Press - Pro
Press - 1 - Inp Signal Input Parameter
Select 5
Press - Pts Scaling Points 2 to 16 Generally select 2
In the event of non linear
response selection may
Press - StYLE Calibration Style be suitably increased
2
Secondary Parameters
Action Flow Display Description Options/Range Remarks
Press - Pro
Signal Input
Press - 1 - Inp Not Used
Parameters
User Input/Function
Press - 2 - Fnc Not Used
Key Parameters
Display/ Program
Press - 3 - Loc Not Used
Lock-out Parameters
Secondary
Press - 4 - Sec Not Used
Function Parameters
Max. Capture
Press - Hi - t Not Used
Delay Time
Min. Capture
Press - Lo - t Not Used
Delay Time
Press - Dsp - t
Display Update 1,2,5, 10, 20
Rate
Select 1
3
Auto - Zero Tracking
Press - At - t Not Used
Delay Time
Press - At - b
Auto - Zero 1 to 4095
Tracking Band
Select 2
Units Label On/ Off
Press - b - Lit
Back Light Off
Press - OFFSt
Display Offset -19999 to 19999
Value
Enter 0.00
Exit From Secondary
Press - End Parameters
4
Analog Output Parameters
Action Flow Display Description Options/Range Remarks
Press - Pro
Signal Input Not Used
Press - 1 - Inp
Parameters
Not Used
Press - no
Factory Setting Not Used
Press - 9 - FCS
Parameters
Analog Output
Press - 8 - Out
Parameters
Press - type Analog Type 0-20/0-10/4-20
Select 0-10
AS In Inp/HI/LO/tot
Press - Analog Assignment Select Inp
Press - An - LO
Analog Low -19999 to 99999
Scale Value
Aggregate = -30
Cement = -10
Water = -5
Additive = -0.5
5
Press - An - Hi
Analog High -19999 to 99999
Scale Value
Enter Value equal
To Maximum
Weigher
Capacity
udt
Analog Update 0.0 to 10.0 Sec.
Press -
Time Select 0.0
Press - End Exit From Analog
Output Parameters
6
Calibration
Pre Calibration Check
Mechanical Observations:
• Check for the hopper to be free suspending without touching any other part.
Press - Pro
Press - 1 - Inp Signal Input Parameter
Not Use
Press - rANGE / 0.02u
Not Use
Press - dECPt/0
Not Use
Press - round/1
Not Use
Press - FiLtr/1
8
Not Use 0.0 to 25
Press - band 10
Pts
Not Use 2 to 16
Press - 2
Press - Style/Key
Zero Calibration:
Input Value For
Inp 1
•Displays the current mV reading
Press -
Scaling Point 1 From load cells.
•Ensure hopper to be empty, free from
obstructions and stable reading.
Press - 2.1234
Display Value For
Press - dSP 1
Scaling Point 1
9
Span Calibration:
10
PC Calibration:
• Run i-batch software
• Ensure PLC is in ‘Connected’ Status
• Go to ‘Calibration Screen’ in Technical Folder, as Shown below
3 40 40 40.00 0 0.0 40 40
.. .. .. .. .. .. .. .. .. ..
.. .. .. .. .. .. .. .. .. ..
.. .. .. .. .. .. .. .. .. ..