Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

Engineering Structures 106 (2016) 436–449

Contents lists available at ScienceDirect

Engineering Structures
journal homepage: www.elsevier.com/locate/engstruct

F2 tornado velocity profiles critical for transmission line structures


A.A. El Damatty a,⇑, A. Hamada b
a
Department of Civil and Environmental Engineering, WindEEE Research Institute, Faculty of Engineering, The University of Western Ontario, Faculty of Engineering, London,
Ontario, Canada
b
Department of Civil and Environmental Engineering, Faculty of Engineering, The University of Western Ontario, Faculty of Engineering, London, Ontario, Canada

a r t i c l e i n f o a b s t r a c t

Article history: In several locations around the globe, many failures of transmission line structures have been observed
Received 26 March 2015 during high intensity wind events in the form of tornadoes and downbursts. There is a lack of procedures
Revised 19 September 2015 in the design codes and manuals of practice related to the estimation of tornado forces on transmission
Accepted 11 October 2015
line systems. As such, the purpose of this paper is to present load cases that simulate the critical effect of
Available online 11 November 2015
F2 tornadoes on tangent lattice transmission line structures. The current study builds on extensive
research previously conducted at the University of Western Ontario, Canada on this subject. A main chal-
Keywords:
lenge in this application of localized wind events is that the forces acting on the structure vary signifi-
F2 tornadoes
Transmission line
cantly based on the location of the tornado and a large parametric study involving varying the tornado
Transmission towers location has to be conducted for each system to determine critical cases. Critical load cases are deter-
Lattice mined in this study based on parametric studies carried out in previous investigations as well as others
Wind conducted in the current study. The vertical profile of three velocity components associated with each
Wind design critical load case as well as the horizontal profile of the associated transverse velocity along the lines
High intensity wind are provided in this paper. A procedure that will allow practicing engineers to use those profiles for ana-
lyzing lattice transmission lines under F2 tornadoes is described. Validation of the developed procedure is
conducted by considering two independent transmission line systems. The results indicate that the
developed load cases estimates peak internal forces that are either slightly higher or 5% less than the
values predicted by the detailed parametric studies.
Ó 2015 Elsevier Ltd. All rights reserved.

1. Introduction Ontario Hydro has reported that five out of six weather-related line
failures in their territory are due to tornadoes [4]. Newark [5] con-
Electricity plays a vital and essential role in our daily life. cluded that, on average, a F3 tornado occurs in Southwestern
Almost all business and activities depend on having a reliable Ontario every five years. In the United States, 800–1000 HIW
source of electricity. Transmission lines are responsible of carrying storms occur each year leading to many transmission structures’
electricity from the source of production to the end users. Failure of damages or failures [4]. CIGRE’ [6] questionnaire on line failures
transmission lines can have devastating social and economical con- in different countries indicated that 65% of weather-related events
sequences, so it is imperative to understand how failures occur and on transmission lines were caused by HIW events such as torna-
how to prevent them. It has been reported that 80% of weather- does. Accordingly, an extensive research program that was initi-
related transmission line failures are attributed to high intensity ated by the authors at The University of Western Ontario,
wind (HIW) events in the form of tornados and downbursts [1,2]. Canada, more than six years ago to study the behavior of transmis-
Ishac and White [3] reported that within populated areas in sion line structures under tornado wind loads. Previously pub-
Canada, Southwestern Ontario experiences the highest rate of tor- lished studies focused on the development and validation of
nado incidence (about two tornadoes per 10,000 km2 every year) numerical models either for characterization of the tornado wind
and most transmission line failures in this area are caused by tor- fields or for prediction of structural response under tornado load-
nadoes. 92% of these tornadoes were F2 or less on the Fujita scale. ing. The developed numerical models were used in previous stud-
ies to assess and understand the behavior of transmission line
structure under such a loading as well as to determine failure loads
⇑ Corresponding author. and describe failure mechanisms. The current study is very unique
E-mail addresses: damatty@uwo.ca (A.A. El Damatty), ahamada@uwo.ca
in the sense that it is the first study in the literature, either carried
(A. Hamada).

http://dx.doi.org/10.1016/j.engstruct.2015.10.020
0141-0296/Ó 2015 Elsevier Ltd. All rights reserved.
A.A. El Damatty, A. Hamada / Engineering Structures 106 (2016) 436–449 437

by the authors or by other investigators, to present load cases that design guidelines, and utilities’ design methodologies are based
can be used in designing transmission line structures to resist tor- solely on the wind loads resulting from large-scale synoptic events
nadoes and specifically F2-tornadoes. with conventional boundary layer wind profiles.
Tornadoes are categorized by the damage-based Fujita scale [7], Few studies related to the behavior of transmission line systems
or the modified Enhanced Fujita scale (EF-scale). Both have six cat- under tornado wind loads are available in the literature. The failure
egories, 0–5 which represent the damage level and take into of a self-supported lattice tower under tornado and microburst
account tornado characteristics such as path width, length, and wind profiles was investigated by Savory et al. [24]. The analysis
wind speed. Due to the complexity and difficulty of obtaining was done for the transmission tower, without modeling the lines,
full-scale data, especially for the near ground region, laboratory and without considering the vertical velocity component of the
simulations such as Tornado Vortex Chambers (TVC) are used in tornado. Hamada [25] and Hamada et al. [18] studied the behavior
which tornadoes are represented as vortices [8–16]. The TVCs pro- of guyed transmission line systems under both F4 and F2 tornado
vide a good simulation of the flow characteristics inside a tornado, wind fields. A procedure to estimate the velocity field for F2 torna-
but the results are quite sensitive and are affected by the applied does relying on both CFD data and the parameters of F2 tornadoes
boundary conditions and the experimental limitations. For the near defined in the Fujita scale was developed in this study. Hamada
ground region, numerical analysis can be done using CFD simula- and El Damatty [19] conducted a comprehensive study to assess
tions, which can provide a good description for the flow in this and understand the performance of transmission line structures
region. The field data for the 1998 Spencer South Dakota F4 tor- under tornado loading. The study investigated the variation of
nado and for the 1999 Mulhal F4 tornado were used to validate the tower members’ internal forces with the location of the tor-
the numerical (CFD) simulations of F4 and F2 tornadoes conducted nado relative to the transmission line system. The dynamic effect
by [17,18]. associated with the translation motion of the tornado was assessed
The complexity in analyzing transmission line structures under and the results of the parametric study were used to determine the
tornadoes arises from the following facts: sensitivity of the members’ peak forces with the parameters defin-
ing the location of the tornado relative to the transmission line.
1. Tornadoes are localized events with complex wind profiles. The Altalmas et al. [26] and El Damatty and Hamada [27] assessed
tornado wind profile has three velocity components. These are the transmission lines’ failure mechanisms under critical tornado
the tangential, radial, and vertical components. The forces act- configurations. In addition, the studies predicted the maximum
ing on a tower and its attached conductors vary based on the tornado velocity that various lines can withstand before experienc-
location of the event relative to the tower [18,19]. In fact, some ing global failure. The study also described the modes of failure and
incidences of transmission line failures were attributed with its progression for a number of transmission towers. Hamada and
tornadoes’ centers located far from the transmission line as El Damatty [28] assessed the behavior of two guyed transmission
reported by ASCE [1] and Hamada and El Damatty [19]. line structures under F2 tornado wind field, boundary layer wind,
2. The conventional wind profiles are characterized by a mono- electrical companies’ recommended wind field, and CIGRE’ [23]
tonic increase in velocity with height, which is different than recommended tornado loading cases. In addition, a comparison
wind profiles attributed to tornadoes where the maximum was carried out between the forces in the transmission tower
wind speed occurs near the ground [18–22] as shown in members resulting from the tornado, and those obtained for the
Fig. 1. In this figure the vertical profiles of the tangential veloc- case of broken wires. Hamada and El Damatty [29] developed a
ity component of an F4 tornado wind field are plotted at differ- nonlinear three-dimensional four-nodded cable element that can
ent radial distances from tornado center ‘‘r”. simulate transmission line conductors while accounting for the
3. The prediction of the structural performance of the conductors nonlinearity resulting from large displacements. The element was
is challenging due to their expected highly nonlinear behavior used by the authors to model multi-span conductors of real trans-
under tornadoes. As a result, the ASCE [1] and CIGRE’ [23] rec- mission line systems. In this study, the authors simulated the
ommend that the tornado loads on the lines should be transmission towers and the insulators springs using a three-
neglected because of such complexity. dimensional spring system with stiffness dependent on the rota-
tion experienced by the insulators. Hamada and El Damatty [30]
Despite the significance of tornado events on transmission tow- developed an in-house nonlinear three-dimensional numerical
ers as manifested by the many failures, the codes of practice, model simulating lattice towers which was coupled with the

