Professional Documents
Culture Documents
Control of A VSC-HVDC
Control of A VSC-HVDC
power is set in the control. The difference between the actual Gen1 Gen3
Gen2 Gen4.1
the block diagram of the power flow. 2 4
Gen4.2
kj
ΔPPFC + ΔP’PFC
Pset +- + Fig. 6. Power System. VSC-HVdc and ac transmission line between Bus 7
1 and Bus 9 are not connected at the same time
TjS
++
P0
+ New P
The ratings of the VSC-HVdc are: Sn = 300 MVA and
fi +- kd
ΔPCLF 1 ΔP’CLF U dc = ±150 kV. Base values of the ac network are: Sb =
1+TfS
fj 100 MVA and U b = 230 kV.
Four cases are studied, namely: 1) Disconnection of 10%
Fig. 5. Block diagram Active Power Control of load at Bus 9 for 100 ms; 2) a three phase short circuit at
Bus 9 during 100 ms, followed by the disconnection of one
3
Voltage Bus 9
of the lines Bus 8 - Bus 9; 3) a trip of generator 4.1; and 4) a 1.04
trip of generator 4.1 and 60 s later a trip of one of the lines Third ac line
1.03 HVdc
Bus 7 - Bus 8. In order to clarify the difference of the results
between a third ac line and HVdc link, curves are shown in 1.02
the same plot for each variable of interest.
1.01
[ pu ]
1
A. Temporary Disconnection of Load (case 1)
The load at Bus 9 was split into two parts, 90% and 10%. 0.99
Power Oscillations
1.6 provided by the VSC-HVdc allows the elimination of the
Third ac line
HVdc oscillations about 5 s after the fault is applied. Once the
1.55
transient period ends, the active power through the VSC-HVdc
1.5 returns to the set value. See Fig. 10.
Fig. 11 and Fig. 12 show the voltage profile at Bus 7 and
1.45
Bus 9, respectively. In the ac system, the voltage drops some
[ pu ]
1.4
volts, at both busses. Meanwhile in the ac/dc system, due to
the voltage control, the voltage is back to the initial value.
1.35 The steady state power transfer through ac line Bus 7 - Bus 8
is lower in the ac system because of the voltage drop. In the
1.3
ac/dc system the power is the same as before the fault.
1.25
0 5 10 15
[s] Power Oscillations
1.8
1.4
1.2
Voltage Bus 7
1.025
1
[ pu ]
Third ac line
1.02 HVdc
0.8
1.015
0.6
1.01
0.4
1.005
[ pu ]
0.99
Fig. 10. Variation of P vs. time (case 2)
0.985
0.98
0 5 10 15
[s]
C. Trip of Generator (case 3)
Fig. 8. Voltage profile at Bus 7 (case 1)
The production of active power at Bus 4 is divided into two
synchronous machines. In this fault one of the machines is
tripped, which means a loss of 350 MW.
B. Short circuit and trip of line (case 2) Fig. 13 illustrates the comparison of variation of P between
A solid three phase short circuit is applied at Bus 9 for a ac and ac/dc systems. The poor damping in the ac system is
time of 100 ms. The fault is cleared by opening one of the ac clear and although the oscillations are becoming larger with
transmission lines between Bus 8 and Bus 9. the time in the plotted window time, the system is stable. In
Although this fault results in large power oscillations the ac/dc system, after 8 s the oscillations are vanished. The
(around 100 MW peak to peak value in the first oscillation), higher amount of transfer of power with respect to the ac
the system is stable for both ac and ac/dc system. The damping system is due to the voltage control.
