Indian Standard
GASEO'US FIRE EXTINGUISHING SYSTEMS -
CARBON DIOXIDE TOTAL FLOODING AND
LOCAL APPLICATION ( SUB-FLOOR AND
IN-CABINET ), HIGH AND LOW PRESSURE
(REFRIGERATED) SYSTEMS
res 13.220.10
© BIS 2004
FOREWORD
This lndian Standard was adopted by the Bureau of Indian Standards, after the draft finalized by the Fire
Fighting Sectional Committee had been approved by the Civil Engineering Division Council.
This standard is intended for use by those concerned with purchasing, designing, installing, testing, inspecting,
approving, and operating carbon dioxide ( CO 2 ) total flooding and local application extinguishing systems, in
order that such equipment/system will function.as intended throughout its life.
It is important that the fire protection of a building or plant be considered as a whole. Carbon dioxide systems
form only a part, though an important part, of the available fire protection facilities. However, it should not be
assumed that their adoption necessarily removes the need to consider supplementary measures, such as the
provision of portable fire extinguishers or mobile appliances for first aid or emergency use, or measures to deal
with special hazards.
Carbon dioxide is recognized as effective for extinguishing Class B fires and where electrical risks are present.
However, it should not be forgotten in the planning of comprehensive schemes that there may be hazards for
which this technique is not suitable, or that, in certain circumstances or situations, there may be dangers in its
use, requiring special precautions.
The discharge of carbon dioxide creates a dangerous oxygen deficiency, which may result in unconsciousness
and subsequent suffocation. Carbon dioxide should be used normally in unoccupied area.
Advice on the above can be obtained from organizations involved with the installation of carbon dioxide total
flooding systems.
The objective of this standard is to provide the users of carbon dioxide systems specific requirements for
the control of fires of Class B type. It does not cover the design of explosion suppression systems.
It is essential that fire extinguishing equipment be carefully maintained to ensure instant readiness when required.
The importance of maintenance cannot be too highly emphasized.
This standard has been prepared to meet the need for the dissemination of information on established
system design. Its requirements represent the best technical data known at the time of preparation but, since a
wide field is covered, it has been impracticable to consider every possible factor or ci,rcumstance that might
affect impleme~tation.
It is a basic assumption that this standard be used only by persons competent in the field of application with
which it deals. This is of particular importance in fire protection work. Acc8l'dingly, it is emphasized that the
design requirements in this Standard are to be interpreted only by trained and experienced designers.
This standard does not include specific requirements for carbon dioxide systems for marine applications. However,
the method of calculation in this standard may be of some assistance in the design of such systems.
IS 15528 : 2004
Indian Standard
GASEOUS FIRE EXTINGUISHING SYSTEMS-
CARBON DIOXIDE TOTAL FLOODING AND
LOCAL APPLICATION (SUB-FLOOR AND
IN-CABINET ), HIGH AND LOW PRESSURE
(REFRIGERATED) SYSTEMS
1 SCOPE due to obscuration of vision and rcduction of oxygen
concentrations below that which wi 11 not support liCe,
1.1 This standard lays down the requirements for not only in the immediate area of discharge, but also in
carbon dioxide systems, util izing high pressure or adjacent areas to \vhich the gas may migrate. Therefore,
refrigerated low pressure carbon dioxide as the fire the safety requirements given in 5.1 shall be strictly
observcu.
extinguishant system.
4.2 Uses of Carbon Dioxide
1.2 The carbon dioxide shall comply with the
requirements ofIS 15222. Carbon dioxide is suitable for extinguishing the
1.3 General principles may well apply for other uses following types of fire:
such as in-cabinet subfloor for which additional a) Under certain conditions, fires involving
considerations may have to be taken into account. carbonaceous so I id materials, usually of an
2 REFERENCES organic nature, in which combustion normally
takes place with the formation of glowing
The standards listed in Annex A contain provisions embers ( Class A fires ).
which through reference in this text, constitute b) Fires involving flammable and combustible
provisions of this standard. At the time of publication, liquids (Class B fires ).
the editions listed were valid. All standards are subject
to revision and the parties to agreements based on c) Fires involving combustible gases, except
this standard are encouraged to apply the most recent when, after extinguishment, an explosive
editions of the standards indicated in Annex A. atmosphere may develop due to a
continuation of escaping gases ( Class C
3 DEFINITIONS fires ).
For the purpose of this standard, the definitions given d) Fires involving live electrical apparatus.
in IS 15493 shall apply.
4.3 Limitations of Carbon Dioxide Systems
4 USES AND LIMITATIONS OF CARBON
Carbon dioxide systems are not suitable for use on
DIOXIDE
fires involving the following:
4.1 General
a) Chemicals containing their own supply of
The extinguishing medium corbon dioxide is a oxygen, such as cellulose nitrate.
colourless, odourless and electrically non-conductive b) Reactive metals and their hydrides ( for
gas. Carbon dioxide is approximately one and a half example, sodium, potassium, magnesium,
times heavier than air. titanium and zirconium ).