110
100
90
80
70 r = 50 (m)
r = 100 (m)
Z (m)

60
r = 158 (m)
50 r = 200 (m)
40 Transmission Wires r = 300 (m)
r = 400 (m)
30
r = 500 (m)
20
10
0
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150
Velocity (m/s)

Fig. 1. Vertical profile of tangential velocity component for different radial distances from F4 tornado center.
438 A.A. El Damatty, A. Hamada / Engineering Structures 106 (2016) 436–449

numerical model of the conductors developed by Hamada and El 2. Description of the transmission line systems used to develop
Damatty [29] and the tornado wind fields discussed by [17,18]. critical load cases
The authors extended the numerical model to study the progres-
sive failure of lattice transmission line systems under tornado wind The transmission line systems simulated in the current study
loads. The study provided an insight about the resilience of trans- are generic guyed and self-supported tower systems used by dif-
mission line system against failures when experiencing tornado ferent hydro companies. The structural layout of the four transmis-
wind fields, described the failure modes using two material mod- sion line system used for the development of the critical load cases
els, and assessed the effect of inclusion of geometric nonlinearities is provided in Figs. 2 and 3. Towers T1 and T2 are guyed towers,
in the failure analysis of lattice towers. while towers T3 and T4 are self-supported towers. Only tangent
It is evident that the state-of-the-art literature for transmission lattice structures are used in the current study. As shown in the fig-
line-related tornado studies includes only characterization of the ures, the considered systems cover single leg, as well as V-shaped
wind field as well assessment for the behavior and failure modes towers. They cover a variation in the shape and number of cross-
of the transmission towers. No study is available yet in the litera- arms, as well as the number of conductors carried by the transmis-
ture guiding structural/line engineers to estimate the forces on sion towers (from two to eight). For the guyed towers, different
transmission towers and lines due to such tornado events. This supporting guys’ configurations are considered including guys con-
becomes very important for tangent towers since the risk of torna- nected to cross-arms, guys connected to the transmission tower
does to cross transmission lines is quite high for tangent towers. As bridge, and guys connected to the tower’s bridge, and conductor’s
such, the objective of the current study is to develop equivalent set cross-arms. In addition, the chosen systems’ spans range between
of load cases that simulate and provide an envelope for the effect of 200 and 480 (m), which covers the common spans used by the
tornadoes on tangent transmission line structures, and can be industry for lattice towers. Different insulator configurations, such
applied by a structural engineer designing such structures. Since as suspension and V-suspension insulators, with various lengths
F2 tornadoes have a cumulative frequency of occurrence of 86% are used.
[1], the current study focuses on providing equivalent load cases Tower T1’s height is 44.36 (m) and is supported by four guys
for this magnitude of tornadoes. The study also focuses on lattice attached to the tower through two guys’ cross-arms. Two conduc-
steel towers. The developed load cases are based on extensive tor bundles are connected to the line’s cross-arms using a 4.27
parametric studies conducted on four different transmission line (m) insulator at a height of 38.23 (m). One ground-wire is con-
systems that cover a broad spectrum of the transmission line sys- nected to the top of the tower. The conductors and ground-wire
tems commonly used in the industry. The paper starts with a spans are 480 (m). The conductors and the ground-wire sags
description of the F2 tornado wind profile and the nonlinear are 20 (m) and 13 (m), respectively. The geometric and material
three-dimensional finite element modeling of transmission line properties of the conductors, ground-wire, and supporting guys
systems. The results of the extensive parametric studies of the four are provided by Shehata et al. [31]. Tower T2’s height is 46.57
transmission line systems are used to identify the critical tornado (m) and is supported by four guys attached to the tower’s bridge
locations that lead to the peak internal forces in the studied sys- as shown in Fig. 2. Three conductor bundles are connected to the
tems. Then, equivalent loading cases with components in the three lines’ cross-arms and bridge using a 4.27 (m) suspension and
orthogonal directions are developed. Two different transmission V-suspension insulators. Two ground-wires are attached to the
line systems, one guyed and one self-supported, are finally used top of the tower. The lines have a span of 460 (m) and a sag of
to verify the recommended tornado loading cases. 16 (m).

Tower T2 Tower T1
Fig. 2. Guyed towers T1 and T2.
A.A. El Damatty, A. Hamada / Engineering Structures 106 (2016) 436–449 439

bays of transmission lines (conductors and ground-wires). Such a


number of spans was recommended by Shehata et al. [31] and
Hamada [25], in order to accurately account for the forces trans-
ferred from the lines to the middle tower (tower of interest).

