BLACK SEA GROUP POWER TRANSFORMERS

1
BLACK SEA GROUP POWER TRANSFORMERS

Power Transformers Prospect

CONTENT:

ƒ Black Sea Group Presentation

ƒ Delivery, Commisioning, Service

ƒ Partners

ƒ Main Features of the Power Transformers offered

ƒ ElectroPutere Transformer Factory Products

ƒ ETRA33 Transformer Factory Products

ƒ BEZ Group - ETD Transformer Factory Products

ƒ Service

2
BLACK SEA GROUP POWER TRANSFORMERS

ABOUT BLACK SEA GROUP

BLACK SEA GROUP is formed of:


1. BLACK SEA TECHNOCHIM CO. S.R.L., having its head office in
Bucharest, Romania, registered at the Register of Commerce under
no. J40/18522/1994 with C.U.I. no. 6286263 and the fiscal attribute R;
Black Sea Technochim Co. is liable for Romania and European markets.

2. BLACK SEA ENERGY GENERATING EQUIPMENT TRADING (L.L.C.) having


its head office in Dubai, U.A.E., registered at the Department of
Economic Development with license no. 515004 and Commercial
Register no. 53617/1999;
Black Sea Energy Generating Equipment Trading L.L.C. is liable for the United
Arab Emirates markets.

3. SUN ORBIT FOR GENERAL TRADING CO., having its head office in
Baghdad-IRAQ, registered at Commercial Register no. 13116/2004;
Sun Orbit for General Trading Co. is liable for Iraqi markets.

4. BLACK SEA POWER GENERATING FZCO, having its head office in Jebel
Ali Free Zone - Dubai, U.A.E., License no.40146 Government of
Dubai.
Black Sea Power Generating FZCO is liable for International, Middle East and
Africa markets.

The main markets for our activities are in the Middle East and Africa countries.
Since its formation, as an international trade company, Black Sea Group has
been dealing in the field of power generation, representing and collaborating with
famous Romanian companies, for supplying of equipments and spare parts and
performing of overhaul for all types of steam power stations with power up to
330MW and boilers with capacity up to 1035t/h.
Due to an extensive experience, we offer to our clients high-quality products,
short time delivery, competitive prices and a transparent collaboration.
Highly-qualified personnel work hard so that all the products, works and
services to be completed according to our clients requirements and in time.

Quality Management
Black Sea Technochim Co. is certified by TÜV Thüringen e.V.
for the implementation and the application of the quality system
according to DIN EN ISO 9001:2000.

3
BLACK SEA GROUP POWER TRANSFORMERS

From the beginning, Black Sea Group was focused intensively on quality,
technical development and marketing.

Black Sea Group’s main competencies include:

• Thigh contacts with old and possible future clients;


• Thorough market studies and discover new possible tenders to take part to;
• Looks for the best designers and manufacturers for each possible future job;
• Black Sea Group buys the tender documents;
• The best offer issued on the name of one BSG member is sent to the client;
• Black Sea Group participates to the negotiations and signs the contracts as
Main Contractor;
• Black Sea Group is responsible for the necessary finances required for each
offer/contract as follows: bid bonds and performance bonds, opens L/C or
makes advance payments for the manufacturers;
• During the development of each contract, in order to assure the best
conditions in accomplishing the job, Black Sea Group is responsible for the
delivery of goods from manufacturers to the client in short time, for the
transportation and accommodation of the employed personnel during the
rehabilitations and/or service period, insurances for the goods during the
shipment and during the erection works;
• Black Sea Group as Main Contractor is responsible in front of the client during
the warranty period of each job performed.

4
BLACK SEA GROUP POWER TRANSFORMERS

BLACK SEA GROUP - CONTACT


ROMANIA
Black Sea Technochim Co.
Contact person: Mrs. Aurelia Neacsu - Commercial Manager
Phone: +40-21-3373951
FAX: +40-21-3366112
E-mail: bsbucharest@blackseagroup.com

UNITED ARAB EMIRATES


Black Sea Energy Generating Power Equipment Trading
L.L.C.
Contact person: Mr. Saud Thuny – Commercial Manager
Mr. Tawfeeq Majeed
Phone: +971-4-2727806
Mobile: +050-6587708
FAX: +971-4-2728553
E-mail: bsdubai@blackseagroup.com

Black Sea Power Generating FZCO


Contact person: Mr. Mohanad Ahmed – Commercial Manager
Phone: +971-4-2727806
Mobile: +050-2589854
FAX: +971-4-2728553
E-mail: bspower@blackseagroup.com

IRAQ
Sun Orbit for General Trading Co.
Contact person: Mr. Ossama M. Hussein Mobile: +964 7901379203
Ms. Sherin Bassam Mobile: +964 7901399163
Mr. Raed Yakub Mobile: +964 7901157503
E-mail: bsbaghdad@blackseagroup.com

5
BLACK SEA GROUP POWER TRANSFORMERS

DELIVERY,
COMMISSIONING & START-UP,
SERVICE.

BLACK SEA GROUP offers:

Compete range of Transformers from 1MVA upto 400MVA; 3kV


upto 420kV:
- Electrical Network Interconnecting Transformers and
Autotransformers;
-Three Phase Power Transformers for internal Services of
Power Plant;
-Three Phase Power Transformers with Off-Load Tap
Changer;
-Three Phase Power Transformers with On-Load Tap
Changer or Off-Load Tap Changer;
-Three Phase Power Transformers with On- Load Voltage
Control;
-Double Wounded, Three Phase Power Transformers with
On-Load Tap Changer;

►Procurement and Delivery on site;


►Erection, Commissioning and Start-up;
►Acceptance and Performance Testing;
►Training on site or in manufacture place;
►Engineering services (inspection, analyzing and evaluation);
►Maintenance services;

BLACK SEA GROUP is certified by TUV Thuringen e.V. for application


of the quality system according with EN ISO 9001:2000.

6
BLACK SEA GROUP POWER TRANSFORMERS

BLACK SEA GROUP PARTNERS FOR POWER TRANSFORMERS


AND FOR RELATED SERVICE ARE:

1. –ELECTROPUTERE CRAIOVA-
Power Transformers, Instrument Transformers,
Electrical Motors, Switching Apparatus
Factory-Romania.
Internet:www.electroputere.ro
Transformers, Motors, Apparatus Manufacturer.

2. –ETRA 33-
Power Transformers
Factory-Slovenija.
Internet:www.etra33.si
Transformers Manufacturer.

3. -BEZ Transformatory-
Power Transformers
Factory-Slovakia.
Internet:www.bez.sk
Transformers Manufacturer.

4. –BEZ-ETD Transformatory -
Power Transformers
Factory-Czech.
Internet:www.etd-bez.cz
Transformers Manufacturer.

5. -ICMET -
Research, development and Testing Institute -Romania.
Internet:www.icmet.ro
Insulation testing.

7
BLACK SEA GROUP POWER TRANSFORMERS

6. –EMON ELECTRIC-
Electric Erection -Romania.
Internet:www.emon.ro
Constructions and Installations in Energetic and
Telecommunication Field. Manufacturing.