Carbon dioxide extinguishes fires principally by 5 SAFETY REQUIREMENTS
reducing the oxygen content in the atmosphere to a
point where it will not support combustion. 5.1 Safety of Personnel
The relationship between the temperature and 5.1.1 Protecf ion of Occupants
pressure of liquid carbon dic'{ide is shown in Fig. I.
The discharge of carbon dioxide in fire extinguishing
At 31 °C, the liquid and vapour have the same density,
concentration creates seriolls hazards for personnel,
and of course the liquid phase disappears. This is sLlch as reduced visibility and suffocation, during and
called critical temperature of carbon dioxide. after discharge period. Suitable safeguards shall also
NOTE - Carbon dioxide concentrations, as required be provided to ensure prompt evacllation, to prevent
for use in extinguishing systems, pose hazards to personnel entry into sllch areas and provide a means for prompt
IS 15528 : 2.004
CRITICAL TEMPERATURE ~
I
10.0
9.0
8.0
7.0
I\.
V
,
'\.1
I
6.0
5.0 /
/V
4.0
V
3.0 /
/
2.0
LIQUID REGIO~
V
ro
0...
2 / VAPOUR
V
SOLID REGION
W
0:::
:J
(f) 1.0 )
(f) 0.9
w 0.8
/
0::: l/
Il.. 0.7
0.6 J
0.5 V
0.4
l"- - TRIPLE-POINT
0.3 /
0.2
V
0.1
V I I I I I
183 193 203 213 223 233 243 253 263 273 283 293 303 313
TEMPERATURE, oK
/i ATMOSPHERIC PRESSURE
I I I II I I I I I I I I I
-90 -80 -70 -60 -50 -40 -30 -20 -10 0 10 20 30 40
TEMPERATURE, °C
FIG. 1 VARIATION OF PRESSURE OF CARBON DIOXIDE WITH CHANGE IN TEMPERATURE { CONSTANT VOLUME)
rescue of any trapped personnel. the system shall be isolated and the lock-off control
activated.
5.1.2 Precautionsfor Entering Confined Spaces and
Low Lying Areas Entry into confined spaces for any purpose shall be
controlled by a permit-to-work system. Provisions
Entry into confined spaces poses additional shall be made for ensuring that the atmosphere within
hazards because of restrictions on freedom of the space is safe for entry and shall remain so for the
movement, ventilation, escape or rescue. Before entry duration of entry. In cases where effective ventilation
into floor and ceiling voids, ducts, process vessels cannot be ensured, the permit shall specify the
or similarly confined spaces, the automatic release of respiratory protective equipment to be used and any
2
IS 15528 : 2004
3
IS 15528 : 2004
the outside atmosphere, where wind conditions may 6.3.2 Leakage and Ventilation
affect the carbon dioxide losses, might necessitate
Since the efficiency of carbon dioxide systems depends
special consideration.
upon the maintenance of an extinguishing concentration
Examples of hazards and their enclosures that can of carbon dioxide, leakage of gas from the area shall
be successfully protected by total flooding systems be kept to a minimum and compensated for by applying
include rooms, vaults, enclosed machines, ducts, ovens, extra gas.
containers, and their contents.
Where possible, openings such as doorways and
6.3 Design Quantity of Carbon Dioxide windows shall be arranged to close automatically before
or simultaneously with the start of the carbon dioxide
6.3.1 Factors to be Considered discharge, or the requirements of 6.7 and 6.11 shall
To determine the quantity of the carbon dioxide be followed. For personnel safety, see 5.1.
required, the volume of the room or of the enclosure Where air handling ventilation systems are involved,
to be protected shall be taken as a basis. From this they shall be shut down or isolated by dampers, or
volume only, solid structural members, such as both, before or simultaneously with the start of the
foundations, columns and beams, are to be deducted. carbon dioxide discharge. Where this is not practical,
The following shall be taken into account: additional compensating gas shall be provided.
a) Room size, 6.3.3 Types o.lFires
b) Material to be protected,
Fires which can be extinguished by total flooding
c) Particular risks, methods can be divided into two categories,
d) Openings that cannot be closed, namely:
e) Ventilation systems which cannot be shut a) Surface fires involving flammable liquids,
down, and gases and solids; and
f) Temperature of protected area. b) Deep-seated fires involving solids subject
For flash or surface type fires, such as will be present to smouldering.
with flammable liquids, any non-closing openings shall Surface fires are the most common hazard suitable
be compensated for by additional carbon dioxide as for extinguishment by total flooding systems. They
specified in 6.4.5. If the quantity of carbon dioxide are extinguished promptly when carbon dioxide is
required for compensation exceeds the basic quantities introduced into the enclosure in sufficient quantity
requirpd for flooding without leakage, the system both to overcome leakage and to provide an
shall be designed for local application in accordance extinguishing concentration suitable for the
with 7. particular materials involved.