2.1. Finite element modeling

The transmission line systems used in the current study are


simulated using an in-house nonlinear three-dimensional numeri-
cal models developed and verified by the authors in previous
studies. The transmission tower members are modeled using
two-noded, three-dimensional frame elements. The element takes
into account the geometric nonlinear effects. Each member is mod-
eled using one element. Rigid connections are assumed between
chord members in order to simulate the typically used multi-
Tower T4
bolted connections. Hinged connections are assumed for diagonal
Tower T3 members to simulate single-bolted connections used to connect
those members to the chord members. A four-noded, nonlinear,
Fig. 3. Self-supported towers T3 and T4. three-dimensional cable element is used to model the transmission
lines and equivalent cable element is used to model the supporting
guys. The cable element has three translational degrees of freedom
The overall height of the self-supported tower T3 is 47.5 (m). at each node. The cable element nonlinear formulation accounts
The conductors’ cross-arms are located at a height of 35.1 (m) for tension stiffness and geometric nonlinearities resulting from
and have a width of 13.4 (m). Conductor bundles are connected large displacements and the P-delta effect. More details regarding
to the tower at three locations. Each of the outer left and right con- the numerical simulation of the transmission line systems are
ductors is attached to a suspension insulator of 4.27 (m). The mid- provided by Hamada and El Damatty [29,30].
dle bundle is attached to the tower’s bridge using a V-suspension
insulator, each 5.9 (m) long. Two ground-wires are attached to 2.2. F2 tornado wind field
the top of the tower. The transmission line span is 420 (m). The
material and geometric properties of the conductors and ground- CFD simulation conducted by Hangan and Kim [17] and used by
wire are provided by Altalmas [32]. For tower T4, the overall height Hamada et al. [18] to obtain the three-dimensional F2 tornado
of the tower is 54.7 (m). The tower has six cross-arms on which wind field is employed in the current study. The CFD simulations
conductors are carried. The lower cross-arms are located at a were conducted in a steady state manner. The F2 tornado wind
height of 34.2 (m), while the upper cross-arms are located at a field is given as a function of the cylindrical coordinates r, h, and
height of 49.6 (m). The middle cross-arms are located at a height Z. It has an approximate path width of 400 (m), accompanied with
of 41.9 (m) with a total width of 14.3 (m). The transmission line an outside gust front width of 2400 (m). Vertical profiles for tan-
spans are 213 (m). Each of the six conductor bundles is attached gential, radial, and vertical velocity components at the near ground
to a single insulator of 2.4 (m) long, which is allowed to swing in (100 m) region are provided in Figs. 4–6. The vertical profiles of the
two perpendicular planes. The ground-wires are attached to the three velocity components are provided at various radial distances
top of the tower. The material and geometric properties of the con- r. As shown in the figures, for radial distance r < 200 (m), the tor-
ductors and ground- wires are provided by Altalmas [32] and Altal- nado wind profile is significantly different than the conventional
mas et al. [26]. boundary wind profile. Near the tornado center, the vertical loca-
The numerical simulation of each of the four transmission line tion of the peak tangential velocity becomes very close to the
systems consists of the tower of interest and two towers from each ground. Also, away from the tornado center, the vertical location
side, which are included in order to properly simulate the stiffness of the peak radial velocity becomes quite close to the ground. In
of the whole system. As such, the nonlinear three-dimensional addition, the radial velocity changes direction with height, where
finite element model includes five transmission towers with six negative values shown in the figures imply velocities acting in an

100
90
80
70
Z height (m)

r = 18 (m)
60
r = 50 (m)
50 r = 73 (m)
Transmission Lines r = 96 (m)
40
r = 120 (m)
30 r = 150 (m)
r = 200 (m)
20
10
0
0 10 20 30 40 50 60 70 80
F2 tangential Velocity (m/sec)

Fig. 4. Vertical profile of tangential velocity component for different radial distances ‘‘r” from tornado center – F2 tornado.
440 A.A. El Damatty, A. Hamada / Engineering Structures 106 (2016) 436–449

100

90

80

70

Z height (m)
r = 18 (m)
60
r = 50 (m)
50 r = 73 (m)
Transmission Lines r = 96 (m)
40
r = 120 (m)
30 r = 150 (m)
r = 200 (m)
20

10

0
-50 -40 -30 -20 -10 0 10 20
F2 RadialVelocity (m/sec)

Fig. 5. Vertical profile of radial velocity component for different radial distances ‘‘r” from tornado center – F2 tornado.

100

90

80

70
r = 18 (m)
Z height (m)

60
r = 50 (m)
50 r = 73 (m)
r = 96 (m)
40
TransmissionLines r = 120 (m)
30 r = 150 (m)
r = 200 (m)
20

10

0
-10 0 10 20 30 40
F2 Axial Velocity (m/sec)

Fig. 6. Vertical profile of axial (vertical) velocity component for different radial distances ‘‘r” from tornado center – F2 tornado.

inward direction while positive values mean velocities acting in towers and the lines are described in detail by Hamada et al. [18]
the outward direction. The vertical component acts in an upward and Hamada and El Damatty [19]. The response of the transmission
direction and is characterized by a zero value at ground level. It line system under wind consists of a mean, background, and a res-
is obvious from the figures that the tangential, radial, and axial onant components. The used F2 tornado model is scaled up to
velocity components change significantly with the location relative match the 3-sec gust velocity of F2 tornado to account for the mean
to the tornado center. The vertical wind profiles of the three veloc- and background responses of the transmission line systems. The
ity components vary for different values of radial distance r. The resonant component is neglected for transmission line systems
maximum tangential gust velocity, which incorporates the tornado due to the high aerodynamic damping of the lines and the relative
translation velocity of the F2 tornado, is 72 m/s and occurs at a high rigidity of the supporting lattice towers [19,33,34]. Accord-
radius r = 96 m and a height Z = 22 m. The maximum radial veloc- ingly, the parametric study for each transmission line system
ity is 45 m/s and corresponds to a radius r = 146 m and a height involves a large number of quasi-static analyses by considering
Z = 6 m. The maximum vertical velocity is 37 m/s and corresponds different values for the tornado location (R and h) as shown in
to a radius r = 171 m and a height Z = 127 m. Fig. 7; R and h are the relative tornado location with respect to
the tower of interest. Combinations of thirteen values for R and six-
teen values for h are considered in each parametric study. Each
3. Parametric study combination represents a different load case for the lines and the
tower of interest. The considered values for R are 50, 75, 90, 100,
As mentioned before, the critical load cases developed in this 125, 150, 200, 250, 300, 350, 400, 450, and 500 (m) and for the
paper are based on extensive parametric studies conducted on angles h are 0°, 30°, 45°, 60°, 90°, 120°, 135°, 150°, 180°, 210°,
the six transmission line systems, four described earlier and two 225°, 240°, 270°, 300°, 315°, and 330°.
described in following sections. The analyses of the towers T1 The approach used in the current study involves presenting first
and T3 were conducted previously and were reported by Hamada the critical tornado configurations that lead to peak forces in the
et al. [18], Hamada and El Damatty [19], and Altalmas [32], respec- tower members as well as to peak transverse and longitudinal
tively. The analyses of the towers T2 and T4 are conducted in the forces transferred from the conductors to the towers. Those are
current study. Only analyses under F2 tornado loading are consid- used to come up with critical velocity profiles for members in both
ered since the aim is to develop load cases simulating this level of the main body of the towers and the cross arms. The validity of the
tornadoes. The self-weight of the towers and the lines are included proposed load cases is then assessed by comparing the internal
in the analyses. The evaluations of F2 tornado forces on the lattice forces in the tower members resulting from the extensive
A.A. El Damatty, A. Hamada / Engineering Structures 106 (2016) 436–449 441