7. –ELECTROMONTAJ-
Electroenergetic Erection -Romania.
Internet:www.electromontaj.ro
Constructions and Installations in Energetic Field.

8. -ICEMENERG Service-
Rehabilitation and Research Institute for National
Energy System –Romania.
Internet:www.icemenerg.ro
Consulting, Implementation and Testing works on site.

8
BLACK SEA GROUP POWER TRANSFORMERS

MAIN FEATURES OF THE POWER TRANSFORMERS


IN OUR PROJECTS

BLACK SEA GROUP is constantly in the development and improvement of


the offered products and services.

Our aim is to satisfy customer’s high demand for a safe


Electrical Power Generation.

THE EQUIPMENTS are carried out with the best quality materials and
components based on tested beyond standard margins.

OUR PARTNERS are the world known companies which care perform the
routine and performance tests on factory and the results are proven with the
best Mean Time Between Failure.

MISCELLANEOUS

The transformers belonging to these classes comply to the requirements of IEC


76 standard or standards required by the customers.
MAIN REFERENCE DOCUMENTS:

IEC 60076-1 POWER TRANSFORMERS-General


IEC 60076-2 POWER TRANSFORMERS-Temperature rise
IEC 60076-3 POWER TRANSFORMERS-Insulation levels, dielectric tests
and external clearances in air.
IEC 60076-3 GUIDE to lightning impulse and switching impulse testing.
IEC 60076-5 POWER TRANSFORMERS-Ability to withstand short circuit.
IEC 60076-10 POWER TRANSFORMERS-Determination of sound
levels.
IEC 60137 Insulated bushings for alternating voltages above 1000V.
IEC 60214 On-Load Tap Changers.
IEC 60354 Loading guide for oil-immersed power transformers.
CONDITIONS OF OPERATION
The transformers operate at ambient standard temperatures of max. +40ºC and
min. -35ºC.
Max. installation standard altitude above the sea level: 1000 m.

9
BLACK SEA GROUP POWER TRANSFORMERS

The transformers operate at ambient temperatures of .max.+ 50ºC and at


altitude higher than 1000m
are available at request.

GENERAL TECHNICAL SPECIFIC FEATURES

Operating frequency: 50 Hz

Operating voltage on the HV side: 110 (132);220 (230);400 (420) kV

Operating voltage on the LV side: 6.3(6.9); 10.5(11); 13.8(15) kV

Operating voltage on the MV side: 20 (33) kV

Taping range on the HV: ± 2 x 2.5%; ± 12 x 1%; ± 17 x 1.25%

Cooling type: ONAN; ONAN / ONAF; OFAF.

Rated continuous power: 1 MVA ÷ 400 MVA

TYPE
The transformer shall be a 50-Hz outdoor type three-phase unit with ON –Load
Tap Changer.
The external cooling medium: air.
The insulation is graded for operation with effectively earthed neutral.

GENERAL
The transformer is suitable for continuous operation on a three-phase 50Hz high
voltage transmission system as specified.
All windings of the transformers are capable of withstanding short circuit for the
periods of time specified in IEC 60076 when operating on any tapping position.
The transformer is suitable for cyclic overloading and long-time emergency
loading duties in accordance IEC 60354.
Ratings are based on the average winding temperature rise, as measured by
resistance, of 55ºC and the top oil temperature rise, as measured by thermometer,
of 50ºC.
With the cooling air maximum temperature of 50ºC.

10
BLACK SEA GROUP POWER TRANSFORMERS

The design and manufacture of the transformers is such that the noise level is
minimum and that the level of vibration does not adversely affect any clamping
or produce excessive stress in any material.
Noises levels shall are in accordance with IEC 60551.
The maximum acceptable level is 88 dB in conformity with NEMA std.TR-1.

MAGNETIC CIRCUITS
The core is “core” type, with 3 parallel legs, made of high grade, non-aging
electrical cold rolled grain oriented silicous steel laminations loss and high
permeability.
The yokes and legs are securely held by means of synthetic resin impregnated
glassfiber strips.
The core is clamped both at the top and bottom by means of clamping structures
of steel.
The structure placed on the same side are stiffened between each other by means
of tie rods made of nonmagnetic alloy. The structures on the HV and LV sides
are clamped between each other by means of clamping frameworks. The live
part(core winding) is centered on the tank bottom by means of four guinding
cones. Within the construction described above, the live part movement during
shipping and installation or while in service is fully avoided.
Particular care is taken to secure even mechanical pressure over the whole of the
core laminations.
Under steady overvoltage condition the maximum flux density not exceed 1,9
Tesla
and the magnetizing current not exceed 5 % of the rated load current at normal
rated voltage.

WINDINGS.
The winding are circular coil concentrically type. The windings shall be formed
using high quality electrolytic copper conductor, insulated with pure cellulose
paper.
The main insulation between windings is of the multi-duct type with cylinders
made of high dielectric strength
transformer pressboard.
The windings and connections are braced to withstand shocks, which may occur
during transport or due to switching or other transient conditions during service.

11
BLACK SEA GROUP POWER TRANSFORMERS

INTERNAL EARTHING ARRANGEMENT.


The magnetic circuit is earthed to the clamping structure at one point only
through a removable link with a captive bolt and nut accessible placed beneath an
inspection opening in the tank cover.

TANK AND COVER.


Transformer tank is made of electrically welded steel sheets and designed
to allow the complete transformer, when arranged for transport to be lifted by
crane and transported without transformer parts stressed.
The plate thickness for the tank sides is of 10 mm. The cover is clamped to
the tank, by screw fastening.
The tank is provided with lugs, boses and hooks to enable the transformer,
complete with all tank mounted accessories and filled with oil, to be lifted by
powerhouse crane and pulling the transformer in 2 orthogonal directions.
The wheels are suitable for a standard track (1.435 metre between inside
of rail heads) for moving the transformer in 2 orthogonal directions.
Four jacking pads are provided on the tank to enable the transformer, complete
with oil, bushings and fittings,to be raised or lowered by jacks.
Means are provided for locking the swivel movement in positions parallel
to and at right angles to the longitudinal axis of the tank.
The wheel loading does not exceed 13,000 kg . Tank covers shall not
permanently distort when lifted. Inspection openings of ample size shall be
provided to give easy access to bushings for changing ratio, or winding
connections, and for testing the earth connections.
The tank cover is fitted with a thermometer pocket, with captive screw cap,
located in the position of maximum oil temperature at continuous maximum
rating.
Facility the bushing remove without removing the tank cover.
A pressure relief device is provided for the rapid release of any pressure
that may be generated within the the tank.
The device operates at a static pressure of less than the hydraulic test
pressure for transformer tanks and prevents further oil flow from the transformer
following its operation.
In the event that the device is a spring operated valve type it shall be
provided with one set of normally open contacts, which will be used for tripping
purposes.

12
BLACK SEA GROUP POWER TRANSFORMERS

OIL / AIR BUSHINGS.


