38YCX-50 HZ Heat Pump-Outdoor Section Installation and Start-Up Instructions
38YCX-50 HZ Heat Pump-Outdoor Section Installation and Start-Up Instructions
38YCX-50 HZ Heat Pump-Outdoor Section Installation and Start-Up Instructions
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 101 Catalog No. 003-880 Printed in U.S.A. Form 38YCX-C3SI Pg 1 2-02 Replaces: 38YCX-C2SI
Tab 5a 5a
More user manuals on ManualsBase.com
NOTES:
1. ALLOW 30″ CLEARANCE TO SERVICE END OF
UNIT, 48″ ABOVE UNIT, 6″ ON ONE SIDE, 12″
ON REMAINING SIDE, AND 24″ BETWEEN
UNITS FOR PROPER AIRFLOW.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS
55° F (UNLESS LOW AMBIENT CONTROL IS USED) MAX. 115° F.
3. MAXIMUM OUTDOOR OPERATING AMBIENT IN HEATING MODE IS 66° F.
4. SERIES DESIGNATION IS THE 13TH POSITION OF THE UNIT
MODEL NUMBER.
A
AIR DISCHARGE
AIR IN
AIR
DISCHARGE
FIELD POWER
E SUPPLY CONN
7/8″ DIA HOLE WITH
AIR
IN 1 1/8″ DIA KNOCKOUT
AIR IN B G AND 1 3/8″ DIA KNOCKOUT
AIR
DISCHARGE
FIELD CONTROL
SUPPLY CONN
7/8″ DIA HOLE
C AIR IN
F DIA SUCTION LINE CONN 3/8″ DIA LIQUID LINE CONN
D
A97004
UNIT A/B C D E F G
SIZE In. mm In. mm In. mm In. mm In. mm In. mm
024 22-1/2 571.5 3-11/16 93.6 18-1/8 460.4 14-3/8 365.1 5/8 15.88 33-15/16 862.0
036 30 762.0 6-1/2 165.1 23-1/2 596.9 20 508.0 3/4 19.05 39-15/16 1014.4
048 30 762.0 6-1/2 165.1 23-1/2 596.9 20 508.0 7/8 22.23 33-15/16 862.0
060 30 762.0 6-1/2 165.1 23-1/2 596.9 20 508.0 7/8 22.23 33-15/16 862.0
A97006
Fig. 3—Accessory Heat Pump Feet
2
More user manuals on ManualsBase.com
Table 1—Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters
LIQUID VAPOR
UNIT SIZE Connection Dia. Tube Dia. Connection DIia. Vapor Dia.
In. mm In. mm In. mm In. mm
024 3/8 9.53 3/8 9.53 5/8 15.88 5/8 15.88
036 3/8 9.53 3/8 9.53 3/4 19.05 3/4 19.05
048 3/8 9.53 3/8 9.53 7/8 22.23 7/8 22.23
060 3/8 9.53 3/8 9.53 7/8 22.23 1-1/8 28.58
NOTES: 1. Tube diameters are for lengths up to 50 ft (15.24m). For tubing lengths greater than 50 ft (15.24m), consult Long-Line Application Guideline.
2. Do not apply capillary tube indoor coils to these units.
To prevent compressor damage DO NOT bury more than 36 OUTDOOR WALL INDOOR WALL
in. of refrigerant tubing. If ANY tubing is buried, provide 6
CAULK
in. vertical rise at service valve. LIQUID TUBE
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
INSTALLATION RECOMMENDATIONS
1. Locate unit away from windows.
1″ MIN
2. Ensure that vapor and liquid tube diameters are appropriate to (25 mm) LIQUID TUBE
capacity of unit. (See Table 1.)
SUSPENSION
3. Run refrigerant tubes as directly as possible by avoiding
unnecessary turns and bends.
A94330
4. Leave some slack between structure and unit to absorb
vibration.
Fig. 4—Piping Installation
5. When passing refrigerant tubes through the wall, seal opening
with RTV or other pliable silicon-based caulk. (See Fig. 4.) PISTON BODY
6. Avoid direct tubing contact with water pipes, ductwork, floor
joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a
rigid wire or strap which comes in direct contact with tubing.
(See Fig. 4.)
8. Ensure that tubing insulation is pliable and completely sur-
rounds vapor tube.
PISTON
9. When necessary, use hangar straps which are 1 in. (25mm)
wide and conform to shape of tubing insulation. (See Fig. 4.) PISTON RETAINER
10. Isolate hangar straps from insulation by using metal sleeves
bent to conform to shape of insulation. SWEAT/FLARE ADAPTER
3
More user manuals on ManualsBase.com
REFRIGERANT TUBING — Connect tubing to fittings on out-
door unit vapor and liquid service valves. (See Fig. 2 and 5.)