Fig. 7. Tornado configurations R and h relative to the tower of interest.

parametric study and the proposed load cases. The four extensive coincides with maximum tangential, radial, and vertical velocities
parametric studies reveal that the internal forces in all transmis- on the tower of interest. To assess the effect of the lines on the
sion tower members change significantly with the variation of forces transmitted to the towers, the variation of transmission lines
the parameters R and h. Different types of transmission tower transverse, vertical, and longitudinal reactions with respect to
members, either chord or diagonal members, have independent R and h are shown in Figs. 8–11, respectively. In the following
critical tornado configurations R and h that lead to the peak discussion, lines’ reactions represent the conductors and ground-
(compression or tension) internal forces in those members. By wire forces that are inverted on the tower of interest. An analogy
examining all the results of the parametric studies, a number of can be made between a self-supported lattice transmission tower
critical tornado configurations (R and h) that lead to peak forces and a cantilever beam, as well as between a guyed tower and an
in the main body of the towers as well as in the cross-arms areas overhanging beam. In both cases, due to tornadoes, the beam will
are identified in the current study. These identified tornado config- be subjected to distributed loads acting on the tower members and
urations are described in the next two subsections. concentrated loads representing the forces (reaction) from the
lines transferred to the tower.
3.1. Critical tornado configuration on transmission tower’s main body
– Cases of R = 100 (m) and h = 0° and 180°: these tornado loca-
Three critical values for R are identified. In addition, four critical tions relative to the tower of interest lead to a large distributed
values of h are identified for each value of R. Those critical config- loads along the tower height with maximum values close to the
urations are: ground followed by a monotonic decrease similar to the wind
velocity profile shown in Figs. 4 and 5. The distributed load on
R = 100 (m), with h = 0°, 90°, 180°, and 270°. tower is accompanied with both minimum transverse and sig-
R = 125 (m), with h = 30°, 150°, 210°, and 330°. nificant longitudinal reactions from the lines as depicted from
R = 150 (m), with h = 60°, 120°, 240°, and 300°. Figs. 8 and 11, respectively. The minimum lines’ transverse
reaction is due to the opposite wind directions, almost counter
A discussion is carried out below to highlight the reason the balancing each other, on the spans adjacent to the tower of
above configurations are critical. According to Figs. 4–6, the interest. The significant lines’ longitudinal reaction is due to
relative distance to the tower of interest R of 100, 125, 150 (m) unbalanced loads on the spans adjacent to the tower of interest.

27000
24000
21000
18000
15000
12000
R = 50 (m)
9000
R = 100 (m)
6000
Force (N)

3000 R = 125 (m)


0 R = 150 (m)
-3000 0 30 60 90 120 150 180 210 240 270 300 330 R = 250 (m)
-6000 R = 350 (m)
-9000 R = 450 (m)
-12000
R = 500 (m)
-15000
-18000
-21000
-24000
-27000
θ (Deg.)

Fig. 8. Variation of transmission line’s transverse reaction with R and h (T1 tower).
442 A.A. El Damatty, A. Hamada / Engineering Structures 106 (2016) 436–449

Fig. 9. Schematic view of critical tornado configuration R = 250 (m) and h = 60° (T1 tower).

28000

27000

26000 R = 50 (m)
Force (N)

R = 100 (m)
R = 125 (m)
25000
R = 150 (m)
R = 250 (m)
R = 350 (m)
24000
R = 450 (m)
R = 500 (m)
23000

22000
0 30 60 90 120 150 180 210 240 270 300 330
θ (Deg.)

Fig. 10. Variation of transmission line’s vertical reaction with R and h (T1 tower).

8000

6000

4000
R = 50 (m)
2000 R = 100 (m)
Force (N)

R = 125 (m)
0 R = 150 (m)
0 30 60 90 120 150 180 210 240 270 300 330 R = 250 (m)
-2000 R = 350 (m)
R = 450 (m)
-4000 R = 500 (m)

-6000

-8000
θ (Deg.)

Fig. 11. Variation of transmission line’s longitudinal reaction with R and h (T1 tower).

– Cases of R = 100 (m) and h = 90° and 270°: similar to the previ- the ground and decreases with height till it reaches almost a
ous case, a large distributed load following the same trend is zero value at the cross-arms height. The transverse loads on
exhibited along the tower height. In this case, a significant the adjacent spans of the towers almost counter balance each
transverse lines‘ reaction exists with a minimum longitudinal other and lead to a minimum transverse reaction, as depicted
reaction, as depicted from Fig. 8 and 11. from Fig. 8. Similar to the case of R = 100 (m) and h = 0° and
– Cases of R = 125 (m) and h = 30°, 150°, 210°, and 330°: These 180°, the unbalanced loads on the adjacent spans result in a
tornado locations lead to larger distributed loads along the significant longitudinal reaction from the lines, as shown in
tower height, especially in the upper region. As shown in Figs. 4 Figs. 11 and 12.
and 5, the tangential velocity profile has a significant wind – Cases of R = 150 (m) and h = 60°, 120°, 240°, and 300°: the dis-
speed that extends from a height of 20 (m) to 50 (m). In addi- tributed loads along the tower height follows the same discus-
tion, the radial velocity component has a maximum value near sion for R = 125 (m). For h = 60°, and 240°; a significant high
A.A. El Damatty, A. Hamada / Engineering Structures 106 (2016) 436–449 443

12000
10000
8000
6000
R = 50 (m)
4000
R = 100 (m)

Force (N)
2000 R = 125 (m)
0 R = 150 (m)
0 30 60 90 120 150 180 210 240 270 300 330
R = 250 (m)
-2000
R = 350 (m)
-4000 R = 450 (m)
-6000 R = 500 (m)

-8000
-10000
-12000
θ (Deg.)

