fc' := 4000⋅ psi Ec := 57000 ⋅ fc' ⋅ psi Ec = 3.605 × 10 ⋅ psi fy := 60000 ⋅ psi
twall := 12 ⋅ in lwall := 27.5 ⋅ ft h := 10 ⋅ ft ( height of entire wall or segment of wall considered )
ϕ := 0.6 ( 9.3.4 ) γconc := 145 ⋅ pcf cover := 2 ⋅ in Acv := twall⋅ ( lwall − cover)
Vu := 326 ⋅ kips
(
result := if Vu > 2 ⋅ Acv ⋅ fc' ⋅ psi , "Use 2 curtains of reinf." , "Use 1 curtain of reinf." ) ( 21.7.2.2 )
2
As_horiz := 0.2 ⋅ in spacing := 12 ⋅ in < 18" O.K. ( 21.7.2.1 )
n ⋅ As_horiz −3
ρt := max 0.0025 , ρt = 2.778 × 10
twall⋅ spacing
( Horiz. reinforcement ratio )
h h h
α := if ≤ 1.5 , 3 , if > 2 , 2 , 6 − 2⋅ ( 21.7.4.1 )
lwall lwall lwall
ϕVn1 := if
h
> 2 , ϕ⋅ 2⋅( ) (
fc' ⋅ psi + ρt ⋅ fy , ϕ ⋅ α ⋅ )
fc' ⋅ psi + ρt ⋅ fy ϕVn1 = 213.842⋅ psi
lwall
Vu
= 82.825 ⋅ psi < ϕVn = 213.842 ⋅ psi O.K.
Acv
2000
1500
1000
500
0
-2000 0 2000 4000 6000 8000 10000 12000
-500
MASONRY WALL PLAN
-1000
CHECK FLEXURAL & AXIAL CAPACITY BY STRENGTH DESIGN (SD)
COMBINATION (1.2+0.2SDS)D+L+ρE
Ultimate compression force Pu = 102.88 kips < φPn = 16208.6 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 8596.58 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.00495 = 2.39 times steel strain at yield
COMBINATION (0.9-0.2SDS)D+ρE
Ultimate compression force Pu = 33.9205 kips < φPn = 16208.6 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 6628.33 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.0086 = 4.16 times steel strain at yield
CHECK MAXIMUM REINFORCEMENTS
COMBINATION D+0.75L+0.525E
Ultimate compression force Pu = 72.9 kips
Strain in extreme tensile reinf. εs= 0.00602 = 2.91 times steel strain at yield [Satisfactory] (TMS 3.3.3.5)
CHECK SHEAR CAPACITY BY STRENGTH DESIGN (SD)
= 4627.6 kips = 3085.1 kips = 1676.09 kips = 3361.37 kips
COMBINATION (1.2+0.2SDS)D+L+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2988.57 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.492 kips < φVn = 2689.1 kips [Satisfactory]
COMBINATION (0.9-0.2SDS)D+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2971.33 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.49 kips < φVn = 2689.1 kips [Satisfactory]
DESIGN SHEAR STRENGTH SHALL EXCEED THE SHEAR CORRESPONDING TO 1.25 TIME NOMINAL FLEXURAL STRENGTH
COMB (1.2+0.2SDS)D+L+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
COMB (0.9-0.2SDS)D+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
3000
2500
2000
1500
1000
500
0
0 5000 10000 15000 20000 25000
-500
-1000
MASONRY WALL PLAN
-1500
CHECK FLEXURAL & AXIAL CAPACITY BY STRENGTH DESIGN (SD)
COMBINATION (1.2+0.2SDS)D+L+ρE
Ultimate compression force Pu = 102.88 kips < φPn = 16204.1 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 17376.2 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.00699 = 3.38 times steel strain at yield
COMBINATION (0.9-0.2SDS)D+ρE
Ultimate compression force Pu = 33.9205 kips < φPn = 16204.1 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 14250.7 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.00995 = 4.81 times steel strain at yield
CHECK MAXIMUM REINFORCEMENTS
COMBINATION D+0.75L+0.525E
Ultimate compression force Pu = 72.9 kips
Strain in extreme tensile reinf. εs= 0.00797 = 3.85 times steel strain at yield [Satisfactory] (TMS 3.3.3.5)
CHECK SHEAR CAPACITY BY STRENGTH DESIGN (SD)
= 4627.6 kips = 3085.1 kips = 1676.09 kips = 3361.37 kips
COMBINATION (1.2+0.2SDS)D+L+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2988.57 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.492 kips < φVn = 2689.1 kips [Satisfactory]
COMBINATION (0.9-0.2SDS)D+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2971.33 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.49 kips < φVn = 2689.1 kips [Satisfactory]
DESIGN SHEAR STRENGTH SHALL EXCEED THE SHEAR CORRESPONDING TO 1.25 TIME NOMINAL FLEXURAL STRENGTH
COMB (1.2+0.2SDS)D+L+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
COMB (0.9-0.2SDS)D+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
1500
1000
500
0
0 2000 4000 6000 8000
-500
MASONRY WALL PLAN
-1000
CHECK FLEXURAL & AXIAL CAPACITY BY STRENGTH DESIGN (SD)
COMBINATION (1.2+0.2SDS)D+L+ρE
Ultimate compression force Pu = 102.88 kips < φPn = 16210.1 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 5278.92 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.00665 = 3.21 times steel strain at yield
COMBINATION (0.9-0.2SDS)D+ρE
Ultimate compression force Pu = 33.9205 kips < φPn = 16210.1 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 4281.74 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.00978 = 4.73 times steel strain at yield
CHECK MAXIMUM REINFORCEMENTS
COMBINATION D+0.75L+0.525E
Ultimate compression force Pu = 72.9 kips
Strain in extreme tensile reinf. εs= 0.00771 = 3.73 times steel strain at yield [Satisfactory] (TMS 3.3.3.5)
CHECK SHEAR CAPACITY BY STRENGTH DESIGN (SD)
= 4627.6 kips = 3085.1 kips = 1676.09 kips = 3361.37 kips
COMBINATION (1.2+0.2SDS)D+L+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2988.57 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.492 kips < φVn = 2689.1 kips [Satisfactory]
COMBINATION (0.9-0.2SDS)D+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2971.33 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.49 kips < φVn = 2689.1 kips [Satisfactory]
DESIGN SHEAR STRENGTH SHALL EXCEED THE SHEAR CORRESPONDING TO 1.25 TIME NOMINAL FLEXURAL STRENGTH
COMB (1.2+0.2SDS)D+L+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
COMB (0.9-0.2SDS)D+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
500
400
300
200
100
0
0 100 200 300 400 500 600
-100
MASONRY WALL PLAN
-200
CHECK FLEXURAL & AXIAL CAPACITY BY STRENGTH DESIGN (SD)
COMBINATION (1.2+0.2SDS)D+L+ρE
Ultimate compression force Pu = 102.88 kips < φPn = 16215.1 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 433.122 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.00702 = 3.39 times steel strain at yield
COMBINATION (0.9-0.2SDS)D+ρE
Ultimate compression force Pu = 33.9205 kips < φPn = 16215.1 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 355.976 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.01086 = 5.25 times steel strain at yield
CHECK MAXIMUM REINFORCEMENTS
COMBINATION D+0.75L+0.525E
Ultimate compression force Pu = 72.9 kips
Strain in extreme tensile reinf. εs= 0.00803 = 3.88 times steel strain at yield [Satisfactory] (TMS 3.3.3.5)
CHECK SHEAR CAPACITY BY STRENGTH DESIGN (SD)
= 4627.6 kips = 3085.1 kips = 1676.09 kips = 3361.37 kips
COMBINATION (1.2+0.2SDS)D+L+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2988.57 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.492 kips < φVn = 2689.1 kips [Satisfactory]
COMBINATION (0.9-0.2SDS)D+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2971.33 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.49 kips < φVn = 2689.1 kips [Satisfactory]
DESIGN SHEAR STRENGTH SHALL EXCEED THE SHEAR CORRESPONDING TO 1.25 TIME NOMINAL FLEXURAL STRENGTH
COMB (1.2+0.2SDS)D+L+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
COMB (0.9-0.2SDS)D+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
1500
1000
500
0
0 2000 4000 6000 8000
-500
MASONRY WALL PLAN
-1000
CHECK FLEXURAL & AXIAL CAPACITY BY STRENGTH DESIGN (SD)
COMBINATION (1.2+0.2SDS)D+L+ρE
Ultimate compression force Pu = 102.88 kips < φPn = 16210.1 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 5489.71 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.00684 = 3.30 times steel strain at yield
COMBINATION (0.9-0.2SDS)D+ρE
Ultimate compression force Pu = 33.9205 kips < φPn = 16210.1 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 4466.67 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.00994 = 4.80 times steel strain at yield
CHECK MAXIMUM REINFORCEMENTS
COMBINATION D+0.75L+0.525E
Ultimate compression force Pu = 72.9 kips
Strain in extreme tensile reinf. εs= 0.00807 = 3.90 times steel strain at yield [Satisfactory] (TMS 3.3.3.5)
CHECK SHEAR CAPACITY BY STRENGTH DESIGN (SD)
= 4627.6 kips = 3085.1 kips = 1676.09 kips = 3361.37 kips
COMBINATION (1.2+0.2SDS)D+L+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2988.57 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.492 kips < φVn = 2689.1 kips [Satisfactory]
COMBINATION (0.9-0.2SDS)D+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2971.33 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.49 kips < φVn = 2689.1 kips [Satisfactory]
DESIGN SHEAR STRENGTH SHALL EXCEED THE SHEAR CORRESPONDING TO 1.25 TIME NOMINAL FLEXURAL STRENGTH
COMB (1.2+0.2SDS)D+L+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
COMB (0.9-0.2SDS)D+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
3000
2500
2000
1500
1000
500
0
0 5000 10000 15000 20000 25000
-500
-1000
MASONRY WALL PLAN
-1500
CHECK FLEXURAL & AXIAL CAPACITY BY STRENGTH DESIGN (SD)
COMBINATION (1.2+0.2SDS)D+L+ρE
Ultimate compression force Pu = 102.88 kips < φPn = 16204.1 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 18021.1 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.00654 = 3.16 times steel strain at yield
COMBINATION (0.9-0.2SDS)D+ρE
Ultimate compression force Pu = 33.9205 kips < φPn = 16204.1 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 14521.3 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.00971 = 4.69 times steel strain at yield
CHECK MAXIMUM REINFORCEMENTS
COMBINATION D+0.75L+0.525E
Ultimate compression force Pu = 72.9 kips
Strain in extreme tensile reinf. εs= 0.00756 = 3.65 times steel strain at yield [Satisfactory] (TMS 3.3.3.5)
CHECK SHEAR CAPACITY BY STRENGTH DESIGN (SD)
= 4627.6 kips = 3085.1 kips = 1676.09 kips = 3361.37 kips
COMBINATION (1.2+0.2SDS)D+L+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2988.57 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.492 kips < φVn = 2689.1 kips [Satisfactory]
COMBINATION (0.9-0.2SDS)D+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2971.33 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.49 kips < φVn = 2689.1 kips [Satisfactory]
DESIGN SHEAR STRENGTH SHALL EXCEED THE SHEAR CORRESPONDING TO 1.25 TIME NOMINAL FLEXURAL STRENGTH
COMB (1.2+0.2SDS)D+L+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
COMB (0.9-0.2SDS)D+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
1000
800
600
400
200
0
0 500 1000 1500 2000 2500 3000
-200
MASONRY WALL PLAN
-400
CHECK FLEXURAL & AXIAL CAPACITY BY STRENGTH DESIGN (SD)
COMBINATION (1.2+0.2SDS)D+L+ρE
Ultimate compression force Pu = 102.88 kips < φPn = 16212.6 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 1995.31 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.00725 = 3.51 times steel strain at yield
COMBINATION (0.9-0.2SDS)D+ρE
Ultimate compression force Pu = 33.9205 kips < φPn = 16212.6 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 1678.01 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.01001 = 4.84 times steel strain at yield
CHECK MAXIMUM REINFORCEMENTS
COMBINATION D+0.75L+0.525E
Ultimate compression force Pu = 72.9 kips
Strain in extreme tensile reinf. εs= 0.00815 = 3.94 times steel strain at yield [Satisfactory] (TMS 3.3.3.5)
CHECK SHEAR CAPACITY BY STRENGTH DESIGN (SD)
= 4627.6 kips = 3085.1 kips = 1676.09 kips = 3361.37 kips
COMBINATION (1.2+0.2SDS)D+L+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2988.57 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.492 kips < φVn = 2689.1 kips [Satisfactory]
COMBINATION (0.9-0.2SDS)D+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2971.33 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.49 kips < φVn = 2689.1 kips [Satisfactory]
DESIGN SHEAR STRENGTH SHALL EXCEED THE SHEAR CORRESPONDING TO 1.25 TIME NOMINAL FLEXURAL STRENGTH
COMB (1.2+0.2SDS)D+L+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
COMB (0.9-0.2SDS)D+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
700
600
500
400
300
200
100
0
0 200 400 600 800 1000 1200 1400
-100
MASONRY WALL PLAN
-200
CHECK FLEXURAL & AXIAL CAPACITY BY STRENGTH DESIGN (SD)
COMBINATION (1.2+0.2SDS)D+L+ρE
Ultimate compression force Pu = 102.88 kips < φPn = 16215.2 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 857.228 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.00809 = 3.91 times steel strain at yield
COMBINATION (0.9-0.2SDS)D+ρE
Ultimate compression force Pu = 33.9205 kips < φPn = 16215.2 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 623.227 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.01373 = 6.64 times steel strain at yield
CHECK MAXIMUM REINFORCEMENTS
COMBINATION D+0.75L+0.525E
Ultimate compression force Pu = 72.9 kips
Strain in extreme tensile reinf. εs= 0.00985 = 4.76 times steel strain at yield [Satisfactory] (TMS 3.3.3.5)
CHECK SHEAR CAPACITY BY STRENGTH DESIGN (SD)
= 4627.6 kips = 3085.1 kips = 1072.70 kips = 2151.28 kips
COMBINATION (1.2+0.2SDS)D+L+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2988.57 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.492 kips < φVn = 1721.02 kips [Satisfactory]
COMBINATION (0.9-0.2SDS)D+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2971.33 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.49 kips < φVn = 1721.02 kips [Satisfactory]
DESIGN SHEAR STRENGTH SHALL EXCEED THE SHEAR CORRESPONDING TO 1.25 TIME NOMINAL FLEXURAL STRENGTH
COMB (1.2+0.2SDS)D+L+ρE φVn = 1721.02 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
COMB (0.9-0.2SDS)D+ρE φVn = 1721.02 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
2500
2000
1500
1000
500
0
0 5000 10000 15000 20000
-500
MASONRY WALL PLAN
-1000
CHECK FLEXURAL & AXIAL CAPACITY BY STRENGTH DESIGN (SD)
COMBINATION (1.2+0.2SDS)D+L+ρE
Ultimate compression force Pu = 102.88 kips < φPn = 10745.1 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 12179.5 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.0061 = 2.95 times steel strain at yield
COMBINATION (0.9-0.2SDS)D+ρE
Ultimate compression force Pu = 33.9205 kips < φPn = 10745.1 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 9663.33 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.00946 = 4.57 times steel strain at yield
CHECK MAXIMUM REINFORCEMENTS
COMBINATION D+0.75L+0.525E
Ultimate compression force Pu = 72.9 kips
Strain in extreme tensile reinf. εs= 0.00715 = 3.46 times steel strain at yield [Satisfactory] (TMS 3.3.3.5)
CHECK SHEAR CAPACITY BY STRENGTH DESIGN (SD)
= 3269.1 kips = 2179.4 kips = 1676.09 kips = 3361.37 kips
COMBINATION (1.2+0.2SDS)D+L+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 3269.06 kips (TMS 3.3.4.1.2)
Vnm = 2118.74 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.492 kips < φVn = 2615.25 kips [Satisfactory]
COMBINATION (0.9-0.2SDS)D+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 3269.06 kips (TMS 3.3.4.1.2)
Vnm = 2101.50 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.49 kips < φVn = 2615.25 kips [Satisfactory]
DESIGN SHEAR STRENGTH SHALL EXCEED THE SHEAR CORRESPONDING TO 1.25 TIME NOMINAL FLEXURAL STRENGTH
COMB (1.2+0.2SDS)D+L+ρE φVn = 2615.25 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
COMB (0.9-0.2SDS)D+ρE φVn = 2615.25 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
2500
2000
1500
1000
500
0
0 5000 10000 15000 20000
-500
MASONRY WALL PLAN
-1000
CHECK FLEXURAL & AXIAL CAPACITY BY STRENGTH DESIGN (SD)
COMBINATION (1.2+0.2SDS)D+L+ρE
Ultimate compression force Pu = 102.88 kips < φPn = 16207.1 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 10105.5 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.00788 = 3.81 times steel strain at yield
COMBINATION (0.9-0.2SDS)D+ρE
Ultimate compression force Pu = 33.9205 kips < φPn = 16207.1 kips [Satisfactory]
Ultimate in-plane bending moment M3u= 71.4152 ft-k < φΜn = 8479.09 ft-kips [Satisfactory]
Strain in extreme tensile reinf. εs= 0.0106 = 5.13 times steel strain at yield
CHECK MAXIMUM REINFORCEMENTS
COMBINATION D+0.75L+0.525E
Ultimate compression force Pu = 72.9 kips
Strain in extreme tensile reinf. εs= 0.0088 = 4.25 times steel strain at yield [Satisfactory] (TMS 3.3.3.5)
CHECK SHEAR CAPACITY BY STRENGTH DESIGN (SD)
= 4627.6 kips = 3085.1 kips = 1676.09 kips = 3361.37 kips
COMBINATION (1.2+0.2SDS)D+L+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2988.57 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.492 kips < φVn = 2689.1 kips [Satisfactory]
COMBINATION (0.9-0.2SDS)D+ρE
Mu = 71.42 ft-kips Vu = 6.49 kips Mu/(Vudv)= 0.091
Vnmax = 4627.63 kips (TMS 3.3.4.1.2)
Vnm = 2971.33 kips (TMS 3.3.4.1.2.1)
Ultimate shear force Vu = 6.49 kips < φVn = 2689.1 kips [Satisfactory]
DESIGN SHEAR STRENGTH SHALL EXCEED THE SHEAR CORRESPONDING TO 1.25 TIME NOMINAL FLEXURAL STRENGTH
COMB (1.2+0.2SDS)D+L+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
COMB (0.9-0.2SDS)D+ρE φVn = 2689.10 kips > Vflexure = 16.23 kips [Satisfactory] (TMS 1.17.3.2.6.1.1)
3
twall⋅ lwall Pu Mu lwall
Ag := lwall ⋅ twall Ig := + ⋅ = 298.035⋅ psi 0.2 ⋅ fc' = 800 ⋅ psi
12 Ag Ig 2
Pu Mu lwall
Check1 := if + ⋅ < 0.2 ⋅ fc' , "B.Z.s are not required" , "B.Z.s are required"
Ag Ig 2
Code References .