Oil/air bushings are designed in accordance with the requirements of IEC 60137.
The HV bushings are of 145 kV condenser type; the HV neutral bushing is
suitable for 72.5 kV level of condenser type; the LV bushings are suitable for
min.12.5 kV level.
The visible oil levels in the gauge corresponds to average oil temperatures from
the minimum ambient stated in the SYSTEM PERFORMANCES to plus 90ºC.
The oil levels at 15ºC and 35ºC are marked.
Neutral bushings shall be mounted in position from which a connection can be
made to a neutral current transformer mounted on a bracket secured to the tank.
The neutral current transformer is not be in transformer manufacture standard
supply.

CONSERVATOR VESSELS, OIL LEVEL GAUGES AND BREATHERS.


The conservator has a level gauge, a filling cap, an adequate sump. The
conservator is provided with a removable end cover at the one end.
The visible oil levels in the gauge shall correspond to average oil temperatures
from the minimum ambient stated in the SYSTEM PERFORMANCES in Annex
no.1 to plus 90ºC.
The oil levels at 15ºC and 35ºC are marked on the gauge.
The oil level gauge incorporates alarm contacts, which close when the oil level
falls below a definite level.
The conservator is connected to a dehumidifying breather, which is mounted at
approximately 1,4 m above ground level.

VALVES
Valves are of the fully-way type.
Padlocks are provided for locking all valves(exception for the individual radiator
valves) in the open and closed positions.
The valves are with an indicator readily visible from ground level which shows
clearly the position of the valve.
All valves hand-wheels are provided with nameplates.

13
BLACK SEA GROUP POWER TRANSFORMERS

COOLING PLANT
Transformer has ONAN/ONAF cooling options. The facilities are provided at
the marshaling kiosk or cubicle for the selection Automatic or Manual control of
the cooling plant motors.
Transformers shall be fitted with sectionalized cooling banks necessary to meet
the continuous maximum rating (CMR).
Transformers shall be capable of remaining in operation at full load for 20
minutes in event of failure of the cooling fans without the calculated winding hot
spot temperature exceeding 150ºC.
Failure of one fan in each group of fans does not reduce the continuous
maximum rating of the transformer.
The fan complete with its motor and supporting structure can be removed
without disturbing or dismantling the cooler framework or pipe - work.

COOLER CONTROL.
The forced air cooling is controlled for automatic starting or stopping from
contacts on the winding temperature indicating devices.

ON-LOAD TAP CHANGING-OLTC- EQUIPMENT.


The transformer is provided with OLTC suitable for the rated current(+20%
overload) of modern design and construction of MR Type from Germany with 17
tapping positions x 1.25% in range of +10% -10% ;
with fully capacitance at all taps.
Tap changing is prevented when the transformer is caring a load above a
predetermined maximum or when on short circuit.
Tap changing however is suitably rated for operation when transformer are
subjected to overload duties in accordance with IEC 60354.
The equipment has an indication at the transformer and electrically at the remote
control points of the tapping in use.

AUTOMATE VOLTAGE REGULATOR AND TAPPING INDICATOR.


The Automate Voltage Regulator is included in the offer; the regulator actuates
to the motor of the OLTC.
The Actual Voltage measurement is taken from existing Instrument Transformers
of the Substation. The instrument transformer will be provided in the delivery by
request.
An Indicator device of the tapping positions for the Control Room is included in
the Offer.

14
BLACK SEA GROUP POWER TRANSFORMERS

TEMPERATURE INDICATING DEVICES, ALARMS AND GAS AND OIL


ACTUATED RELAYS.

1. TEMPERATURE INDICATING DEVICES, ALARMS


Oil temperature indicating devices are fitted with alarm and trip contacts.
Winding temperature indicating devices indicate the temperature of the hottest
spot of the winding and have a load –temperature characteristic approximating to
that of the main winding.
Alarm and trip contacts are provided. Alarm contacts of oil and winding
temperature indicating devices are adjustable over a range of 60ºC to 110ºC and
trip contacts adjustable over a range 80ºC to 150ºC.
Temperature indicating devices incorporate a dial and a pointer indicator and a
separate pointer to register the maximum temperature reached.
All temperature indicators are housed in the marshalling kiosk or cabinet and are
not affected by vibration.

2. GAS AND OIL ACTUATED RELAYS.


Gas and oil actuated relays are fitted to each tap selector compartment.
They have alarm contacts that close on collection of gas or at low oil level and
tripping contacts, which close following an oil surge.
The relays are fitted in the expansion pipe connecting the transformer
tank to the conservator.

OIL FLOW INDICATORS.


Forced oil cooled transformers shall be provided with a visual oil indicator
including contacts, in each outlet pipe connection from coolers.

OIL QUALITY.
Uninhibited new insulating mineral oil for transformers type NITRO by
NYNAS-Austrian manufacture which assures a safe transformer
energizing at a temperature -30ºC.
The U-30ºC transformer insulating mineral oil is used as an
insulating and cooling environment in high-power transformers.
It can be used in warm(tropical) and mild climate countries, for altitudes
up to 1500 m.
The technical and quality conditions according to EN 60 296/2004.

15
BLACK SEA GROUP POWER TRANSFORMERS

One oil container with 5% from oil quantity in the main body(tank)of
the transformer is recommended and it is delivered by client request on
extra cost.

TRANSFORMER MARSHALLING KIOSK.


A weatheproof and dustproof control housing located on the transformer near the
base. It is equipped with the following:

(a)Earth bus for circuits requiring earth points. The bus includes one bolted
type connectors of 10 mm2 stranded copper cable size for each earthed
circuit.
(b)Terminal blocks for termination of secondary leads, alarm, control, relay
and thermocouple leads.
(c)A suitable pocket or holder inside for one copy of the instruction manual.
(d)A plain, removable plate located in the bottom for terminating all conduits
leaving the transformer (the plate will be drilled in the field).
(e)Contactors for fan motors.
(f)Necessary glands for power and control cables
(g)Thermostatically controlled, anti-condensation heater for 220V,single –
phase system.

16
BLACK SEA GROUP POWER TRANSFORMERS

THE ACCESSORIES AND MATERIALS USED BY THE


ELECTROPUTERE CRAIOVA-ROMANIA one of our Partner.

1.The HVand MV Bushings are GOB type from ABB-Germany manufacturer.

2.ON –LOAD TAP CHANGER is from MR manufacturer Germany.

3. Oil transformer-NITRO 3000x from NYNAS manufacturer Austrian.


It can be used in warm (tropical) and mild climate countries, for
altitudes up to 1500m and assures a safe energizing at a temp of -30ºC.

4. Radiator panel type from EuroCooller manufacturer-France / AGUN


manufacture-Turkey.

5. Cooling Battery from Solivent Ventek-France.

6. Fan 0.37kW/230/400V axial type, from ELECTROPUTERE -Romania.

7. Buchholz relay type from EMB manufacturer –Germany.

8. Magnetic oil level indicator- CAOM Pascani-Romania

9. Oil temperature indicator, type OTI Serie 34, AB Qualitrol AKM


manufacturer,Sweden.

10. Winding temperature indicator,type OTI Serie 35,AB Qualitrol AKM


manufacturer,Sweden.