Fig. 12. Variation of transmission line’s longitudinal reaction with R and h (T2 tower).

transverse reaction from the lines is observed accompanied always less than the gravity of the lines and, therefore, no vertical
with a significant longitudinal reaction, as depicted from uplift movement is anticipated for the lines. There is a 20% reduc-
Figs. 8–12. tion in the vertical reaction of the wire due to some tornado con-
figurations, as shown in Fig. 10.
Further discussions regarding the behavior of transmission lines
under tornadoes are provided by [18,19,29,30,32].
3.2.2. Cases of maximum longitudinal reactions of the conductors
Longitudinal reactions of transmission lines lead to an impor-
3.2. Critical tornado configuration on cross-arms
tant loading case which is caused by the unbalanced tornado loads
on the adjacent spans of the tower of interest. Hamada and El
This section is divided into two Sections 3.2.1 and 3.2.2.
Damatty [19] concluded that these cases can lead to compression
Section 3.2.1 assesses the critical tornado configurations that lead
forces in the transmission tower’s cross-arms that are not typically
to the maximum transverse force applied on the supporting tower
considered in the design of these tower sections. There was evi-
from the transmission lines. Section 3.2.2 discusses the critical
dence of failure of a transmission tower during a downburst event
tornado configurations that lead to the maximum longitudinal
as a result of an unbalanced load case as reported by Shehata and
force for the lines.
El Damatty [35]. The results of one conductor for transmission line
system T1 are shown in Fig. 11, and for transmission line system T2
3.2.1. Cases of maximum transverse reactions of the conductors are shown in Fig. 12. As shown in both figures, the variation of the
The extensive parametric study results are used to evaluate the longitudinal reactions with R and h is following the same trend
maximum transverse (perpendicular to the lines) reactions of with difference in magnitudes. The results show that the critical
the transmission lines on the supporting towers. The main objec- tornado configurations that give the maximum transmission lines
tive is to identify the critical tornado configuration R and h that longitudinal reactions are as follows:
lead to the maximum transverse reactions of the lines. The trans-
verse and vertical reactions of all the considered thirteen values R = 450 (m), with h = 90° and 270°.
of R and the corresponding sixteen values of h are calculated for R = 125 (m), with h = 0° and 180°.
each conductor and ground-wire of towers T1, T2, T3, and T4.
The variation of the transverse and vertical reactions with R and The results also indicate that the longitudinal reaction can reach
h is shown to follow the same trend for all cases with change only up to 40% of the maximum transverse reaction. This is can be con-
in magnitudes. Thus, only the results for one transmission line sys- cluded from Fig. 12, as the maximum longitudinal reaction of
tem, transmission tower T1, are presented in Figs. 8 and 10, where transmission line T2 is 11,071 (N), while the maximum transverse
the variations with R and h of transverse and vertical reactions are reaction is 28,859 (N).
plotted, respectively. As shown in Fig. 8, the transmission line’s
transverse reaction varies significantly with R and h. Based on
the results of the study, the maximum transmission line’s trans- 4. Velocity profiles for critical load cases for the towers – tower
verse reaction is found to be associated with tornado configura- profiles
tion: R = 250 (m) and h = 60° and 240°.
The maximum transverse reaction critical configuration The basic velocity profiles of the twelve recommended load
(R = 250 (m) and h = 60°) can be explained in view of the schematic configurations reported in Section 3.1 are resolved from the tan-
shown in Fig. 9. The angle h = 60° and 240° leads to a maximum gential and radial directions into the Cartesian coordinates
resultant of the tangential and radial velocity components, as (X and Y), where X is the direction perpendicular to the lines and
shown in Fig. 9. For this tornado location, the transverse velocity Y is the direction parallel to the lines. The vertical components of
profile along the tributary length (mid-span to mid-span of adja- the basic velocity profiles are along the Z direction. After careful
cent conductors) carried by the tower of interest is unidirectional. examination of the X, Y, and Z basic velocity profiles along the
This is found to happen regardless of the span length. height of the towers for the twelve cases, it is found that they
The weight of the conductors and ground-wires is considered as can be described in view of five tower velocity profiles
a main component in the design of the lines’ cross-arms and the denotes as profiles A–G. Those six tower profiles are illustrated
tower. The uplift force generated by F2 tornado is found to be in Appendix A.
444 A.A. El Damatty, A. Hamada / Engineering Structures 106 (2016) 436–449

Table 1
Recommended twelve case of loading of transmission towers and lines for peak internal forces in the tower of interest.

Load Tornado config. R = 100 (m) Load Tornado config. R = 125 (m) Load Tornado config. R = 150 (m)
case case case
Tornado Applied Cables Tornado Applied tower Cables Tornado Applied tower Cables
# # #
config. h tower transverse config. h velocity (m/s) transverse config. h velocity (m/s) transverse
velocity velocity velocity (m/s) velocity (m/s)
(m/s) (m/s)
x y z x y z x y z
1 0° A B G H 5 30° C D G L 9 60° B F 0.75 P
G
2 90° B A G I 6 150° F B 0.80 M 10 120° D C 0.75 Q
G G
3 180° A B G J 7 210° C D G N 11 240° B 0.80 0.75 R
F G
4 270° B A G K 8 330° F B 0.80 O 12 300° 0.80 C 0.75 S
G D G

A profile of wind velocity acting along the transverse direction values for the transverse and longitudinal forces transmitted from
of the transmission lines is also associated with each one of the the conductors to the tower.
twelve load cases. Also by examining those profiles, it is found that The parametric studies conducted on the four lines predict six
they have twelve different shapes and those are donated by pro- critical load cases for the cross-arm members (reported in Sections
files H–S and are illustrated in Appendix B. The tower profile des- 3.2.1 and 3.2.2). Those cases are described in Table 2, where the
ignation describing the three velocity components of the wind field values of the radial distance R and the angle h are provided for each
along the height of the towers as well as describing the variation of case. As shown in the table, the variation of the three velocity com-
the transverse velocity along the spans of the conductors adjacent ponents along the height of a tower can be represented by four
to the tower of interest are given in Table 1 for the twelve load basic profiles (C1–C4). Those line profiles are presented graphically
cases. It should be noted, that for some diagonal members, it is and are described mathematically in Appendix C. Similar to the
found that the peak internal forces occur when the conductors load cases for the main body of the tower, each load case for the
and ground-wires forces are not included. As such, it is recom- cross-arm is associated with a specific profile for transverse veloc-
mended that those twelve load cases be repeated twice; firstly ity acting along the conductor spans adjacent to the tower of inter-
with inclusion of both conductors and ground-wires and the sec- est. Those profiles are denoted in Table 2 as C6–C11 and are
ondly without the inclusion of both the conductors and ground- illustrated in Appendix D.
wires.
6. Steps of applying critical load cases on transmission lines

5. Velocity profiles for critical load cases for cross-arms – line The steps below describe how the above developed critical tor-
profiles nado profiles can be applied to a transmission line system in order
to predict the response of a tangent tower to F2 tornadoes:
The twelve load cases presented above embrace all configura-
tions leading to peak forces in members of the main body of a tan- 1. The tower, the conductors, the ground-wires, and the support-
gent lattice transmission tower. However, the analyses indicate ing guys of guyed towers are modeled as described in Sec-
that other tornado configurations can lead to peak forces in mem- tion 2.1 using any available commercial software. At least two
bers of the towers’ cross-arms. The internal forces in the cross-arm conductors’ spans from each side of the tower of interest should
members depend mainly on the forces transmitted from the con- be included in the analyses. As shown in Appendices B and D,
ductors to the tower as a result of the wind loads acting on those the conductor loads are provided for a distance of 500 (m) from
conductors. It should be noted that the longitudinal forces result each side of the tower. Beyond this distance, the loading should
from the case where the wind loads acting on two spans adjacent be maintained constant with a value corresponding to that at
to a tower are unequal. This case leads to a variation in the conduc- the 500 (m) distance.
tor’s internal tension forces between the two spans and, conse- 2. For each load case,
quently, a resultant longitudinal force is transferred to the i. The velocity profiles in the X, Y, and Z directions are used to
cross-arms through the insulators. As such, the critical tornado evaluate the velocities at the nodal points of the tower and
configurations for the cross-arms are those leading to maximum supporting guys.