For deep-seated fires such as those involving solids, For deep-seated fires, the extinguishing concentration
non-closing openings shall be restricted to those shall be maintained for a sufficient period to allow
bordering on, or actually in the ceiling, if the size of the smouldering to be extinguished and the material
the openings exceed the pressure relief venting to cool to a point at which reignition will not occur
requirements set out in 6.5. after dissipation of the inert atmosphere.
To prevent fire from spreading through openings 6.3.4 Pressure Adjustment
to adjacent hazards or work areas, which may be
possible reignition sources, such openings shall be The quantity of carbon dioxide shall be adjusted
provided with automatic closures or local application to compensate for ambient pressures that vary
nozzles. The gas required for such protection shall more than 11 percent ( equivalent to approximately
be in addition to the normal requirement for total 915 m of elevation change) from standard sea level
flooding (see 6.15). When neither method is practical, pressure ( 760 mm Hg). The ambient pressure is
protection shall be extended to include these adjacent affected by changes in altitude, pressurization or
hazards or work areas. depressurization of the protected enclosure,
and weather-related barometric pressure changes.
In the case of process and storage tanks, where safe The adjusted storage quantity is determined by
venting of flammable vapours and gases cannot be multiplying the number of carbon dioxide containers
realized, external local application systems are used (N), determ ined in accordance with 6.2, by the ratio
for protection across the openings, and the area per of average ambient enclosure pressure to standard
nozzle given by specific approval or listing may be sea level pressure. The atmospheric correction factors
increased by 20 percent. are given in Table 2.
4
IS 15528 : 2004
i) Acetylene 55 66
Acetone 27 ( see Note 2 ) 34
Aviation gas grades 1151145 30 36
i i) Benzol benzene 31 37
Butadiene 34 41
Butane 28 34
iii) Butane~I 31 37
Carbon disulfide 60 72
Carbon monoxide 53 64
iv) Coal gas or natural gas 31 ( see Note 2 ) 37
Cyclopropane 31 37
Diethyl ether 33 40
v) Dimethyl ether 33 40
Dowtherm 38 ( see Note 2 ) 46
Ethane 33 40
vi) Ethyl alcohol 36 43
Ethyl ether 38 ( see Note 2 ) 46
Ethylene 41 49
vii) Ethylene dichloride 21 34
Ethylene oxide 44 53
Gasoline 28 34
viii) Hexane 29 35
Higher paraffin 28 34
Hydrocarbons 62 75
C N H2m + 2M - 5
Hydrogen
ix) Hydrogen sulfide 30 36
Isobutane 20 ( see Note 2 ) 36
Isobutylene 26 34
x) Isobutyl formate 26 34
.IP 4 30 36
Kerosene 28 34
xi) Methane 25 34
Methyl acetate 29 35
Methyl alcohol 33 40
xii) Methyl butene-l 30 36
Methyl ethyl ketone 33 40
Methyl formate 32 39
xiii) Pentane 29 35
Propane 30 36
Propylene 30 36
xiv) Quench, lubrication oils 28 34
NOTES
1 The theoretical minimum extinguishing concentrations in air for the above materials were obtained from a compilation
of USA Bureau of Mines' Limits of flammability of gases and vapours ( Bulletins 503 and 627 ).
2 Concentrations calculated from accepted oxygen values.
shall be added to the space through the regular when the design concentration is greater than 34
distribution system, in an amount computed by dividing percent.
the volume moved during the liquid discharge period
6.4.5.3 High temperature
by the flooding factor. This shall be multiplied by
the material conversion factor ( determined in Fig. 2 ) For applications where the normal temperature of the
6
IS 15528 : 2004
4 J
'f'
W'"
CY:
a , 1.1'
I-
u ., 101"
«
LL
3
.tl
~
Z
o "'"
~ "
Ci5 ~ ""
CY: ~
IJ.J
> ",
... '
~ 2 r..-.
~
u A~
...-
...-"
, 'J"'"
fill'
l..o"",,
7
IS 15528 : 2004
The design concentrations in Table 5 shall be achieved The minimum design rate of application shall be based
for the hazards listed. Generally, the flooding on the quantity of carbon dioxide and the maxilTIum
factors in Table 5 provide the design concentration time to achieve design concentration as follows:
for the rooms and enclosures listed.
a) For surface fires, the design concentration
Flooding factors for other deep-seated fires shall be shall be achieved within 1 min.
justified to the satisfaction of the appropriate authority b) For high pressure systems, if a part of the
before use. Consideration shall be given to the mass hazard is to be protected by local
of material to be protected because the rate of cooling application, the discharge rate for the total
is reduced by the thermal insulating effects. flood ing portion shall be caJcu lated as
6.5.3 Volume Consideration specified in 6.12.
When calculating the net cubic capacity to be c) For deep-seated fires, the design
concentration shall be achieved within
protected, allowance should be made for the
1 min and maintained for 7 min, but the rate
reduction of volume by permanent non-removable
impermeable structures materially reducing the shall be not less than that required to
develop a concentration of 30 percent
volume.
in:2 min.