Calculations per ACI 318-11, IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : ASCE 7-10
General Information
f'c : Concrete 28 day strength = 4.0 ksi Overall Column Height = 10.0 ft
E= = 3,605.0 ksi End Fixity Top & Bottom Pinned
Density = 145.0 pcf Brace condition for deflection (buckling) along columns :
β = 0.850 X-X (width) axis :
fy - Main Rebar = 60.0 ksi Unbraced Length for X-X Axis buckling = 10.0 ft, K = 1.0
E - Main Rebar = 29,000.0 ksi Y-Y (depth) axis :
Allow. Reinforcing Limits ASTM A615 Bars Used Unbraced Length for X-X Axis buckling = 10.0 ft, K = 1.0
Min. Reinf. = 0.250 %
Max. Reinf. = 8.0 %
Load Combination : ASCE 7-10
..
Column Cross Section
Y
Column Dimensions :340.0in high x 12.0in Wide, Column Edge to Rebar
Edge Cover = 2.0in #5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
Column Reinforcing : 4 - #5 bars @ corners,, 27 - #5 bars left & right X #5
#5
X
#5
#5
#5
#5
#5
#5
#5
#5
between corner bars #5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
Y
Applied Loads Entered loads are factored per load combinations specified by user.
.
Governing Factored Moment Source Dist. from Axial Load k Bending Analysis k-ft Utilization
Load Combination
X-X Y-Y base ft Pu ϕ * Pn δ x δ x * Mux δ y δy * Muy Alpha (deg) δ Mu ϕ Mn Ratio
+1.40D+1.60H Actual 9.93 57.52 7,742.63 1.000 -22.25 180.000 22.25 2,827.90 0.008
Title Block Line 1 Project Title:
You can change this area Engineer: Project ID:
using the "Settings" menu item Project Descr:
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 8 FEB 2016, 9:06PM
File = X:\KNA\15120-10 Virgil Melose\Calculation\concrete shear wall.ec6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.7.30, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PG1
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
Height = 10.0 ft
M-y Loads
#5
#5 ###.##kft
#5
#5 Height = 10.0 ft
#5
#5
#5
#5
#5
#5
X #5
#X5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5 Looking along X-X Axis
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
Interaction Diagrams .
Title Block Line 1 Project Title:
You can change this area Engineer: Project ID:
using the "Settings" menu item Project Descr:
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 8 FEB 2016, 9:06PM
File = X:\KNA\15120-10 Virgil Melose\Calculation\concrete shear wall.ec6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.7.30, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PG1
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,175.0 8,175.0
7,357.5 7,357.5
6,540.0 6,540.0
5,722.5 5,722.5
4,905.0 4,905.0
Phi * Pn (k)
Phi * Pn (k)
4,087.5 4,087.5
3,270.0 3,270.0
2,452.5 2,452.5
1,635.0 1,635.0
817.5 817.5
0.0 4,630.69,261.213,891.8
18,522.4
23,153.0
27,783.6
32,414.2
37,044.8
41,675.4
46,306.0 0.0 4,630.69,261.213,891.8
18,522.4
23,153.0
27,783.6
32,414.2
37,044.8
41,675.4
46,306.0
Load Comb. = +1.40D+1.60H, Alpha= 180.0deg, (57.52, 22.25) Load Comb. = +1.20D+0.50Lr+1.60L+1.60H, Alpha= 180.0deg, (49.30, 22.25)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,175.0 8,175.0
7,357.5 7,357.5
6,540.0 6,540.0
5,722.5 5,722.5
4,905.0 4,905.0
Phi * Pn (k)
Phi * Pn (k)
4,087.5 4,087.5
3,270.0 3,270.0
2,452.5 2,452.5
1,635.0 1,635.0
817.5 817.5
0.0 4,630.69,261.213,891.8
18,522.4
23,153.0
27,783.6
32,414.2
37,044.8
41,675.4
46,306.0 0.0 4,630.69,261.213,891.8
18,522.4
23,153.0
27,783.6
32,414.2
37,044.8
41,675.4
46,306.0
Load Comb. = +1.20D+1.60Lr+0.50L+1.60H, Alpha= 180.0deg, (49.30, 22.25) Load Comb. = +1.20D+1.60Lr+0.50W+1.60H, Alpha= 180.0deg, (49.30, 22.25)
Title Block Line 1 Project Title:
You can change this area Engineer: Project ID:
using the "Settings" menu item Project Descr:
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 8 FEB 2016, 9:06PM
File = X:\KNA\15120-10 Virgil Melose\Calculation\concrete shear wall.ec6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.7.30, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PG1
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,175.0 8,175.0
7,357.5 7,357.5
6,540.0 6,540.0
5,722.5 5,722.5
4,905.0 4,905.0
Phi * Pn (k)
Phi * Pn (k)
4,087.5 4,087.5
3,270.0 3,270.0
2,452.5 2,452.5
1,635.0 1,635.0
817.5 817.5
0.0 4,630.69,261.213,891.8
18,522.4
23,153.0
27,783.6
32,414.2
37,044.8
41,675.4
46,306.0 0.0 4,630.69,261.213,891.8
18,522.4
23,153.0
27,783.6
32,414.2
37,044.8
41,675.4
46,306.0
Load Comb. = +1.20D+1.60S+0.50W+1.60H, Alpha= 180.0deg, (49.30, 22.25) Load Comb. = +1.20D+0.50Lr+0.50L+W+1.60H, Alpha= 180.0deg, (49.30, 22.25)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,175.0 8,175.0
7,357.5 7,357.5
6,540.0 6,540.0
5,722.5 5,722.5
4,905.0 4,905.0
Phi * Pn (k)
Phi * Pn (k)
4,087.5 4,087.5
3,270.0 3,270.0
2,452.5 2,452.5
1,635.0 1,635.0
817.5 817.5
0.0 4,630.69,261.213,891.8
18,522.4
23,153.0
27,783.6
32,414.2
37,044.8
41,675.4
46,306.0 0.0 4,630.69,261.213,891.8
18,522.4
23,153.0
27,783.6
32,414.2
37,044.8
41,675.4
46,306.0
Load Comb. = +1.549D+0.50L+0.20S+E+1.60H, Alpha= 180.0deg, (63.62, 1,268.83) Load Comb. = +0.90D+W+0.90H, Alpha= 180.0deg, (36.98, 12.52)
Concrete Shear Wall Check ( P72)
6
fc' := 4000⋅ psi Ec := 57000 ⋅ fc' ⋅ psi Ec = 3.605 × 10 ⋅ psi fy := 60000 ⋅ psi
twall := 12 ⋅ in lwall := 16.2 ⋅ ft h := 11 ⋅ ft ( height of entire wall or segment of wall considered )
ϕ := 0.6 ( 9.3.4 ) γconc := 145 ⋅ pcf cover := 2 ⋅ in Acv := twall⋅ ( lwall − cover)
Vu := 295 ⋅ kips
(
result := if Vu > 2 ⋅ Acv ⋅ fc' ⋅ psi , "Use 2 curtains of reinf." , "Use 1 curtain of reinf." ) ( 21.7.2.2 )
2
As_horiz := 0.2 ⋅ in spacing := 12 ⋅ in < 18" O.K. ( 21.7.2.1 )
n ⋅ As_horiz −3
ρt := max 0.0025 , ρt = 2.778 × 10
twall⋅ spacing
( Horiz. reinforcement ratio )
h h h
α := if ≤ 1.5 , 3 , if > 2 , 2 , 6 − 2⋅ ( 21.7.4.1 )
lwall lwall lwall
ϕVn1 := if
h
> 2 , ϕ⋅ 2⋅( ) (
fc' ⋅ psi + ρt ⋅ fy , ϕ ⋅ α ⋅ )
fc' ⋅ psi + ρt ⋅ fy ϕVn1 = 213.842⋅ psi
lwall
Vu
= 127.772⋅ psi < ϕVn = 213.842 ⋅ psi O.K.
Acv
Therefore, use 12" Con'c w/ #4 @12" O.C Horiz. Rebar @ Each Face
Shear Wall Boundary Elements Detail Requirements
3
twall⋅ lwall Pu Mu lwall
Ag := lwall ⋅ twall Ig := + ⋅ = 422.684⋅ psi 0.2 ⋅ fc' = 800 ⋅ psi
12 Ag Ig 2
Pu Mu lwall
Check1 := if + ⋅ < 0.2 ⋅ fc' , "B.Z.s are not required" , "B.Z.s are required"
Ag Ig 2
.
Code References
Calculations per ACI 318-11, IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : ASCE 7-10
General Information
f'c : Concrete 28 day strength = 4.0 ksi Overall Column Height = 11.0 ft
E= = 3,605.0 ksi End Fixity Top & Bottom Pinned
Density = 145.0 pcf Brace condition for deflection (buckling) along columns :
= 0.850 X-X (width) axis :
fy - Main Rebar = 60.0 ksi Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
E - Main Rebar = 29,000.0 ksi Y-Y (depth) axis :
Allow. Reinforcing Limits ASTM A615 Bars Used Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
Min. Reinf. = 0.250 %
Max. Reinf. = 8.0 %
Load Combination : ASCE 7-10
..
Column Cross Section
Column Dimensions :195.0in high x 12.0in Wide, Column Edge to Rebar Y
Applied Loads .
Entered loads are factored per load combinations specified by user.
Column self weight included : 25,918.8 lbs * Dead Load Factor
BENDING LOADS . . .
Moment acting about X-X axis, E = 927.0, H = 60.0 k-ft
DESIGN SUMMARY .
Load Combination +0.5514D+E+0.90H Maximum SERVICE Load Reactions . .
Location of max.above base 10.926 ft Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k
Maximum Stress Ratio = 0.202 : 1 Top along X-X 84.273 k Bottom along X-X 84.273 k
Ratio = (Pu^2+Mu^2)^.5 / (PhiPn^2+PhiMn^2)^.5
Pu = 14.292 k * Pn = 78.178 k
Maximum SERVICE Load Deflections . . .
Mu-x = -981.0 k-ft * Mn-x = 4,969.69 k-ft
Along Y-Y -0.000469 in at 6.423 ft above base
Mu-y = 0.0 k-ft * Mn-y = 0.0 k-ft for load combination : E Only
Mu Angle = 180.0 deg Along X-X 0.0in at 0.0 ft above base
Mu at Angle = 981.0 k-ft Mn at Angle = 4,858.45 k-ft for load combination :
Pn & Mn values located at Pu-Mu vector intersection with capacity curve
General Section Information . . . = 0.650 = 0.850 = 0.80
Column Capacities . . .
: % Reinforcing 0.4504 % Rebar % Ok
Pnmax : Nominal Max. Compressive Axial Capacity 8,552.56 k
Pnmin : Nominal Min. Tension Axial Capacity -632.40 k Reinforcing Area 10.540 in^2
Concrete Area 2,340.0 in^2
Pn, max : Usable Compressive Axial Capacity 4,447.33 k
Pn, min : Usable Tension Axial Capacity -411.060 k
Governing Load Combination Results .
Governing Factored Moment Source Dist. from Axial Load k Bending Analysis k-ft Utilization
Load Combination X-X Y-Y base ft Pu * Pn x x * Mux y y * Muy Alpha (deg) Mu Mn Ratio
+1.40D+1.60H Actual 10.93 36.29 3,748.76 1.000 -96.00 180.000 96.00 9,863.01 0.010
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : P72
#5#5
#5#5
#5#5
#5#5
M-y Loads
#5#5
Height = 11.0 ft
987.00kft
Height = 11.0 ft
#5#5
#5#5
#5#5
X X
#5#5
#5#5
#5#5
#5#5
Looking along X-X Axis
#5#5
#5#5
#5#5
#5#5
#5#5
Interaction Diagrams .
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : P72
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) 4,700.0
Phi * Mn @ Alpha (k-ft)
4,700.0
4,230.0 4,230.0
3,760.0 3,760.0
3,290.0 3,290.0
2,820.0 2,820.0
Phi * Pn (k)
Phi * Pn (k)
2,350.0 2,350.0
1,880.0 1,880.0
1,410.0 1,410.0
940.0 940.0
470.0 470.0
0.0 1,526.13,052.14,578.26,104.37,630.39,156.410,682.5
12,208.513,734.6
15,260.7 0.0 1,526.13,052.14,578.26,104.37,630.39,156.410,682.512,208.5
13,734.6
15,260.7
Load Comb. = +1.40D+1.60H, Alpha= 180.0deg, (36.29, 96.00) Load Comb. = +1.20D+0.50Lr+1.60L+1.60H, Alpha= 180.0deg, (31.10, 96.00)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
4,700.0 4,700.0
4,230.0 4,230.0
3,760.0 3,760.0
3,290.0 3,290.0
2,820.0 2,820.0
Phi * Pn (k)
Phi * Pn (k)
2,350.0 2,350.0
1,880.0 1,880.0
1,410.0 1,410.0
940.0 940.0
470.0 470.0
0.0 1,526.13,052.14,578.26,104.37,630.39,156.410,682.512,208.5
13,734.6
15,260.7 0.0 1,526.13,052.14,578.26,104.37,630.39,156.410,682.5
12,208.5
13,734.6
15,260.7
Load Comb. = +1.20D+1.60Lr+0.50L+1.60H, Alpha= 180.0deg, (31.10, 96.00) Load Comb. = +1.20D+1.60Lr+0.50W+1.60H, Alpha= 180.0deg, (31.10, 96.00)
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : P72
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
4,700.0 4,700.0
4,230.0 4,230.0
3,760.0 3,760.0
3,290.0 3,290.0
2,820.0 2,820.0
Phi * Pn (k)
Phi * Pn (k)
2,350.0 2,350.0
1,880.0 1,880.0
1,410.0 1,410.0
940.0 940.0
470.0 470.0
0.0 1,526.13,052.14,578.26,104.37,630.39,156.410,682.512,208.5
13,734.6
15,260.7 0.0 1,526.13,052.14,578.26,104.37,630.39,156.410,682.512,208.5
13,734.6
15,260.7
Load Comb. = +1.20D+1.60S+0.50W+1.60H, Alpha= 180.0deg, (31.10, 96.00) Load Comb. = +1.20D+0.50Lr+0.50L+W+1.60H, Alpha= 180.0deg, (31.10, 96.00)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
4,700.0 4,700.0
4,230.0 4,230.0
3,760.0 3,760.0
3,290.0 3,290.0
2,820.0 2,820.0
Phi * Pn (k)
Phi * Pn (k)
2,350.0 2,350.0
1,880.0 1,880.0
1,410.0 1,410.0
940.0 940.0
470.0 470.0
0.0 1,526.13,052.14,578.26,104.37,630.39,156.410,682.512,208.5
13,734.6
15,260.7 0.0 1,526.13,052.14,578.26,104.37,630.39,156.410,682.512,208.5
13,734.6
15,260.7
Load Comb. = +1.549D+0.50L+0.20S+E+1.60H, Alpha= 180.0deg, (40.14, 1,023.00) Load Comb. = +0.90D+W+0.90H, Alpha= 180.0deg, (23.33, 54.00)
Concrete Shear Wall Check ( P201)
6
fc' := 4000⋅ psi Ec := 57000 ⋅ fc' ⋅ psi Ec = 3.605 × 10 ⋅ psi fy := 60000 ⋅ psi
twall := 12 ⋅ in lwall := 16.8 ⋅ ft h := 11 ⋅ ft ( height of entire wall or segment of wall considered )
ϕ := 0.6 ( 9.3.4 ) γconc := 145 ⋅ pcf cover := 2 ⋅ in Acv := twall⋅ ( lwall − cover)
Vu := 601 ⋅ kips
(
result := if Vu > 2 ⋅ Acv ⋅ fc' ⋅ psi , "Use 2 curtains of reinf." , "Use 1 curtain of reinf." ) ( 21.7.2.2 )
2
As_horiz := 0.2 ⋅ in spacing := 12 ⋅ in < 18" O.K. ( 21.7.2.1 )
n ⋅ As_horiz −3
ρt := max 0.0025 , ρt = 2.778 × 10
twall⋅ spacing
( Horiz. reinforcement ratio )
h h h
α := if ≤ 1.5 , 3 , if > 2 , 2 , 6 − 2⋅ ( 21.7.4.1 )
lwall lwall lwall
ϕVn1 := if
h
> 2 , ϕ⋅ 2⋅( ) (
fc' ⋅ psi + ρt ⋅ fy , ϕ ⋅ α ⋅ )
fc' ⋅ psi + ρt ⋅ fy ϕVn1 = 213.842⋅ psi
lwall
Vu
= 250.919⋅ psi < ϕVn = 213.842 ⋅ psi O.K.