Table 2
Recommended six case of loading of transmission towers and lines for maximum longitudinal and transverse reactions of transmission lines.

Maximum longitudinal reaction Maximum transverse reaction


Load Tornado config. R = 450 Load Tornado config. R = 125 Load Tornado config. R = 250
case case case
Tornado Applied tower Cables Tornado Applied tower Cables Tornado Applied tower Cables
# # #
config. h velocity transverse config. h velocity transverse config. h velocity transverse
velocity velocity velocity
x y z x y z x y z
(m/s) (m/s) (m/s)
13 90° C1 C2 – C6 15 0° C3 C4 C5 C8 17 60° 0.8 0.5 0.25 C10
C4 C3 C5
14 270° C1 C2 – C7 16 180° C3 C4 C5 C9 18 240° 0.8 0.5 0.25 C11
C4 C3 C5
A.A. El Damatty, A. Hamada / Engineering Structures 106 (2016) 436–449 445

ii. The lines velocity profile is used to evaluate the transverse higher peak forces as long as the difference is less than 5%. A justi-
velocity at the conductors and ground-wire nodal points. fication for accepting such a difference is provided below.
iii. The horizontal and vertical forces acting on the nodal points
of the tower, conductors, ground-wire, and supporting guys 7.1. Description of the two transmission line systems
are evaluated using the procedures specified in the design
code or manual of practice employed by the user (e.g. ASCE The two transmission lines systems employed for verification
[1]). are generic self-supported and guyed transmission tower systems
iv. Nonlinear (with geometric nonlinearity included) elastic used by several hydro companies. The towers are labeled as T5
static analysis is conducted for the transmission line system. (self-supported) and T6 (guyed) and are shown in Fig. 13. Tower
v. Tower‘s members peak internal forces are evaluated. T5 height is 51.81 (m) and has six conductors’ bundles connected
3. Envelop of the tower‘s members peak internal force resulting to the line’s cross-arms using a 2.4 (m) insulator strings. Two
from all critical cases is evaluated. ground-wires are connected to the top of the tower. The transmis-
sion line system spans are 450 (m). The conductors and ground-
7. Verification using different towers configurations wires sags are 20 and 12 (m), respectively. Tower T6 height is
43.44 (m) and is supported by eight guys attached to the cross-
The load cases presented above are developed based on exten- arms as shown in Fig. 13. Three conductor’s bundles are connected
sive parametric studies conducted on four different tangent lattice to the cross-arms using a 4.27 (m) insulator. Two ground-wires are
transmission line systems. The approach adopted to verify the ade- attached to the top of the tower. The transmission line system
quacy of those load cases involves considering two other indepen- spans are 400 (m) and conductors and ground-wires sags are 16
dent and different transmission line systems. As extensive and 11 (m), respectively.
parametric study is conducted for those two lines by moving the
tornado in space (at different R and h values). For each specific 7.2. Analysis and discussion
value of R and h, a nonlinear analysis is conducted for the three-
dimensional finite element model of the transmission line system Towers T5 and T6 are divided into different zones as shown in
and the internal forces in the members of the tower of interest Fig. 13. For each zone, some chord and diagonal members are
are recorded. The peak forces in the members obtained from the selected to present the results. In addition, the results are shown
entire parametric studies are determined. for several chord and cross-arm’s upper and lower chord members.
Meanwhile, the lines are analyzed nonlinearly under the 18 For each selected member, the peak internal forces resulting from
load cases proposed in this paper and the envelope for the peak the critical load cases and the extensive parametric studies analy-
forces in various members of the tower due to those load cases ses are reported in Tables 3 and 4.
are determined. The peak forces obtained from both the critical The following observations can be concluded:
load cases analyses and the parametric study are compared
together. The proposed load cases would be considered conserva- – The critical tornado configurations (R and h) that lead to peak
tive if they estimate peak internal forces exceeding those resulting internal forces in the two systems coincide with the counterpart
from the extensive parametric studies. It is considered here that values reported earlier in the paper.
the load cases are acceptable even if the parametric studies give

Tower T6

Tower T5
Fig. 13. Verification transmission towers – tower T5 and T6.
446 A.A. El Damatty, A. Hamada / Engineering Structures 106 (2016) 436–449

Table 3
Parametric study and equivalent loading cases results for tower T5.

Member Parametric study Critical load cases Critical load cases/


parametric study
Peak axial force Peak axial force %
No. Type (kN) Tornado (kN)
Zone 1 439 Chord 811 R = 125 873 108
h = 180
Zone 2 7 Chord 743 R = 125 802 108
h = 210
Zone 3 19 Chord 654 R = 150 691 106
h = 210
Zone 4 31 Chord 649 R = 150 678 104
h = 210
Zone 5 39 Chord 701 R = 150 719 103
h = 210
Zone 6 Tower 47 Chord 526 R = 150 565 108
h = 240
Conductor 327 Upper Chord 14 R = 400 14 98
h = 270
322 Lower Chord 32 R = 150 30 95
h=0
Zone 7 Tower 59 Chord 243 R = 150 276 113
h = 210
Conductor 335 Upper Chord 25 R = 150 24 97
h=0
330 Lower Chord 65 R = 125 61 95
h=0

Table 4
Parametric study and equivalent loading cases results for tower T6.

