Date: 08.08.2012 Natural Ventilation Calculation Sheet
Date: 08.08.2012 Natural Ventilation Calculation Sheet
Date: 08.08.2012 Natural Ventilation Calculation Sheet
Ltd
Project Name : Bangalore Green Field
Project Number : 012 - 01137 - 00
Date: 08.08.2012
NATURAL VENTILATION CALCULATION SHEET
Area Height Volume ACPH Ventilation Selected fan
SR NO Description of Area cfm Nos.
f2 f f3 cfm
EXHAUST AIR OPENING REQUIRED 2,581 SQ.FT 80 NOS. 2M x 1.5M VENTILATION LOUVERS TO BE PROVIDED ON BUILDING
2] 240 SQ.MTR. WALL + 91 NOS TURBO VENTILATIOR FANS COSIDERED ON THE ROOF
[ CAP:2161 CFM EACH ].EXHUAST LOUVER SHALL BE AT THE LEVEL OF 10 MTR
1.5MTR HIGH LOUVER REQUIRED 197 MTR LENGTH FROM FFL.
Required wall Opening for Natural Smoke VENTILATION EXHAUST AIR OPENING IS MORE THAN SMOKE EXHAUST
3] Ventilation 1,800 SQ.FT
OPENING, HENCE NO NEED ANOTHER OPENING.NATURAL VENTILATION WILL
SERVE DUAL PURPOSE OF NORMAL & SMOKE VENTILATION.
( As per NBC Chapter-4 FIRE AND LIFE
SAFETY ) 3% of total floor area.
TSI= 31.8
31.8°C INSIDE EXPECTED TEMPRATURE IN PROCESS AREA DURING PEAK AMBIENT TEMPERATURE