Acv
Therefore, use 12" Con'c w/ #4 @12" O.C Horiz. Rebar @ Each Face
Shear Wall Boundary Elements Detail Requirements
3
twall⋅ lwall Pu Mu lwall
Ag := lwall ⋅ twall Ig := + ⋅ = 402.731⋅ psi 0.2 ⋅ fc' = 800 ⋅ psi
12 Ag Ig 2
Pu Mu lwall
Check1 := if + ⋅ < 0.2 ⋅ fc' , "B.Z.s are not required" , "B.Z.s are required"
Ag Ig 2
.
Code References
Calculations per ACI 318-11, IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : ASCE 7-10
General Information
f'c : Concrete 28 day strength = 4.0 ksi Overall Column Height = 11.0 ft
E= = 3,605.0 ksi End Fixity Top & Bottom Pinned
Density = 145.0 pcf Brace condition for deflection (buckling) along columns :
= 0.850 X-X (width) axis :
fy - Main Rebar = 60.0 ksi Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
E - Main Rebar = 29,000.0 ksi Y-Y (depth) axis :
Allow. Reinforcing Limits ASTM A615 Bars Used Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
Min. Reinf. = 0.250 %
Max. Reinf. = 8.0 %
Load Combination : ASCE 7-10
..
Column Cross Section
Column Dimensions :202.0in high x 12.0in Wide, Column Edge to Rebar Y
Applied Loads .
Entered loads are factored per load combinations specified by user.
Column self weight included : 26,849.2 lbs * Dead Load Factor
BENDING LOADS . . .
Moment acting about X-X axis, E = 1,260.0, H = 101.0 k-ft
DESIGN SUMMARY .
Load Combination +0.5514D+E+0.90H Maximum SERVICE Load Reactions . .
Location of max.above base 10.926 ft Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k
Maximum Stress Ratio = 0.259 : 1 Top along X-X 114.545 k Bottom along X-X 114.545 k
Ratio = (Pu^2+Mu^2)^.5 / (PhiPn^2+PhiMn^2)^.5
Pu = 14.805 k * Pn = 69.858 k
Maximum SERVICE Load Deflections . . .
Mu-x = -1,350.90 k-ft * Mn-x = 5,345.24 k-ft
Along Y-Y -0.000574 in at 6.423 ft above base
Mu-y = 0.0 k-ft * Mn-y = 0.0 k-ft for load combination : E Only
Mu Angle = 180.0 deg Along X-X 0.0in at 0.0 ft above base
Mu at Angle = 1,350.90 k-ft Mn at Angle = 5,225.79 k-ft for load combination :
Pn & Mn values located at Pu-Mu vector intersection with capacity curve
General Section Information . . . = 0.650 = 0.850 = 0.80
Column Capacities . . .
: % Reinforcing 0.4604 % Rebar % Ok
Pnmax : Nominal Max. Compressive Axial Capacity 8,873.26 k
Pnmin : Nominal Min. Tension Axial Capacity -669.60 k Reinforcing Area 11.160 in^2
Concrete Area 2,424.0 in^2
Pn, max : Usable Compressive Axial Capacity 4,614.09 k
Pn, min : Usable Tension Axial Capacity -435.240 k
Governing Load Combination Results .
Governing Factored Moment Source Dist. from Axial Load k Bending Analysis k-ft Utilization
Load Combination X-X Y-Y base ft Pu * Pn x x * Mux y y * Muy Alpha (deg) Mu Mn Ratio
+1.40D+1.60H Actual 10.93 37.59 2,915.68 1.000 -161.60 180.000 161.60 12,551.29 0.013
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : P201
#5#5
#5#5
#5#5
#5#5
#5#5 M-y Loads
Height = 11.0 ft
###.##kft
#5#5
Height = 11.0 ft
#5#5
#5#5
X #5#5
X
#5#5
#5#5
#5#5
#5#5 Looking along X-X Axis
#5#5
#5#5
#5#5
#5#5
#5#5
Interaction Diagrams .
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : P201
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
4,875.0 4,875.0
4,387.5 4,387.5
3,900.0 3,900.0
3,412.5 3,412.5
2,925.0 2,925.0
Phi * Pn (k)
Phi * Pn (k)
2,437.5 2,437.5
1,950.0 1,950.0
1,462.5 1,462.5
975.0 975.0
487.5 487.5
0.0 1,642.53,285.14,927.66,570.28,212.79,855.311,497.813,140.4
14,782.9
16,425.4 0.0 1,642.53,285.14,927.66,570.28,212.79,855.311,497.813,140.4
14,782.9
16,425.4
Load Comb. = +1.40D+1.60H, Alpha= 180.0deg, (37.59, 161.60) Load Comb. = +1.20D+0.50Lr+1.60L+1.60H, Alpha= 180.0deg, (32.22, 161.60)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
4,875.0
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
4,875.0
4,387.5 4,387.5
3,900.0 3,900.0
3,412.5 3,412.5
2,925.0 2,925.0
Phi * Pn (k)
Phi * Pn (k)
2,437.5 2,437.5
1,950.0 1,950.0
1,462.5 1,462.5
975.0 975.0
487.5 487.5
0.0 1,642.53,285.14,927.66,570.28,212.79,855.311,497.813,140.4
14,782.9
16,425.4 0.0 1,642.53,285.14,927.66,570.28,212.79,855.311,497.8
13,140.4
14,782.9
16,425.4
Load Comb. = +1.20D+1.60Lr+0.50L+1.60H, Alpha= 180.0deg, (32.22, 161.60) Load Comb. = +1.20D+1.60Lr+0.50W+1.60H, Alpha= 180.0deg, (32.22, 161.60)
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : P201
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
4,875.0 4,875.0
4,387.5 4,387.5
3,900.0 3,900.0
3,412.5 3,412.5
2,925.0 2,925.0
Phi * Pn (k)
Phi * Pn (k)
2,437.5 2,437.5
1,950.0 1,950.0
1,462.5 1,462.5
975.0 975.0
487.5 487.5
0.0 1,642.53,285.14,927.66,570.28,212.79,855.311,497.813,140.4
14,782.9
16,425.4 0.0 1,642.53,285.14,927.66,570.28,212.79,855.311,497.813,140.4
14,782.9
16,425.4
Load Comb. = +1.20D+1.60S+0.50W+1.60H, Alpha= 180.0deg, (32.22, 161.60) Load Comb. = +1.20D+0.50Lr+0.50L+W+1.60H, Alpha= 180.0deg, (32.22, 161.60)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
4,875.0 4,875.0
4,387.5 4,387.5
3,900.0 3,900.0
3,412.5 3,412.5
2,925.0 2,925.0
Phi * Pn (k)
Phi * Pn (k)
2,437.5 2,437.5
1,950.0 1,950.0
1,462.5 1,462.5
975.0 975.0
487.5 487.5
0.0 1,642.53,285.14,927.66,570.28,212.79,855.311,497.813,140.4
14,782.9
16,425.4 0.0 1,642.53,285.14,927.66,570.28,212.79,855.311,497.813,140.4
14,782.9
16,425.4
Load Comb. = +1.549D+0.50L+0.20S+E+1.60H, Alpha= 180.0deg, (41.58, 1,421.60) Load Comb. = +0.90D+W+0.90H, Alpha= 180.0deg, (24.16, 90.90)
Concrete Shear Wall Check ( PD1)
6
fc' := 4000⋅ psi Ec := 57000 ⋅ fc' ⋅ psi Ec = 3.605 × 10 ⋅ psi fy := 60000 ⋅ psi
twall := 12 ⋅ in lwall := 20ft h := 11 ⋅ ft ( height of entire wall or segment of wall considered )
ϕ := 0.6 ( 9.3.4 ) γconc := 145 ⋅ pcf cover := 2 ⋅ in Acv := twall⋅ ( lwall − cover)
Vu := 209 ⋅ kips
(
result := if Vu > 2 ⋅ Acv ⋅ fc' ⋅ psi , "Use 2 curtains of reinf." , "Use 1 curtain of reinf." ) ( 21.7.2.2 )
2
As_horiz := 0.2 ⋅ in spacing := 12 ⋅ in < 18" O.K. ( 21.7.2.1 )
n ⋅ As_horiz −3
ρt := max 0.0025 , ρt = 2.778 × 10
twall⋅ spacing
( Horiz. reinforcement ratio )
h h h
α := if ≤ 1.5 , 3 , if > 2 , 2 , 6 − 2⋅ ( 21.7.4.1 )
lwall lwall lwall
ϕVn1 := if
h
> 2 , ϕ⋅ 2⋅( ) (
fc' ⋅ psi + ρt ⋅ fy , ϕ ⋅ α ⋅ )
fc' ⋅ psi + ρt ⋅ fy ϕVn1 = 213.842⋅ psi
lwall
Vu
= 73.179⋅ psi < ϕVn = 213.842 ⋅ psi O.K.
Acv
Therefore, use 12" Con'c w/ #4 @12" O.C Horiz. Rebar @ Each Face
Shear Wall Boundary Elements Detail Requirements
3
twall⋅ lwall Pu Mu lwall
Ag := lwall ⋅ twall Ig := + ⋅ = 277.917⋅ psi 0.2 ⋅ fc' = 800 ⋅ psi
12 Ag Ig 2
Pu Mu lwall
Check1 := if + ⋅ < 0.2 ⋅ fc' , "B.Z.s are not required" , "B.Z.s are required"
Ag Ig 2
.
Code References
Calculations per ACI 318-11, IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : ASCE 7-10
General Information
f'c : Concrete 28 day strength = 4.0 ksi Overall Column Height = 11.0 ft
E= = 3,605.0 ksi End Fixity Top & Bottom Pinned
Density = 145.0 pcf Brace condition for deflection (buckling) along columns :
= 0.850 X-X (width) axis :
fy - Main Rebar = 60.0 ksi Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
E - Main Rebar = 29,000.0 ksi Y-Y (depth) axis :
Allow. Reinforcing Limits ASTM A615 Bars Used Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
Min. Reinf. = 0.250 %
Max. Reinf. = 8.0 %
Load Combination : ASCE 7-10
..
Column Cross Section
Column Dimensions :240.0in high x 12.0in Wide, Column Edge to Rebar Y
Applied Loads .
Entered loads are factored per load combinations specified by user.
Column self weight included : 31,900.0 lbs * Dead Load Factor
BENDING LOADS . . .
Moment acting about X-X axis, E = 1,011.0, H = 5.50 k-ft
DESIGN SUMMARY .
Load Combination +0.5514D+E+0.90H Maximum SERVICE Load Reactions . .
Location of max.above base 10.926 ft Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k
Maximum Stress Ratio = 0.132 : 1 Top along X-X 91.909 k Bottom along X-X 91.909 k
Ratio = (Pu^2+Mu^2)^.5 / (PhiPn^2+PhiMn^2)^.5
Pu = 17.590 k * Pn = 134.943 k
Maximum SERVICE Load Deflections . . .
Mu-x = -1,015.95 k-ft * Mn-x = 7,871.10 k-ft
Along Y-Y -0.000274 in at 6.423 ft above base
Mu-y = 0.0 k-ft * Mn-y = 0.0 k-ft for load combination : E Only
Mu Angle = 180.0 deg Along X-X 0.0in at 0.0 ft above base
Mu at Angle = 1,015.95 k-ft Mn at Angle = 7,700.15 k-ft for load combination :
Pn & Mn values located at Pu-Mu vector intersection with capacity curve
General Section Information . . . = 0.650 = 0.850 = 0.80
Column Capacities . . .
: % Reinforcing 0.4521 % Rebar % Ok
Pnmax : Nominal Max. Compressive Axial Capacity 10,528.9 k
Pnmin : Nominal Min. Tension Axial Capacity -781.20 k Reinforcing Area 13.020 in^2
Concrete Area 2,880.0 in^2
Pn, max : Usable Compressive Axial Capacity 5,475.05 k
Pn, min : Usable Tension Axial Capacity -507.78 k
Governing Load Combination Results .
Governing Factored Moment Source Dist. from Axial Load k Bending Analysis k-ft Utilization
Load Combination X-X Y-Y base ft Pu * Pn x x * Mux y y * Muy Alpha (deg) Mu Mn Ratio
+1.40D+1.60H Actual 10.93 44.66 5,475.04 1.000 -8.80 180.000 8.80 1,123.58 0.008
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PD1
#5#5
#5#5
#5#5
#5#5
#5#5
#5#5 M-y Loads
Height = 11.0 ft
###.##kft
#5#5
#5#5 Height = 11.0 ft
#5#5
#5#5
X #5#5
X
#5#5
#5#5
#5#5
#5#5 Looking along X-X Axis
#5#5
#5#5
#5#5
#5#5
#5#5
#5#5
Interaction Diagrams .
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PD1
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
5,775.0 5,775.0
5,197.5 5,197.5
4,620.0 4,620.0
4,042.5 4,042.5
3,465.0 3,465.0
Phi * Pn (k)
Phi * Pn (k)
2,887.5 2,887.5
2,310.0 2,310.0
1,732.5 1,732.5
1,155.0 1,155.0
577.5 577.5
0.0 2,313.94,627.76,941.69,255.411,569.3
13,883.1
16,197.018,510.9
20,824.7
23,138.6 0.0 2,313.94,627.76,941.69,255.411,569.3
13,883.1
16,197.018,510.9
20,824.7
23,138.6
Load Comb. = +1.40D+1.60H, Alpha= 180.0deg, (44.66, 8.80) Load Comb. = +1.20D+0.50Lr+1.60L+1.60H, Alpha= 180.0deg, (38.28, 8.80)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
5,775.0 5,775.0
5,197.5 5,197.5
4,620.0 4,620.0
4,042.5 4,042.5
3,465.0 3,465.0
Phi * Pn (k)
Phi * Pn (k)
2,887.5 2,887.5
2,310.0 2,310.0
1,732.5 1,732.5
1,155.0 1,155.0
577.5 577.5
0.0 2,313.94,627.76,941.69,255.411,569.3
13,883.1
16,197.018,510.9
20,824.7
23,138.6 0.0 2,313.94,627.76,941.69,255.411,569.3
13,883.1
16,197.018,510.9
20,824.7
23,138.6
Load Comb. = +1.20D+1.60Lr+0.50L+1.60H, Alpha= 180.0deg, (38.28, 8.80) Load Comb. = +1.20D+1.60Lr+0.50W+1.60H, Alpha= 180.0deg, (38.28, 8.80)
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PD1
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
5,775.0 5,775.0
5,197.5 5,197.5
4,620.0 4,620.0
4,042.5 4,042.5
3,465.0 3,465.0
Phi * Pn (k)
Phi * Pn (k)
2,887.5 2,887.5
2,310.0 2,310.0
1,732.5 1,732.5
1,155.0 1,155.0
577.5 577.5
0.0 2,313.94,627.76,941.69,255.411,569.3
13,883.1
16,197.018,510.9
20,824.7
23,138.6 0.0 2,313.94,627.76,941.69,255.411,569.3
13,883.1
16,197.018,510.9
20,824.7
23,138.6
Load Comb. = +1.20D+1.60S+0.50W+1.60H, Alpha= 180.0deg, (38.28, 8.80) Load Comb. = +1.20D+0.50Lr+0.50L+W+1.60H, Alpha= 180.0deg, (38.28, 8.80)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
5,775.0 5,775.0
5,197.5 5,197.5
4,620.0 4,620.0
4,042.5 4,042.5
3,465.0 3,465.0
Phi * Pn (k)
Phi * Pn (k)
2,887.5 2,887.5
2,310.0 2,310.0
1,732.5 1,732.5
1,155.0 1,155.0
577.5 577.5
0.0 2,313.94,627.76,941.69,255.411,569.3
13,883.1
16,197.018,510.9
20,824.7
23,138.6 0.0 2,313.94,627.76,941.69,255.411,569.3
13,883.1
16,197.018,510.9
20,824.7
23,138.6
Load Comb. = +1.549D+0.50L+0.20S+E+1.60H, Alpha= 180.0deg, (49.40, 1,019.80) Load Comb. = +0.90D+W+0.90H, Alpha= 180.0deg, (28.71, 4.95)
Concrete Shear Wall Check ( PO1)
6
fc' := 4000⋅ psi Ec := 57000 ⋅ fc' ⋅ psi Ec = 3.605 × 10 ⋅ psi fy := 60000 ⋅ psi
twall := 12 ⋅ in lwall := 30.75 ⋅ ft h := 11 ⋅ ft ( height of entire wall or segment of wall considered )
ϕ := 0.6 ( 9.3.4 ) γconc := 145 ⋅ pcf cover := 2 ⋅ in Acv := twall⋅ ( lwall − cover)
Vu := 596 ⋅ kips
(
result := if Vu > 2 ⋅ Acv ⋅ fc' ⋅ psi , "Use 2 curtains of reinf." , "Use 1 curtain of reinf." ) ( 21.7.2.2 )
2
As_horiz := 0.2 ⋅ in spacing := 12 ⋅ in < 18" O.K. ( 21.7.2.1 )
n ⋅ As_horiz −3
ρt := max 0.0025 , ρt = 2.778 × 10
twall⋅ spacing
( Horiz. reinforcement ratio )
h h h
α := if ≤ 1.5 , 3 , if > 2 , 2 , 6 − 2⋅ ( 21.7.4.1 )
lwall lwall lwall
ϕVn1 := if
h
> 2 , ϕ⋅ 2⋅( ) (
fc' ⋅ psi + ρt ⋅ fy , ϕ ⋅ α ⋅ )
fc' ⋅ psi + ρt ⋅ fy ϕVn1 = 213.842⋅ psi
lwall
Vu
= 135.332⋅ psi < ϕVn = 213.842 ⋅ psi O.K.
