BMS BOQ

SL NO DESCRIPTION OF WORK QTY UNIT SUPPLY INR INSTALLATION INR


RATE AMOUNT RATE AMOUNT

Supply, Installation, Testing and Commissioning of the following items with 2


Years Warranty
1

HMI
HMI display of 4.3" LCD Touch screen display, Panel mounting, with RS232 No.
Connection, Local supervisory port, USB, Backlight of LED with Autodim,
requires 24VAC/DC, operating temperature of 0°C to 45°C, with HMI Software
to view and adjust operating times, monitor alarms, to display and control the
parameters and display graphs of logged data, security settings, power failure
protection. The Display shall be IP50 rating when panel mounted with all other
mounting accessories complete as required.
1.1 1

AHU
DDC
2
a DDC controller supporting TCP/IP over Ethernet protocol or BACnet IP Nos
protocol and I/O's designed as per the IO Summary with necessary expansion
IO module and VFD Integration modules and BTU Meter integration with all
other mounting accessories complete as required.
1

2.1 Control Panel


a Control Panel of IP64 protection standard for mounting the DDC with Base Nos
Plate, Cable Truf, Glands for Cable Entry, transformer, relays, Fan, MCB's,
Switches with all other mounting accessories complete as required.
1

b Exposed Area - IP 64
Non Exposed Area - IP22

3 Third Party Systems Integration


Supply, Installation, Testing & Commissioning of Gateway/Router/Converter for Lot
Integration of the following third party systems supporting multi protocols like
BACnet, Modbus, Lonworks, JBUS, RS232, RS485 etc with all other mounting 1
accessories complete as required.

a VFD
b BTU meter

Field Devices
4
Immersion Temperature sensor
Supply, Installation (In co ordination with HVAC Contractor), Testing &
Commissioning of Immersion type temperature sensor with Thermo well and
all other accessories. Temperature sensor shall be Pt1000 RTD type/
Thermistor with 0 to 10v or 4 to 20mA transmitter, NPT Compression/Spring
compression fitting, Stainless steel/Brass Thermowell, Polycarbonate/Impact
resistant ABS Housing, IP66/67 rating. The measurement range shall be -10oC
to +110oC with all other mounting accessories complete as required.
4.1

4.1.1 Chilled Water Inlet pipe line Nos


1
4.1.2 Chilled Water Outlet pipe line Nos
1
4.2 Differential Pressure Switch for Filter
a Supply, Installation, Testing & Commissioning of Filter DPS with all the Nos
mounting accessories included. The DPS shall be with Silicone diaphragm,
Compatible to Air, non-combustible, non-aggressive gases, SPDT switch type,
maximum operating temperature range shall be -20 to 85°C, maximum
operating pressure shall be 10Kpa. IP54 rating. The maximum pr limit shall be
20-300Pa as technical specification with all other mounting accessories
complete as required.
1

Differential Pressure Switch for Fan


4.3
a Supply, Installation, Testing & Commissioning of Filter DPS with all the Nos
mounting accessories included. The DPS shall be with Silicone diaphragm,
Compatible to Air, non-combustible, non-aggressive gases, SPDT switch type,
maximum operating temperature range shall be -20 to 85°C, maximum
operating pressure shall be 10Kpa. IP54 rating. The maximum pr limit shall be
20-300Pa as technical specification with all other mounting accessories
complete as required.
1

4.4 Duct Static pressure sensor


a Supply, Installation, Testing & Commissioning of Static pressure sensor with all Nos
the mounting accessories included. The sensor shall be Magnetic
sensing/Piezo-resistive pressure transducer, Compatible to
air,non-combustible, non-aggressive gases, Stability +/- 1% or 2.5% FS/Year ,
Temperature limits shall be -18 to 50°C, 40kpa burst pressure, the output shall
be 0 to 10v or 4 to 20mA transmitter, ABS/POM housing material, IP54/66
rating. The maximum pr limit shall be 0-500Pa all other mounting accessories
complete as required.
1

4.5 Supply air Temperature & RH Sensor


a Supply, Installation, Testing & Commissioning of Supply Air Temperature & RH Nos
sensor with all the mounting accessories included. The sensor shall be Pt1000
RTD type/thermistor for temperature measurement with 0 to 10VDC or 4-20mA
transmitters. The temperature measurement range shall be 0oC to 40oC,
accuracy ±0.2 °C . RH sensor shall be Capacitance type and measurement
range 0-100%RH,accuracy ±2 %RH, Drift <1% RH/Year. The sensor shall be
Polycarbonate/Impact resistance ABS housing, IP65/66 rating.

4.6 Room Temperature & RH Sensor


a Supply, Installation, Testing & Commissioning of Room Temperature & RH Nos
sensor with all the mounting accessories included. The sensor shall be Pt1000
RTD type/thermistor for temperature measurement with 0 to 10VDC or 4-20mA
transmitters. The temperature measurement range shall be 0°C to 40°C,
accuracy ±0.4 °C . RH sensor shall be Capacitance type and measurement
range 0-100%RH,accuracy ±2 %RH, Drift <1% RH/Year. The sensor shall be
Polycarbonate/Impact resistance ABS housing, IP20 rating.
1