The basic quantity of carbon dioxide required to
protect an enclosure shall be obtained by treating the 6.7 Extended Rate of Application
volume of the enclosure by the appropriate flooding
Where leakage is appreciable and the design
factor given in 6.4.2.
concentration must be obtained quickly and maintained
6.5.4 Special Conditions for an extended period of time, carbon dioxide provided
for leakage compensation may be applied at a reduced
6.5.4.1 General rate.
Additional quantities of carbon dioxide shall be Figure 3 may be used as a guide in estimating discharge
provided to compensate for any special conditions systems.
that may adversely affect the extinguishing efficiency
( see 6.3.2, 6.3.3 and 6.3.4 ). 6.7.1 This type of system is particularly appl icable
to enclosed rotating electrical apparatus, such as
6.5.4.2 Unclosable openings generators, motors and converters, but it may also
Any open ings that cannot be closed at the time of be used on ordinary total flooding applications where
extinguishment shall be compensated for by the suitable.
addition of carbon dioxide equal in volume to the 6.7.2 The minimum design concentration shall be
expected leakage volulne,/dJJring the extinguishing obtained within the time I imits specified in 6.6( c).
period. If leakage is appreciable, consideration
shall be given to an extended disc\;arge system 6.7.3 The extended rate of discharge shall be sufficient
(see 6.7). to maintain the minimum concentration.
8
IS 15528 : 2004
./ /'
V ..v V / V /
",."
293.40
/ / ~V V v 7 V V ~
244.60
/ V
j,;"
V ioo""
v v
~
~V / V
......- ./
~
./
195.60
cO> ~ V ~/
7 V ~
g
QO/o
:/
V ~
/ ./
V
146.]0 ~
~
V
~V
:,/
V' V .......
N
E V 1
0%
c°'1,.- /
/
V
./ V
V
/
V .; '/
",.. -"
~ 97.80
~ V
V
~V
~
'E / V
oo
Cl
N
.:.:.
uj 48.90 r--O!~
!;( 4 4.01 . /
% c;,oolo
~
c~V
V
/'
V
:/
/
V
~
/
V
V
/
/ ./
19.58
14.67 V
f---
r Cp'L.
:/
/"
vV
V
9.78
V
~
4.89
:yV \0
%
o.3 0.6 0.9 1.2 1.5 1.8 2.4 3.1 6.1 9.2 12.2 18 24 3
2.1 2.7 15.3 21 27
HEIGHT OF ATMOSPHERE ABOVE CENTRE OF OPENING, METRES
6.7.4 For enclosed rotating electrical equipment, a The method for the venting of flammable vapours
minimum concentration of 30 percent shall be and pressure build-up from the discharge of
maintained for the deceleration period, but not less quantities of carbon dioxide into closed areas shall
than 20 min. be considered. The pressure venting consideration
involves such variables as enclosure strength and
6.8 Piping Systems injection rate.
Piping shall be designed in accordance with 8 and 6.10 Hazard Specification
IS 15493 to deliver the required rate of application
at each nozzle. The hazard shall be isolated from other hazards or
combustibles in such a way that fire will not spread
High pressure storage temperatures can range from outside the protected area. The entire hazard shall
-18° to 54°C without requiring special methods of be protected. The hazard shall include all areas that
compensation for changing flow rates. are likely to be coated with combustible liquids or
shallow solids coatings, such as areas subject to
6.9 Local Application/In-cabinet Subfloor Systems
spillage, leakage, dripping, splashing, or condensation,
Local application systems shall be designed, installed and all associated materials or equipment, such as
and tested in accordance with the applicable freshly coated stock, drain boards, hoods and ducts,
requirements covered in 6.5 and with the additional that might extend fire outside or lead fire into the
requirements of this clause. protected area.
9
IS 15528 : 2004
10
IS 15528 : 2004
The design discharge rate through individual nozzles Nozzles should be installed perpendicular to the
shall be determined on the basis of location or hazard and centred over the area protected by the
projection distance, in accordance with specific nozzle. They may also be installed at angles between
approvals or listings. 45° and 90° ( see 3.2 ) from the plane of the hazard
surface as prescribed in 9.8. The distance used in
The discharge rate for overhead type nozzles shall determining the necessary flow rate and area coverage
be determined solely on the basis of distance from shall be the distance from the aiming point on the
the surface each nozzle protects. protected surface to the face of the nozzle measured
along the axis of the nozzle.
6.14.3 Area Protected by Nozzle
When installed at an angle, nozzles shall be aimed at
The maximum area protected by each nozzle shall be
a point measured from the near side of the area protected
determined on the basis of location or projection
by the nozzle, the location of which is calculated by
distance and the design discharge rate, in accordance
multiplying the fractional aiming factor in Table 6 by
with specific approvals or listings.
the width of the area protected by the nozzle.
