The document lists 12 design failures related to a construction project. It includes issues like strainers fouling with foundations for filter feed pumps and fire water pumps, missing flow meters and hydrant points, improper elevations and access ways for fuel piping and pumps, missing dyke protection and staircase design for tanks, incorrect nozzle sizing for foam pourers, and missing spray systems, foundations, and suction line alignments for fire pumps. The failures span areas like water treatment, fire pumps, fuel systems, and administration buildings across different contractors.
The document lists 12 design failures related to a construction project. It includes issues like strainers fouling with foundations for filter feed pumps and fire water pumps, missing flow meters and hydrant points, improper elevations and access ways for fuel piping and pumps, missing dyke protection and staircase design for tanks, incorrect nozzle sizing for foam pourers, and missing spray systems, foundations, and suction line alignments for fire pumps. The failures span areas like water treatment, fire pumps, fuel systems, and administration buildings across different contractors.
The document lists 12 design failures related to a construction project. It includes issues like strainers fouling with foundations for filter feed pumps and fire water pumps, missing flow meters and hydrant points, improper elevations and access ways for fuel piping and pumps, missing dyke protection and staircase design for tanks, incorrect nozzle sizing for foam pourers, and missing spray systems, foundations, and suction line alignments for fire pumps. The failures span areas like water treatment, fire pumps, fuel systems, and administration buildings across different contractors.
1 Filter feed pumps Y type strainers fouling with Foundation
2 Fire water pumps Y type strainers fouling with foundation
3 Flow meter not provided in recirculation line to check pump capacity
No proper location provided in drawing for hydrant points provided in
4 adminstration building Fuel piping elevations & pumps access ways for easy movement & 5 maintenance
6 trestile 1A provided Platform on the top in drawing and no access and no
proper reason provided for the platform.
7 LSHS & HSD Tank farm Dyke protection not provided in any drawings
8 LSHS tank staircase design
HSD Tank Foam pourer nozzle must be 100 NB instead it is provided 65 NB in
9 tank. Spray system is not provided for both the tanks and not provided in any 10 drawings Diesel & electric Fire water pumps foundations doesnt have pockets for 11 pump foundation bolts to be placed Diesel & Electric Fire water pumps suction center line is not matching with 12 Suction header center line. ailures points