Control Valve Seat Leakage Classifications
Control Valve Seat Leakage Classifications
No test required
I --- --- --- provided user and
supplier so agree.
Pressure applied to
valve inlet, with
3-4 bar (45−60 outlet open to
psig) or max. atmosphere or
Air or water at
0.5% of rated operating connected to a low
II 10−52_C
capacity differential, head loss
(50−125_F)
whichever is measuring device,
lower. full normal closing
thrust provided by
actuator.
0.1% of rated
III As above As above As above.
capacity
0.01% of rated
IV As above As above As above.
capacity
Pressure applied to
valve inlet after
filling entire body
0.0005ml per
cavity and
minute of water
Max. service connected piping
per inch of orifice
pressure drop with water and
diameter per psi
across valve plug, stroking valve plug
differential Water at 10−52_C
V not to exceed closed. Use net
(5 X 10−12m3 per (50−125_F)
ANSI body rating, specified max.
second of water
or lesser pressure actuator thrust, but
per mm of orifice
by agreement. no more, even if
diameter per bar
available during
differential).
test. Allow time for
leakage flow to
stabilize.
Pressure applied to
valve inlet. Actuator
should be adjusted
3.5 bar (50 psig) to operating
Not to exceed or max. rated conditions specified
amounts shown Air or nitrogen at differential with full normal
VI in following table 10−52_C pressure across closing thrust
based on port (50−125_F) valve plug, applied to valve
diameter. whichever is plug seat. Allow
lower. time for leakage
flow to stabilize and
use suitable
measuring device.
93
Chapter 5. Control Valve Selection