GTP ACSR Tern Conductor 22.05.2018

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Accepted by: Electrical - J de Bruyn

Date: 24 May 2018

Project: North West Transmission Grid Connection Project 400kV transmission line Morupule B -
Letlhakane and 220kV transmission line Letlhakane – Orapa 2
Project No. : 9078/13/01-02
Client : Botswana Power Corporation (BPC)
TECHNICAL SCHDULE FOR 400kV
REQUIRED OFFERED
ITEM DESCRIPTION UNIT
SCHEDULE A SCHEDULE B
A Phase Conductors

1 Name of Manufacturer/Supplier Specify JSK Industries Pvt. Ltd.

2 Applicable Standard IEC 61089 IEC 61089 / ASTM B232

3 Type Triple ACSR – Tern Triple ACSR – Tern

4 Current Rating A 830A 830A

5 Overall Diameter mm 27.03 27.03

6 Cross Sectional Area sq mm 431.6 431.6

7 Strand And Wire Diameter 45/3.38+7/2.25 45/3.38+7/2.25

8 Ultimate Strength Kg 10020 10020

9 Maximum DC resistance of conductor Ohm/Km 0.07191

10 Modulus of Elasticity Kg / sqmm 6789 6789

11 Coefficient of linear expansion (1/°C) 21.12 x 10-6 21.12 X 10-6

12 Mass Kg / m 1.337 1.337

13 Standard drum length m Specify 2500 ± 5%

14 Type Tested Y /N Y Y (Similar Type of conductor)