Dania Air Control System Factory

P.O. Box 60479 Riyadh 11545 K.S.A.


SQUARE / ROUND
FIRE / SMOKE DAMPERS
Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385
Email: dania@sunaid.com.sa
Dania Air Control System Factory
P.O. Box 60479 Riyadh 11545 K.S.A.
Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385
Email: dania@sunaid.com.sa

FIRE / SMOKE DAMPERS SFD-20R SERIES


SFD-20R (MOTORIZED)
COMBINATION FIRE / SMOKE DAMPERS
2 HOUR RATED
(by an Independent Laboratory)
U.L. 555 2hr. Fire Endurance Test Rated
U.L. 555S CLASS II Leakage Test Rated
Shock Impact Tested for 30g and 51g
STANDARD CONSTRUCTION
FRAME : 4” wide 16 Ga. Galvanized steel sheet , Duct
Insertion type HAT Frame provides rigidity and
strength.
SLEEVE : 16 Ga. Galvanized steel, min. 300 mm depth.
ANGLE FLANGE : Standard 32 x 32 mm x 3mm thk Flange
on both ends of Sleeves
BLADE : 16 Ga. Galvanized steel Max. 6” spacing.
Parallel action Designed with reinforced 3 grooves
for more strength and overlap coverage.
Max. length is 48”.
SMOKE SEALS: Vinyl blade smoke seals and Stainless
steel jamb seals for U.L. 555S CLASS II Leakage VARIATION FEATURES :
Classification.
ADAPTOR : Ga.16 Galv. Steel Spigot Adaptor for
LINKAGES : 14 Ga. Galv. steel formed brackets and link Round or Oval Duct.
bars, face linkages inside of air stream.
BLADES: Damper 10”H to12” H with 2 blades Opposed
AXLES & STRAP : ½” ø galvanized steel with axle blade action only.
straps bolted to blades.
DRIVE SHAFTS:
BEARINGS : Bronze Sleeve Bearings. A. Jack Shaft and Linkages.
CLOSURE SPRING : 10mm Ø x 1mm Stainless steel coil B. Full Length Drive Shaft .
Spring mounted on 16 Ga. Galv. bracket. LONGER SLEEVE DEPTH: Sleeve wider than 12”.
DRIVE SHAFT : ¾” Ø x ½” Ø Step-up Direct Power drive AXLES: Stainless steel.
shaft assembly to actuator / motor.
DUCT FLANGE : in place of Std. Angle Flange.
MOTOR / ACTUATOR : For motorized operation assembled
with a wide range of electrical actuators “ BELIMO”
NOTE :
or SIEMENS” readily available as required.
For proper operation all dampers must be installed square & free from racking.
SIZES : Made to exact size as required. Any dampers installed over 1 section wide and 1 section high shall have
appropriate bracing at every horizontal mullion and vertical bracing min. 8’0
Max. size 48”W x 96”H : Divider frame shall be provide for
O.C. Fire Dampers are designed for operation with blades running
dampers over max. size. horizontally.
Min. size – 6”W x 5”H: Dampers 11 inches high and smaller
shall be single blade type. Designs are subject to change without prior notice.
Dampers 12 inches high and larger shall be multi-blade type.

IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Designs are subject to change without prior notice.
Page 1
Dania Air Control System Factory
P.O. Box 60479 Riyadh 11545 K.S.A.
Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385
Email: dania@sunaid.com.sa