Acv
Therefore, use 12" Con'c w/ #4 @12" O.C Horiz. Rebar @ Each Face
Shear Wall Boundary Elements Detail Requirements
3
twall⋅ lwall Pu Mu lwall
Ag := lwall ⋅ twall Ig := + ⋅ = 353.477⋅ psi 0.2 ⋅ fc' = 800 ⋅ psi
12 Ag Ig 2
Pu Mu lwall
Check1 := if + ⋅ < 0.2 ⋅ fc' , "B.Z.s are not required" , "B.Z.s are required"
Ag Ig 2
.
Code References
Calculations per ACI 318-11, IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : ASCE 7-10
General Information
f'c : Concrete 28 day strength = 4.0 ksi Overall Column Height = 11.0 ft
E= = 3,605.0 ksi End Fixity Top & Bottom Pinned
Density = 145.0 pcf Brace condition for deflection (buckling) along columns :
= 0.850 X-X (width) axis :
fy - Main Rebar = 60.0 ksi Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
E - Main Rebar = 29,000.0 ksi Y-Y (depth) axis :
Allow. Reinforcing Limits ASTM A615 Bars Used Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
Min. Reinf. = 0.250 %
Max. Reinf. = 8.0 %
Load Combination : ASCE 7-10
..
Column Cross Section
Column Dimensions :369.0in high x 12.0in Wide, Column Edge to Rebar Y
Applied Loads .
Entered loads are factored per load combinations specified by user.
Column self weight included : 49,046.3 lbs * Dead Load Factor
BENDING LOADS . . .
Moment acting about X-X axis, E = 1,989.0, H = 16.0 k-ft
DESIGN SUMMARY .
Load Combination +0.5514D+E+0.90H Maximum SERVICE Load Reactions . .
Location of max.above base 10.926 ft Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k
Maximum Stress Ratio = 0.106 : 1 Top along X-X 180.818 k Bottom along X-X 180.818 k
Ratio = (Pu^2+Mu^2)^.5 / (PhiPn^2+PhiMn^2)^.5
Pu = 27.044 k * Pn = 278.324 k
Maximum SERVICE Load Deflections . . .
Mu-x = -2,003.40 k-ft * Mn-x = 19,353.4 k-ft
Along Y-Y -0.000149 in at 6.423 ft above base
Mu-y = 0.0 k-ft * Mn-y = 0.0 k-ft for load combination : E Only
Mu Angle = 180.0 deg Along X-X 0.0in at 0.0 ft above base
Mu at Angle = 2,003.40 k-ft Mn at Angle = 18,952.7 k-ft for load combination :
Pn & Mn values located at Pu-Mu vector intersection with capacity curve
General Section Information . . . = 0.650 = 0.850 = 0.80
Column Capacities . . .
: % Reinforcing 0.4481 % Rebar % Ok
Pnmax : Nominal Max. Compressive Axial Capacity 16,178.1 k
Pnmin : Nominal Min. Tension Axial Capacity -1,190.40 k Reinforcing Area 19.840 in^2
Concrete Area 4,428.0 in^2
Pn, max : Usable Compressive Axial Capacity 8,412.64 k
Pn, min : Usable Tension Axial Capacity -773.76 k
Governing Load Combination Results .
Governing Factored Moment Source Dist. from Axial Load k Bending Analysis k-ft Utilization
Load Combination X-X Y-Y base ft Pu * Pn x x * Mux y y * Muy Alpha (deg) Mu Mn Ratio
+1.40D+1.60H Actual 10.93 68.66 8,412.63 1.000 -25.60 180.000 25.60 3,321.57 0.008
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PO1
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
Height = 11.0 ft
#5
#5 M-y Loads
#5
#5
Height = 11.0 ft
###.##kft
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
X #5
#X5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5 Looking along X-X Axis
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
Interaction Diagrams .
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PO1
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) 8,875.0
Phi * Mn @ Alpha (k-ft)
8,875.0
7,987.5 7,987.5
7,100.0 7,100.0
6,212.5 6,212.5
5,325.0 5,325.0
Phi * Pn (k)
Phi * Pn (k)
4,437.5 4,437.5
3,550.0 3,550.0
2,662.5 2,662.5
1,775.0 1,775.0
887.5 887.5
0.0 5,466.2
10,932.4
16,398.6
21,864.7
27,330.9
32,797.1
38,263.3
43,729.5
49,195.7
54,661.9 0.0 5,466.210,932.4
16,398.6
21,864.727,330.9
32,797.1
38,263.343,729.5
49,195.7
54,661.9
Load Comb. = +1.40D+1.60H, Alpha= 180.0deg, (68.66, 25.60) Load Comb. = +1.20D+0.50Lr+1.60L+1.60H, Alpha= 180.0deg, (58.86, 25.60)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
8,875.0
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,875.0
7,987.5 7,987.5
7,100.0 7,100.0
6,212.5 6,212.5
5,325.0 5,325.0
Phi * Pn (k)
Phi * Pn (k)
4,437.5 4,437.5
3,550.0 3,550.0
2,662.5 2,662.5
1,775.0 1,775.0
887.5 887.5
0.0 5,466.210,932.4
16,398.6
21,864.727,330.9
32,797.1
38,263.343,729.5
49,195.7
54,661.9 0.0 5,466.210,932.4
16,398.6
21,864.7
27,330.9
32,797.1
38,263.3
43,729.549,195.7
54,661.9
Load Comb. = +1.20D+1.60Lr+0.50L+1.60H, Alpha= 180.0deg, (58.86, 25.60) Load Comb. = +1.20D+1.60Lr+0.50W+1.60H, Alpha= 180.0deg, (58.86, 25.60)
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PO1
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,875.0 8,875.0
7,987.5 7,987.5
7,100.0 7,100.0
6,212.5 6,212.5
5,325.0 5,325.0
Phi * Pn (k)
Phi * Pn (k)
4,437.5 4,437.5
3,550.0 3,550.0
2,662.5 2,662.5
1,775.0 1,775.0
887.5 887.5
0.0 5,466.210,932.4
16,398.6
21,864.727,330.9
32,797.1
38,263.343,729.5
49,195.7
54,661.9 0.0 5,466.210,932.4
16,398.6
21,864.727,330.9
32,797.1
38,263.343,729.5
49,195.7
54,661.9
Load Comb. = +1.20D+1.60S+0.50W+1.60H, Alpha= 180.0deg, (58.86, 25.60) Load Comb. = +1.20D+0.50Lr+0.50L+W+1.60H, Alpha= 180.0deg, (58.86, 25.60)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,875.0 8,875.0
7,987.5 7,987.5
7,100.0 7,100.0
6,212.5 6,212.5
5,325.0 5,325.0
Phi * Pn (k)
Phi * Pn (k)
4,437.5 4,437.5
3,550.0 3,550.0
2,662.5 2,662.5
1,775.0 1,775.0
887.5 887.5
0.0 5,466.210,932.4
16,398.6
21,864.7
27,330.9
32,797.1
38,263.3
43,729.5
49,195.7
54,661.9 0.0 5,466.210,932.4
16,398.6
21,864.727,330.9
32,797.1
38,263.343,729.5
49,195.7
54,661.9
Load Comb. = +1.549D+0.50L+0.20S+E+1.60H, Alpha= 180.0deg, (75.95, 2,014.60) Load Comb. = +0.90D+W+0.90H, Alpha= 180.0deg, (44.14, 14.40)
Concrete Shear Wall Check ( PB1)
6
fc' := 4000⋅ psi Ec := 57000 ⋅ fc' ⋅ psi Ec = 3.605 × 10 ⋅ psi fy := 60000 ⋅ psi
twall := 12 ⋅ in lwall := 28 ⋅ ft h := 11 ⋅ ft ( height of entire wall or segment of wall considered )
ϕ := 0.6 ( 9.3.4 ) γconc := 145 ⋅ pcf cover := 2 ⋅ in Acv := twall⋅ ( lwall − cover)
Vu := 617 ⋅ kips
(
result := if Vu > 2 ⋅ Acv ⋅ fc' ⋅ psi , "Use 2 curtains of reinf." , "Use 1 curtain of reinf." ) ( 21.7.2.2 )
2
As_horiz := 0.2 ⋅ in spacing := 12 ⋅ in < 18" O.K. ( 21.7.2.1 )
n ⋅ As_horiz −3
ρt := max 0.0025 , ρt = 2.778 × 10
twall⋅ spacing
( Horiz. reinforcement ratio )
h h h
α := if ≤ 1.5 , 3 , if > 2 , 2 , 6 − 2⋅ ( 21.7.4.1 )
lwall lwall lwall
ϕVn1 := if
h
> 2 , ϕ⋅ 2⋅( ) (
fc' ⋅ psi + ρt ⋅ fy , ϕ ⋅ α ⋅ )
fc' ⋅ psi + ρt ⋅ fy ϕVn1 = 213.842⋅ psi
lwall
Vu
= 153.942⋅ psi < ϕVn = 213.842 ⋅ psi O.K.
Acv
Therefore, use 12" Con'c w/ #4 @12" O.C Horiz. Rebar @ Each Face
Shear Wall Boundary Elements Detail Requirements
3
twall⋅ lwall Pu Mu lwall
Ag := lwall ⋅ twall Ig := + ⋅ = 489.636⋅ psi 0.2 ⋅ fc' = 800 ⋅ psi
12 Ag Ig 2
Pu Mu lwall
Check1 := if + ⋅ < 0.2 ⋅ fc' , "B.Z.s are not required" , "B.Z.s are required"
Ag Ig 2
.
Code References
Calculations per ACI 318-11, IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : ASCE 7-10
General Information
f'c : Concrete 28 day strength = 4.0 ksi Overall Column Height = 11.0 ft
E= = 3,605.0 ksi End Fixity Top & Bottom Pinned
Density = 145.0 pcf Brace condition for deflection (buckling) along columns :
= 0.850 X-X (width) axis :
fy - Main Rebar = 60.0 ksi Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
E - Main Rebar = 29,000.0 ksi Y-Y (depth) axis :
Allow. Reinforcing Limits ASTM A615 Bars Used Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
Min. Reinf. = 0.250 %
Max. Reinf. = 8.0 %
Load Combination : ASCE 7-10
..
Column Cross Section
Column Dimensions :336.0in high x 12.0in Wide, Column Edge to Rebar Y
Applied Loads .
Entered loads are factored per load combinations specified by user.
Column self weight included : 44,660.0 lbs * Dead Load Factor
BENDING LOADS . . .
Moment acting about X-X axis, E = 1,875.0, H = 25.0 k-ft
DESIGN SUMMARY .
Load Combination +0.5514D+E+0.90H Maximum SERVICE Load Reactions . .
Location of max.above base 10.926 ft Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k
Maximum Stress Ratio = 0.126 : 1 Top along X-X 170.455 k Bottom along X-X 170.455 k
Ratio = (Pu^2+Mu^2)^.5 / (PhiPn^2+PhiMn^2)^.5
Pu = 24.626 k * Pn = 200.122 k
Maximum SERVICE Load Deflections . . .
Mu-x = -1,897.50 k-ft * Mn-x = 15,376.9 k-ft
Along Y-Y -0.000186 in at 6.423 ft above base
Mu-y = 0.0 k-ft * Mn-y = 0.0 k-ft for load combination : E Only
Mu Angle = 180.0 deg Along X-X 0.0in at 0.0 ft above base
Mu at Angle = 1,897.50 k-ft Mn at Angle = 15,043.8 k-ft for load combination :
Pn & Mn values located at Pu-Mu vector intersection with capacity curve
General Section Information . . . = 0.650 = 0.850 = 0.80
Column Capacities . . .
: % Reinforcing 0.4459 % Rebar % Ok
Pnmax : Nominal Max. Compressive Axial Capacity 14,726.5 k
Pnmin : Nominal Min. Tension Axial Capacity -1,078.80 k Reinforcing Area 17.980 in^2
Concrete Area 4,032.0 in^2
Pn, max : Usable Compressive Axial Capacity 7,657.76 k
Pn, min : Usable Tension Axial Capacity -701.22 k
Governing Load Combination Results .
Governing Factored Moment Source Dist. from Axial Load k Bending Analysis k-ft Utilization
Load Combination X-X Y-Y base ft Pu * Pn x x * Mux y y * Muy Alpha (deg) Mu Mn Ratio
+1.40D+1.60H Actual 10.93 62.52 7,657.76 1.000 -40.00 180.000 40.00 4,928.82 0.008
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PB1
#5#5
#5#5
#5#5
#5#5
#5#5
#5#5
#5#5
#5#5
Height = 11.0 ft
M-y Loads
#5#5
Height = 11.0 ft
###.##kft
#5#5
#5#5
#5#5
#5#5
X #5#
#5 5
#X5
#5#5
#5#5
#5#5
#5#5
#5#5 Looking along X-X Axis
#5#5
#5#5
#5#5
#5#5
#5#5
#5#5
#5#5
#5#5
#5#5
Interaction Diagrams .
