1.0 Technical Particulars / Parameters of Transformers (400/220/33 KV Auto Transformer)
1.0 Technical Particulars / Parameters of Transformers (400/220/33 KV Auto Transformer)
HV kVp 1300
IV kVp 950
LV kVp 250
Neutral kVp 95
iii) Switching Impulse withstand Voltage
HV kVp 1050
iv) One Minute Power Frequency withstand
Voltage
HV kVrms 570
IV kVrms 395
LV kVrms 95
Neutral kVrms 38
v) Neutral Grounding Solidly grounded
vi) Insulation
HV Graded
IV Graded
LV Uniform
vii) Tertiary Connection Ungrounded Delta
viii) Tan delta of winding % < 0.5
1.15 Vector Group (3 –ph) YNaOd11
(unless specified differently elsewhere)
1.16 Tap Changer OLTC
i) Tap Range & No. of steps 10% of HV variation in the step
of 1.25%, 16 steps
ii) Location of Tap changer On the 220 kV side of the series
winding
iii) Design Constant flux voltage variation type
as per cl. 6.2 of IEC 60076 part-I
iv) Tap control Full capacity - on load tap changer
suitable for group / independent,
remote /local electrical and local manual
operation and bi-directional power flow
1.17 Bushing
i) Rated voltage
HV kV 420
IV kV 245
LV kV 52
Neutral kV 36
ii) Rated current (Min.)
HV A 1250
IV A 2000
LV A 3150
Neutral A 2000
iii) Lightning Impulse withstand Voltage
HV kVp 1425
Clause No. Description Unit Technical Parameters
IV kVp 1050
LV kVp 250
Neutral kVp 170
iv) Switching Impulse withstand Voltage
HV kVp 1050
IV kVp 850
v) One Minute Power Frequency withstand
Voltage
HV kVrms 695
IV kVrms 505
LV kVrms 105
Neutral kVrms 77
vi) Minimum total creepage distances
HV mm 10500
IV mm 6125
LV mm 1300
Neutral mm 900
vii) Tan delta of bushings
HV % < 0.4
IV % < 0.4
LV % < 0.4
Neutral
viii) Max Partial discharge level at Um
HV pC 10
IV pC 10
LV pC 10
Neutral -
1.18 Max Partial discharge level at 1.58 * Ur / pC 100
√3