SWEAT CONNECTION — Use refrigerant grade tubing. Service The unit cabinet must have an uninterrupted or unbroken
valves are closed from factory and ready for brazing. After ground to minimize personal injury if an electrical fault
wrapping service valve with a wet cloth, tubing set can be brazed should occur. The ground may consist of electrical wire or
to service valve using either silver bearing or non-silver bearing metal conduit when installed in accordance with existing
brazing material. Consult local code requirements. Refrigerant electrical codes. Failure to follow this warning can result in an
tubing and indoor coil are now ready for leak testing. This check electric shock, fire, or death.
should include all field and factory joints. NOTE: Use No. 18 AWG (American Wire Gage) color-coded,
Step 6—Make Electrical Connections insulated (35°C minimum) wires. If thermostat is located more
than 100 ft (30.5m) from unit (as measured along the control
voltage wires), use No. 16 AWG color-coded wires to avoid
To avoid personal injury or death, do not supply power to unit excessive voltage drop.
with compressor terminal box cover removed. CONNECT CONTROL WIRING — Route 24-v control wires
through control wiring grommet and connect leads to control
Be sure field wiring complies with local and national fire, safety, wiring terminal board. (See Fig. 7.)
and electrical codes, and voltage to system is within limits shown
Use furnace transformer, fan coil transformer, or accessory trans-
on unit rating plate. Contact local power company for correction of
former for control power, 24-v/40-va minimum.
improper voltage. See unit rating plate for recommended circuit
protection device. NOTE: Use of available 24-v accessories may exceed the mini-
mum 40-va power requirement. Determine total transformer load-
NOTE: Operation of unit on improper line voltage constitutes
ing and increase the transformer capacity or split the load with an
abuse and could affect unit reliability. See unit rating plate. Do not
accessory transformer as required.
install unit in system where voltage may fluctuate above or below
permissible limits. NOTE: The defrost timer is factory set for 90-minute cycles. The
timer can be field set for 30- and 50-minute cycles depending on
NOTE: Use copper wire only between disconnect switch and
defrost conditions in your geographic location.
unit.
Step 7—Compressor Crankcase Heater
NOTE: Install branch circuit disconnect per local codes to handle
unit starting current. Locate disconnect within sight from and When equipped with a crankcase heater, energize heater a mini-
readily accessible from unit per local codes. mum of 24 hr before starting unit. To energize heater only, set
thermostat to OFF and close electrical disconnect to outdoor unit.
ROUTE GROUND AND POWER WIRES — Remove access
panel and control box cover to gain access to unit wiring. Extend A crankcase heater is required if the refrigerant tubing is longer
wires from disconnect through power wiring hole provided and than 50 ft.
into unit control box. (See Fig. 2.) Size wires per local codes but Step 8—Install Electrical Accessories
not smaller than minimum wire size shown on unit rating plate. Refer to the individual instructions packaged with the kits or
CONNECT GROUND AND POWER WIRES — Connect ground accessories when installing.
wire to ground connection in control box for safety. Connect Step 9—Start-up and Check Charge
power wiring to contactor as shown in Fig. 6.
DISCONNECT PER
IEC AND/OR To prevent compressor damage or personal injury, observe
LOCAL CODES
the following:
FIELD POWER • Do not overcharge system with refrigerant.
WIRING CONTACTOR
• Do not operate unit in a vacuum or at negative pressure.
L1 L1 • Do not disable low-pressure switch
In scroll compressor applications:
N FOR 1-PHASE ONLY
L2/N L2/N • Dome temperatures may be hot.
3-PHASE ONLY
L3 L3
4
More user manuals on ManualsBase.com
FB4ASX FB4ASX
FAN COIL HEAT PUMP FAN COIL HEAT PUMP
THERMOSTAT THERMOSTAT
R R R R R R
G G G G
C C C C C C
W2 W2 W2 W2 W2 W2
E E E
ODTS
BLU
L L W3
O O O O
Y Y Y Y
FB4ASX
THERMOSTAT FAN COIL HEAT PUMP
R R R
G G
C C C
W2 W2 W2
ODTS1
BLU
L W3
E E VIO
ODTS2
O O
Y Y
C 1 4 7 C 9 6 3
A97052
Fig. 7—24-v Control Circuit Connections
5
More user manuals on ManualsBase.com
Do not vent refrigerant to atmosphere. Recover during system
repair or final unit disposal.
6
More user manuals on ManualsBase.com
If defrost thermostat is in open position, and speedup pins are
T2 C C O
shorted (with a flat head screwdriver) for 5 sec and released, a
OF1
short defrost cycle will be observed (actual length is dependent
OF2
upon the selected Quiet Shift position). When Quiet Shift switch is
DFT
O R W2 Y C
in ON position, the length of defrost is 1 minute (30 sec
T1
compressor off period followed by 30 sec of defrost with com-
pressor operation). On return to heating operation, compressor will
Y
again turn off for an additional 30 sec and the fan for 40 sec. When
the Quiet Shift is in OFF position, only a brief 30 sec cycle will be
P1
observed.
SPEEDUP
60
30
INTERVAL TIMER OFF
J1
120
If it is desirable to observe a complete defrost in warmer weather,
90
30
60
the thermostat must be closed as follows:
P3
DFT
ON
1. Turn off power to outdoor unit.
SHIFT
QUIET
CESO130076–00
2. Disconnect outdoor fan motor lead from OF2 on control board
(See Fig. 9.) Tape to prevent grounding. Speedup Quiet Defrost interval
Pins Shift DIP switches
3. Restart unit in heating mode, allowing frost to accumulate on A99442
outdoor coil. Fig. 9—Defrost Control
4. After a few minutes in heating mode, liquid line temperature CARE AND MAINTENANCE
should drop below closing point of defrost thermostat (ap- For continuing high performance and to minimize possible equip-
proximately 30°F). ment failure, periodic maintenance must be performed on this
NOTE: Unit will remain in defrost until defrost thermostat equipment.
reopens at approximately 80°F coil temperature at liquid line or Leave User’s Manual with owner. Explain system operation and
remainder of defrost cycle time. periodic maintenance requirements outlined in manual. Frequency
5. Turn off power to outdoor and reconnect fan motor lead to of maintenance may vary depending upon geographic areas, such
OF2 on control board after above forced defrost cycle. as coastal applications.