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PB1
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,075.0 8,075.0
7,267.5 7,267.5
6,460.0 6,460.0
5,652.5 5,652.5
4,845.0 4,845.0
Phi * Pn (k)
Phi * Pn (k)
4,037.5 4,037.5
3,230.0 3,230.0
2,422.5 2,422.5
1,615.0 1,615.0
807.5 807.5
0.0 4,529.39,058.513,587.8
18,117.022,646.3
27,175.5
31,704.836,234.0
40,763.3
45,292.5 0.0 4,529.39,058.513,587.8
18,117.022,646.3
27,175.5
31,704.836,234.0
40,763.3
45,292.5
Load Comb. = +1.40D+1.60H, Alpha= 180.0deg, (62.52, 40.00) Load Comb. = +1.20D+0.50Lr+1.60L+1.60H, Alpha= 180.0deg, (53.59, 40.00)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) 8,075.0
Phi * Mn @ Alpha (k-ft)
8,075.0
7,267.5 7,267.5
6,460.0 6,460.0
5,652.5 5,652.5
4,845.0 4,845.0
Phi * Pn (k)
Phi * Pn (k)
4,037.5 4,037.5
3,230.0 3,230.0
2,422.5 2,422.5
1,615.0 1,615.0
807.5 807.5
0.0 4,529.39,058.513,587.8
18,117.0
22,646.3
27,175.5
31,704.8
36,234.0
40,763.3
45,292.5 0.0 4,529.39,058.513,587.8
18,117.022,646.3
27,175.5
31,704.836,234.0
40,763.3
45,292.5
Load Comb. = +1.20D+1.60Lr+0.50L+1.60H, Alpha= 180.0deg, (53.59, 40.00) Load Comb. = +1.20D+1.60Lr+0.50W+1.60H, Alpha= 180.0deg, (53.59, 40.00)
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PB1
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,075.0 8,075.0
7,267.5 7,267.5
6,460.0 6,460.0
5,652.5 5,652.5
4,845.0 4,845.0
Phi * Pn (k)
Phi * Pn (k)
4,037.5 4,037.5
3,230.0 3,230.0
2,422.5 2,422.5
1,615.0 1,615.0
807.5 807.5
0.0 4,529.39,058.513,587.8
18,117.022,646.3
27,175.5
31,704.836,234.0
40,763.3
45,292.5 0.0 4,529.39,058.513,587.8
18,117.022,646.3
27,175.5
31,704.836,234.0
40,763.3
45,292.5
Load Comb. = +1.20D+1.60S+0.50W+1.60H, Alpha= 180.0deg, (53.59, 40.00) Load Comb. = +1.20D+0.50Lr+0.50L+W+1.60H, Alpha= 180.0deg, (53.59, 40.00)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,075.0 8,075.0
7,267.5 7,267.5
6,460.0 6,460.0
5,652.5 5,652.5
4,845.0 4,845.0
Phi * Pn (k)
Phi * Pn (k)
4,037.5 4,037.5
3,230.0 3,230.0
2,422.5 2,422.5
1,615.0 1,615.0
807.5 807.5
0.0 4,529.39,058.513,587.8
18,117.022,646.3
27,175.5
31,704.836,234.0
40,763.3
45,292.5 0.0 4,529.39,058.513,587.8
18,117.0
22,646.3
27,175.5
31,704.8
36,234.0
40,763.3
45,292.5
Load Comb. = +1.549D+0.50L+0.20S+E+1.60H, Alpha= 180.0deg, (69.16, 1,915.00) Load Comb. = +0.90D+W+0.90H, Alpha= 180.0deg, (40.19, 22.50)
Concrete Shear Wall Check ( PB2)
6
fc' := 4000⋅ psi Ec := 57000 ⋅ fc' ⋅ psi Ec = 3.605 × 10 ⋅ psi fy := 60000 ⋅ psi
twall := 12 ⋅ in lwall := 19.33 ⋅ ft h := 11 ⋅ ft ( height of entire wall or segment of wall considered )
ϕ := 0.6 ( 9.3.4 ) γconc := 145 ⋅ pcf cover := 2 ⋅ in Acv := twall⋅ ( lwall − cover)
Vu := 212 ⋅ kips
(
result := if Vu > 2 ⋅ Acv ⋅ fc' ⋅ psi , "Use 2 curtains of reinf." , "Use 1 curtain of reinf." ) ( 21.7.2.2 )
2
As_horiz := 0.2 ⋅ in spacing := 12 ⋅ in < 18" O.K. ( 21.7.2.1 )
n ⋅ As_horiz −3
ρt := max 0.0025 , ρt = 2.778 × 10
twall⋅ spacing
( Horiz. reinforcement ratio )
h h h
α := if ≤ 1.5 , 3 , if > 2 , 2 , 6 − 2⋅ ( 21.7.4.1 )
lwall lwall lwall
ϕVn1 := if
h
> 2 , ϕ⋅ 2⋅( ) (
fc' ⋅ psi + ρt ⋅ fy , ϕ ⋅ α ⋅ )
fc' ⋅ psi + ρt ⋅ fy ϕVn1 = 213.842⋅ psi
lwall
Vu
= 76.825 ⋅ psi < ϕVn = 213.842 ⋅ psi O.K.
Acv
Therefore, use 12" Con'c w/ #4 @12" O.C Horiz. Rebar @ Each Face
Shear Wall Boundary Elements Detail Requirements
3
twall⋅ lwall Pu Mu lwall
Ag := lwall ⋅ twall Ig := + ⋅ = 321.894⋅ psi 0.2 ⋅ fc' = 800 ⋅ psi
12 Ag Ig 2
Pu Mu lwall
Check1 := if + ⋅ < 0.2 ⋅ fc' , "B.Z.s are not required" , "B.Z.s are required"
Ag Ig 2
.
Code References
Calculations per ACI 318-11, IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : ASCE 7-10
General Information
f'c : Concrete 28 day strength = 4.0 ksi Overall Column Height = 11.0 ft
E= = 3,605.0 ksi End Fixity Top & Bottom Pinned
Density = 145.0 pcf Brace condition for deflection (buckling) along columns :
= 0.850 X-X (width) axis :
fy - Main Rebar = 60.0 ksi Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
E - Main Rebar = 29,000.0 ksi Y-Y (depth) axis :
Allow. Reinforcing Limits ASTM A615 Bars Used Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
Min. Reinf. = 0.250 %
Max. Reinf. = 8.0 %
Load Combination : ASCE 7-10
..
Column Cross Section
Column Dimensions :232.0in high x 12.0in Wide, Column Edge to Rebar Y
Applied Loads .
Entered loads are factored per load combinations specified by user.
Column self weight included : 30,836.7 lbs * Dead Load Factor
BENDING LOADS . . .
Moment acting about X-X axis, E = 523.0, H = 18.0 k-ft
DESIGN SUMMARY .
Load Combination +0.5514D+E+0.90H Maximum SERVICE Load Reactions . .
Location of max.above base 10.926 ft Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k
Maximum Stress Ratio = 0.066 : 1 Top along X-X 47.545 k Bottom along X-X 47.545 k
Ratio = (Pu^2+Mu^2)^.5 / (PhiPn^2+PhiMn^2)^.5
Pu = 17.003 k * Pn = 257.373 k
Maximum SERVICE Load Deflections . . .
Mu-x = -539.20 k-ft * Mn-x = 8,274.06 k-ft
Along Y-Y -0.000157 in at 6.423 ft above base
Mu-y = 0.0 k-ft * Mn-y = 0.0 k-ft for load combination : E Only
Mu Angle = 180.0 deg Along X-X 0.0in at 0.0 ft above base
Mu at Angle = 539.20 k-ft Mn at Angle = 8,120.56 k-ft for load combination :
Pn & Mn values located at Pu-Mu vector intersection with capacity curve
General Section Information . . . = 0.650 = 0.850 = 0.80
Column Capacities . . .
: % Reinforcing 0.4454 % Rebar % Ok
Pnmax : Nominal Max. Compressive Axial Capacity 10,167.4 k
Pnmin : Nominal Min. Tension Axial Capacity -744.0 k Reinforcing Area 12.40 in^2
Concrete Area 2,784.0 in^2
Pn, max : Usable Compressive Axial Capacity 5,287.07 k
Pn, min : Usable Tension Axial Capacity -483.60 k
Governing Load Combination Results .
Governing Factored Moment Source Dist. from Axial Load k Bending Analysis k-ft Utilization
Load Combination X-X Y-Y base ft Pu * Pn x x * Mux y y * Muy Alpha (deg) Mu Mn Ratio
+1.40D+1.60H Actual 10.93 43.17 5,287.07 1.000 -28.80 180.000 28.80 3,596.42 0.008
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PB2
#5#5
#5#5
#5#5
#5#5
#5#5
M-y Loads
Height = 11.0 ft
#5#5 541.00kft
Height = 11.0 ft
#5#5
#5#5
#5#5
X #5#5
X
#5#5
#5#5
#5#5
#5#5
Looking along X-X Axis
#5#5
#5#5
#5#5
#5#5
#5#5
#5#5
Interaction Diagrams .
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PB2
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) 5,600.0
Phi * Mn @ Alpha (k-ft)
5,600.0
5,040.0 5,040.0
4,480.0 4,480.0
3,920.0 3,920.0
3,360.0 3,360.0
Phi * Pn (k)
Phi * Pn (k)
2,800.0 2,800.0
2,240.0 2,240.0
1,680.0 1,680.0
1,120.0 1,120.0
560.0 560.0
0.0 2,158.34,316.56,474.88,633.010,791.3
12,949.5
15,107.8
17,266.119,424.3
21,582.6 0.0 2,158.34,316.56,474.88,633.010,791.3
12,949.5
15,107.817,266.1
19,424.3
21,582.6
Load Comb. = +1.40D+1.60H, Alpha= 180.0deg, (43.17, 28.80) Load Comb. = +1.20D+0.50Lr+1.60L+1.60H, Alpha= 180.0deg, (37.00, 28.80)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
5,600.0 5,600.0
5,040.0 5,040.0
4,480.0 4,480.0
3,920.0 3,920.0
3,360.0 3,360.0
Phi * Pn (k)
Phi * Pn (k)
2,800.0 2,800.0
2,240.0 2,240.0
1,680.0 1,680.0
1,120.0 1,120.0
560.0 560.0
0.0 2,158.34,316.56,474.88,633.010,791.3
12,949.5
15,107.817,266.1
19,424.3
21,582.6 0.0 2,158.34,316.56,474.88,633.010,791.3
12,949.5
15,107.817,266.1
19,424.3
21,582.6
Load Comb. = +1.20D+1.60Lr+0.50L+1.60H, Alpha= 180.0deg, (37.00, 28.80) Load Comb. = +1.20D+1.60Lr+0.50W+1.60H, Alpha= 180.0deg, (37.00, 28.80)
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PB2
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
5,600.0 5,600.0
5,040.0 5,040.0
4,480.0 4,480.0
3,920.0 3,920.0
3,360.0 3,360.0
Phi * Pn (k)
Phi * Pn (k)
2,800.0 2,800.0
2,240.0 2,240.0
1,680.0 1,680.0
1,120.0 1,120.0
560.0 560.0
0.0 2,158.34,316.56,474.88,633.010,791.3
12,949.5
15,107.817,266.1
19,424.3
21,582.6 0.0 2,158.34,316.56,474.88,633.010,791.3
12,949.5
15,107.817,266.1
19,424.3
21,582.6
Load Comb. = +1.20D+1.60S+0.50W+1.60H, Alpha= 180.0deg, (37.00, 28.80) Load Comb. = +1.20D+0.50Lr+0.50L+W+1.60H, Alpha= 180.0deg, (37.00, 28.80)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
5,600.0 5,600.0
5,040.0 5,040.0
4,480.0 4,480.0
3,920.0 3,920.0
3,360.0 3,360.0
Phi * Pn (k)
Phi * Pn (k)
2,800.0 2,800.0
2,240.0 2,240.0
1,680.0 1,680.0
1,120.0 1,120.0
560.0 560.0
0.0 2,158.34,316.56,474.88,633.010,791.3
12,949.5
15,107.817,266.1
19,424.3
21,582.6 0.0 2,158.34,316.56,474.88,633.010,791.3
12,949.5
15,107.817,266.1
19,424.3
21,582.6
Load Comb. = +1.549D+0.50L+0.20S+E+1.60H, Alpha= 180.0deg, (47.75, 551.80) Load Comb. = +0.90D+W+0.90H, Alpha= 180.0deg, (27.75, 16.20)
Concrete Shear Wall Check ( PA8)
6
fc' := 4000⋅ psi Ec := 57000 ⋅ fc' ⋅ psi Ec = 3.605 × 10 ⋅ psi fy := 60000 ⋅ psi
twall := 14 ⋅ in lwall := 9.6 ⋅ ft h := 11 ⋅ ft ( height of entire wall or segment of wall considered )
ϕ := 0.6 ( 9.3.4 ) γconc := 145 ⋅ pcf cover := 2 ⋅ in Acv := twall⋅ ( lwall − cover)
Vu := 8 ⋅ kips
(
result := if Vu > 2 ⋅ Acv ⋅ fc' ⋅ psi , "Use 2 curtains of reinf." , "Use 1 curtain of reinf." ) ( 21.7.2.2 )
2
As_horiz := 0.2 ⋅ in spacing := 12 ⋅ in < 18" O.K. ( 21.7.2.1 )
n ⋅ As_horiz −3
ρt := max 0.0025 , ρt = 2.5 × 10
twall⋅ spacing
( Horiz. reinforcement ratio )
h h h
α := if ≤ 1.5 , 3 , if > 2 , 2 , 6 − 2⋅ ( 21.7.4.1 )
lwall lwall lwall
ϕVn1 := if
h
> 2 , ϕ⋅ 2⋅( ) (
fc' ⋅ psi + ρt ⋅ fy , ϕ ⋅ α ⋅ )
fc' ⋅ psi + ρt ⋅ fy ϕVn1 = 203.842⋅ psi
lwall
Vu
= 5.048 ⋅ psi < ϕVn = 203.842⋅ psi O.K.
Acv
Therefore, use 14" Con'c w/ #4 @12" O.C Horiz. Rebar @ Each Face
Shear Wall Boundary Elements Detail Requirements
3
twall⋅ lwall Pu Mu lwall
Ag := lwall ⋅ twall Ig := + ⋅ = 106.492⋅ psi 0.2 ⋅ fc' = 800 ⋅ psi
12 Ag Ig 2
Pu Mu lwall
Check1 := if + ⋅ < 0.2 ⋅ fc' , "B.Z.s are not required" , "B.Z.s are required"
Ag Ig 2
.
Code References
Calculations per ACI 318-11, IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : ASCE 7-10
General Information
f'c : Concrete 28 day strength = 4.0 ksi Overall Column Height = 11.0 ft
E= = 3,605.0 ksi End Fixity Top & Bottom Pinned
Density = 145.0 pcf Brace condition for deflection (buckling) along columns :
= 0.850 X-X (width) axis :
fy - Main Rebar = 60.0 ksi Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
E - Main Rebar = 29,000.0 ksi Y-Y (depth) axis :
Allow. Reinforcing Limits ASTM A615 Bars Used Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
Min. Reinf. = 0.250 %
Max. Reinf. = 8.0 %
Load Combination : ASCE 7-10
..
Column Cross Section
Column Dimensions :115.0in high x 14.0in Wide, Column Edge to Rebar Y
Applied Loads .
Entered loads are factored per load combinations specified by user.
Column self weight included : 17,833.0 lbs * Dead Load Factor
BENDING LOADS . . .
Moment acting about X-X axis, E = 60.0, H = 2.0 k-ft
DESIGN SUMMARY .
Load Combination +0.5514D+E+0.90H Maximum SERVICE Load Reactions . .
Location of max.above base 10.926 ft Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k
Maximum Stress Ratio = 0.016 : 1 Top along X-X 5.455 k Bottom along X-X 5.455 k
Ratio = (Pu^2+Mu^2)^.5 / (PhiPn^2+PhiMn^2)^.5
Pu = 9.833 k * Pn = 617.52 k
Maximum SERVICE Load Deflections . . .
Mu-x = -61.80 k-ft * Mn-x = 3,933.44 k-ft
Along Y-Y -0.000127 in at 6.423 ft above base
Mu-y = 0.0 k-ft * Mn-y = 0.0 k-ft for load combination : E Only
Mu Angle = 180.0 deg Along X-X 0.0in at 0.0 ft above base
Mu at Angle = 61.80 k-ft Mn at Angle = 3,899.28 k-ft for load combination :
Pn & Mn values located at Pu-Mu vector intersection with capacity curve
General Section Information . . . = 0.650 = 0.850 = 0.80
Column Capacities . . .
: % Reinforcing 0.4236 % Rebar % Ok
Pnmax : Nominal Max. Compressive Axial Capacity 5,860.01 k
Pnmin : Nominal Min. Tension Axial Capacity -409.20 k Reinforcing Area 6.820 in^2
Concrete Area 1,610.0 in^2
Pn, max : Usable Compressive Axial Capacity 3,047.21 k
Pn, min : Usable Tension Axial Capacity -265.980 k
Governing Load Combination Results .
Governing Factored Moment Source Dist. from Axial Load k Bending Analysis k-ft Utilization
Load Combination X-X Y-Y base ft Pu * Pn x x * Mux y y * Muy Alpha (deg) Mu Mn Ratio
+1.40D+1.60H Actual 10.93 24.97 3,047.21 1.000 -3.20 180.000 3.20 383.18 0.008
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PA8
#5 #5
#5 #5
M-y Loads
#5 #5 62.00kft
Height = 11.0 ft
#5 #5 Height = 11.0 ft
#5 #5
X X
#5 #5
#5 #5
#5 #5
#5 #5
#5 #5
Interaction Diagrams .
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PA8
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
3,225.0 3,225.0
2,902.5 2,902.5
2,580.0 2,580.0
2,257.5 2,257.5
1,935.0 1,935.0
Phi * Pn (k)
Phi * Pn (k)
1,612.5 1,612.5
1,290.0 1,290.0
967.5 967.5
645.0 645.0
322.5 322.5
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) 3,225.0
Phi * Mn @ Alpha (k-ft)
3,225.0
2,902.5 2,902.5
2,580.0 2,580.0
2,257.5 2,257.5
1,935.0 1,935.0
Phi * Pn (k)
Phi * Pn (k)
1,612.5 1,612.5
1,290.0 1,290.0
967.5 967.5
645.0 645.0
322.5 322.5
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
3,225.0 3,225.0
2,902.5 2,902.5
2,580.0 2,580.0
2,257.5 2,257.5
1,935.0 1,935.0
Phi * Pn (k)
Phi * Pn (k)
1,612.5 1,612.5
1,290.0 1,290.0
967.5 967.5
645.0 645.0
322.5 322.5
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
3,225.0 3,225.0
2,902.5 2,902.5
2,580.0 2,580.0
2,257.5 2,257.5
1,935.0 1,935.0
Phi * Pn (k)
Phi * Pn (k)
1,612.5 1,612.5
1,290.0 1,290.0
967.5 967.5
645.0 645.0
322.5 322.5
ϕ := 0.6 ( 9.3.4 ) γconc := 145 ⋅ pcf cover := 2 ⋅ in Acv := twall⋅ ( lwall − cover)
Vu := 397 ⋅ kips
(
result := if Vu > 2 ⋅ Acv ⋅ fc' ⋅ psi , "Use 2 curtains of reinf." , "Use 1 curtain of reinf." ) ( 21.7.2.2 )
2
As_horiz := 0.2 ⋅ in spacing := 12 ⋅ in < 18" O.K. ( 21.7.2.1 )
n ⋅ As_horiz −3
ρt := max 0.0025 , ρt = 2.778 × 10
twall⋅ spacing
( Horiz. reinforcement ratio )
h h h
α := if ≤ 1.5 , 3 , if > 2 , 2 , 6 − 2⋅ ( 21.7.4.1 )
lwall lwall lwall
ϕVn1 := if
h
> 2 , ϕ⋅ 2⋅( ) (
fc' ⋅ psi + ρt ⋅ fy , ϕ ⋅ α ⋅ )
fc' ⋅ psi + ρt ⋅ fy ϕVn1 = 213.842⋅ psi
lwall
Vu
= 92.412⋅ psi < ϕVn = 213.842 ⋅ psi O.K.
