY (TP) fine wire C/C: 2000 V
▯ Colour: pebble grey (RAL 7032) Stranded copper conductor, fine C/S: 1000 V
UNITRONIC Li2YCY (TP) fine wire Loop resistance
▯ As UNITRONIC Li2YCY (TP) however with UNITRONIC Li2YCY (TP)
fine-wired conductor design. UNITRONIC Li2YCYv (TP)
0.22 mm² max. 186 Ohm/km
UNITRONIC Li2YCYv (TP)
0.34 mm² max. 115 Ohm/km
▯ As UNITRONIC Li2YCY (TP), however with 0.5 mm² max. 78.4 Ohm/km
reinforced Yv PVC outer sheath UNITRONIC Li2YCY (TP) fine wire
▯ Colour: black (RAL 9005) 0.25mm² max. 160 Ohm/km
Range of temperature
fixed installation: -30 °C to +70 °C
Characteristic impedance
100 Ohm +- 15

Part number Number of pairs and mm² per conductor Outer diameter Copper index Weight
in mm approx. kg/km kg/km approx.
UNITRONIC Li2YCY (TP)
0031320 2 x 2 x 0,22 7.0 20.0 41.0
0031321 3 x 2 x 0,22 7.1 26.0 61.0
0031322 4 x 2 x 0,22 7.3 31.0 76.0
0031323 8 x 2 x 0,22 9.1 54.0 118.0
0031324 10 x 2 x 0,22 10.4 65.0 149.0
0031335 1 x 2 x 0,34 5.8 18.0 40.0
0031325 2 x 2 x 0,34 8.3 29.0 62.0
0031326 3 x 2 x 0,34 8.4 38.0 72.0
0031327 4 x 2 x 0,34 8.7 47.0 87.0
0031328 8 x 2 x 0,34 11.0 78.0 150.0
0031336 1 x 2 x 0,5 6.3 22.0 56.0
0031330 2 x 2 x 0,5 9.2 37.0 65.0
0031331 3 x 2 x 0,5 9.3 49.0 98.0
0031332 4 x 2 x 0,5 9.6 60.0 119.0
0031333 8 x 2 x 0,5 12.7 106.0 213.0
0031334 10 x 2 x 0,5 14.8 148.0 258.0

www.lappgroup.com 261