4.7 Air Flow measuring Station


a Supply, Installation, Testing & Commissioning of Air Flow measuring Station @ Nos
Fresh Air Duct (1000X350mm) with 0 to 10v or 4 20mA transmitters,
Rectangular configuration, Galvanized steel casing, Anadized aluminium flow
sensors, 100 to 10,000FPM,accuracy ±2%,IP65 rating with all the mounting
accessories included.
1

b Supply, Installation, Testing & Commissioning of Air Flow Station @ Supply Air Nos
Duct (1500X450mm) with 0 to 10v or 4 20mA transmitters,Rectangular
configuration, Galvanized steel casing, Anadized aluminium flow sensors, 100
to 10,000FPM,accuracy ±2%,IP65 rating with all the mounting accessories
included.
1

BTU Meter
4.8
a Supply, Installation, Testing & Commissioning of Clamp on BTU meter with less Nos
than 2% accuracy on any flow with RS485/Modbus RTU/M-Bus communication
for BMS integration. The BTU meter shall be for 50mm dia pipe/6mm
thickness/ms
1

5 Network switch
a Network switch with all other mounting accessories complete as required Nos
1

6 Cable & Conducting


a Supply, Laying, Termination of ISI Certified 2 Core 1.5 sq.mm ATC, PVC Mtr
insulated, armored, Tinned Copper, twisted, shielded, PE insulated, Cable with
proper ferrules, lugs and other necessary accessories. The spec shall meet the
system manufacturer specifications
300

b Supply, Laying, Termination of ISI Certified 3 Core 1.0 sq.mm ATC, PVC Mtr
insulated, armored, Tinned Copper, twisted, shielded, PE insulated, Cable with
proper ferrules, lugs and other necessary accessories. The spec shall meet the
system manufacturer specifications 150

c Supply, Laying, Termination of ISI Certified 4 Core 1.5 sq.mm ATC, PVC Mtr
insulated, armored, Tinned Copper, twisted, shielded, PE insulated, Cable with
proper ferrules, lugs and other necessary accessories. The spec shall meet the
system manufacturer specifications 200

d Supply, Laying, Termination of ISI Certified Cat 6 cable and PVC conduit with all Mtr
other mounting accessories complete as required.
50

Sub Total ' '' '' '0 ' '' '' '0
Grand Total ' '' '' '0
GST - 18% ' '' '' '0

Grand Total (Including GST) ' '' '' '0

Note:
a. If there is no provision for immersion thermo-wells then surface
mounted temperature sensor will be selected accordingly.
PERFORMANCE MONITOR OF AHU - BMS IO SUMMARY
S.No. Point Description Qty AI AO DI DO Soft IO IBMS Vendor Scope Builder/ HVAC / Utility Vendor Scope
A AHU 1
Air Flow Station at Fresh Air Duct for Monitoring BMS Supplier to provide and mount Air flow station with all HVAC Vendor to co-ordinate and confirm the location of
1 1 accessories. Cabling from sensor to DDC under BMS fixing the sensor.
Vendor scope
AHU Filter status via Differential pressure switch BMS Supplier to provide and mount Differential pressure HVAC Vendor to co-ordinate and confirm the location of
switch with all accessories. Cabling from DP Switch to DDC fixing the DP Switch
under BMS Vendor scope
2 1

AHU Run status via Differential pressure switch BMS Supplier to provide and mount Differential pressure HVAC Vendor to co-ordinate and confirm the location of
switch with all accessories. Cabling from DP Switch to DDC fixing the DP Switch
under BMS Vendor scope
3 1

Chilled water Inlet & Outlet temperature sensor BMS Supplier to provide and mount Immersion temperature HVAC Vendor to co-ordinate and confirm the location of
sensor with all accessories. Cabling from temperature fixing the sensor.
4 2 sensor to DDC under BMS Vendor scope

2 way modulating valve control & Feedback (Cooling Cabling from DDC to Valve actuator - BMS Vendor scope HVAC Vendor to provide the required Valve with actuator
Coil) of 0-10 VDC/ 4-20mA analog input/ output for control &
5 1 1 monitoring in BMS. HVAC Vendor to supply and mount the
valve with actuator.

Air Flow Station at Supply Air Duct for Monitoring BMS Supplier to provide and mount Air flow station with all HVAC Vendor to co-ordinate and confirm the location of
6 1 accessories. Cabling from sensor to DDC under BMS fixing the sensor.
Vendor scope
Duct Static pressure sensor BMS Supplier to provide and mount Duct static pressure HVAC Vendor to co-ordinate and confirm the location of
sensor with all accessories. Cabling from sensor to DDC fixing the sensor.
under BMS Vendor scope
7 1

Supply air Temperature and RH BMS Supplier to provide and mount Supply air temperature HVAC Vendor to co-ordinate and confirm the location of
& RH sensor with all accessories. Cabling from sensor to fixing the sensor.
DDC under BMS Vendor scope
8 2

Room T & RH sensor BMS Supplier to provide and mount Room temperature & HVAC Vendor to co-ordinate and confirm the location of
RH sensor with all accessories. Cabling from sensor to fixing the sensor.
9 2 DDC under BMS Vendor scope

VFD integration BMS vendor to consider 10 software points for each VFD. HVAC Vendor to provide RS 485 MODBUS/Bacnet interface
in each VFD panel. HVAC Vendor to show the parameters
on the MODSCAN / Bacstack /Cimetrics software before
integrating to BMS. All mapping details & ID setting in the
VFD to be done by the VFD vendor
10 1 10

BTU Meter integration BMS vendor to consider 5 software points for BTU meter. HVAC Vendor to provide RS 485 MODBUS/M-Bus interface
in BTU meter. All mapping details & ID setting in the BTU
meters to be shown to BMS Vendor before integrating.
11 1 5

Total for A 10 1 2 0 15

Note:
Consider 15 to 20% spare I/Os in each DDC Panel