Activities After Unit Shutdown (Short Shutdown 8Hrs To 72 HRS) Stage-1
Activities After Unit Shutdown (Short Shutdown 8Hrs To 72 HRS) Stage-1
d) MS line is depressurized.
6. Throttle the condenser bring the flow 7-8000 T and stop one CW pump.
8. Close only the cooling water inlet valve of seal oil cooler.
9. Close only the cooling water inlet valve of Stator water cooler.
12. Close Audco valve in HFO line (horizontally located at firing floor.
13. Ensure that main Audco valve in HFO line at Firing floor remains open Put HFO in Short
recirculation
Boiler side
Turbine side
a) Barring speed