Suzlon Pune Case Study Green Building

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

1.

Introduction -Suzlon

Campus for world’s largest integrated wind turbine manufacturers.


a. Office Complex
b. Corporate learning center
Plot area – 45,392 sqm
Built up area- 70,865 sqm
Capacity – 3000 employees

2.Building Performance Targets

• Envelope Performance
– Minimal Heat Gain (40% better than ASHRAE 90.1 2007 and ECBC
envelope standards)
– 100% shaded Glazing during summer (April-October)
– Natural Ventilation Potential in transition spaces
– Daylighting (>90% Daylit spaces)

3.Optimum Orientation and Massing

Fig. 1 - Annual Radiation Chart –


Source Climate Responsive Architecture 2004
Fig. 2 - Solar Radiation Chart for
Gurgaon, summers –
Source Climate Responsive Architecture
2004
4. Controlled Solar Access Shading with Mass articulation

21 Sep 2:00 pm

21 Dec 2:00 pm
21 June 2:00 pm

21 March 2:00 pm
5.Shading Strategies

Fig. 3a – Large glazed areas on North face to allow


diffused light for office spaces.
Source : World Architecture News.com

Vertical
Fins
Fig. 3b – Window with vertical shades to cut off
early morning and late evening sun, from North
side.
6.Energy end use

¾ Optimize building design to reduce the conventional energy demand

¾ Optimize the energy performance of the building within specified comfort limits

7.Envelope

¾ HIGH PERFORMANCE GLAZING-


¾ The exposed glass is 4mm Clear Annealed + 0.76mm PVB + 6mm KT 455 +
12mm Air gap + 6mm Clear Heat-Strengthened.
¾ U value- 0.32 Btu/hr.ft2.ºF; Solar Factor- 0.26 which is less than 0.3 prescribed
by ECBC for moderate climate zones. Thus, no additional shading is necessary
for these.
8.Day lighting
More than 75% of Regularly occupied spaces are day lit with a DF of >2.5%
9.Energy Efficient HVAC System

¾ SYSTEM FLEXIBILTY OF VARIABLE REFRIGERANT VOLUME


SYSTEM- The indoor unit's cooling operation can be controlled to maintain
desired temperature in any location in the premises according to end user's needs
and preferences.
¾ PRE-COOLING AND HEAT RECOVERY AT T.F.A.s-
¾ A sensible heat exchanger is used as pre-cooler to sink the temperature of
incoming air (say 38.4°C DBT approx.) to approx.27.66°C.
¾ DIRECT-INDIRECT EVAPORATIVE COOLING
¾ 1) Sensible cooling of approx 130% of fresh air in an efficient heat exchanger,
using pre-cooled water.
¾ 2) Further cooling of air, and simultaneous cooling of water in indirect
evaporative cooling section of the unit. Air required for cooling tower part this
section is drawn from the outlet of the same section. (This is the excess 30%
quantity which has been cooled in the first and the second sections). This air is
termed commonly as "scavenge air“.
¾ 3) Direct evaporative cooling of 100% air in the final section.

10.Energy performance

Projected
Energy
savings –
47.2% over
Benchmarked
Energy
Consumption
Recommende
d by GRIHA.
The building has been evaluated using Visual DOE, a front-end to the DOE- 2.1E engine
as the simulation tool.
11.Net impact

Performance Metric Impact/Savings

Energy use ~ 47 %

GHG impact ~ 50%

Water use ~ 60%

Material use ~ 40% offset by recycled and renewable

Cost (incremental) ~ 10%

Pay back period ~ 2 years