4
[ pu ]
[ pu ]
1 0.96
0.98 0.95
0.96
0.94
0.94
0.93 Third ac line
0.92
HVdc
0.9 0.92
0 5 10 15 0 5 10 15
[s] [s]
Fig. 11. Voltage profile at Bus 7 (case 2) Fig. 14. Voltage profile at Bus 7 (case 3)
0.98
1.02
[ pu ]
[ pu ]
0.97
1
0.96
0.98
0.95
0.96 Third ac line
HVdc
0.94
0 5 10 15
0 5 10 15 [s]
[s]
V. C ONCLUSIONS
1.4
0 5 10 15
[s] An adaptive control was developed for VSC-HVdc operat-
ing in parallel with ac transmission lines. The control was able
Fig. 13. Variation of P vs. time (case 3) to define the mode of operation according to the local signals
at the buses where the HVdc link was connected.
5
Power Oscillations
5
VI. F UTURE W ORK
4.5 Future steps on the analysis of the adaptive control include:
4
control strategy for first swing oscillation based on CLF; a
3.5
modal analysis of the electric power system for studying small
signal stability; implementation of the adaptive control in a
3
detailed model of VSC-HVdc; and use of more complex power
[ pu ]
2.5
system, which demands a co-ordination with other control
2 devices present in the network.
1.5
1 R EFERENCES
0.5 Third ac line
HVdc [1] www.abb.com/hvdc
0 [2] S. G. Johansson, L. Carlsson and G. Russberg, “Explore the Power of
60 65 70 75 80 85 90 95 100
[s] HVDC Light - a web based System Interaction Tutorial,” presented at
Power Systems Conference and Exposition, IEEE PES, 2004.
[3] S. G. Johansson, G. Asplund, E. Jansson and R. Rudervall, “Power System
Fig. 16. Variation of P vs. time (case 4) Stability Benefits with dc-Transmission Systems,” presented at CIGRE,
Session 2004.
Voltage Bus 7 [4] H. Zhaoqing, M. Chengxiong and L. Jiming “Improvement of Transient
1.05 Stability in ac Systems by HVdc Light,” presented at IEEE PES Trans-
mission and Distribution Conference and Exhibition, Dalian, China, 2005.
1 [5] A. Castro, R. Ellström, Y. J. Häfner and C. Liljegren, “Co-ordination of
0.95
Parallel ac-dc Systems for Optimum Performance,” presented at Power
Delivery Conference, Madrid, Spain, 1999
0.9 [6] H. R. Frankhauser, T. Adielsson, K. Aneros, A. A. Edris, L. Lindkvist and
S. Torseng:“SIMPOW - a Digital Power System Simulator,” ABB Review
0.85
[ pu ]
No. 7, 1990
0.8 [7] M. Ghandhari, G. Andersson and I. A. Hiskens, “Control Lyapunov
Functions for Controllable Series Devices,” IEEE Transactions on Power
0.75 Systems, vol. 16, no. 4, Nov. 2001.
[8] P. Kundur, “Power System Stability and Control,” New York: McGraw-
0.7
Hill, 1994, pp 813
0.65 Third ac line
HVdc
0.6
60 65 70 75 80 85 90 95 100
B IOGRAPHIES
[s]
Héctor F. Latorre received the M.Sc. degree in Electrical Engineering from
Royal Institute of Technology, Stockholm, Sweden, in 2002. He was employed
Fig. 17. Voltage profile at Bus 7 (case 4)
by Interconexión Eléctrica S.A. -ISA-, Colombia, in the area of design of
substations for 9 years. He is currently Ph.D. student at the Royal Institute
Voltage Bus 9 of Technology (KTH).
1.1
Mehrdad Ghandhari received the M.Sc., Tech. Lic. and Ph.D. degrees
in Electrical Engineering from Royal Institute of Technology, Stockholm,
1 Sweden, in 1995, 1997, and 2000, respectively. He is currently Assistant
Professor at the Royal Institute of Technology (KTH).
0.9
Lennart H. Söder (M 91) was born in Solna, Sweden in 1956. He received his
M.Sc. and Ph.D. degrees in Electrical Engineering from the Royal Institute
[ pu ]
0.6
Third ac line
HVdc
0.5
60 65 70 75 80 85 90 95 100
[s]