Electrical Layout

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

LP - 1

GENERAL NOTES:
CKT DESCRIPTION OUTLET VOLTS WATTS AMPS PROTEC SIZE OF WIRE CONDUIT
1. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH NO. -TION
THE PROVISION OF THE LATEST PHILIPPINE ELECTRICAL CODE, THE RULES PB

FCU -1 2-3.5mm2 + 1-2.0mm2


AND REGULATION OF THE LOCALITY AND WITH REQUIREMENTS OF THE 1
1.5 HP
1 230 1120 4.90 20
THHN 1/4" diam IMC
4
UTILITY POWER COMPANY. LP-1

2. ALL ELECTRICAL WORKS HEREIN SHALL BE EXECUTED BY EXPERIENCE MEN FCU -2 2-3.5mm2 + 1-2.0mm2
2 1 230 1120 4.90 20
1.5 HP THHN 1/4" diam IMC
UNDER DIRECT SUPERVISION OF A FULL TIME LICENSE ELECTRICAL ENGINEER,
WORKS SHALL BE NEATLY PLACED, SECURELY FASTENED AND PROPERLY 3
CONVENIENCE
7 230 1260 5.49 10
2-3.5mm2 + 1-2.0mm2
OUTLET THHN 1/4" diam IMC
FINISHED.

FCU -2

1.5 HP
3. ALL CONDUITS EXCEPT FOR FEEDER LINE SHALL BE NELTEX ELECTRICAL PIPE CONVENIENCE 2-3.5mm2 + 1-2.0mm2
2
LP-1

4 4 230 720 3.13 10


FEEDER LINE SHALL BE AN INTERMEDIATE METALLIC CONDUIT. OUTLET THHN 1/4" diam IMC

4. ALL CONDUIT SHALL BE PROTECTED AGAINST DAMAGES BY ENTRANCE OF


LIGHTING 2-3.5mm2 + 1-2.0mm2
WATER AND FOREIGN MATTERS DURING CONSTRUCTION. ALL ENDS OF 5
OUTLET
8 230 800 3.48 10
THHN 1/4" diam IMC
CONDUIT SHALL BE PLUGGED TO EXCLUDE MOISTURE AND DUST IMMEDIATELY
AFTER THE CONDUITS ARE PLACED. LIGHTING 2-3.5mm2 + 1-2.0mm2
6 8 230 800 3.48 10
OUTLET THHN 1/4" diam IMC
5. WALL SWITCHES SHALL BE RATED 15 AMPERES, 300 VOLTS TUMBLER TYPE
AND CONVENIENCE OUTLETS SHALL BE OF GROUNDING TYPE THREE WIRES LIGHTING
10 2-3.5mm2 + 1-2.0mm2
7 OUTLET 11 230 1100 4.78

FCU -1

1.5 HP
230 VOLTS THHN 1/4" diam IMC
1
LP-1
6. SINGLE CONDUCTOR INSULATED THHN/THWAN THERMOPLASTIC SHALL BE LIGHTING
10 2-3.5mm2 + 1-2.0mm2
USED IN CONDUIT. THE MINIMUM SIZE OF WIRES SHALL BE 2.0 SQ. MM 8 OUTLET 5 230 500 2.17
THHN 1/4" diam IMC TEL

COCM
( AWG NO. 12 ) SEE LOAD SCHEDULE. 3
LP-1

7. MOUNTING HEIGHTS SHALL BE APPROVED BY THE ARCHITECT AND OR AS CONVENIENCE 10 2-3.5mm2 + 1-2.0mm2
9 OUTLET 5 230 900 3.91
THHN 1/4" diam IMC
FOLLOWS:
10 2-3.5mm2 + 1-2.0mm2
PANEL BOARDS..........................................1.40 M ABOVE FINISHED FLOOR LINE 10 SPARE 1 230

WALL SWITCHES........................................1.40 M ABOVE FINISHED FLOOR LINE


THHN 1/4" diam IMC
POWER LAYOUT
CONVENIENCE OUTLET............................0.30 M ABOVE FINISHED FLOOR LINE TOTAL 8,320 W 36.24 A SCALE 1:100 MTS.
SPECIAL PURPOSE OUTLET.....................0.15 M ABOVE FINISHED COUNTER TOP
COMPUTATION
SERVICE PROVIDER I = 36.24 @ 80% USE 70A, PB, 230V 60HZ,
3 WIRES + GROUND = 30 + (25% OF HIGHEST APPLIANCES LOAD) 2-5.5mm sq. diam. + 1-3.5mm sq. diam.
230 VOLTS, 3Ø, 60Hz = 31.37 AMPS THHN STANDARD COPPER IN 1/2" diam. IMC

SCHEDULE OF LOADS & COMPUTATIONS


LP1 SCALE NTS. 7
LP-1

70 AT 3P COCM COCM

20 AT 2P 20 AT 2P

1 10 AT 2P 10 AT 2P
2
LEGENDS
3 10 AT 2P 10 AT 2P
4 GFCI
TEL 8
LP-1

COCM
5 10 AT 2P 10 AT 2P
6 COCM
6
LP-1
S1

7 10 AT 2P SPARE
8 S2
C 5
LP-1

9 10 REF.
S3

DVR

1-14mm² Ø GROUNDING

COCM

COCM
CONDUCTOR 8

LIGHTING LAYOUT
LP-1

SCALE 1:100 MTS.

SINGLE LINE DIAGRAM CCTV LAYOUT


SCALE 1:100 MTS.
SCALE NTS.

PROFESSIONAL ELECTRICAL ENGINEER CIVIL ENGINEER: PROJECT TITLE: SHEET CONTENT:

YOUR HIGHNESS NAIL & BEAUTY LOUNGE


AS SHOWN
E
PRC NO:
PTR NO.:
VALIDITY:
DATE ISSUED:
PRC NO:
PTR NO.:
VALIDITY:
DATE ISSUED: LOCATION: UNIT 308A, 3RD FLOOR, AYALA FAIRVIEW TERRACES, QUIRINO HIGHWAY COR. 1
MALIGAYA DRIVE, NOVALICHES, QUEZON CITY, 1118 METRO MANILA
PLACE ISSUED: TIN NO.: PLACE ISSUED: TIN NO.:

You might also like