Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

ALTA SPATIAL

KARUHATAN ROAD, VALENZUELA CITY

COMPARISON FOR WATERLINE PIPES SPECS


REQUIRED THICKNESS (SERIES 8 or CLASS 150), mm
PIPE NELTEX
DIAMETER
CWSI FLI REMARKS
(PNS 65:1993)
(ISO 4422) (AWWA C-900)
*based on test result submitted by NELTEX

50 3.8 3.6 3.735 Compliant with FLI specs but not with CWSI
75 5.4 5.1 5.415 Compliant with FLI specs but not with CWSI
100 6.6 6.3 6.585 Compliant with FLI specs but not with CWSI
150 9.5 9.1 9.565 Compliant with FLI specs but not with CWSI
200 13.4 12.8 13.07 Compliant with FLI specs but not with CWSI
250 16.6 15.9 16.3 Compliant with FLI specs but not with CWSI
300 18.7 17.9 18.575 Compliant with FLI specs but not with CWSI