Member Parametric study Critical load cases Critical load cases/


parametric study
Peak axial force Peak axial force %
No. Type (kN) Tornado (kN)
Zone 1 16 Chord 368 R = 125 351 95
h = 150
Zone 2 91 Chord 1076 R = 125 1032 96
h = 180
Zone 3 131 Chord 1259 R = 125 1221 97
h = 180
Zone 4 299 Chord 488 R = 125 465 95
h = 180
Zone 5 Conductors cross-arms 1034 Upper Chord 24 R = 125 25 105
h=0
1010 Lower Chord 23 R = 125 26 114
h=0
Zone 6 1090 Chord 51 R = 125 58 114
h=0

– For chord members, the peak internal forces due to the equiva- Considering the results of the six towers, the developed load
lent F2 loading cases are higher than the parametric study cases provide conservative design loads for the vast majority of
results with a maximum difference of 14%. the towers members. This is true with the exception of few chord
– For cross-arms members, the peak internal forces due to the and cross-arms members, where the parametric studies predict
extensive parametric study are 5% higher than the peak internal internal forces that are 1% to 5% higher than the corresponding
forces obtained from the equivalent F2 tornado loading cases. values obtained by the critical load cases. The authors believe that
This is within the limit set as acceptable difference. 5% difference in the peak internal forces of the transmission tower
members between the detailed parametric study and the load
It was also useful to compare the results of the extensive para- cases is acceptable for the following reasons:
metric studies conducted on transmissions towers T1–T4 to the
corresponding values obtained by applying the proposed critical (1) Tornadoes are extreme wind events with wind velocities
load cases to those structures. It should be noted that the results typically exceeding the normal synoptic winds used for
of the parametric studies conducted on those towers were pub- the design of transmission line systems. A range of veloci-
lished elsewhere [18,19,25–30,32]. A summary of this comparison ties is estimated by Fujita and Pearson [7] for F2-tronadoes.
is presented in this section. For all members of the towers, the The equivalent F2 tornado load case recommended in the
ratios critical load cases/parametric studies are found to vary current study are developed using the upper limit of this
between 1.06 and 1.1 for T1, 0.96 and 1.1 for T2, 0.97 and 1.1 for range.
T3 and 0.96 and 1.07 for T4.
A.A. El Damatty, A. Hamada / Engineering Structures 106 (2016) 436–449 447

(2) Transmission towers usually possess redundancy such that R = 125 (m), with h = 0° and 180°.
they can sustain loads beyond the failure of one or more
members. Failure studies conducted by Hamada and El For each of the above eighteen critical load configurations, the
Damatty [30] under tornado loading has shown that the velocity wind fields have been resolved from the tangential and
towers are able to sustain 13–41% increase in the applied radial directions into the Cartesian directions aligned parallel and
wind velocity beyond the failure of the first members till full perpendicular to the transmission lines. Each critical configuration
collapse occurred. represents a load case and the vertical profile for the three perpen-
dicular velocity components along the height of the tower are pro-
8. Conclusion vided for each case. In addition, the corresponding horizontal
profile for the transverse velocity acting on the lines are given
The current study summarizes the major findings of research for each load case. These equivalent load cases represent an envel-
conducted during the past seven years on the effect of F2 tornadoes ope for the effect of F2 tornadoes on transmission line systems, and
on tangent lattice transmission line systems. It also builds on this can be applied by a structural engineer in the design process of lat-
research to develop critical load cases for the analysis of such sys- tice tangent transmission line structures. Validation for these
tems under F2 tornadoes. The study focuses on F2 tornadoes since developed load cases is conducted by comparing the results of
they are shown to have a cumulative frequency of occurrence of the parametric to those obtained using the developed load cases.
86%. In the current paper, the F2 tornado wind field is discussed, The results indicate that the developed critical load cases lead to
where the tangential, radial, and vertical basic velocity profiles of peak internal forces in the transmission tower members that are
such events are described. Transmission line systems that are com- typically higher than the values predicted by the detailed paramet-
monly used by utility companies and covers different transmission ric studies. Few members have shown an opposite trend where the
lines variation aspects are used in the current study. The descrip- ratios between critical load case and parametric study results are
tion of the nonlinear three-dimensional finite element modeling between 0.96 and 1.0. The use of the peak value of the F2 tornado
of the different transmission lines is provided. Based on the results velocity and the redundancy that those structures possess justify
of extensive parametric studies, a number of critical tornado con- this 5% difference. It should be noticed that these cases do not
figurations (R and h) that lead to peak forces in the transmission include the effect of debris on transmission line structures that
tower members are identified. For transmission towers’ main body, might happen during large tornado events.
three critical values for R, combined with four critical values of h
for each value of R, are identified. Those critical configurations are: Acknowledgments

R = 100 (m), with h = 0°, 90°, 180°, and 270°. The authors gratefully acknowledge Hydro One Inc. for the in-
R = 125 (m), with h = 30°, 150°, 210°, and 330°. kind support, the collaboration, and the financial support provided
R = 150 (m), with h = 60°, 120°, 240°, and 300°. for this research. The second author is indebted to the Vanier
Canada Graduate and the Natural Science and Engineering
For transmission tower’s cross-arms, critical tornado configura- Research Council of Canada (NSERC) for the financial support
tions that lead to the maximum transverse and longitudinal forces provided for this research.
transferred from the lines to the transmission towers are identi-
fied. Critical tornado configurations leading to maximum trans-
verse reactions are: Appendix A

R = 250 (m) and h = 60° and 240°. See Fig. 14.

and critical tornado configurations of maximum longitudinal reac- Appendix B


tions are:
R = 450 (m), with h = 90° and 270° See Figs. 15 and 16.

50

45

40

35

C 30
Height (m)

A B

25

D F G
20

15

10

0
-30 -20 -10 0 10 20 30 40 50 60 70 80
Velocity (m/s)

Fig. 14. Tower velocity profiles A–G along tower height – F2 tornado.
448 A.A. El Damatty, A. Hamada / Engineering Structures 106 (2016) 436–449

80

60

40

20

Velocity (m/s)
0
500 400 300 200 100 0 -100 -200 -300 -400 -500

-20
H
I
-40
J
K
-60
L
M
-80
Distance from main tower (m)

Fig. 15. Line velocity profiles H–M – F2 tornado transverse velocity profile along the lines.

80

60

40

Velocity (m/s)
20

0
500 400 300 200 100 0 -100 -200 -300 -400 -500
-20
N
O
-40
P
Q
-60
R
S
-80
Distance from main tower (m)

Fig. 16. Line velocity profiles N–S – F2 tornado transverse velocity profile along the lines.

50

45
C1
40 C2
C3
35 C4
C5
30
Height (m)

25

20

15

10

0
0 10 20 30 40 50 60 70 80
Velocity (m/s)

Fig. 17. Tower velocity profile C1–C5 along tower height – F2 tornado.
A.A. El Damatty, A. Hamada / Engineering Structures 106 (2016) 436–449 449

80

60

40

Velocity (m/s)
20

0
500 400 300 200 100 0 -100 -200 -300 -400 -500

-20
C6
-40 C7
C8

-60 C9
C10

-80 C11

Distance from main tower (m)

Fig. 18. Line velocity profiles C6–C11 – F2 tornado transverse velocity profile along the lines.