The same factors used to determine the design
Table 6 Aiming Factors for Angular Placement of
discharge rate shall be used to determine the maximum
Nozzles Based on 150 mm Freeboard
area to be protected by each nozzle.
The portion of the hazard protected by individual 81 No. Dischal'ge Angle l ) Aiming Factor 2)
overhead-type nozzles shall be considered as a square (1) (2) (3)
area. i) 45° to 60° 114
6.14.4 Location and Number a/Nozzles The volume method of system design is used where
the fire hazard consists ofthree-dimensional irregular
A sufficient number of nozzles shall be installed over objects that cannot be easily reduced to equivalent
the entire area on the basis of the unit areas protected surface areas.
by each nozzle.
6.15.2 Assumed Enclosure
Tank side or linear-type nozzles shall be located in
accordance with spacing and discharge rate limitations 'Fhe total discharge rate of the system shall be based
11
IS 15528 : 2004
on the volume of an assumed enclosure entirely 6.15.4 Location and Number of Nozzles
surrounding the hazard.
A sufficient number of nozzles shall be used to
The assumed enclosure shall be based on an actual adequately cover the entire hazard volume on the basis
closed floor unless special provisions are made to take of the system discharge rate as determined by the
care of bottom conditions. assumed volume. The design discharge rate through
individual nozzles shall be determined on the basis
The assumed walls and ceiling ofthis enclosure shall of location or projection distance.
be at least 0.6 m from the main hazard unless walls
are involved, and shall enclose all areas of possible 6.16 Distribution System
leakage, splashing or spillage.
6.16.1 General
No deductions shall be made for solid objects within
The system shall be designed to provide prompt and
this volume.
effective discharge of carbon dioxide before excessive
A minimum dimension of 1.2 m shall be used in amounts of heat can be absorbed by materials within
calculating the volume of the assumed enclosure. the hazard.
lithe hazard is likely to be subjected to winds or forced The carbon dioxide supply shall be located as near
drafts, the assumed volume shall be increased to to the hazard as practicable and yet not exposed to
compensate for losses on the windward sides. the fire. The pipeline shall be as direct as practicable
with a minimum number oftums in order to get carbon
6.15.3 Total Discharge Rate
dioxide to the fire promptly.
The total discharge rate for the basic system shall be
The system shall be designed for automatic operation
equal to 16 kg/min/m3 of assumed volume.
except where the appropriate regulatory authority
If the assumed enclosure has a closed floor and is permits manual operation.
partly defined by permanent continuous walls
6.16.2 Piping Systems
extending at least 0.6 m above the hazard ( where
the walls are not normally part of the' hazard ), the Piping shall be designed in accordance with 9 to deliver
discharge rate may be reduced proportionally to not the required rate of app I ication at each nozzle.
less than 4 kg/min/m3 for actual walls completely
surrounding the enclosure ( see Fig. 4 ). High pressure storage temperatures can range from
100
~~i'..
a:::
....w
"
w 75
"""""" "'",,- RATE BY VOLUME· MATHEMATICAL METHOD
~
£r I'.... e.g. 50% ENCLOSED, F = (0.5 x 12) + 4
""
w .. DISCHARGE RATE =10 Ekg I min 1m 3
a.. .... ~
0
w
U) ,,~
0
-J """~
U
z
w
u.
60
'I\..~
0 '" f'
w
t9 .... 1"..
«
I-
z
w
u
25 " ....
~
a::
w
a.. "",,- """r--....
~
a -T l~
4 6 8 10 12 14 16
kglminlm 3
12
IS 15528 : 2004
0° to 49°C without requiring special methods of tolerance of ~~.5 percent the mass being
compensating for changing flow rates. determined by weighing.
NOTE - The filling ratio is the ratio of mass ofliquefiable
7 PROTECTED ENCLOSURE REQUIREMENTS
gas in the containers to the mass of water the container
7.1 Where venting of an enclosure may be necessary will hold at 15°C.
to relieve pressure build-up due to the discharge of Where the container design does not 'incorporate a
large quantities of carbon dioxide, the area necessary safety pressure relief device, it shall be incorporated
for free venting shall be not less than that determined in the container valve.
from the following equation:
8.2.2 Storage Container Arrangement
2.236 x 10 2 x QX V
X=
Kx{Px VI The arrangement of storage containers and accessories
shall be as follows:
where
a) The necessary carbon dioxide quantity
X vent opening area, in mm 2 ;
shall be contained in one bank. The supply
Q extinguishant mass flow rate, in kg/min; to separate distinct hazards could be from
P enclosure max. structural safe working a single bank where there is no likelihood
pressure, in kPa; of the fire spreading from one hazard to
V specific volume of extinguish ant at another and provided that the cylinder bank
room temperature and pressure, in is not placed within any of the hazards. The
m 3 /kg; total quantity of the bank shall correspond
to the largest quantity of carbon dioxide
VI specific volume of vented
required to protect anyone area or object.