FIRE
FIRE DAMPERS
DAMPERS SFD-20R
SFD-20R

FIRE DAMPERS
2 HOUR RATED
(by an Independent Laboratory)
SFD-20R (FUSIBLE LINK TYPE)
MULTI-BLADES FIRE DAMPER
U.L. 555 2hr. Fire Endurance Test Rated
STANDARD CONSTRUCTION
FRAME : 4” wide 16 Ga. Galvanized steel sheet , Duct
Insertion type HAT Frame provides rigidity and
strength.
BLADE : 16 Ga. Galvanized steel Max. 6” spacing.
Parallel action Designed with reinforced 3 grooves
for more strength and overlap coverage.
Max. length is 48”.
BLADE STOP : 16 Ga. Galvanized Steel
BLADE CATCH: 1.6 mm Thk. Stainless Steel Flat Spring.
FUSIBLE LINK : U. L. Approved fuse.
Standard 160°F (others available)
AXLES & STRAP : ½” ø galvanized steel with axle
straps bolted to blades.
LINKAGES : 14 Ga. Galv. steel formed brackets and link
bars, face linkages inside of air stream.
BEARINGS : Bronze Sleeve Bearings.
CLOSURE SPRING : 10mm Ø x 1mm Stainless steel coil
Spring mounted on 16 Ga. Galv. bracket.
SIZES : Made to exact size as required.
Max. size 48”W x 96”H : Divider frame shall be provide for
dampers over max. size.
Min. size – 6”W x 5”H: Dampers 11 inches high and smaller
shall be single blade type.
Dampers 12 inches high and larger shall be multi-blade type.

NOTE :
For proper operation all dampers must be installed square
& free from racking. Any dampers installed over 1 section
wide and 1 section high shall have appropriate bracing at
every horizontal mullion and vertical bracing min. 8’0 O.C.
Fire Dampers are designed for operation with blades
running horizontally.

IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Designs are subject to change without prior notice.
Page 2
Dania Air Control System Factory
P.O. Box 60479 Riyadh 11545 K.S.A.
Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385
Email: dania@sunaid.com.sa

FIRE DAMPERS RFD-50 SERIES


U.L. Classified FIRE DAMPERS
1-1/2 HOUR RATED
RFD – 50 SERIES
U.L. 555 1-1/2 Hr. Fire Endurance Rated

CURTAIN TYPE STANDARD CONSTRUCTION


VERTICAL OR HORIZONTAL TYPE,
100% FREE AREA
FRAME : 20 ga. galvanized steel
BLADE : 22 ga. Galvanized steel blades
with interlocking Joints.
SPIGOT : 20 ga. Galvanized steel
(available in Square, Rectangular, Round or
Oval Spigots)
FUSIBLE LINK : U. L. Approved fuse.
Standard 160°F (others available)
MIN. SIZE : 4”W x 4” H
MAX. SIZE : 36"W x 36"W (Single Section)
FOR HORIZONTAL TYPE UNITS :
(Specify if Horizontal Mounted) SPIGOT OPTIONS :
BLADE LOCK : 16 ga. Galvanized steel blade lock.
SPRING : Stainless steel closure springs for
Horizontal type units.

VARIATIONS :
1. Special finishes.
2. Special made sleeve or collar. STYLE (RE)
Square or Rectangular
3. Special materials, Stainless Steel. spigot
4. Special micro switch attachments.

HOW TO SPECIFY :
1. Model / Type.
2. Mounting type.
3. Duct size.
4. Spigot type.
STYLE (R)
5. Quantity.
Round or Circular spigot

STYLE (O)
Flat Oval spigot

DIMENSIONAL DETAIL
IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Designs are subject to change without prior notice.
Page 3
Dania Air Control System Factory
P.O. Box 60479 Riyadh 11545 K.S.A.
Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385
Email: dania@sunaid.com.sa

FIRE DAMPERS SFD-70 SERIES


U.L. Classified FIRE DAMPERS
1-1/2 HOUR RATED
SFD - 70 SERIES
U.L. 555 1-1/2 Hr. Fire Endurance Rated

CURTAIN TYPE STANDARD CONSTRUCTION


VERTICAL OR HORIZONTAL TYPE
WITH BLADES IN AIR STREAMS
85% Free Area, Duct Insertion Type
FRAME : 20 ga. galvanized steel
BLADE : 22 ga. Galvanized steel blades
with interlocking Joints.
FUSIBLE LINK : U. L. Approved fuse.
Standard 160°F (others available)
MIN. SIZE : 4”W x 4” H
MAX. SIZE : 36"W x 36"W (Single Section)
FOR HORIZONTAL TYPE UNITS :
(Specify if Horizontal Mounted)
BLADE LOCK : 16 ga. Galvanized steel blade lock.
SPRING : Stainless steel closure springs for
Horizontal type units.