11. Oil filtering valve and Oil draining valve, Fratelli Fortis- Italy or Armatura
Cluj-Romania.

12. Copper wire with Specific Electrical Resistance 0.0214 Wmm2/mat 75ºC;
99.98% Cu BORR manufacture-Serbia.

13. Silicous steel sheet, MOH type, specific loss 1.03w/kg at 1.7 T
from British Steel- England.

17
BLACK SEA GROUP POWER TRANSFORMERS

ELECTROPUTERE CRAIOVA-Romania.

TRANSFORMERS FACTORY.

◘ Network Interconnecting Transformers;

◘ Step –up Transformers;

◘ Auxiliary Transformers;

◘ Three phase Regulating Power Transformers;

◘ Service;

THE MOSTLY RECENT REFERENCE LIST AS BELOW:

18
BLACK SEA GROUP POWER TRANSFORMERS

VOLTAGE APPLI-
RATED OUTPUT VOLTAGE VECTOR NOS YEAR of
TYPE CONTROL CABLE COUNTRY-CUSTOMER REMARKS
(KVA) (KV) GROUP (pcs) DELIVERY
(%) CODE/STD
TTOS – +12,5 - 17,5 GREECE – PPC
40000/50000 150/21 YNyn-0 8 2003 IEC
ONAN/ONAF
TTOS – +12,5 - 17,5 GREECE – PPC
40000/50000 150/21 YNyn-0 10 2003 IEC
ONAN/ONAF
TTOS – +10x1,25 - GERMANIA – ABB// IRAQ -
31500/25000/12500 132/33/11,5 2 2003 IEC S/S
ONAN/ONAF 10x1,25 YNyn0-d1 KALLAR
TTOS – GERMANIA – ABB// IRAQ -
44000/63000 132/34,5 16 1,25 YNd1 1 2003 IEC S/S
ONAN/ONAF TASLUJA
TTOS – GERMANIA – ABB// IRAQ -
17500/2500 132/33 10 YNd1 2 2003 IEC S/S
ONAN/ONAF OLD DOKAN
TTOS – GERMANIA – ABB// IRAQ -
6300 132/6,3 12 YNd1 1 2003 IEC S/S
ONAN/ONAF NEW DOKAN
TTOS – +7,5 -10,5 GERMANIA – ABB // IRAQ -
7000/10000 33/11,5 Dyn11 1 2003 IEC S/S
ONAN/ONAF ARBAT
TTOS – +7,5 -10,5 GERMANIA – ABB// IRAQ -
7000/10000 33/11,05 Dyn11 2 2003 IEC S/S
ONAN/ONAF QALADIZA
TTOS – +7,5 -10,5 GERMANIA – ABB// IRAQ -
11200/16000 33/11,5 Dyn11 3 2003 IEC S/S
ONAN/ONAF MALKANDY
16 10
TTO-OFAF 250000/250000/80000 400/121/20 30 15 Ynyn-0 1 2003 IEC ROMANIA ST-ORADEA T
11 15
9x1,78 SYRIA PEEGT
TTOS - ONAN 30000 66/20 Ynd11 4 2003 IEC S/S
SYRIA PEEGT
TTO - ONAN 250 20/0,4 - Znyn1 4 2003 IEC S/S
TTOS – +12,5 - 17,5 GREECE – PPC
40000/50000 150/21 YNyn-0 5 2003 IEC S/S
ONAN/ONAF
SIRYA ACBMC CEMENT
TTUS – OFAF 16000 66/6,6 9x1,78 YNd11 1 2003 IEC S
PLANT
+10x1,25 - GREECE – PPC
ATOS 280000/280000/60000 400/157,5/30 YNyn0-d1 5 2003 IEC T
10x1,25
TTOS -
42000 11,5/150 5 YNd1 2 2003 IEC GREECE - PPC S/S
ONAN/ONAF
EGIPT - CEPC CAIRO NORTH
TTOS – ONAF 24000/12000/12000 15/6,3/6,3 10 Dy 2 2003 ANSI T
POWER St.

19
BLACK SEA GROUP POWER TRANSFORMERS

VOLTAGE APPLI-
RATED OUTPUT VOLTAGE VECTOR NOS YEAR of
TYPE CONTROL ( CABLE COUNTRY-CUSTOMER REMARKS
(KVA) (KV) GROUP (pcs) DELIVERY
%) CODE/STD
+10x1,25 -
ATOS 280000/280000/60000 400/157,5/30 YNyn0-d1 3 2004 IEC GREECE – PPC T
10x1,25
TTOS – ONAN 3000 15/0,4 + 8 x1,25 YMd11 1 2004 IEC GREECE – PPC S/S
TTOS – +3x1.67 -
16000 132/33 Ynd-1 1 2004 IEC JORDAN -NEPCO S/S
ONAN/ONAF 9x1.67
+2x2.5 -
TTOS – ONAN 200 33/0.4 Znyn11 1 2004 IEC JORDAN - NEPCO S/S
2x2.5
TTOS - ONAN 30000 66/20 ?9x1,78 Ynd11 4 2004 IEC SYRIA – PEEGT S/S

TTO - ONAN 100 20/0,4 - Znyn1 4 2004 IEC SYRIA - PEEGT S/S

TTOS - OFAF 180000 161,25/15,75 +5; -15x0,93 YNd1 1 2004 IEC GREECE - PPC S/S
TTOS – GRECIA – PPC HERON
48000/67300 150/11,5 8x1,25 Ynd1 4 2004 IEC S/S
ONAN/ONAF THERMOELECTRICAL
TTOS – GREECE – PPC TERNA SA –
36000/60000/67300 150/11,5 3x2,5 Ynd1 1 2004 IEC S/S
ONAN/ONAF/OFAF GEK GROUP
TTOS – GREECE – PPC TERNA SA –
50000/83500/93500 150/11,5 3x2,5 Ynd1 1 2004 IEC S/S
ONAN/ONAF/OFAF GEK GROUP
BOSNIA & HERTEGOVINA-
ATOS-OFAF 400000 400/231/22 - Yn a-d5 1 2004 IEC T
ELECTROISTOK
+10 -5
TTOS-ONAN/ONAF 12000 157,5/6.3 Ymd1 1 2004 IEC GREECE-PPC S/S
+12,5 -17,5 GREECE-PPC AREVA
TTOS-ONAN/ONAF 40000/50000 150/21 Ynyn-0 1 2004 IEC S/S
GREECE
8x1,2 GREECE-PPC HERACLES
TTOS-ONAN/ONAF 30000/35000 150/15/6,6 Ynynod11 1 2004 IEC S/S
HGC
+6x1,25 - GREECE-PPC ABB GREECE
TTOS-ONAN/ONAF 40000/50000 150/15,75-21 Dyn1 1 2004 IEC S/S
10x1.25
TTOS – ONAF 100000 150/20-20 +12x1,25 Dy 1 2004 IEC GREECE-PPC S/S
ROMANIA- PFI VATECH
TTO - OFWF 216000 15,75/242 - Ynd5 2 2004 IEC P/P

P = ELECTRIC POWER PRODUCTION; S/S = ELECTRIC SUBSTATION; T = ELECTRIC POWER TRANSPORT P/P = POWER
PLANTS; D = ELECTRIC POWER DISTRIBUTION; MI = MINING INDUSTRY; S = SPECIAL