extinguishant/air mixture in m3/kg; and
The release systems of the bank and the
K orifice flow coefficient ( dimensionless, pipes shall be arranged in such a way that
and usually 0.5 to 0.6 for small openings each protected zone wi II be flooded
in walls ). individually. A typical high pressure storage
facility using a number of cylinders is shown
If values of Vand VI corresponding to 35 percent
in Fig. 5.
concentration and standard room temperature and
pressure are substituted, and if X is in mm 2 and Q in b) Storage temperatures should not exceed, nor
kg/min, the equation becomes fall below, the following range unless the
system is designed to operate effectively at
247.3 xQ storage temperatures outside this range:
X=
K{P 1) Total flooding systems temperature
8 CARBON DIOXIDE SUPPLY range A1ax 55°C; Min - 18°C.
2) Local application systems temperature
8.1 Quality
range Max 49°C; Min O°C.
The extinguishant used shall be carbon dioxide External heating or cooling should be used
complying with the requirements of IS 15222. to keep the temperature located within the
A non-combustible, non-toxic trace gas that is desired range. Where special container
compatible with the extinguishant and the materials charges are used, the container shou Id be
of construction may be added to the charge to facilitate appropriately marked.
leak testing. c) Where gas pressure, from pilot cyl inders
fed through the system discharge manifcld
8.2 High-Pressure Systems
( that is using back pressure rather than a
8.2.1 Storage Containers separate pilot line ), is used to release the
remaining slave cylinders, and the supply
The carbon dioxide supply shall be stored in
consists of three cylinders, one cylinder shall
containers designed to hold carbon dioxide. The
be used for such operation. If the supply
containers shall comply with the following:
consists of three cylinders or more, there shall
a) Requirements as per IS 8198 ( Part 1 ) and be one pilot cylinder more than the minimum
IS 8198 ( Part 3 ) required to actuate the system. During the
full discharge acceptance test, the extra pilot
b) The container shall be internally dry and
cylinder shall be arranged to operate as a slave
be filled with dry carbon dioxide to the
cylinder.
maximum filling ratio of 0.667 within a
13
IS 15528 : 2004
NOZZLES
VENT
1\ DIRECTIONAL VALVES
CHECK
VALVES
I\ RELIEF VALVE
DISCHARGE PIPED
INTO OUTSIDE
ATMOSPHERE
L INITIAL
CYLINDERS
~C3 RESERVE
CYLINDERS
J
RELIEF
VALVE
14
IS 15528 : 2004
g) The audible warning connected with loss, in net content of more than 10 percent, it shall be
pressure monitoring shall be independent refilled/replaced. Online continuous gas weight monitoring
arrangement is recommended.
of the electrical circuit supplying the
refrigeration unit. 9 DISTRIBUTION SYSTEM
h) The cylinder shall have sufficient insulation
to limit the loss of carbon dioxide to not more 9.1 General
than 1.5 percent or 5 kg, whichever is the In addition to the requirements of IS 15493, the
greater, up to 6 t charge, not more than piping shall withstand the maximum developed
0.8 percent for 6 to lOt charge and not more storage pressure, as per Table 7.
than 0.5 percent for over lOt charge in 24 h
in the event of a failure of the refrigerating Table 7 Typical System Pressures
system at the highest expected ambient
temperature. SI Examples Nominal Maximum
No. of System Storage Developed
j) Insulation materials shall be protected to Pressure Pressure Storage Pressure
avoid mechanical damage. MPa at 55°C, MPa
k) Containers shall be fitted with pressure (1 ) (2) (3) (4)
gauge(s), safety valve(s) and pressure relief i) Low-pressure 2.1 3.1 manifold relief
valves as per IS 14150. Care shall be taken systems valve setting
to ensure that during the filling of the ii) High-pressure 5.2 15.5
containers the temperature of the carbon systems
dioxide corresponds to the value necessary
to the proper functioning of the system. For determining the size of distribution systems,
m) The pressure relief valves shall be mounted see 6.
in pairs on a two-way changeover valve
arranged to ensure that one reliefvalve always 9.2 Steel Pipe
provides protection against excessive Discharge pipes and pipe fittings shall be in
pressure within the container and the accordance with IS 15493.
discharge from the valve shall be piped to
a safe location external to the building. It Stainless steel pipe and fittings may be used in all
shall not be possible for the two-way applications, but shall be sebject to appropriate design
changeover valve to isolate both relief valves strength calculations.
at the same time.
9.3 Piping Joints
n) Shall have means provided to prevent
containers from being overfilled. 9.3.1 Joint olFerrous Pipes
p) Where the entire contents of a low-
Jointing of ferrous pipes shall be mechanical, welded,
pressure container are not to be discharged
screwed or flanged and comply with IS 10234.
at the same time, all contro I or directional
valves shall be arranged to close after the 9.4 Dirt Traps
required quantity has been discharged.