VARIATIONS :
1. Special finishes.
2. Special made sleeve or collar.
3. Special materials, Stainless Steel.
4. Special micro switch attachments.
HOW TO SPECIFY :
1. Model / Type.
2. Mounting type.
3. Duct size.
4. Spigot type.
5. Quantity.

DIMENSIONAL DETAIL

IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Designs are subject to change without prior notice.
Page 4
Dania Air Control System Factory
P.O. Box 60479 Riyadh 11545 K.S.A.
Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385
Email: dania@sunaid.com.sa

FIRE DAMPERS SFD-70 SERIES

U.L. Classified FIRE DAMPERS


1-1/2 HOUR RATED
SFD - 70 HC
U.L. 555 1-1/2 Hr. Fire Endurance Rated
CURTAIN TYPE STANDARD CONSTRUCTION
VERTICAL OR HORIZONTAL TYPE
WITH HEAD CAP
100% Free Area Duct Insertion Type
FRAME : 20 ga. galvanized steel
BLADE : 22 ga. Galvanized steel blades
with interlocking Joints.
FUSIBLE LINK : U. L. Approved fuse.
Standard 160°F (others available)
MIN. SIZE : 4”W x 4” H
MAX. SIZE : 36"W x 36"W (Single Section)
FOR HORIZONTAL TYPE UNITS :
(Specify if Horizontal Mounted)
BLADE LOCK : 16 ga. Galvanized steel blade lock.
SPRING : Stainless steel closure springs for
Horizontal type units.

VARIATIONS :
1. Special finishes.
2. Special made sleeve or collar.
3. Special materials, Stainless Steel.
4. Special micro switch attachments.
HOW TO SPECIFY :
1. Model / Type.
2. Mounting type.
3. Duct size. MOUNTING DETAIL
4. Spigot type.
5. Quantity.

DIMENSIONAL DETAIL

IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Designs are subject to change without prior notice.
Page 5
Dania Air Control System Factory
P.O. Box 60479 Riyadh 11545 K.S.A.
Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385
Email: dania@sunaid.com.sa

FIRE DAMPERS

RFD-50

SFD-70

SFD-70 w/ Head Cap

IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Design and Sizes are subject to change without
Page 6
Dania Air Control System Factory
P.O. Box 60479 Riyadh 11545 K.S.A.
Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385
Email: dania@sunaid.com.sa

FIRE DAMPERS HEAD SIZING

RFD-50 SFD-70 w/ Head Cap

H H H1 Ho H H H1 Ho
Listed Size Actual Size Head Size Overall Size Listed Size Actual Size Head Size Overall Size
(mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm)
150 144 28 197 150 144 28 172
175 169 32 226 175 169 32 201
200 194 32 251 200 194 32 226
250 244 44 313 250 244 44 288
300 294 50 369 300 294 50 344
350 344 54 423 350 344 54 398
400 394 62 481 400 394 62 456
450 444 66 535 450 444 66 510
500 494 74 593 500 494 74 568
550 544 78 647 550 544 78 622
600 594 86 705 600 594 86 680
650 644 90 759 650 644 90 734
700 694 98 817 700 694 98 792
750 744 110 879 750 744 110 854
800 794 114 933 800 794 114 908
850 844 122 991 850 844 122 966
900 894 126 1045 900 894 126 1020
950 944 134 1103 950 944 134 1078
1000 994 138 1157 1000 994 138 1132
1050 1044 146 1215 1050 1044 146 1190
1100 1094 150 1269 1100 1094 150 1244
1150 1144 158 1327 1150 1144 158 1302
1200 1194 170 1389 1200 1194 170 1364
1250 1244 174 1443 1250 1244 174 1418
1300 1294 187 1506 1300 1294 187 1481
1350 1344 191 1560 1350 1344 191 1535
1400 1394 199 1618 1400 1394 199 1593

NOTE :
• All dimensions are given in millimeters.
• Dampers are normally fabricated approximately ¼” less than given duct dimensions.

IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Design and Sizes are subject to change without
Page 7
Dania Air Control System Factory
P.O. Box 60479 Riyadh 11545 K.S.A.
Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385
Email: dania@sunaid.com.sa

FIRE DAMPERS PERFORMANCE DATA

TYPE : RFD-50 & SFD-70 w/ Head Cap

FREE AREA (SQ. FT)

Duct Width (In.)


4 8 12 16 20 24 28 32 36 40 44 48 52 56 60

4 0.1 0.2 0.3 0.4 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.6 1.7

8 0.2 0.4 0.7 0.9 1.1 1.3 1.6 1.8 2.0 2.2 2.4 2.7 2.9 3.1 3.3

12 0.3 0.7 1.0 1.3 1.7 2.0 2.3 2.7 3.0 3.3 3.7 4.0 4.3 4.7 5.0

16 0.4 0.9 1.3 1.8 2.2 2.7 3.1 3.6 4.0 4.4 4.9 5.3 5.8 6.2 6.7

20 0.6 1.1 1.7 2.2 2.8 3.3 3.9 4.4 5.0 5.6 6.1 6.7 7.2 7.8 8.3
Duct Height (In.)

24 0.7 1.3 2.0 2.7 3.3 4.0 4.7 5.3 6.0 6.7 7.3 8.0 8.7 9.3 10.0

28 0.8 1.6 2.3 3.1 3.9 4.7 5.4 6.2 7.0 7.8 8.6 9.3 10.1 10.9 11.7

32 0.9 1.8 2.7 3.6 4.4 5.3 6.2 7.1 8.0 8.9 9.8 10.7 11.6 12.4 13.3

36 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0

40 1.1 2.2 3.3 4.4 5.6 6.7 7.8 8.9 10.0 11.1 12.2 13.3 14.4 15.6 16.7

44 1.2 2.4 3.7 4.9 6.1 7.3 8.6 9.8 11.0 12.2 13.4 14.7 15.9 17.1 18.3

48 1.3 2.7 4.0 5.3 6.7 8.0 9.3 10.7 12.0 13.3 14.7 16.0 17.3 18.7 20.0

52 1.4 2.9 4.3 5.8 7.2 8.7 10.1 11.6 13.0 14.4 15.9 17.3 18.8 20.2 21.7

56 1.6 3.1 4.7 6.2 7.8 9.3 10.9 12.4 14.0 15.6 17.1 18.7 20.2 21.8 23.3

60 1.7 3.3 5.0 6.7 8.3 10.0 11.7 13.3 15.0 16.7 18.3 20.0 21.7 23.3 25.0

TYPE : SFD-70

FREE AREA (SQ. FT)

Duct Width (In.)


4 8 12 16 20 24 28 32 36 40 44 48

4 0.03 0.09 0.10 0.20 0.30 0.30 0.40 0.40 0.50 0.60 0.60 0.70

8 0.09 0.20 0.40 0.60 0.70 0.90 1.00 1.20 1.40 1.50 1.70 1.80

12 0.10 0.40 0.70 0.90 1.20 1.50 1.80 2.00 2.30 2.60 2.80 3.10

16 0.20 0.60 0.90 1.30 1.70 2.00 2.40 2.80 3.10 3.50 3.90 4.20
Duct Height (In.)

20 0.20 0.70 1.20 1.70 2.10 2.60 3.10 3.50 4.00 4.50 5.00 5.40

24 0.30 0.90 1.40 2.00 2.60 3.20 3.70 4.30 4.90 5.40 6.00 6.60

28 0.40 1.00 1.70 2.40 3.00 3.70 4.40 5.00 5.70 6.40 7.00 7.00

32 0.40 1.20 2.00 2.70 3.50 4.30 5.10 5.80 6.60 7.40 8.20 9.00

36 0.50 1.30 2.20 3.10 4.00 4.80 5.70 6.60 7.40 8.40 9.20 10.10

40 0.50 1.50 2.50 3.50 4.40 5.40 6.40 7.40 8.40 9.30 10.30 11.30

44 0.60 1.70 2.70 3.80 4.90 6.00 7.00 8.00 19.20 10.30 11.40 12.30

48 0.60 1.80 3.00 4.20 5.40 6.60 7.70 8.90 10.10 11.30 12.50 13.70

cfm = Free area (sq.ft.) X Free area velocity (fpm or cfm/sq.ft.)

IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Designs are subject to change without prior notice.
Page 8
Dania Air Control System Factory
P.O. Box 60479 Riyadh 11545 K.S.A.
Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385
Email: dania@sunaid.com.sa

FIRE DAMPERS OPERATION & MAINTENANCE

INSPECTION
Before installing, make sure :

The unit
• Has not been damaged in shipping.
• Is the model and size specified.
If there are discrepancies, check with the job
superintendent before installing.
The installation site
• Is the correct size.
• Is straight, plumb and clean. The mounting
surface should be as level as possible.

INSTALLATION

Secure to the collar or sleeve with ¼” dia. Bolts and


nuts, or back tack welding with beads ½” (+, -) ¼” in
length, or with #10 sheet metal screws, or with 3/16”
steel pop rivets. Fasteners or weld beads should be 6 OPERATION & MAINTENANCE
to 8 in. on centers.
Operate dampers as per Building Management System
The collar shall be on the same gauge or heavier than Operation.
the duct sleeve to which it is attached. Gauges shall Enter the location and description of each damper with
conform to SMACNA or ASHRAE duct standards. maintenance instructions on the building’s inspection
form.
When the following duct collar connections are used,
the minimum gauge of the collar shall be 16ga. On 1. Check units semi-annually, unless instructed to
dampers not exceeding 36” wide by 24” high and inspect more often.
14ga. On large dampers.
1. Angle reinforced standing steam. 2. Check Stainless Steel Jamb and Blade Seals.
2. Angle reinforced pocket lock. 3. Check for loosen Bearings, Axles, Straps, Bolts
3. Companion angles. and Nuts.
4. Metal fasteners spaced a minimum of 16” on
center. 4. Check Operating Linkages.

Secure angles to collar only so as to frame the wall 5. Check Damper Actuator. (If Motorized)
opening. Angles shall be a minimum of 1 ½” x 1 ½” x (See attached Actuator Manufacturer Data
14 ga. Fasten to collar only using the same means as Sheet)
required for fastening the damper to the collar. Damper 6. Check Actuator Shaft and connection bolts.
shall have a clearance of 1/8” per foot on height and
width, and angles shall increase in size 7. Replace defective parts.
proportionately, so that there will be a minimum of 1” of
overlap on the partition. 8. Replace Fusible Links ( Model: RFD , SFD70)
9. Tighten all necessary Bolts and Nuts.
At light see the duct sleeve connections which may be
used on all systems. 10. Clean with Mild Detergent Soap.

IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Designs are subject to change without prior notice.
Page 9
CERTIFICATE OF COMPLIANCE
Certificate Number 20120912-R26744
Report Reference R26744-20110831
Issue Date 2012-SEPTEMBER-12

Issued to: DANIA AIR CONTROL SYSTEM FACTORY


EXIT 9
AL-IMAM SAUD BIN
ABDUL AZIZ BIN MOHD RD
KING FAHAD DISTRICT AREA
RIYADH SAUDI ARABIA

This is to certify that DAMPERS FOR FIRE BARRIER AND SMOKE


representative samples of APPLICATIONS
Fire damper, Model SFD-70 and RFD-50, curtain type, for
vertical installation only and for use in static and dynamic
systems for 1.5 hr rating

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: UL 555 - Fire Dampers


Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information

Only those products bearing the UL Classification Mark should be considered as being covered by
UL’s Classification and Follow-Up Service.

The UL Classification Mark includes: UL in a circle: with the word “CLASSIFIED” (as shown); a control
number (may be alphanumeric) assigned by UL; a statement to indicate the extent of UL’s evaluation of
the product; and the product category name (product identity) as indicated in the appropriate UL
Directory.

Look for the UL Classification Mark on the product.

William R. Carney, Director, North American Certification Programs

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at www.ul.com/contactus