20
BLACK SEA GROUP POWER TRANSFORMERS

VOLTAGE
RATED OUTPUT VOLTAGE VECTOR NOS YEAR of APPLICABLE
TYPE CONTROL ( COUNTRY-CUSTOMER REMARKS
(KVA) (KV) GROUP (pcs) DELIVERY CODE/STD
%)
TTOS – +3x1,67 -
80000 132/33 Ynd1 3 2005 IEC JORDAN - NEPCO S/S
ONAN/ONAF 9x1,67
+2x2.5 -2x2.5
TTOS-ONAN 200 33/0.4 Znyn11 1 2005 IEC JORDAN - NEPCO Special
TTOS – +3x1,67 -
45000 132/33 Ynd1 2 2005 IEC JORDAN - NEPCO S/S
ONAN/ONAF 9x1,67
ROMANIA - PFI
TTO - OFWF 216000 15,75/242 - Ynd5 1 2005 IEC P/P
VATECH
TTOS – +7x1,33 -
20000/26000 33/11,5 Dyn1 2 2005 IEC GHANA S/S
ONAN/ONAF 8x1,33
231+8x1,25 ROMANIA /
ATOS-OFAF 200000/200000/60000 231/121/10,5 Yna0d5 7 2005 IEC S/S
231-8x1,25 TRANSELECTRICA
TTOS- +8x1,25 -
67500/78000 11-11,5/150 Ynd1 1 2005 IEC GREECE - PPC S/S
ONAN/ONAF 8x1,25
TTOS- +8x1,25 -
21250 19/6,3 Yny0 1 2005 IEC GREECE – PPC/RODAX S/S
ONAN/ONAF 8x1,25
TTOS- +12,5 -17,5
40000/50000 150/21 Ynyn-0 1 2005 IEC GREECE – PPC/AREVA S/S
ONAN/ONAF
TTOS- +8x1,25 -
53000/66000 161,25/6,3/6,3 Ynd1 1 2005 IEC GREECE – PPC/RODAX S/S
ONAN/ONAF 8x1,25
TTOS- +6x1,25 -
40000/50000 150/15,75-21 Dyn1 2 2005 IEC GREECE - PPC/VA TECH S/S
ONAN/ONAF 10x1,25
+10x1,25 -
ATOS 280000/280000/60000 400/157,5/30 YNyn0-d1 1 2005 IEC GREECE - PPC S/S
10x1,25
P = ELECTRIC POWER PRODUCTION; S/S = ELECTRIC SUBSTATION; T = ELECTRIC POWER TRANSPORT P/P = POWER PLANTS; D =
ELECTRIC POWER DISTRIBUTION; MI = MINING INDUSTRY; S = SPECIA

21
BLACK SEA GROUP POWER TRANSFORMERS

ELECTROPUTERE PRODUCT-POWER TRANSFORMER

280 MVA; 400 / 15 kV; OFAF

22
BLACK SEA GROUP POWER TRANSFORMERS

ELECTROPUTERE product . 90 MVA; 161/ 15.75kV/kV; OFAF

23
BLACK SEA GROUP POWER TRANSFORMERS

ELECTROPUTERE product. 72 MVA; 21/6.3/6.3 kV/kV/kV; ONAN/ ONAF

24
BLACK SEA GROUP POWER TRANSFORMERS

ELECTROPUTERE product. 40/ 50 MVA; 150/ 21 kV/kV; ONAN/ ONAF.

25
BLACK SEA GROUP POWER TRANSFORMERS

ELECTROPUTERE product. 18 MVA; 21/ 6.3 kV/ kV; ONAN

26
BLACK SEA GROUP POWER TRANSFORMERS

ELECTRICAL NETWORK INTERCONNECTING TRANSFORMERS

Overall Overall
Rating Voltage Uk Po Pk Connection Wdg.
Weight Dimensions
(MVA) (kV) (%) (kW) (kW) group Material
(kg) (LxWxH)(mm)
63/44 132 / 34.5 12.5 39 265 YNd1 Cu 90.000 8200x5100x6000

27
BLACK SEA GROUP POWER TRANSFORMERS

THREE PHASE POWER TRANSFORMERS WITH NO LOAD TAP CHANGING

Overall
Rating Voltage Uk Po Pk Connection Wdg. Overall Dimensions
Weight
(MVA) (kV) (%) (kW) (kW) group Material (LxWxH)(mm)
(kg)
10.5/
138
135 13.83 68 315 Y0d-11 Cu 125.000 8000x5600x6500
±2x2.5%

10.5/
420
160 17 89 445 YNd-1 Cu 230.000 12900x6500x10500
±2x2.5%

15/
420
160 13 89 445 YNd-1 Cu 230.000 12900x6500x10500
±2x2.5%

18/
400
250 13.83 130 570 YNd-1 Cu 290.000 12900x6500x10900
±2x2.5%

(45)/60/75 11.5/132 14 34 224 YNd-1 Cu 112.000 8000x5600x6900

28
BLACK SEA GROUP POWER TRANSFORMERS

29
BLACK SEA GROUP POWER TRANSFORMERS

30
BLACK SEA GROUP POWER TRANSFORMERS

31
BLACK SEA GROUP POWER TRANSFORMERS

32
BLACK SEA GROUP POWER TRANSFORMERS

33
BLACK SEA GROUP POWER TRANSFORMERS

DOUBLE WOUNDED, THREE PHASE POWER TRANSFORMERS WITH


ON LOAD VOLTAGE CONTROL

Overall Overall
Rating Voltage Uk Po Pk Connection Wdg.
Weight Dimensions
(MVA) (kV) (%) (kW) (kW) group Material
(kg) (LxWxH)(mm)
63/50/25 132/33/11.5 19 31 233 YNd1yn0 Cu 102500 8500x5400x6500

34
BLACK SEA GROUP POWER TRANSFORMERS

35
BLACK SEA GROUP POWER TRANSFORMERS

THREE PHASE POWER TRANSFORMERS FOR THE INTERNAL


SERVICES OF THE POWER PLANT

Overall
Rating Voltage Uk Po Pk Connection Wdg. Overall Dimensions
Weight
(MVA) (kV) (%) (kW) (kW) group Material (LxWxH)(mm)
(kg)
132±2x2.5%/6.6
56 19 28 189 YNd-11 Cu 86.000 6900x4300x6000

16 33±9x1.78%/6.3 10 10.5 75 YNd-1 Cu 37.000 4700x3150x3500


12.5 132±8x1.25%/6.9 10.65 10 65 YNd-1 Cu 40.000 5000x4000x4800
8 15±2x2.5%/6.9 10 7.5 50 Dyn-1 Cu 18.000 3800x2350x3600
8 132±2x2.5%/6.6 10 7 50 YNyn0 Cu 32.000 4500x3500x4200
3/3.36 11.5±2x2.5%/0.4 5.75 2.9 24 Dyn-1 Cu 5.100 3150x2100x2550
4/4.48 11.5±2x2.5%/3.3 5.75 5.5 33 Dyn-1 Cu 5.100 3150x2600x3000
5 10.5±2x2.5%/6.6 7.5 6.2 38 Dyn-1 Cu 5.100 2900x2800x3050
1.6 11±2x2.5%/0.4 5.75 2.2 14.96 Dyn-11 Cu 5.100 2150x1950x2400