Acv
Therefore, use 12" Con'c w/ #4 @12" O.C Horiz. Rebar @ Each Face
Shear Wall Boundary Elements Detail Requirements
3
twall⋅ lwall Pu Mu lwall
Ag := lwall ⋅ twall Ig := + ⋅ = 213.426⋅ psi 0.2 ⋅ fc' = 800 ⋅ psi
12 Ag Ig 2
Pu Mu lwall
Check1 := if + ⋅ < 0.2 ⋅ fc' , "B.Z.s are not required" , "B.Z.s are required"
Ag Ig 2
.
Code References
Calculations per ACI 318-11, IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : ASCE 7-10
General Information
f'c : Concrete 28 day strength = 4.0 ksi Overall Column Height = 10.0 ft
E= = 3,605.0 ksi End Fixity Top Fixed, Bottom Fixed
Density = 145.0 pcf Brace condition for deflection (buckling) along columns :
= 0.850 X-X (width) axis :
fy - Main Rebar = 60.0 ksi Unbraced Length for X-X Axis buckling = 10.0 ft, K = 1.0
E - Main Rebar = 29,000.0 ksi Y-Y (depth) axis :
Allow. Reinforcing Limits ASTM A615 Bars Used Unbraced Length for X-X Axis buckling = 10.0 ft, K = 1.0
Min. Reinf. = 0.250 %
Max. Reinf. = 8.0 %
Load Combination : ASCE 7-10
..
Column Cross Section
Column Dimensions :360.0in high x 12.0in Wide, Column Edge to Rebar Y
Applied Loads .
Entered loads are factored per load combinations specified by user.
Column self weight included : 43,500.0 lbs * Dead Load Factor
BENDING LOADS . . .
Moment acting about X-X axis, E = 1,691.0, H = 170.0 k-ft
DESIGN SUMMARY .
Load Combination +0.5514D+E+0.90H Maximum SERVICE Load Reactions . .
Location of max.above base 9.933 ft Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k
Maximum Stress Ratio = 0.101 : 1 Top along X-X 13.117 k Bottom along X-X 13.117 k
Ratio = (Pu^2+Mu^2)^.5 / (PhiPn^2+PhiMn^2)^.5
Pu = 23.986 k * Pn = 216.546 k
Maximum SERVICE Load Deflections . . .
Mu-x = 1,747.34 k-ft * Mn-x = 17,645.1 k-ft
Along Y-Y 0.0 in at 0.0 ft above base
Mu-y = 0.0 k-ft * Mn-y = 0.0 k-ft for load combination :
Mu Angle = 180.0 deg Along X-X 0.0in at 0.0 ft above base
Mu at Angle = 1,747.34 k-ft Mn at Angle = 17,262.7 k-ft for load combination :
Pn & Mn values located at Pu-Mu vector intersection with capacity curve
General Section Information . . . = 0.650 = 0.850 = 0.80
Column Capacities . . .
: % Reinforcing 0.4449 % Rebar % Ok
Pnmax : Nominal Max. Compressive Axial Capacity 15,775.9 k
Pnmin : Nominal Min. Tension Axial Capacity -1,153.20 k Reinforcing Area 19.220 in^2
Concrete Area 4,320.0 in^2
Pn, max : Usable Compressive Axial Capacity 8,203.44 k
Pn, min : Usable Tension Axial Capacity -749.58 k
Governing Load Combination Results .
Governing Factored Moment Source Dist. from Axial Load k Bending Analysis k-ft Utilization
Load Combination X-X Y-Y base ft Pu * Pn x x * Mux y y * Muy Alpha (deg) Mu Mn Ratio
+1.40D+1.60H Actual 9.93 60.90 7,315.68 1.000 257.74 180.000 257.74 31,028.59 0.008
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : P74
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
Height = 10.0 ft
#5
#5 M-y Loads
Height = 10.0 ft
###.##kft
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
X #5
#X5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5 Looking along X-X Axis
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
Interaction Diagrams .
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : P74
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,650.0 8,650.0
7,785.0 7,785.0
6,920.0 6,920.0
6,055.0 6,055.0
5,190.0 5,190.0
Phi * Pn (k)
Phi * Pn (k)
4,325.0 4,325.0
3,460.0 3,460.0
2,595.0 2,595.0
1,730.0 1,730.0
865.0 865.0
0.0 5,197.710,395.4
15,593.1
20,790.925,988.6
31,186.3
36,384.041,581.7
46,779.4
51,977.2 0.0 5,197.710,395.4
15,593.1
20,790.925,988.6
31,186.3
36,384.041,581.7
46,779.4
51,977.2
Load Comb. = +1.40D+1.60H, Alpha= 180.0deg, (60.90, 257.74) Load Comb. = +1.20D+0.50Lr+1.60L+1.60H, Alpha= 180.0deg, (52.20, 257.74)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,650.0 8,650.0
7,785.0 7,785.0
6,920.0 6,920.0
6,055.0 6,055.0
5,190.0 5,190.0
Phi * Pn (k)
Phi * Pn (k)
4,325.0 4,325.0
3,460.0 3,460.0
2,595.0 2,595.0
1,730.0 1,730.0
865.0 865.0
0.0 5,197.710,395.4
15,593.1
20,790.925,988.6
31,186.3
36,384.041,581.7
46,779.4
51,977.2 0.0 5,197.710,395.4
15,593.1
20,790.925,988.6
31,186.3
36,384.041,581.7
46,779.4
51,977.2
Load Comb. = +1.20D+1.60Lr+0.50L+1.60H, Alpha= 180.0deg, (52.20, 257.74) Load Comb. = +1.20D+1.60Lr+0.50W+1.60H, Alpha= 180.0deg, (52.20, 257.74)
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : P74
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,650.0 8,650.0
7,785.0 7,785.0
6,920.0 6,920.0
6,055.0 6,055.0
5,190.0 5,190.0
Phi * Pn (k)
Phi * Pn (k)
4,325.0 4,325.0
3,460.0 3,460.0
2,595.0 2,595.0
1,730.0 1,730.0
865.0 865.0
0.0 5,197.710,395.4
15,593.1
20,790.925,988.6
31,186.3
36,384.041,581.7
46,779.4
51,977.2 0.0 5,197.710,395.4
15,593.1
20,790.925,988.6
31,186.3
36,384.041,581.7
46,779.4
51,977.2
Load Comb. = +1.20D+1.60S+0.50W+1.60H, Alpha= 180.0deg, (52.20, 257.74) Load Comb. = +1.20D+0.50Lr+0.50L+W+1.60H, Alpha= 180.0deg, (52.20, 257.74)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
8,650.0
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,650.0
7,785.0 7,785.0
6,920.0 6,920.0
6,055.0 6,055.0
5,190.0 5,190.0
Phi * Pn (k)
Phi * Pn (k)
4,325.0 4,325.0
3,460.0 3,460.0
2,595.0 2,595.0
1,730.0 1,730.0
865.0 865.0
0.0 5,197.710,395.4
15,593.1
20,790.925,988.6
31,186.3
36,384.041,581.7
46,779.4
51,977.2 0.0 5,197.710,395.4
15,593.1
20,790.9
25,988.6
31,186.3
36,384.0
41,581.746,779.4
51,977.2
Load Comb. = +1.549D+0.50L+0.20S+E+1.60H, Alpha= 180.0deg, (67.36, 1,860.10) Load Comb. = +0.90D+W+0.90H, Alpha= 180.0deg, (39.15, 144.98)
Concrete Shear Wall Check ( PO2)
6
fc' := 4000⋅ psi Ec := 57000 ⋅ fc' ⋅ psi Ec = 3.605 × 10 ⋅ psi fy := 60000 ⋅ psi
twall := 12 ⋅ in lwall := 36 ⋅ ft h := 10 ⋅ ft ( height of entire wall or segment of wall considered )
ϕ := 0.6 ( 9.3.4 ) γconc := 145 ⋅ pcf cover := 2 ⋅ in Acv := twall⋅ ( lwall − cover)
Vu := 569 ⋅ kips
(
result := if Vu > 2 ⋅ Acv ⋅ fc' ⋅ psi , "Use 2 curtains of reinf." , "Use 1 curtain of reinf." ) ( 21.7.2.2 )
2
As_horiz := 0.2 ⋅ in spacing := 12 ⋅ in < 18" O.K. ( 21.7.2.1 )
n ⋅ As_horiz −3
ρt := max 0.0025 , ρt = 2.778 × 10
twall⋅ spacing
( Horiz. reinforcement ratio )
h h h
α := if ≤ 1.5 , 3 , if > 2 , 2 , 6 − 2⋅ ( 21.7.4.1 )
lwall lwall lwall
ϕVn1 := if
h
> 2 , ϕ⋅ 2⋅( ) (
fc' ⋅ psi + ρt ⋅ fy , ϕ ⋅ α ⋅ )
fc' ⋅ psi + ρt ⋅ fy ϕVn1 = 213.842⋅ psi
lwall
Vu
= 110.271 ⋅ psi < ϕVn = 213.842 ⋅ psi O.K.
Acv
Therefore, use 12" Con'c w/ #4 @12" O.C Horiz. Rebar @ Each Face
Shear Wall Boundary Elements Detail Requirements
3
twall⋅ lwall Pu Mu lwall
Ag := lwall ⋅ twall Ig := + ⋅ = 474.473⋅ psi 0.2 ⋅ fc' = 800 ⋅ psi
12 Ag Ig 2
Pu Mu lwall
Check1 := if + ⋅ < 0.2 ⋅ fc' , "B.Z.s are not required" , "B.Z.s are required"
Ag Ig 2
.
Code References
Calculations per ACI 318-11, IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : ASCE 7-10
General Information
f'c : Concrete 28 day strength = 4.0 ksi Overall Column Height = 10.0 ft
E= = 3,605.0 ksi End Fixity Top & Bottom Pinned
Density = 145.0 pcf Brace condition for deflection (buckling) along columns :
= 0.850 X-X (width) axis :
fy - Main Rebar = 60.0 ksi Unbraced Length for X-X Axis buckling = 10.0 ft, K = 1.0
E - Main Rebar = 29,000.0 ksi Y-Y (depth) axis :
Allow. Reinforcing Limits ASTM A615 Bars Used Unbraced Length for X-X Axis buckling = 10.0 ft, K = 1.0
Min. Reinf. = 0.250 %
Max. Reinf. = 8.0 %
Load Combination : ASCE 7-10
..
Column Cross Section
Column Dimensions :432.0in high x 12.0in Wide, Column Edge to Rebar Y
Applied Loads .
Entered loads are factored per load combinations specified by user.
Column self weight included : 52,200.0 lbs * Dead Load Factor
BENDING LOADS . . .
Moment acting about X-X axis, E = 2,239.0, H = 65.0 k-ft
DESIGN SUMMARY .
Load Combination +0.5514D+E+0.90H Maximum SERVICE Load Reactions . .
Location of max.above base 9.933 ft Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k
Maximum Stress Ratio = 0.065 : 1 Top along X-X 223.90 k Bottom along X-X 223.90 k
Ratio = (Pu^2+Mu^2)^.5 / (PhiPn^2+PhiMn^2)^.5
Pu = 28.783 k * Pn = 470.226 k
Maximum SERVICE Load Deflections . . .
Mu-x = -2,282.08 k-ft * Mn-x = 35,433.1 k-ft
Along Y-Y -.0000860 in at 5.839 ft above base
Mu-y = 0.0 k-ft * Mn-y = 0.0 k-ft for load combination : E Only
Mu Angle = 180.0 deg Along X-X 0.0in at 0.0 ft above base
Mu at Angle = 2,282.08 k-ft Mn at Angle = 34,897.7 k-ft for load combination :
Pn & Mn values located at Pu-Mu vector intersection with capacity curve
General Section Information . . . = 0.650 = 0.850 = 0.80
Column Capacities . . .
: % Reinforcing 0.6181 % Rebar % Ok
Pnmax : Nominal Max. Compressive Axial Capacity 19,439.1 k
Pnmin : Nominal Min. Tension Axial Capacity -1,922.40 k Reinforcing Area 32.040 in^2
Concrete Area 5,184.0 in^2
Pn, max : Usable Compressive Axial Capacity 10,108.3 k
Pn, min : Usable Tension Axial Capacity -1,249.56 k
Governing Load Combination Results .
Governing Factored Moment Source Dist. from Axial Load k Bending Analysis k-ft Utilization
Load Combination X-X Y-Y base ft Pu * Pn x x * Mux y y * Muy Alpha (deg) Mu Mn Ratio
+1.40D+1.60H Actual 9.93 73.0810,108.31 1.000 -103.30 180.000 103.30 14,311.70 0.007
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PO2
#5
#5
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
Height = 10.0 ft
#6
#6 M-y Loads
Height = 10.0 ft
###.##kft
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
X #6
X
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6 Looking along X-X Axis
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#6
#5
#5
Interaction Diagrams .
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PO2
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
10,650.0 10,650.0
9,585.0 9,585.0
8,520.0 8,520.0
7,455.0 7,455.0
6,390.0 6,390.0
Phi * Pn (k)
Phi * Pn (k)
5,325.0 5,325.0
4,260.0 4,260.0
3,195.0 3,195.0
2,130.0 2,130.0
1,065.0 1,065.0
0.0 7,834.415,668.8
23,503.2
31,337.6
39,172.0
47,006.4
54,840.8
62,675.2
70,509.6
78,344.0 0.0 7,834.415,668.8
23,503.2
31,337.6
39,172.0
47,006.4
54,840.8
62,675.2
70,509.6
78,344.0
Load Comb. = +1.40D+1.60H, Alpha= 180.0deg, (73.08, 103.30) Load Comb. = +1.20D+0.50Lr+1.60L+1.60H, Alpha= 180.0deg, (62.64, 103.30)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
10,650.0 10,650.0
9,585.0 9,585.0
8,520.0 8,520.0
7,455.0 7,455.0
6,390.0 6,390.0
Phi * Pn (k)
Phi * Pn (k)
5,325.0 5,325.0
4,260.0 4,260.0
3,195.0 3,195.0
2,130.0 2,130.0
1,065.0 1,065.0
0.0 7,834.415,668.8
23,503.2
31,337.6
39,172.0
47,006.4
54,840.8
62,675.2
70,509.6
78,344.0 0.0 7,834.415,668.8
23,503.2
31,337.6
39,172.0
47,006.4
54,840.8
62,675.2
70,509.6
78,344.0
Load Comb. = +1.20D+1.60Lr+0.50L+1.60H, Alpha= 180.0deg, (62.64, 103.30) Load Comb. = +1.20D+1.60Lr+0.50W+1.60H, Alpha= 180.0deg, (62.64, 103.30)
File = C:\Users\Jon\Desktop\CONCRE~1.EC6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.10.6, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PO2
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
10,650.0 10,650.0
9,585.0 9,585.0
8,520.0 8,520.0
7,455.0 7,455.0
6,390.0 6,390.0
Phi * Pn (k)
Phi * Pn (k)
5,325.0 5,325.0
4,260.0 4,260.0
3,195.0 3,195.0
2,130.0 2,130.0
1,065.0 1,065.0
0.0 7,834.415,668.8
23,503.2
31,337.6
39,172.0
47,006.4
54,840.8
62,675.2
70,509.6
78,344.0 0.0 7,834.415,668.8
23,503.2
31,337.6
39,172.0
47,006.4
54,840.8
62,675.2
70,509.6
78,344.0
Load Comb. = +1.20D+1.60S+0.50W+1.60H, Alpha= 180.0deg, (62.64, 103.30) Load Comb. = +1.20D+0.50Lr+0.50L+W+1.60H, Alpha= 180.0deg, (62.64, 103.30)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
10,650.0 10,650.0
9,585.0 9,585.0
8,520.0 8,520.0
7,455.0 7,455.0
6,390.0 6,390.0
Phi * Pn (k)
Phi * Pn (k)
5,325.0 5,325.0
4,260.0 4,260.0
3,195.0 3,195.0
2,130.0 2,130.0
1,065.0 1,065.0
0.0 7,834.415,668.8
23,503.2
31,337.6
39,172.0
47,006.4
54,840.8
62,675.2
70,509.6
78,344.0 0.0 7,834.415,668.8
23,503.2
31,337.6
39,172.0
47,006.4
54,840.8
62,675.2
70,509.6
78,344.0
Load Comb. = +1.549D+0.50L+0.20S+E+1.60H, Alpha= 180.0deg, (80.84, 2,327.28) Load Comb. = +0.90D+W+0.90H, Alpha= 180.0deg, (46.98, 58.11)
Concrete Shear Wall Check ( PB5)
6
fc' := 4000⋅ psi Ec := 57000 ⋅ fc' ⋅ psi Ec = 3.605 × 10 ⋅ psi fy := 60000 ⋅ psi
twall := 12 ⋅ in lwall := 17.5 ⋅ ft h := 10 ⋅ ft ( height of entire wall or segment of wall considered )
ϕ := 0.6 ( 9.3.4 ) γconc := 145 ⋅ pcf cover := 2 ⋅ in Acv := twall⋅ ( lwall − cover)
Vu := 70 ⋅ kips
(
result := if Vu > 2 ⋅ Acv ⋅ fc' ⋅ psi , "Use 2 curtains of reinf." , "Use 1 curtain of reinf." ) ( 21.7.2.2 )
2
As_horiz := 0.2 ⋅ in spacing := 12 ⋅ in < 18" O.K. ( 21.7.2.1 )
n ⋅ As_horiz −3
ρt := max 0.0025 , ρt = 2.778 × 10
twall⋅ spacing
( Horiz. reinforcement ratio )
h h h
α := if ≤ 1.5 , 3 , if > 2 , 2 , 6 − 2⋅ ( 21.7.4.1 )
lwall lwall lwall
ϕVn1 := if
h
> 2 , ϕ⋅ 2⋅( ) (
fc' ⋅ psi + ρt ⋅ fy , ϕ ⋅ α ⋅ )
fc' ⋅ psi + ρt ⋅ fy ϕVn1 = 213.842⋅ psi
lwall
Vu
= 28.045 ⋅ psi < ϕVn = 213.842 ⋅ psi O.K.
