Professional Documents
Culture Documents
A Comparison Between A Single and A Double Tuned Hybrid
A Comparison Between A Single and A Double Tuned Hybrid
1292
AC Bus
p, q Power Reference p *, q
vs vs 10 Circuit 10
abc DE
Linear load iG
3 abc 2 iL
Detection
Pq Theory
Power Grid
2 Circuit
Active Filter
vsh 10 DC-link
DE
C1
MSOGI-FLL if* if* Nonlinear load icomp
vs1 DE
abc abc
C Lf
if Hysteresis
DE
2 2 3
abc TRIGGER
iloss
r
Current DE L1
3 control 6 DC-link voltage
VDC regulator 2
*
i fabc 3
Current [A]
These currents are input for the hysteresis control , which 0
generates the trigger signals to the switches of the converter.
It is worth to highlight that the dc-link regulator provides the 50
V. CASE STUDY Figure 6 shows the nonlinear load current in the first
interval. In this interval there is no harmonic compensation.
It was compared the harmonic mitigate capability and Thus, the grid current presents the same behavior of the load
the power processed in the active power filters for current.
the both topologies (STHF and DTHF). The software Figure 7 shows the load and grid currents when the STHF
PSCAD/EMTDC was used as an assessment tool. is connected and Fig. 8 shows the load and grid currents
The active filter of the DTHF topology does not need to
when the DTHF is connected. It can be seen that the DTHF
tune the 3th because the passive filter does it. However the operation produces a lower notch characteristic in the current
active filter of the STHF topology needs to tune the 3th behavior for this interval. This occurs because the DTHF is
because its passive filter is not able to do it. The hybrid able to tune the 3th harmonic.
active power filter and the system considered in this work is Figures 9 and 10 shows the load and grid current at the last
depicted in Fig. 5. The three-phase system is balanced with interval. In this interval the active filter is connected, i.e, the
linear and non-linear loads (3 single-phase converters and 1
three-phase converter). Producing harmonics symmetric and
200
asymmetric besides phase shift between current and voltage Grid Load
of the system. It’s important to note that for STHF the 150
first interval consists in the operation without filter, that starts 50
at time t = 0s and ends at time t = 1.5s. The second interval
100
is characterized by the insertion of the passive filter. It starts
at t = 1.5s and stays until t = 3s. The last interval starts 150
when the active filter is connected at t = 3s. The simulation 200
2.94 2.95 2.96 2.97 2.98 2.99 3
was carried out using the PSCAD/EMTDC and the simulation Time [s]
parameters are shown in Table I. The simulation results are
shown in Figs. 6-18. Fig. 7. Load and grid currents in the second interval (STHF).
1293
200 60
Grid Load Neutral current on the grid side
Neutral current on the load side
150
40
100
20
50
Current [A]
Current [A]
0 0
50
20
100
40
150
200 60
2.94 2.95 2.96 2.97 2.98 2.99 3 1.44 1.45 1.46 1.47 1.48 1.49 1.5
Time [s] Time [s]
Fig. 8. Load and grid currents in the second interval (DTHF). Fig. 11. Load and grid neutral currents in the first interval.
200 60
Grid Load Neutral current on the grid side
Neutral current on the load side
150
40
100
20
50
Current [A]
Current [A]
0 0
50
20
100
40
150
200 60
4.94 4.95 4.96 4.97 4.98 4.99 5 2.94 2.95 2.96 2.97 2.98 2.99 3
Time [s] Time [s]
Fig. 9. Load and grid currents in the third interval (STHF). Fig. 12. Load and grid neutral currents in the second interval
(STHF).
100 20
Current [A]
50
Current [A]
0
0
20
50
100 40
150
60
2.94 2.95 2.96 2.97 2.98 2.99 3
200 Time [s]
4.94 4.95 4.96 4.97 4.98 4.99 5
Time [s]
Fig. 13. Load and grid neutral currents in the second interval
Fig. 10. Load and grid currents in the third interval (DTHF). (DTHF).
1294
60 1.6
Neutral current on the grid side System without HF System with STHF System with DTHF
Neutral current on the load side 1.4
40
1.2
0.8
0 0.6
0.4
20
0.2
40 0
1 2 3 4 5
Time [s]
0.5 0.02
0 0.25 0.01
0 0
STHF DTHF
20
Fig. 18. Converter active and reactive power, total power of the
hybrid filter (SF).