A dirt trap consisting of a tee with a capped nipple,
8.4 Container Condition at least 51 mm long, shall be installed at the end of
Container shall be thoroughly dried before filling, each pipe run.
especially if the container has been hydrostatically
9.5 Safety Devices
tested.
9.5.1 Pressure Relief Device
NOTES
1 A likely source of contamination would be the presence Where there is a possibility of carbon dioxide
of free water in the system container before filling with entrapment in pipework ( for example, between
carbon dioxide.
container valves and directional valves ), a suitable
2 The requirements of the appropriate authorities pressure-relief device shall be fitted as follows:
covering containers could take precedence over the
requirements of this Standard, for example, in marine a) For 2.1 MPa systems, the device shall be
or aviation areas. Accordingly, the appropriate authority
designed to operate at 3.1 MPa ± 5 percent.
should be contacted for advice.
3 All high pressure cylinders shall be weighed atleast b) For 5.2 MPa systems, the device shall be
once in six months. If at any time a container shows a designed to operate at 15.0 MPa ± 5 percent.
15
IS 15528 : 2004
o
Q
::2
w
0:::
::l
(J)
(J)
w
0:::
Q
16
IS 15528 : 2004
5 .17
5.0
lo., - . ....
~ ~ ~t3=: t"--"r--
~~
'-
-- r- _-I-- - r--..
--r::--.:.::::-- r-.- Q/D<
I
I
I
1
~"
I
~i" ~t---.~ r---" I""~
,..... "
i---t-.. ::: 0.07 k,
~
~" r\.~
...
, ~~ r--....... .......... ~ r--...:r--...r--.~ ~~/min/m
~\~ ", \. I' .....
L\\ \.I\.
1\1\ ' , " '\ ....
"
,""
" I~--........ "
, ,, ,
\ 1\ 1\ ~ '\ I'\. ~ ....f'.,
co
a.. 4.0
\ \ 1\ \
\ \ \ r\ \.,~ '" '\.."
"
..< 1"'-
['\. o·~ ~
~
~
'\
~
W
~
\~\~ ,~ , ~\ ~~.> q:~ 1\ ~
~ .~
~
~
~~
~~ \; I'\~ \ ~ \ \1\
::::> 3.5
CJ)
CJ)
1, \
w
l?~~
~ rr,
0:: r\
a.. 3.0 .
~tn
~o
~ \~ '~ \ 1\
\~ !\~
2.5
\ \\ \ \ \~
2.0
1 .5 0
\ , \ \ \ , 1\ ,
0.5 1 2 3 4 5 6 7 8
LID 1.25 ,m/mm 1.25
9.7.6 Nozzles shall be capable of withstanding Table 8 Orifice Code Numbers and Equivalent
pressures up to 14 Mpa and shall be of Leaded tin Orifice Sizes
bronze ( see IS 318 ). (Clauses 9.7.4 and9.2.8)
9.7.7 Nozzles used in the local application installations
SI Orifice Equivalent Equivalent Single
shall be so connected and supported that these may No. Single O.-ifice Orifice Area
not be readily put out of adjustment. Diameter
~
9.7.8 Irrespective ofthe number of orifice or the shape mm inch 'mm 2 inch 2
of the nozzle, it shall be marked, permanently and (1) (2) (3) (4) (5) (6)
indelibly, to show its equivalent single orifice diameter. i) 1 0.79 1132 0.49 0.000 8
All nozzles having an equivalent single orifice diameter l.5 1.19 3/64 1.11 0.001 7
of2.38 mm and more shall also be marked with a code 2 1.59 1116 1.98 0.003 1
number as given in Table 8. ii) 2.5 1.98 5/64 3.09 0.004 7
3 2.38 3/32 4.45 0.006 9
9.7.9 The limitations for nozzle spacing and 3.5 2.78 7/64 6.06 0.009 4
coverage as well as minimum and maximum distance iii) 4 3.18 1/8 7.94 0.012 3
above flammable liquid surfaces ( in depth) shall be 4.5 3.57 9/64 10.00 0.0] 5 5
determined for each type and size of nozzle and 5 3.97 5/32 12.39 0.019 2
checked and verified by a testing laboratory. Where iv) 5.5 4.37 11164 14.97 0.023 2
this information is not provided, the limitations 6 4.76 3116 17.81 0.027 6
for spacing and location of nozzles shall be governed 6.5 5.16 13/64 20.90 0.032 4
by the following: v) 7 5.56 7/32 24.26 0.037 6
7.5 5.95 15/64 27.82 0.043 1
a) Nozzles shall not be spaced more than 1 m 8 6.35 1/4 31.68 0.049 1
apart. A single row of nozzles may be vi) 8.5 6.75 17/64 35.74 0.055 4
satisfactory for area, up to 1.25 m width; and 9 7.14 9/32 40.06 0.062 1
9.5 7.54 19/64 44.65 0.069 2
b) One additional row of nozzles shall be
provided for each additional 1.25 m width of vii) 10 7.94 5116 49.48 0.076 7
1] 8.73 11/32 59.87 0.092 8
hazard area, or fraction thereof.
