VFD Commissioning Format
VFD Commissioning Format
VFD Commissioning Format
CUSTOMER : DATE :
PROJECT :6MW POWER PLANT PANEL NAME :Fuel Feeder VFD
VFD MODEL NO :ACS850 VFD SERIAL NO :
Motor: Traveling Gear Motor
REPORT NO :Traveling Gear Motor
v MOTOR DATA :-
S NO : AMP :6.8 A
KW : 3.7 kw VOLT :440 Volts
RPM : 1750 DUTY :
HZ : 60 Hz EFF% :
S.No. Control & Power Circuits Checks afer Charging of Panel. Result
1 Keep Drive for Slow Firing with DC Source for 8 Hours to avoid IGBT Failure. NO
2 Switch on Main Voltage correctly and keep drive for idle charging for 4 Hours. OK
3 Enter Correct Motor data in 99 groups before proceeding of ID Run. OK
4 Switch drive in Local mode & Do the ID Run for drive. -
5 Take No-Load trial for Motor in De-coupled & Record all data as below. OK
6 Check for On / Of / Raise / Lower operations of VFD in Panel / LCS / DCS) OK
7 Check all DI / DO / AI/AO (4-20 mA) Signals for DCS system as per Drawing. OK
8 Check for Standby / Bypass logic as per Drawing if Any. -
v MOTOR TRIALS.
NO LOAD TRIAL
TOTAL RUN TIME-20 Min
S. NO. CURRENT VOLTAGE RPM FREQUENCY KW REMARKS
1 2.4 A 200 895 27.29 0.09
2 2.57 A 421 1720 57.33 0.11
LOAD TRIAL
TOTAL RUN TIME-24 Hr
S. NO. CURRENT VOLTAGE RPM FREQUENCY KW REMARKS
1 2.79 75 302.6 10.6 0.15 2.15pm
2 2.76 75 302.6 10.6 0.15 9:00 am
3 2.75 75 302.6 10.6 0.15 1:00 pm
v REMARKS IF ANY :- As no availability of variac and client taken responsibility of that drive that’s
why drive is not slow fired . And trail done from local and LPBS. DCS trial is not Done.