36
BLACK SEA GROUP POWER TRANSFORMERS

37
BLACK SEA GROUP POWER TRANSFORMERS

38
BLACK SEA GROUP POWER TRANSFORMERS

39
BLACK SEA GROUP POWER TRANSFORMERS

40
BLACK SEA GROUP POWER TRANSFORMERS

41
BLACK SEA GROUP POWER TRANSFORMERS

SUPPLY MOBILE TRANSFORMER,

for emergency cases where have to solve the problem of


power transformer failure :

10MVA;33/11 kV power transformer


20MVA;33/11 kV power transformer

The supply consists of:


-the power transformer loaded on the truck and well fitted
-the low-bed semitrailler is dedicated to be hooked to a horseshoe-
shaped coupling device at a rear of the engine drive; 4 axles with air
hydraulic suspension.
Accessories: ABS breaking system; 24 V electrical part.
-the transformer and the truck are well earthed
-the spare parts of the power transformer
-the spare parts of the truck
General dimensions are:
(a)total length:13 700…12 200 mm
(b)width: 2500 mm
(c)total height:4 800…4 500 mm
(d) max. weight:58 000…45 50

Mobile substation. 20MVA(10MVA); 33/11kV. Type SJ44 (SJ35)

42
BLACK SEA GROUP POWER TRANSFORMERS

BLACK SEA GROUP PARTNER IN SLOVENIA:

ETRA 33 factory - Slovenia:

◘ Power transformers;

◘ Step –up Transformers;

◘ Distribution transformers;

◘ Special transformers;

43
BLACK SEA GROUP POWER TRANSFORMERS

ETRA 33 TRANSFORMERS FACTORY


(SLOVENIA)

REFERENCE LIST OF TRANSFORMERS


LEGEND of symbols:

ANT 3-phase autotransformer with OFF-LOAD tap changer


ART 3-phase autotransformer with ON-LOAD tap changer
BT 3-phase generator (block) transformer
NT,VT 3-phase transformer with OFF-LOAD tap changer
RT 3-phase transformer with ON-LOAD tap changer
RNT 3-phase transformer with ON-LOAD tap changer and OFF-LOAD tap
Changer
ERT single phase transformer with ON-LOAD tap changer
M transformer is filled with organic ester MIDEL 7131

Voltage Ratio
Rated Year
in [kV],
Type Power Qty. of Deli Country Customer
Tappings and
[MVA] very
Vector Group
BT 150 121/13.8; 1 2003 Slovenia Termoelektrarna Trbovlje
YNd5
RT 150 220±12x1.25%/ 1 2000 Slovenia Elektro Slovenija,
115/10.5; Ljublajana ***
YNyn0 d5
RT 80 138±9x1,67%/5 1 2004 Sweden Fortum Distribution AB,
2/20; Holmagärde
YNyn0(d5)
BT 75 121/10.65; 1 2001 Slovenia Dravske elektrarne
YNd5 Maribor, HE Formin ***
RT 65 130±10x1.42%/ 1 2001 Norway Stratnett SF SS Mosjøen
66/22;
YNd11d11
UT 63,12 112/0.7001+ 1 2004 Slovenia Talum Kidričevo
0,7071/20;
YNy0d11 d11

NT 63 145±2x2,5%/ 1 2006 Sweden Billerud AB, Gruvöns Bruk


10,7; YNd11
RT 63 110±10x1.5%/3 2 2005 Yugoslavia Elektroprivreda Crne Gore
6.75/10.5,
YNyn0(d5)
RT 60 66±6x1,5%/22 1 2006 Norway Nord Trøndelag
YNyn0 Elektrisitetsverk FKF

44
BLACK SEA GROUP POWER TRANSFORMERS

Voltage Ratio
Rated Year
in [kV],
Type Power Qty. of Deli Country Customer
Tappings and
[MVA] very
Vector Group
NT 55 44±2x2,5%/ 1 2006 Sweden Billerud AB, Karlborg
10,5; YNd11
NT 55 116±2x2,5%/ 1 2001 Slovenia Soške elektrarne Nova
10.5; YNd5 Gorica, HE Doblar
RT 50 76±9x1,33%/22, 1 2006 Sweden Fortum Distribution AB
5, YNyn0
NT 50 115±1x5%/ 1 2004 Slovenia Termoelektrarna –
10.5; YNd5 Toplarna Lubljana
RT 50 145±9x1,67%/1 1 2003 Sweden Fortum Distribution AB,
1,5/1,5; Hagfors
YNyn0(d11)
RT 50 77±9x1.67%/ 3 2001 Sweden Hallsta pappersbruk
10.5; YNyn0
RT 48 132±9x1.67%/1 1 2003 Sweden Stora enso Newsprint,
1, YNd5 Hylte Bruk
RT 40 126±13x1,154% 1 2006 Hungary ETV-Eröterv Rt
/11, YNd11
NT 40 110±1x2,5%/6,3 2 2006 Slovakia U.S.Steel Košice
, YNd1
RT 40 145±9x1,67%/1 1 2006 Sweden Billerud AB, Gruvöns Bruk
1, YNyn0
RT 40 145±9x1,67%/1 3 2005 Sweden Billerud AB, Gruvöns Bruk
1, YNyn0
RT 40 110±12x1.33%/ 2 2005 Slovenia Elektro Maribor, RTP Ptuj
21(10.5)/10.5,
YNyn6(d5)
RT 40 110±10x1.5%/3 1 2005 R/F of BiH Elektroprivreda BiH TPP
6.75/6.3, Tuzla
YNyn0d5
RT 40 110±10x1.5%/1 2 2005 Yugoslavia Elektroprivreda Crne Gore
0.5/10.5,
YNyn0(d5)
RT 40 132±8x1,67%/2 2 2002 Norway Tafjord Kraftnett AS
2/22,
YNyn0(d11)
RT 40 132±10x1,2%/1 1 2002 Norway Ǿstnett AS
8,6(22) , YNyn0
RT 40 65±8x1,5%/23, 1 2001 Norway Trønder Energi Nett,
YNyn0 Trondheim
NT 35 33±2.5%/11, 4 2005 Saudi Siemens DDIT for
YNd11 Arabia Yamama Project
NT 35 33±2.5%/11, 5 2004 Saudi Siemens DDIT for
YNd11 Arabia Yamama Project

45
BLACK SEA GROUP POWER TRANSFORMERS

Voltage Ratio
Rated Year
in [kV],
Type Power Qty. of Deli Country Customer
Tappings and
[MVA] very
Vector Group
RT 31,5 132±9x1,67%/6 1 2004 Iceland Landsvirkjun, Bessastadir
6(33)/11, Substation
YNyn0d11
RT 31,5 110±12x1.33%/ 2 2004 Slovenia Elektro Ljubljana
21/10.5,
YNyn6(d5)