Appendix C [18] Hamada A, Damatty AAE, Hangan H, Shehata AY. Finite element modelling of
transmission line structures under tornado wind loading. Wind Struct 2010;13
(5):451–69.
See Fig. 17. [19] Hamada A, El Damatty AA. Behaviour of guyed transmission line structures
under tornado wind loading. Comput Struct 2011;89(11–12):986–1003.
[20] Holmes JD, Oliver SE. An empirical model of a downburst. Eng Struct 2000;22
Appendix D (9):1167–72.
[21] Letchford CW, Chay MT. Pressure distributions on a cube in a simulated
See Fig. 18. thunderstorm downburst. Part B: Moving downburst observations. J Wind Eng
Ind Aerodyn 2002;90(7):733–53.
[22] Kareem A. Bluff body aerodynamics and aeroelasticity: a wind effects
References perspective. J Wind Eng 2010;7(1):30–74.
[23] CIGRÉ (Conseil International des Grands Réseaux Électriques/International
[1] American Society of Civil Engineers. Guidelines for electrical transmission line Council on Large Electrical Systems). Overhead line design guidelines for
structural loading. ASCE manuals and reports on engineering practice, no. 74 mitigation of severe wind storm damage. Scientific Committee B2 on
(3rd ed.). New York (NY): American Society of Civil Engineers; 2010. Overhead Lines, B2. 06.09; 2009.
[2] Dempsey D, White HB. Winds wreak havoc on lines. Transm Distrib World [24] Savory E, Parke GAR, Zeinoddini M, Toy N, Disney P. Modelling of tornado and
1996;48:32–42. microburst-induced wind loading and failure of a lattice transmission tower.
[3] Ishac MF, White HB. Effect of tornado loads on transmission lines. In: Eng Struct 2001;23(4):365–75.
Proceedings of the 1994 IEEE power engineering society transmission and [25] Hamada A. Analysis and behaviour of guyed transmission line structure under
distribution conference; April 10, 1994–April 15, 1994. p. 521–7. tornado wind loading. PhD thesis. London, Ont: School of Graduate and
[4] Behncke RH, White HB. Applying gust loadings to your lines. In: Proceedings of Postdoctoral Studies, University of Western Ontario; 2009.
the 9th international conference on overhead lines. Fort Collins (CO): American [26] Altalmas A, El Damatty AA, Hamada A. Progressive failure of transmission
Society of Civil Engineers (ASCE); 2006. towers under tornado loading. In: Annual conference of the Canadian Society
[5] Newark MJ. Canadian tornadoes, 1950–1979. Atmosph-Ocean for Civil Engineering 2012: leadership in sustainable infrastructure, CSCE
1984;22:243–53. 2012, June 6, 2012–June 9. Edmonton, AB, Canada: Canadian Society for Civil
[6] CIGRÉ (Conseil International des Grands Réseaux Électriques/International Engineering; 2012. p. 2220–29.
Council on Large Electrical Systems) SC-22 WG22-06. Review of IEC 826: [27] El Damatty AA, Hamada A. Behaviour of guyed transmission line structures
Loading and Strength of Overhead Lines. Part 3: Analysis of Recent under tornado wind loads – case studies. Electrical transmission and
Transmission Line Failures. Scientific Committee B2 on Overhead Lines; 2006. substation structures 2012: solutions to building the grid of tomorrow,
[7] Fujita TT, Pearson AD. Results of FPP classification of 1971 and 1972 tornadoes. November 4, 2012–November 8. Columbus, OH, United states: American
In: 8th Conference on severe local storms (abstracts only), USA; 1973. p. 609. Society of Civil Engineers (ASCE); 2013. p. 193–204.
[8] Wan C, Chang C. Measurement of the velocity field in a simulated tornado-like [28] Hamada A, El Damatty AA. Analysis and behaviour of guyed transmission lines
vortex using a three dimensional velocity probe. J Atmos Sci 1972;29:116–27. under tornado wind loads – case studies. In: Annual conference of the
[9] Davies-Jones RP. The dependence of core radius on swirl ratio in a tornado Canadian Society for Civil Engineering 2013: general conference, CSCE 2013,
simulator. J Atmos Sci 1973;30:1427–30. May 29, 2013–June 1. Montreal, QC, Canada: Canadian Society for Civil
[10] Church CJ, Snow JT, Agee EM. Tornado vortex simulation at Purdue University. Engineering; 2012.
Bull Am Meteor Soc 1977;58:900–8. [29] Hamada A, El Damatty AA. Nonlinear formulation of four-noded cable element
[11] Baker GL, Church CR. Measurements of core radii and peak velocities in and application to transmission lines under tornadoes. In: 2014 International
modeled atmospheric vortices. J Atmos Sci 1979;36:2413–24. conference on advances in wind and structures (AWAS14) – ACEM14. Busan,
[12] Church CR, Snow JT, Baker GL, Agee EM. Characteristics of tornado-like vortices Korea; 2014.
as a function of swirl ratio: a laboratory investigation. J Atmos Sci [30] Hamada A, El Damatty AA. Failure analysis of guyed transmission lines during
1979;36:1755–76. F2 tornado event. Eng Struct 2015;85:11–25.
[13] Rotunno R. A study in tornado-like vortex dynamics. J Atmos Sci [31] Shehata AY, El Damatty AA, Savory E. Finite element modeling of transmission
1979;36:140–55. line under downburst wind loading. Finite Elements Anal Des 2005;42
[14] Lund DE, Snow J. The tornado: its structure, dynamics, prediction and hazards. (1):71–89.
Geophys Monogr Ser 1993;79:297–306. [32] Altalmas A. Behaviour of self-supported transmission lines under tornado
[15] Wang H, James D, Letchford CW, Peterson R, Snow J. Development of a loading. M.E.Sc. thesis. London, Ont: School of Graduate and Postdoctoral
prototype tornado simulator for the assessment of fluid–structure interaction. Studies, University of Western Ontario; 2011.
In: First American conference on wind engineering, Clemson, SC. [33] Holmes JD. Recent developments in the specification of wind loads on
[16] Sarkar P, Haan F, Gallus W, Jr., Le K, Wurman J. Velocity measurements in a transmission lines. J Wind Eng 2008;5(1):8–18.
laboratory tornado simulator and their comparison with numerical and full- [34] Holmes JD, Hangan H, Schroeder JL, Letchford CW, Orwig KD. A forensic study
scale data. In: 37th Joint meeting panel on wind and seismic effects. Tsukuba, of the Lubbock-Reese downdraft of 2002. Wind Struct 2008;11(2):137–52.
Japan; May 2005. [35] Shehata AY, El Damatty AA. Failure analysis of a transmission tower during a
[17] Hangan H, Kim J. Swirl ratio effects on tornado vortices in relation to the Fujita microburst. Wind Struct 2008;11(3):193–208.
scale. Wind Struct 2008;11(4):291–302.

You might also like