40
60
4.94 4.95 4.96 4.97 4.98 4.99 5 factor and compensate harmonic distortions. The STHF was
Time [s]
slightly better than DTHF in this characteristics and STFH
Fig. 15. Load and grid neutral currents in the third interval has also more simple construction. However, the DTHF
(DTHF). topology could mitigate the 3th harmonic and STFH could
not do it. The active power processed by DTFH is lower than
the active power processed by STHF. This result revealed a
Figure 18 compares the active and reactive power pro- great advantage of DTHF compared to the STHF, which was
cessed by converters with DTHF and STHF topologies. always considered one of the best structures for harmonic
Considering the same apparent output power specification of filtering. The DTHF topology also provides neutral current
both filters, it could be seen that DTHF topology presented a reduction better than STHF, considering only passive filter
relevant active power reduction compared to STHF topology. operation.
11
Power Factor
10 0.92
9
8 0.9
7
0.88
6
5 0.86
4
3 0.84
2
0.82
1
0 0.8
1 2 3 4 5 1 2 3 4 5
Time [s] Time [s]
Fig. 16. Total harmonic distortion of the grid and load current. Fig. 19. Power factor on the low-voltage side.
1295
TABLE I vices without energy storage components. Industry
Simulation Parameters. Applications, IEEE Transactions on, IA-20(3):625–630,
Parameters Values 1984.
Line to line voltage 220 V
Frequency 600 Hz [6] S. Srianthumrong and H. Akagi. A medium-voltage
Power factor of the system 0.82 transformerless ac/dc power conversion system consist-
THD of the current 14.5 % ing of a diode rectifier and a shunt hybrid filter. Industry
THD of the current 1.41 % Applications, IEEE Transactions on, 39(3):874–882,
RL linear load 3.5 kVA 2003.
Rectifier full wave single phase 14.42kVA
Six pulse bridge rectifier 14.86 kVA
[7] L. F. C. Monteiro, L. F. Encarnação, and M. Aredes.
Capacitor C1 670 μF A novel selective control algorithm for the shunt active
Inductor L1 411.5μH filter. In Power Electronics Conference (IPEC), 2010
Inductor L2 244μH International, pages 2288–2293, 2010.
[8] L. Asiminoaei, W. Wiechowski, F. Blaabjerg, T. Krzes-
zowiak, and B. Kedra. A new control structure for
under non-ideal source and load conditions. In Power
hybrid power filter to reduce the inverter power rating.
Energy Society General Meeting, 2009. PES ’09. IEEE,
In IEEE Industrial Electronics, IECON 2006 - 32nd
pages 1–6, 2009. Annual Conference on, pages 2712–2717, 2006.
[2] H. Akagi, S. Srianthumrong, and Y. Tamai. Compar-
[9] S. Senini and P. Wolfs. Analysis and comparison of new
isons in circuit configuration and filtering performance
and existing hybrid active filter topologies for current
between hybrid and pure shunt active filters. In In-
harmonic removal. In Proc. Australasian Universities
dustry Applications Conference, 2003. 38th IAS Annual
Power Engineering Conference (AUPEC), pages 227–
Meeting. Conference Record of the, volume 2, pages
232, 1999.
1195–1202 vol.2, 2003.
[10] P. Rodrı́guez, A. Luna, I. Candela, R. Mujal, R. Teodor-
[3] S. Senini and P. Wolfs. An active filter capable of
escu, and F. Blaabjerg. Multiresonant frequency-locked
eliminating multiple harmonics with a single tuned
loop for grid synchronization of power converters under
branch. Journal of Electrical and Electronics Engineer-
distorted grid conditions. Industrial Electronics, IEEE
ing, Australia, 19(1&2):59–65, 1999.
Transactions on, 58(1):127–138, 2011.
[4] F. L. Encarnação, J. A. Moor Neto, S. M. Dos Reis,
[11] P. Rodriguez, A. Luna, M. Ciobotaru, R. Teodorescu,
and M. Aredes. Improved structure for three-phase
and F. Blaabjerg. Advanced grid synchronization
four-wires hybrid active power filters. In International
system for power converters under unbalanced and
Conference on Renewable Energies and Power Quality,
pages 1–6, 2013. distorted operating conditions. In IEEE Industrial
Electronics, IECON 2006 - 32nd Annual Conference
[5] H. Akagi, Y. Kanazawa, and A. Nabae. Instantaneous on, pages 5173–5178, 2006.
reactive power compensators comprising switching de-
1296