12 9.53 3/8 71.29 0.110 5
9.7.10 Where nozzles are likely to get clogged by viii) 13 10.32 13/32 83.61 0.129 6
foreign materials these shall be provided with 14 11.11 7116 96.97 0.150 3
frangible discs which shall automatically rupture 15 11.91 15/32 111.29 0.172 5
by the pressure of the discharging gas. ix) 16 12.70 112 126.71 0.196 4
18 14.29 9116 160.32 0.248 5
10 IDENTIFICATION 20 15.88 5/8 197.94 0.308 6
x) 22 17.46 1111 6 239.48 0.371 2
Each container shall be identified by being coloured
24 19.05 3/4 285.03 0.441 8
red approximating Signal Red of IS 5 over the whole 32 25.40 1 506.45 0.785 0
of the cylinder.
xi) 48 38.40 1 112 1 138.7 1.765 0
11 COMMISSIONING AND ACCEPTANCE 64 50.80 2 2 025.8 3.140 0
TESTING NOTE - Formerly, a plus sign following the orifice
code number indicated equivalent diameters 0.4 mm
11.1 Criteria for Acceptance greater than that indicated by the numbering
system, for example, No.4 indicated an equivalent
The completed carbon dioxide system shall be diameter of3.18 mm (4/32 inch) and No. 4+,3.47 mm
commissioned in accordance with IS 15.493 and the ( 9164 inch ).
system's performance proved by at least one of the
following methods: hydrostatic pressure test of 1.25 times
the calculated pipework's maximum
a) Subject the system to a full discharge developed storage pressure at 55°C, then
test, performed in accordance with purge the system to remove the moisture
IS 15493 and the results shall comply and prove free passage.
with 6.
2) Subect the protected area to an enclosure
b) Where a full discharge test using carbon integrity test.
dioxide is not required by the appropriate
authority, the following procedure shall 11.2 Commissioning Certification
apply:
When the system is commissioned, the installation
1) Subject the distribution system to a contractor shall issue a test certificate.
18
IS 15528 : 2004
Table 9 Discharge Rate per 64.5 mm 2 or Table 10 Discharge Rate per 64.5 mm 2 or
Equivalent Orifice Area for Low-Pressure Equivalent Orifice Area for High-Pressure
Storage 2.07 MPa Storage 5.17 MPa
(Clauses 9.6 and9.7.5 ) ( Clause 9.6 )
SI No. Orifice Pressure Discharge Rate SI No. Oi-ifice P.·cssure Discharge Rate
MPa kg/rninlrnrn2 MPa kg/rnin/rnrn 2
(1 ) (2) (3) (1) (2) (3)
i) 2.07 2.970 i) 5.17 3.258
2.00 2.041 ii) 5.00 2.706
1.93 1.671
iii) 4.83 2.403
ii) 1.86 1.443
1.79 1.284 iv) 4.65 2.174
1.72 1.165 v) 4.48 1.995
iii) 1.65 1.073 vi) 4.31 1.840
1.59 0.992
vii) 4.14 1.706
1.52 0.918
viii) 3.96 1.590
iv) 1.45 0.851
1.38 0.792 ix) 3.79 1.488
1.31 0.737 x) 3.62 1.397
v) 1.24 0.688 xi) 3.45 1.309
1.17 0.642
xii) 3.28 1.224
1.10 0.600
xiii) 3.10 1.140
vi) 1.03 0.559
xiv) 2.93 1.063
xv) 2.76 0.985
11.3 Failure xvi) 2.59 0.908
xvii) 2.41 0.830
Where the system fails to comply with either
xviii) 2.24 0.760
IS 15493 or this clause, the fault shall be rectified
and, if necessary, the system retested. xix) 2.07 0.690
ANNEXA
(Clause 2)
LIST OF REFERRED INDIAN STANDARDS
IS No Title IS No Title
5: 1995 Colours for ready mixed paints 10234: 1982 Recommendation for general pipe
and enamels (fourth revision) line welding
318:1981 Specification for leaded tin bronze 14150: 1994 Hydraulic fluid power - Pressure
ingots and castings relief valves Mounting
surfaces
7689: 1989 Guide for the control of
undesirable static electricity/ 15222:2002 Specification for carbon dioxide
(first revision) as fire extinguishing media for
fire protection
8198 Code of practice for steel cylinders
for compressed gases: 15493: 2004 Gaseous fire extinguishing
systems - General requirements
(Part 1 ) : 1984 Atmospheric gases first
revision)
19