RT 30 45±8x1,67%11, 2 2005 Sweden Jönköping Energi Nät AB


5/11,5,YNyn0
RT 30 65±8x1,5%/23/1 1 2004 Norway Trønder Energi Nett AS
1,5;
YNyn0(d5)
RT 30 67(48)±10x1%/2 1 2002 Norway Østnett AS
3(10,6);
YNyn0
RT 30 65±8x1,5/23,YN 1 2002 Norway Trønder Energi Nett,
yn0 Trondheim
RT 30 67(48)±10x1%/2 1 2001 Norway Østnett AS
3(10,6);
YNyn0
RT 25 110±8x1.25%/2 1 2004 Romania ROMENERGO Romania
1,YNyd11
RT 25 110±8x2%/6.3,Y 2 2004 Romania OLTCHIM Romania
Nyd11
RT 25 67(48)±10x1%/2 1 2002 Norway Østnett AS
3(10,6);
YNyn0
RT 25 33±8x1.67%/ 5 2004 Saudi Siemens DDIT for
6.3;Dyn11 Arabia Yamama Project

46
BLACK SEA GROUP POWER TRANSFORMERS

47
BLACK SEA GROUP POWER TRANSFORMERS

ETRA 33 TRANSFORMER FACTORY.

48
BLACK SEA GROUP POWER TRANSFORMERS

BLACK SEA GROUP PARTNER IN SLOVAKIA:

BEZ TRANSFORMATORY factory –


Slovak Republic

◘ Distribution transformers:

-Oil filled transformers;


-Dry and cast resin transformers;

◘ Ecological cast resin transformers;

◘ Amorphous transformers

BEZ-ETD TRANSFORMATORY factory –


Czech Republic

◘ Power Transformers;

◘ Step –up Transformers;

◘ Service( repair works; technical activities );


49
BLACK SEA GROUP POWER TRANSFORMERS

ETD Transformers Factory


(former SKODA ENERGO)
– Czech Republic

REFERENCE LIST OF TRANSFORMERS

TRANSFORMERS UP TO 72, 5 kV

Year of Country of No. of


Power plant Output MVA Voltage ratio kV
manufacture destination pcs
Czech
2001 Foxconn 2 16 35/6,3
Republic
Czech
2004 Strekov 1 16 23/10,5 kV
Republic
De Eendracht
2004 Netherlands 1 16 20/10,5
Karton
Czech
2005 Vyskov u Loun 1 16 23/10,5
Republic
2005 Cuba 15 20 13,8\34,5
Slovak
2005 Zilinska teplar 2 16 22/6.3
Republic
Slovak
2005 Zilinska teplar 1 32 22/6.3
Republic
2006 Pakistan MAN SRN 1 25 21/11
Czech Sokolovska
2006 1 25 10,5/6,6
Republic uhelna Vresova
2006 Cuba BEZ Transf 2 20 34,5/13,8

50
BLACK SEA GROUP POWER TRANSFORMERS

Transformers up to 120 kV

Year of Country Voltage ratio


Power plant No. of pcs Output MVA
manufacture of destination kV/kV
Slovak 1 40 110/23
2005
Republic Sukany
Czech 1 40 115/23
2005 Republic Vyskov
Czech Opocinek 1 40 110/36,75
2005
Republic
Czech Prostejov 1 40 110/23
2005
Republic
Czech CEZ, SCE 1 40 110/23
2005
Republic
Czech EZ Praha/Hostejn 2 16 110/23
2005
Republic
Czech PRE Praha/Zlicin 1 40 110/23,25
2005
Republic
Slovak ZS Brno/Breclav 1 16 110/23
2005
Republic Gemerska Horka
Slovak Kechnek 2 40 110/23
2005
Republic
Slovak Sucany 1 25 110/23
2005
Republic
Czech OHL ZS / Breclav 1 12,5 110/27
2006
Republic
Czech VaTech/Krupta 1 40 110/23
2006
Republic
Czech CEZ/ Razecek 1 40 110/23
2006
Republic
Czech OHL ZS/Grygov 2 25 110/23
2006
Republic
Slovak SSE Zilina 1 40 110/23
2006
Republic
Czech ABB/Kladno 1 60 110/11,5
2006
Republic
Czech Sokolovska uhelna 1 63 110/1,5
2006
Republic Vresova
Czech CEZ/Rokycany 1 40 110/23
2006
Republic
Czech CEZ/Vsetin 1 50 110/23
2006
Republic
Czech JM montze 1 25 110/23
2006
Republic Cernovice

51
BLACK SEA GROUP POWER TRANSFORMERS

Transformers up to 145 kV

Year of Country of No. of Voltage ratio


Power plant Output MVA
manufacture destination pcs kV/kV
Czech 1 91 121/11
2004 Republic Trebovice
Slovak 3 63 121/10,5
2005 Liptovska Mara
Republic
Slovak 1 63 121/10,5
2006 Liptovska Mara
Republic

Transformers up to 240 kV

Year of Country of No. of Voltage ratio


Power plant Output MVA
manufacture destination pcs kV/kV
Czech 4 220/3 242/15/15
2000
Republic VE Orlik
Czech Actherm 1 25 220/23/(6,3)
2003 Republic

2004 Egypt Egyptalum 2 150 220/132/11

Transformers up to 420 kV

Year of Country of No. of Voltage ratio


Power plant Output MVA
manufacture destination pcs kV/kV
1 410 410/22
2000 Yugoslavia Kolubara B
Bangladesh Ashuganj 1 200/3 245/15,75
2001

52
BLACK SEA GROUP POWER TRANSFORMERS

53
BLACK SEA GROUP POWER TRANSFORMERS

54
BLACK SEA GROUP POWER TRANSFORMERS

55
BLACK SEA GROUP POWER TRANSFORMERS

56
BLACK SEA GROUP POWER TRANSFORMERS

57
BLACK SEA GROUP POWER TRANSFORMERS

58
BLACK SEA GROUP POWER TRANSFORMERS

59
BLACK SEA GROUP POWER TRANSFORMERS

Partners of BLACK SEA GROUPfor services concerning to


Power Transformers.

ICMET craiova-Researche institute-


TEST INSULATING MATERIALS

ICMET CRAIOVA -ROMANIA

S ERVICES OFFERED

High voltage tests for HV equipment


(transformers, cables, switchgears, GIS, etc.) High voltage tests on site:
inside the electromagnetic screened hall of ICMET
-Full wave (1.2 / 50 s ) and tail chopped wave voltage
impulse tests (between 2 and 8 s) at voltages up to
4200 kV and energy 336 kWs

AC sparkover voltage test of arresters


- Applied voltage tests at frequencies between 25 and up to 60 kV
150 Hz up to 800 kV

- AC or DC voltage test of high voltage


- Single and three-phase induced voltage test, 5 MVA, 2 cables up to 100 kV
min.

- AC voltage test of SF6 enclosed


- DC voltage tests uo to 1200 kV 30 mA, up to 1200 kV stations up to 250 kV (resonant
equipment)

- Oscillating switching impulse tests


- Induced voltage test of distribution
transformers
- Aperiodic switching impulse tests up to 2600 kV
- Switching impulse test for instrument
and power transformers by
- External insulation test under artificial rain for electromagnetic induction
equipment up to 400 kV rated voltage

- Partial discharge measurement at


- Partial discharge and radio interference instrument and power transformers by
measurements electric and ultrasonic method.