Acv
Therefore, use 12" Con'c w/ #4 @12" O.C Horiz. Rebar @ Each Face
Shear Wall Boundary Elements Detail Requirements
3
twall⋅ lwall Pu Mu lwall
Ag := lwall ⋅ twall Ig := + ⋅ = 224.989⋅ psi 0.2 ⋅ fc' = 800 ⋅ psi
12 Ag Ig 2
Pu Mu lwall
Check1 := if + ⋅ < 0.2 ⋅ fc' , "B.Z.s are not required" , "B.Z.s are required"
Ag Ig 2
Code References .
Calculations per ACI 318-11, IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : ASCE 7-10
General Information
f'c : Concrete 28 day strength = 4.0 ksi Overall Column Height = 10.0 ft
E= = 3,605.0 ksi End Fixity Top & Bottom Pinned
Density = 145.0 pcf Brace condition for deflection (buckling) along columns :
β = 0.850 X-X (width) axis :
fy - Main Rebar = 60.0 ksi Unbraced Length for X-X Axis buckling = 10.0 ft, K = 1.0
E - Main Rebar = 29,000.0 ksi Y-Y (depth) axis :
Allow. Reinforcing Limits ASTM A615 Bars Used Unbraced Length for X-X Axis buckling = 10.0 ft, K = 1.0
Min. Reinf. = 0.250 %
Max. Reinf. = 8.0 %
Load Combination : ASCE 7-10
..
Column Cross Section
Y
Column Dimensions :210.0in high x 12.0in Wide, Column Edge to Rebar
Edge Cover = 2.0in #5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
Column Reinforcing : 4 - #5 bars @ corners,, 16.0 - #5 bars left & right X #5
X
#5
#5
#5
#5
#5
between corner bars #5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
Y
Applied Loads Entered loads are factored per load combinations specified by user.
.
Governing Factored Moment Source Dist. from Axial Load k Bending Analysis k-ft Utilization
Load Combination
X-X Y-Y base ft Pu ϕ * Pn δ x δ x * Mux δ y δy * Muy Alpha (deg) δ Mu ϕ Mn Ratio
+1.40D+1.60H Actual 9.93 35.53 4,783.82 1.000 -6.36 180.000 6.36 865.10 0.007
Title Block Line 1 Project Title:
You can change this area Engineer: Project ID:
using the "Settings" menu item Project Descr:
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 8 FEB 2016, 9:34PM
File = X:\KNA\15120-10 Virgil Melose\Calculation\concrete shear wall.ec6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.7.30, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PB5
#5#5
#5#5
#5#5
#5#5
#5#5 M-y Loads
Height = 10.0 ft
239.00kft
Interaction Diagrams .
Title Block Line 1 Project Title:
You can change this area Engineer: Project ID:
using the "Settings" menu item Project Descr:
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 8 FEB 2016, 9:34PM
File = X:\KNA\15120-10 Virgil Melose\Calculation\concrete shear wall.ec6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.7.30, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PB5
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
5,050.0
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
5,050.0
4,545.0 4,545.0
4,040.0 4,040.0
3,535.0 3,535.0
3,030.0 3,030.0
Phi * Pn (k)
Phi * Pn (k)
2,525.0 2,525.0
2,020.0 2,020.0
1,515.0 1,515.0
1,010.0 1,010.0
505.0 505.0
0.0 1,766.43,532.85,299.37,065.78,832.110,598.5
12,364.9
14,131.4
15,897.8
17,664.2 0.0 1,766.43,532.85,299.37,065.78,832.110,598.5
12,364.9
14,131.4
15,897.8
17,664.2
Load Comb. = +1.40D+1.60H, Alpha= 180.0deg, (35.53, 6.36) Load Comb. = +1.20D+0.50Lr+1.60L+1.60H, Alpha= 180.0deg, (30.45, 6.36)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
5,050.0 5,050.0
4,545.0 4,545.0
4,040.0 4,040.0
3,535.0 3,535.0
3,030.0 3,030.0
Phi * Pn (k)
Phi * Pn (k)
2,525.0 2,525.0
2,020.0 2,020.0
1,515.0 1,515.0
1,010.0 1,010.0
505.0 505.0
0.0 1,766.43,532.85,299.37,065.78,832.110,598.5
12,364.9
14,131.4
15,897.8
17,664.2 0.0 1,766.43,532.85,299.37,065.78,832.110,598.5
12,364.9
14,131.4
15,897.8
17,664.2
Load Comb. = +1.20D+1.60Lr+0.50L+1.60H, Alpha= 180.0deg, (30.45, 6.36) Load Comb. = +1.20D+1.60Lr+0.50W+1.60H, Alpha= 180.0deg, (30.45, 6.36)
Title Block Line 1 Project Title:
You can change this area Engineer: Project ID:
using the "Settings" menu item Project Descr:
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 8 FEB 2016, 9:34PM
File = X:\KNA\15120-10 Virgil Melose\Calculation\concrete shear wall.ec6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.7.30, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PB5
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
5,050.0 5,050.0
4,545.0 4,545.0
4,040.0 4,040.0
3,535.0 3,535.0
3,030.0 3,030.0
Phi * Pn (k)
Phi * Pn (k)
2,525.0 2,525.0
2,020.0 2,020.0
1,515.0 1,515.0
1,010.0 1,010.0
505.0 505.0
0.0 1,766.43,532.85,299.37,065.78,832.110,598.5
12,364.9
14,131.4
15,897.8
17,664.2 0.0 1,766.43,532.85,299.37,065.78,832.110,598.5
12,364.9
14,131.4
15,897.8
17,664.2
Load Comb. = +1.20D+1.60S+0.50W+1.60H, Alpha= 180.0deg, (30.45, 6.36) Load Comb. = +1.20D+0.50Lr+0.50L+W+1.60H, Alpha= 180.0deg, (30.45, 6.36)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
5,050.0 5,050.0
4,545.0 4,545.0
4,040.0 4,040.0
3,535.0 3,535.0
3,030.0 3,030.0
Phi * Pn (k)
Phi * Pn (k)
2,525.0 2,525.0
2,020.0 2,020.0
1,515.0 1,515.0
1,010.0 1,010.0
505.0 505.0
0.0 1,766.43,532.85,299.37,065.78,832.110,598.5
12,364.9
14,131.4
15,897.8
17,664.2 0.0 1,766.43,532.85,299.37,065.78,832.110,598.5
12,364.9
14,131.4
15,897.8
17,664.2
Load Comb. = +1.549D+0.50L+0.20S+E+1.60H, Alpha= 180.0deg, (39.30, 239.78) Load Comb. = +0.90D+W+0.90H, Alpha= 180.0deg, (22.84, 3.58)
Concrete Shear Wall Check ( PA2)
6
fc' := 4000⋅ psi Ec := 57000 ⋅ fc' ⋅ psi Ec = 3.605 × 10 ⋅ psi fy := 60000 ⋅ psi
twall := 14 ⋅ in lwall := 10.15 ⋅ ft h := 10 ⋅ ft ( height of entire wall or segment of wall considered )
ϕ := 0.6 ( 9.3.4 ) γconc := 145 ⋅ pcf cover := 2 ⋅ in Acv := twall⋅ ( lwall − cover)
Vu := 30 ⋅ kips
(
result := if Vu > 2 ⋅ Acv ⋅ fc' ⋅ psi , "Use 2 curtains of reinf." , "Use 1 curtain of reinf." ) ( 21.7.2.2 )
2
As_horiz := 0.2 ⋅ in spacing := 12 ⋅ in < 18" O.K. ( 21.7.2.1 )
n ⋅ As_horiz −3
ρt := max 0.0025 , ρt = 2.5 × 10
twall⋅ spacing
( Horiz. reinforcement ratio )
h h h
α := if ≤ 1.5 , 3 , if > 2 , 2 , 6 − 2⋅ ( 21.7.4.1 )
lwall lwall lwall
ϕVn1 := if
h
> 2 , ϕ⋅ 2⋅( ) (
fc' ⋅ psi + ρt ⋅ fy , ϕ ⋅ α ⋅ )
fc' ⋅ psi + ρt ⋅ fy ϕVn1 = 203.842⋅ psi
lwall
Vu
= 17.887⋅ psi < ϕVn = 203.842⋅ psi O.K.
Acv
Therefore, use 14" Con'c w/ #4 @12" O.C Horiz. Rebar @ Each Face
Shear Wall Boundary Elements Detail Requirements
3
twall⋅ lwall Pu Mu lwall
Ag := lwall ⋅ twall Ig := + ⋅ = 249.865⋅ psi 0.2 ⋅ fc' = 800 ⋅ psi
12 Ag Ig 2
Pu Mu lwall
Check1 := if + ⋅ < 0.2 ⋅ fc' , "B.Z.s are not required" , "B.Z.s are required"
Ag Ig 2
Code References .
Calculations per ACI 318-11, IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : ASCE 7-10
General Information
f'c : Concrete 28 day strength = 4.0 ksi Overall Column Height = 10.0 ft
E= = 3,605.0 ksi End Fixity Top & Bottom Pinned
Density = 145.0 pcf Brace condition for deflection (buckling) along columns :
β = 0.850 X-X (width) axis :
fy - Main Rebar = 60.0 ksi Unbraced Length for X-X Axis buckling = 10.0 ft, K = 1.0
E - Main Rebar = 29,000.0 ksi Y-Y (depth) axis :
Allow. Reinforcing Limits ASTM A615 Bars Used Unbraced Length for X-X Axis buckling = 10.0 ft, K = 1.0
Min. Reinf. = 0.250 %
Max. Reinf. = 8.0 %
Load Combination : ASCE 7-10
..
Column Cross Section
Y
Column Dimensions :122.0in high x 12.0in Wide, Column Edge to Rebar
Edge Cover = 2.0in #5#5
#5#5
#5#5
#5#5
#5#5
Column Reinforcing : 4 - #5 bars @ corners,, 9.0 - #5 bars left & right X #5#5
X
Applied Loads Entered loads are factored per load combinations specified by user.
.
Governing Factored Moment Source Dist. from Axial Load k Bending Analysis k-ft Utilization
Load Combination
X-X Y-Y base ft Pu ϕ * Pn δ x δ x * Mux δ y δy * Muy Alpha (deg) δ Mu ϕ Mn Ratio
+1.40D+1.60H Actual 9.93 20.64 2,789.08 1.000 -4.77 180.000 4.77 654.39 0.007
Title Block Line 1 Project Title:
You can change this area Engineer: Project ID:
using the "Settings" menu item Project Descr:
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 8 FEB 2016, 9:34PM
File = X:\KNA\15120-10 Virgil Melose\Calculation\concrete shear wall.ec6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.7.30, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PA2
#5 #5
#5 #5
M-y Loads 307.00kft
#5 #5
Height = 10.0 ft
#5 #5 Height = 10.0 ft
#5 #5
X X
#5 #5
#5 #5
#5 #5
Looking along X-X Axis
#5 #5
#5 #5
#5 #5
Interaction Diagrams .
Title Block Line 1 Project Title:
You can change this area Engineer: Project ID:
using the "Settings" menu item Project Descr:
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 8 FEB 2016, 9:34PM
File = X:\KNA\15120-10 Virgil Melose\Calculation\concrete shear wall.ec6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.7.30, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : PA2
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
2,975.0 2,975.0
2,677.5 2,677.5
2,380.0 2,380.0
2,082.5 2,082.5
1,785.0 1,785.0
Phi * Pn (k)
Phi * Pn (k)
1,487.5 1,487.5
1,190.0 1,190.0
892.5 892.5
595.0 595.0
297.5 297.5
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
2,975.0 2,975.0
2,677.5 2,677.5
2,380.0 2,380.0
2,082.5 2,082.5
1,785.0 1,785.0
Phi * Pn (k)
Phi * Pn (k)
1,487.5 1,487.5
1,190.0 1,190.0
892.5 892.5
595.0 595.0
297.5 297.5
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
2,975.0 2,975.0
2,677.5 2,677.5
2,380.0 2,380.0
2,082.5 2,082.5
1,785.0 1,785.0
Phi * Pn (k)
Phi * Pn (k)
1,487.5 1,487.5
1,190.0 1,190.0
892.5 892.5
595.0 595.0
297.5 297.5
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
2,975.0 2,975.0
2,677.5 2,677.5
2,380.0 2,380.0
2,082.5 2,082.5
1,785.0 1,785.0
Phi * Pn (k)
Phi * Pn (k)
1,487.5 1,487.5
1,190.0 1,190.0
892.5 892.5
595.0 595.0
297.5 297.5
ϕ := 0.6 ( 9.3.4 ) γconc := 145 ⋅ pcf cover := 2 ⋅ in Acv := twall⋅ ( lwall − cover)
Vu := 728 ⋅ kips
(
result := if Vu > 2 ⋅ Acv ⋅ fc' ⋅ psi , "Use 2 curtains of reinf." , "Use 1 curtain of reinf." ) ( 21.7.2.2 )
2
As_horiz := 0.2 ⋅ in spacing := 12 ⋅ in < 18" O.K. ( 21.7.2.1 )
n ⋅ As_horiz −3
ρt := max 0.0025 , ρt = 2.778 × 10
twall⋅ spacing
( Horiz. reinforcement ratio )
h h h
α := if ≤ 1.5 , 3 , if > 2 , 2 , 6 − 2⋅ ( 21.7.4.1 )
lwall lwall lwall
ϕVn1 := if
h
> 2 , ϕ⋅ 2⋅( ) (
fc' ⋅ psi + ρt ⋅ fy , ϕ ⋅ α ⋅ )
fc' ⋅ psi + ρt ⋅ fy ϕVn1 = 213.842⋅ psi
lwall
Vu
= 158.813 ⋅ psi < ϕVn = 213.842 ⋅ psi O.K.
Acv
Therefore, use 14" Con'c w/ #4 @12" O.C Horiz. Rebar @ Each Face
Shear Wall Boundary Elements Detail Requirements
3
twall⋅ lwall Pu Mu lwall
Ag := lwall ⋅ twall Ig := + ⋅ = 210.327⋅ psi 0.2 ⋅ fc' = 800 ⋅ psi
12 Ag Ig 2
Pu Mu lwall
Check1 := if + ⋅ < 0.2 ⋅ fc' , "B.Z.s are not required" , "B.Z.s are required"
Ag Ig 2
.
Code References
Calculations per ACI 318-11, IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : ASCE 7-10
General Information
f'c : Concrete 28 day strength = 4.0 ksi Overall Column Height = 11.0 ft
E= = 3,605.0 ksi End Fixity Top & Bottom Pinned
Density = 145.0 pcf Brace condition for deflection (buckling) along columns :
= 0.850 X-X (width) axis :
fy - Main Rebar = 60.0 ksi Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
E - Main Rebar = 29,000.0 ksi Y-Y (depth) axis :
Allow. Reinforcing Limits ASTM A615 Bars Used Unbraced Length for X-X Axis buckling = 11.0 ft, K = 1.0
Min. Reinf. = 0.250 %
Max. Reinf. = 8.0 %
Load Combination : ASCE 7-10
..
