Professional Documents
Culture Documents
2 Transformer Sizing Calculation
2 Transformer Sizing Calculation
2 Transformer Sizing Calculation
1 of 5
This note outlines the basic calculations for voltage drop of 380V motor during starting & the adequacy of
transformer capacity. For load details & grouping of loads refer Annexure 1
2 LEGENDS
Vms is the per-phase voltage at motor terminal at the commencement of start in volts.
V1 is per-phase value of pre-start voltage at 400V Bus in volts.
Vbs is per-phase value of voltage at 400V bus at the start of motor in volts
Cos is motor starting power factor
Xg is MV (10kV) source reactance in ohms.
Xt is Transformer reactance in ohms.
Xso is the combined Source reactance at 400V Bus = Xg + Xt in ohms.
In1 is the base load current
In2 is base current increase due to decrease in bus voltage from V1 to Vbs in amperes.
Is is motor starting current in amperes
Xc is the motor cable reactance in ohms
Rc is the motor cable resistance in ohms
In addition to meeting the load requirements of the process plant, the selection should also meet other
2.1.1
requirements such as,
The selected transfomer shall provide at motor terminals, a minimum voltage of 85 % of nominal
(i)
voltage during starting of the motor
2.1.2 Actual demand is assumed as the base load on the transformer prior to the largest motor starting
2.1.3 Motor power factor & efficiency data as per standard motors are considered
2.1.5 For the motor starting a power factor of 0.3 is assumed as per IEEE 141.
For the motor starting voltage drop calculations, a source fault level of 50 MVA coresponding to 2.62 kA, at 10kV
2.1.6
is adopted.
Selected Quantity in
Sl.No Department / Transformer No. Required kVA Total kVA
kVA Nos
5C1/5D1/5E1, 5F1/5J15J1/5K1/6C1,
3.2.01 6C1/6G1, WT1, WT1(2), UA1-1, WT2, 1785.96 2000 1 2000
UA1, QL1, 5Z1, 9Z1, 10Z1 / DTR-01
Largest motor
Rating in Base load in Base load Transform
Sl.No Application to be started
kVA kVA current er imp. %
in kW
5C1/5D1/5E1,
5F1/5J15J1/5K1/6C1,
3.3.01 2,000 6C1/6G1, WT1, WT1(2), 1374 2088 160 6.00
UA1-1, WT2, UA1, QL1,
5Z1, 9Z1, 10Z1 / DTR-01
5C1/5D1/5E1,
5F1/5J15J1/5K1/6C1,
3.4.01 2,000 6C1/6G1, WT1, WT1(2), 160 293.00 185 100 2
UA1-1, WT2, UA1, QL1,
5Z1, 9Z1, 10Z1 / DTR-01
V12 (VmsCos IsRc ) 2 {VmsSin IsXc IsXso Xso ( In2 In1 )}2 Equation 4.1
Where,
Rc= Maximum conductor resistance for cables Ohms/km
Xc= Reactance at 50Hz for cables Ohms/km
Lc= Length of cable kms
n= Number of runs of cable nos.
Is= Motor starting current Amps
In1= Base load current
Base current increase due to decrease in bus voltage from V1 to Vbs Amps
In2=
Per-phase voltage at motor terminal at the commencement of start
Vms= Volts
V1= Per-phase value of pre-start voltage at 400V Bus Volts 219.4
Vbs= Per-phase value of voltage at 400V bus at the start of motor Volts
10kV Fault level at the transformer terminal MVA 50
Xg= MV (10kV) source reactance PU per MVA 0.02
Power Factor (Cos ) 0.3
Sin 0.953939201
Equation 4.2
Vbs2 (Vms Cos Is Rc )2 (Vms Sin Is Xc ) 2
In the following specimen calculation Equation 4.1 & 4.2 with motor starting power factor is used for calculating
4.2.2
the starting voltage drop.
Substituting values of Is as 1758.00 Amps, Xc as 0.0036 Ohms, Rc as 0.0105 Ohms, In2-In1 as 177.9 Amps and
V1 as 219.40 Volts and solving equation 4.1, we get
Vms = 194.206 Volts
Vms = 88.517 % of V1
Substituting values of Is as 1758.00 Amps, Xc as 0.0036 Ohms, Rc as 0.0105 Ohms and Vms as 194.21 Volts
and solving equation 4.2, we get
Vbs = 206.363 Volts
Vbs = 94.058 % of V1
While starting the 160 kW motor on the 2000 kVA, 11/0.400kV transformer with an impedance of 6.00 %
and a base load of 1171 kVA on the transformer prior to the start of the 160 kW motor, the motor terminal
4.3.3 voltage at the commencement of motor starting will be 88.517 % of V1, which is more than the
requirement of minimum voltage of 85.00 % of V1. The voltage at 400V bus will be 94.058% of V1. Hence,
the selected transformer of 2000 kVA rating is adequate.