- Combined voltage tests: LI - AC, SI - AC, DC - LI, DC -


SI

60
BLACK SEA GROUP POWER TRANSFORMERS

ICMET CRAIOVA -ROMANIA


Reference list:

I. Three Phases Power Transformers


Type and routine tests
S(MVA) / U (kV) Factory Made for

(0.063; 0.1; 0.16; 0.2; 0.2; 0.4; 0.63; 0.8) MVA / ABB Bucharest Dubay
(20; 20; 20; 20; 33; 20; 20; 6) kV Romania
Sudan
Syria
1 MVA / 6.6 kV ELECTROPUTERE Bangladesh
(1.5; 5; 10; 15; 20) MVA / (34.5; 69; 69; 69; 69) kV ELECTROPUTERE Brazil
(0.15; 0.25; 20; 50) MVA / (15; 22; 115; 115) kV ELECTROPUTERE Cambodgia
176 MVA / 72 kV ELECTROPUTERE Canada
(0.4; 1; 6.3; 16; 40; 63; 90; 405)MVA / ELECTROPUTERE China
(6; 6; 35; 38; 24; 110; 345; 363) kV
(1.6; 1.6) MVA / (6; 33) kV ELECTROPUTERE Cuba
(10; 31.5; 38) MVA / (66; 132; 154) kVA ELECTROPUTERE Cyprus
(16; 20; 21; 25) MVA / (132; 66; 132; 66) kV ELECTROPUTERE Egypt
20 MVA / 33 kV ELECTROPUTERE Ghana
(10; 18.75; 25; 50; 60; 72; 72; 90)MVA / ELECTROPUTERE Greece
(150; 66; 150; 150; 150; 161.25; 21; 161.25) kV
8 MVA / 54 kV ELECTROPUTERE India
(10; 18; 86) MVA / (150; 11.5; 156.8) kV ELECTROPUTERE Indonesia
(0.2; 63) MVA / (33; 132) kV ELECTROPUTERE Jordan
(1; 7.5; 15; 30; 45; 90) MVA / ELECTROPUTERE Malaysia
(11; 33; 33; 33; 132; 132) kV
(0.3; 50; 75; 100; 100; 100) MVA / ELECTROPUTERE Philippines
(13.8 138; 138; 138; 138) kV
(400; 250; 216) MVA / (400; 400; 242) kV ELECTROPUTERE Romania
4 MVA / 10 kV ELECTROPUTERE Russia
(0.1; 0.25; 0.4; 0.63; 1; 2.5; 16; 20; 30; 80; 125) MVA ELECTROPUTERE Syria
/ (20; 66; 20; 20; 20; 66; 66; 66; 230; 230) kV

(2.5; 40; 63) MVA / (35; 150; 150) kV ELECTROPUTERE Sudan


(20; 40) MVA / (132; 132) kV ELECTROPUTERE Uganda
(15; 20; 25; 31.5; 50; 65) MVA / ELECTROPUTERE Turkey
(154; 30; 154; 132; 154; 154) kV
200 MVA / 231 kV ELECTROPUTERE Yugoslavia

61
BLACK SEA GROUP POWER TRANSFORMERS

Partners of BLACK SEA GROUPfor services concerning to


Power Transformers.

ICEMENERG SA-Rehabilitation and Research Institute


for National Energy System (Romania).

ICEMENERG SA offers professional services, as:

◘ Services in Power Substations field for Apparatus andTransformers insulation and


life duration assessment,
◘ Prophylactic and Routine Tests for electrical Equipment in Primary and Secondary
substations,
◘ Strength assessment of the overhead and underground Lines,
◘ Tests and Measurements concerning switching overvoltages, overcurrents, Electric
and Magnetic fields and their influence to the electric Networks.

References:

Dielectric properties of power transformers insulation by dielectric loss (tgd)


measurement in the automate mode.

62
BLACK SEA GROUP POWER TRANSFORMERS

System front panel.

Diagnose result.

Equipment for quantity evaluation of moisture content of a Paper-Oil


transformer insulation, based on the bias factor.

Three Phase RC group.


Switching overvoltage protection for Generators and Motors

63
BLACK SEA GROUP POWER TRANSFORMERS

Partners of BLACK SEA GROUPfor services concerning to


Power Transformers.

EMON Electric as erection company -Romania.

EMON Electric has a large experience in Primary / Secondary


Electrical Distribution Substations with Projects development in
Romania and Overseas. EMON Electric Company is certified by
Germanischer Lloyd Certification GmbH,20459 Hamburg for the
application of the quality system according to DIN EN ISO 9001:2000.
Business Areas:
-Hitgh Voltage up to 400 kV Power Substation,
-Hitgh Voltage up to 400 kV Power Lines,
-Medium Voltage Power Substation and power Network

CLIENT PROJECT
ELECTRICA MUNTENIA NORD SA –A SDFEE Deviation works of 20 kV electrical line – PT Pompe
PLOIESTI – ACM 4 Azuga
SIEMENS AG – TRANSPORTATION SYSTEMS - ES Columbia HV outgoings and cable connection to
in progress Substation Ploiesti Vest
220/110/20kV Targoviste Substation Retrofit – 220-
TRANSELECTRICA SA – AREVA – in progress
110Kv switchgears – primary switching equipment
CSI – V1, 20/0,4 KV, 2*630KVA concrete envelope
ELECTROEXPERT
substation, Busteni DUCATI hall electrical power supply.
ELECTRICA MUNTENIA NORD SA – SDFEE
CHIRESCU PENSION electrical power supply
PLOIESTI
ELECTICA SA – SISE MUNTENIA NORD 110/20kv Busteni station warning installation repair
EUROELECTRIC SA BUCURESTI CSI- V0 concrete envelope substation
CSI-V3 20/0,4 KV, 630KVA Fagaras concrete envelope
CD ELECTRIC SRL BRASOV
substation
CSI-V0, 20/0,4 KV, 160KVA concrete envelope
ELECON SA BRASOV
substation
Aerial concrete envelope substation current repair and
CN CFR SA – REGIONALA CFR BUCURESTI low voltage connector for VALEA CALUGAREASCA
RAILWAY
TRANSELECTRICA SA – in progress 200 MVA Targoviste electrical station, AT3 current repair
2*630KVA DUCATTI concrete envelope substation
DUCATTI ENERGIA ROMANIA SA BUSTENI
service
CSI-V2 20/0.4 KV 1000 KVA concrete envelope
BEN ELECTRO SERV SRL BRAILA
substation
ELECTRICA MUNTENIA NORD SA – SDFEE PLOIESTI VEST substation electrical power supply –
PLOIESTI – in progress 110 kv Columbia station works
ELCO BUCURESTI SA 1000Kva 10/0,4 Kv metallic envelope substation
MULTIPROD ENERGO SRL BUZAU 6/0,4 KV 250 KVA concrete envelope substation

64

You might also like