Column Cross Section
Column Dimensions :384.0in high x 12.0in Wide, Column Edge to Rebar Y
Applied Loads .
Entered loads are factored per load combinations specified by user.
Column self weight included : 51,040.0 lbs * Dead Load Factor
BENDING LOADS . . .
Moment acting about X-X axis, E = 1,716.0, H = 25.0 k-ft
DESIGN SUMMARY .
Load Combination +0.5514D+E+0.90H Maximum SERVICE Load Reactions . .
Location of max.above base 10.926 ft Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k
Maximum Stress Ratio = 0.081 : 1 Top along X-X 156.0 k Bottom along X-X 156.0 k
Ratio = (Pu^2+Mu^2)^.5 / (PhiPn^2+PhiMn^2)^.5
Pu = 28.143 k * Pn = 363.184 k
Maximum SERVICE Load Deflections . . .
Mu-x = -1,738.50 k-ft * Mn-x = 21,776.2 k-ft
Along Y-Y -0.000114 in at 6.423 ft above base
Mu-y = 0.0 k-ft * Mn-y = 0.0 k-ft for load combination : E Only
Mu Angle = 180.0 deg Along X-X 0.0in at 0.0 ft above base
Mu at Angle = 1,738.50 k-ft Mn at Angle = 21,352.1 k-ft for load combination :
Pn & Mn values located at Pu-Mu vector intersection with capacity curve
General Section Information . . . = 0.650 = 0.850 = 0.80
Column Capacities . . .
: % Reinforcing 0.4440 % Rebar % Ok
Pnmax : Nominal Max. Compressive Axial Capacity 16,825.2 k
Pnmin : Nominal Min. Tension Axial Capacity -1,227.60 k Reinforcing Area 20.460 in^2
Concrete Area 4,608.0 in^2
Pn, max : Usable Compressive Axial Capacity 8,749.12 k
Pn, min : Usable Tension Axial Capacity -797.94 k
Governing Load Combination Results .
Governing Factored Moment Source Dist. from Axial Load k Bending Analysis k-ft Utilization
Load Combination X-X Y-Y base ft Pu * Pn x x * Mux y y * Muy Alpha (deg) Mu Mn Ratio
+1.40D+1.60H Actual 10.93 71.46 8,749.12 1.000 -40.00 180.000 40.00 5,029.74 0.008
Title Block Line 1 Project Title:
You can change this area Engineer: Project ID:
using the "Settings" menu item Project Descr:
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 8 FEB 2016, 9:28PM
File = X:\KNA\15120-10 Virgil Melose\Calculation\concrete shear wall.ec6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.7.30, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : P71
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
Height = 11.0 ft
#5
#5 M-y Loads
Height = 11.0 ft
###.##kft
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
X #5
#X5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5 Looking along X-X Axis
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
Interaction Diagrams .
Title Block Line 1 Project Title:
You can change this area Engineer: Project ID:
using the "Settings" menu item Project Descr:
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 8 FEB 2016, 9:28PM
File = X:\KNA\15120-10 Virgil Melose\Calculation\concrete shear wall.ec6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.7.30, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : P71
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
9,225.0 9,225.0
8,302.5 8,302.5
7,380.0 7,380.0
6,457.5 6,457.5
5,535.0 5,535.0
Phi * Pn (k)
Phi * Pn (k)
4,612.5 4,612.5
3,690.0 3,690.0
2,767.5 2,767.5
1,845.0 1,845.0
922.5 922.5
0.0 5,912.611,825.1
17,737.7
23,650.2
29,562.8
35,475.4
41,387.9
47,300.5
53,213.0
59,125.6 0.0 5,912.611,825.1
17,737.7
23,650.2
29,562.8
35,475.4
41,387.9
47,300.5
53,213.0
59,125.6
Load Comb. = +1.40D+1.60H, Alpha= 180.0deg, (71.46, 40.00) Load Comb. = +1.20D+0.50Lr+1.60L+1.60H, Alpha= 180.0deg, (61.25, 40.00)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
9,225.0 9,225.0
8,302.5 8,302.5
7,380.0 7,380.0
6,457.5 6,457.5
5,535.0 5,535.0
Phi * Pn (k)
Phi * Pn (k)
4,612.5 4,612.5
3,690.0 3,690.0
2,767.5 2,767.5
1,845.0 1,845.0
922.5 922.5
0.0 5,912.611,825.1
17,737.7
23,650.2
29,562.8
35,475.4
41,387.9
47,300.5
53,213.0
59,125.6 0.0 5,912.611,825.1
17,737.7
23,650.2
29,562.8
35,475.4
41,387.9
47,300.5
53,213.0
59,125.6
Load Comb. = +1.20D+1.60Lr+0.50L+1.60H, Alpha= 180.0deg, (61.25, 40.00) Load Comb. = +1.20D+1.60Lr+0.50W+1.60H, Alpha= 180.0deg, (61.25, 40.00)
Title Block Line 1 Project Title:
You can change this area Engineer: Project ID:
using the "Settings" menu item Project Descr:
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 8 FEB 2016, 9:28PM
File = X:\KNA\15120-10 Virgil Melose\Calculation\concrete shear wall.ec6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.7.30, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : P71
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
9,225.0 9,225.0
8,302.5 8,302.5
7,380.0 7,380.0
6,457.5 6,457.5
5,535.0 5,535.0
Phi * Pn (k)
Phi * Pn (k)
4,612.5 4,612.5
3,690.0 3,690.0
2,767.5 2,767.5
1,845.0 1,845.0
922.5 922.5
0.0 5,912.611,825.1
17,737.7
23,650.2
29,562.8
35,475.4
41,387.9
47,300.5
53,213.0
59,125.6 0.0 5,912.611,825.1
17,737.7
23,650.2
29,562.8
35,475.4
41,387.9
47,300.5
53,213.0
59,125.6
Load Comb. = +1.20D+1.60S+0.50W+1.60H, Alpha= 180.0deg, (61.25, 40.00) Load Comb. = +1.20D+0.50Lr+0.50L+W+1.60H, Alpha= 180.0deg, (61.25, 40.00)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
9,225.0 9,225.0
8,302.5 8,302.5
7,380.0 7,380.0
6,457.5 6,457.5
5,535.0 5,535.0
Phi * Pn (k)
Phi * Pn (k)
4,612.5 4,612.5
3,690.0 3,690.0
2,767.5 2,767.5
1,845.0 1,845.0
922.5 922.5
0.0 5,912.611,825.1
17,737.7
23,650.2
29,562.8
35,475.4
41,387.9
47,300.5
53,213.0
59,125.6 0.0 5,912.611,825.1
17,737.7
23,650.2
29,562.8
35,475.4
41,387.9
47,300.5
53,213.0
59,125.6
Load Comb. = +1.549D+0.50L+0.20S+E+1.60H, Alpha= 180.0deg, (79.04, 1,756.00) Load Comb. = +0.90D+W+0.90H, Alpha= 180.0deg, (45.94, 22.50)
Concrete Shear Wall Check ( P73)
6
fc' := 4000⋅ psi Ec := 57000 ⋅ fc' ⋅ psi Ec = 3.605 × 10 ⋅ psi fy := 60000 ⋅ psi
twall := 12 ⋅ in lwall := 28 ⋅ ft h := 10 ⋅ ft ( height of entire wall or segment of wall considered )
ϕ := 0.6 ( 9.3.4 ) γconc := 145 ⋅ pcf cover := 2 ⋅ in Acv := twall⋅ ( lwall − cover)
Vu := 202 ⋅ kips
(
result := if Vu > 2 ⋅ Acv ⋅ fc' ⋅ psi , "Use 2 curtains of reinf." , "Use 1 curtain of reinf." ) ( 21.7.2.2 )
2
As_horiz := 0.2 ⋅ in spacing := 12 ⋅ in < 18" O.K. ( 21.7.2.1 )
n ⋅ As_horiz −3
ρt := max 0.0025 , ρt = 2.778 × 10
twall⋅ spacing
( Horiz. reinforcement ratio )
h h h
α := if ≤ 1.5 , 3 , if > 2 , 2 , 6 − 2⋅ ( 21.7.4.1 )
lwall lwall lwall
ϕVn1 := if
h
> 2 , ϕ⋅ 2⋅( ) (
fc' ⋅ psi + ρt ⋅ fy , ϕ ⋅ α ⋅ )
fc' ⋅ psi + ρt ⋅ fy ϕVn1 = 213.842⋅ psi
lwall
Vu
= 50.399 ⋅ psi < ϕVn = 213.842 ⋅ psi O.K.
Acv
Therefore, use 14" Con'c w/ #4 @12" O.C Horiz. Rebar @ Each Face
Shear Wall Boundary Elements Detail Requirements
3
twall⋅ lwall Pu Mu lwall
Ag := lwall ⋅ twall Ig := + ⋅ = 293.739⋅ psi 0.2 ⋅ fc' = 800 ⋅ psi
12 Ag Ig 2
Pu Mu lwall
Check1 := if + ⋅ < 0.2 ⋅ fc' , "B.Z.s are not required" , "B.Z.s are required"
Ag Ig 2
.
Code References
Calculations per ACI 318-11, IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : ASCE 7-10
General Information
f'c : Concrete 28 day strength = 4.0 ksi Overall Column Height = 10.0 ft
E= = 3,605.0 ksi End Fixity Top & Bottom Pinned
Density = 145.0 pcf Brace condition for deflection (buckling) along columns :
= 0.850 X-X (width) axis :
fy - Main Rebar = 60.0 ksi Unbraced Length for X-X Axis buckling = 10.0 ft, K = 1.0
E - Main Rebar = 29,000.0 ksi Y-Y (depth) axis :
Allow. Reinforcing Limits ASTM A615 Bars Used Unbraced Length for X-X Axis buckling = 10.0 ft, K = 1.0
Min. Reinf. = 0.250 %
Max. Reinf. = 8.0 %
Load Combination : ASCE 7-10
..
Column Cross Section
Column Dimensions :336.0in high x 12.0in Wide, Column Edge to Rebar Y
Applied Loads .
Entered loads are factored per load combinations specified by user.
Column self weight included : 40,600.0 lbs * Dead Load Factor
BENDING LOADS . . .
Moment acting about X-X axis, E = 2,545.0, H = 228.0 k-ft
DESIGN SUMMARY .
Load Combination +0.5514D+E+0.90H Maximum SERVICE Load Reactions . .
Location of max.above base 9.933 ft Top along Y-Y 0.0 k Bottom along Y-Y 0.0 k
Maximum Stress Ratio = 0.190 : 1 Top along X-X 254.50 k Bottom along X-X 254.50 k
Ratio = (Pu^2+Mu^2)^.5 / (PhiPn^2+PhiMn^2)^.5
Pu = 22.387 k * Pn = 142.880 k
Maximum SERVICE Load Deflections . . .
Mu-x = -2,731.74 k-ft * Mn-x = 14,710.7 k-ft
Along Y-Y -0.000208 in at 5.839 ft above base
Mu-y = 0.0 k-ft * Mn-y = 0.0 k-ft for load combination : E Only
Mu Angle = 180.0 deg Along X-X 0.0in at 0.0 ft above base
Mu at Angle = 2,731.74 k-ft Mn at Angle = 14,375.1 k-ft for load combination :
Pn & Mn values located at Pu-Mu vector intersection with capacity curve
General Section Information . . . = 0.650 = 0.850 = 0.80
Column Capacities . . .
: % Reinforcing 0.4459 % Rebar % Ok
Pnmax : Nominal Max. Compressive Axial Capacity 14,726.5 k
Pnmin : Nominal Min. Tension Axial Capacity -1,078.80 k Reinforcing Area 17.980 in^2
Concrete Area 4,032.0 in^2
Pn, max : Usable Compressive Axial Capacity 7,657.76 k
Pn, min : Usable Tension Axial Capacity -701.22 k
Governing Load Combination Results .
Governing Factored Moment Source Dist. from Axial Load k Bending Analysis k-ft Utilization
Load Combination X-X Y-Y base ft Pu * Pn x x * Mux y y * Muy Alpha (deg) Mu Mn Ratio
+1.40D+1.60H Actual 9.93 56.84 5,301.98 1.000 -362.35 180.000 362.35 33,655.92 0.011
Title Block Line 1 Project Title:
You can change this area Engineer: Project ID:
using the "Settings" menu item Project Descr:
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 8 FEB 2016, 9:24PM
File = X:\KNA\15120-10 Virgil Melose\Calculation\concrete shear wall.ec6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.7.30, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : P73
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
Height = 10.0 ft
#5
#5 M-y Loads ###.##kft
#5
#5 Height = 10.0 ft
#5
#5
#5
#5
#5
#5
X #5
#X5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5 Looking along X-X Axis
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
#5
Interaction Diagrams .
Title Block Line 1 Project Title:
You can change this area Engineer: Project ID:
using the "Settings" menu item Project Descr:
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 8 FEB 2016, 9:24PM
File = X:\KNA\15120-10 Virgil Melose\Calculation\concrete shear wall.ec6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.7.30, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : P73
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,075.0 8,075.0
7,267.5 7,267.5
6,460.0 6,460.0
5,652.5 5,652.5
4,845.0 4,845.0
Phi * Pn (k)
Phi * Pn (k)
4,037.5 4,037.5
3,230.0 3,230.0
2,422.5 2,422.5
1,615.0 1,615.0
807.5 807.5
0.0 4,529.39,058.513,587.8
18,117.0
22,646.3
27,175.5
31,704.8
36,234.0
40,763.3
45,292.5 0.0 4,529.39,058.513,587.8
18,117.0
22,646.3
27,175.5
31,704.8
36,234.0
40,763.3
45,292.5
Load Comb. = +1.40D+1.60H, Alpha= 180.0deg, (56.84, 362.35) Load Comb. = +1.20D+0.50Lr+1.60L+1.60H, Alpha= 180.0deg, (48.72, 362.35)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,075.0 8,075.0
7,267.5 7,267.5
6,460.0 6,460.0
5,652.5 5,652.5
4,845.0 4,845.0
Phi * Pn (k)
Phi * Pn (k)
4,037.5 4,037.5
3,230.0 3,230.0
2,422.5 2,422.5
1,615.0 1,615.0
807.5 807.5
0.0 4,529.39,058.513,587.8
18,117.0
22,646.3
27,175.5
31,704.8
36,234.0
40,763.3
45,292.5 0.0 4,529.39,058.513,587.8
18,117.0
22,646.3
27,175.5
31,704.8
36,234.0
40,763.3
45,292.5
Load Comb. = +1.20D+1.60Lr+0.50L+1.60H, Alpha= 180.0deg, (48.72, 362.35) Load Comb. = +1.20D+1.60Lr+0.50W+1.60H, Alpha= 180.0deg, (48.72, 362.35)
Title Block Line 1 Project Title:
You can change this area Engineer: Project ID:
using the "Settings" menu item Project Descr:
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 8 FEB 2016, 9:24PM
File = X:\KNA\15120-10 Virgil Melose\Calculation\concrete shear wall.ec6
Concrete Column ENERCALC, INC. 1983-2015, Build:6.15.7.30, Ver:6.14.12.31
Lic. # : KW-06010316 Licensee : Kim and Associates, Structural Engineers
Description : P73
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,075.0 8,075.0
7,267.5 7,267.5
6,460.0 6,460.0
5,652.5 5,652.5
4,845.0 4,845.0
Phi * Pn (k)
Phi * Pn (k)
4,037.5 4,037.5
3,230.0 3,230.0
2,422.5 2,422.5
1,615.0 1,615.0
807.5 807.5
0.0 4,529.39,058.513,587.8
18,117.0
22,646.3
27,175.5
31,704.8
36,234.0
40,763.3
45,292.5 0.0 4,529.39,058.513,587.8
18,117.0
22,646.3
27,175.5
31,704.8
36,234.0
40,763.3
45,292.5
Load Comb. = +1.20D+1.60S+0.50W+1.60H, Alpha= 180.0deg, (48.72, 362.35) Load Comb. = +1.20D+0.50Lr+0.50L+W+1.60H, Alpha= 180.0deg, (48.72, 362.35)
Concrete Column P-M Interaction Diagram Concrete Column P-M Interaction Diagram
Phi * Mn @ Alpha (k-ft) Phi * Mn @ Alpha (k-ft)
8,075.0 8,075.0
7,267.5 7,267.5
6,460.0 6,460.0
5,652.5 5,652.5
4,845.0 4,845.0
Phi * Pn (k)
Phi * Pn (k)
4,037.5 4,037.5
3,230.0 3,230.0
2,422.5 2,422.5
1,615.0 1,615.0
807.5 807.5
0.0 4,529.39,058.513,587.8
18,117.0
22,646.3
27,175.5
31,704.8
36,234.0
40,763.3
45,292.5 0.0 4,529.39,058.513,587.8
18,117.0
22,646.3
27,175.5
31,704.8
36,234.0
40,763.3
45,292.5
Load Comb. = +1.549D+0.50L+0.20S+E+1.60H, Alpha= 180.0deg, (62.87, 2,890.27) Load Comb. = +0.90D+W+0.90H, Alpha= 180.0deg, (36.54, 203.82)