BATTERY CALCULATION

BCA LANTAI 7

1. Total Module Capacity 250 KVA SOCOMEC : Modulys GP 2.0

2. Power Factor 1

3. Aging Factor 1.2

4. Efficiency UPS 96.5%

5. Number of Battery 38

6. Number of Bank 6

7. Number of cell per block 6

8. Type of Battery Valve Regulated Lead Acid Battery C&D 12-400MR

9. Backup time 30 minutes at Full Load

10. Load 250 KW

11. Consumtion load "watt/cell" 189.4 Load ( Watt )


No Batt x No Bank x Efficiency
12. Up 20% Factor Consumtion load 227.3
"Watt/Cell"

13. Watt/cell for battery from table 241 End Voltage 1.70V

14. Calculation If Watt/cell for battery from table Consumption


241 > 227.3

15. Conclusion Backup enough for 30 min at Full load per UPS with End Voltage 1.70V

Jakarta , 10 Oktober 2019