Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

GTP (KEI INDS - WBSEDCL).

PM5

CUSTOMER : WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (WBSEDCL)


CONTRACTOR : KEIINDUSTRIES LTD
PROJECT : CONVERSION OF HT AND LT OVERHEAD NETWORKS INTO UNDERGROUND SYSTEM AT
CHINSURAH TOWN IN DISTRICT-HOOGHLY, WEST BENGAL UNDER SPECIAL
INFRASTRUCTURE PROJECT (IPDS SPECIAL) SCHEME.
LOI NO. : CE/PROJECT-III/UG CABLE/LOI/CHINSURAH/SUPPLY/2017-18/NIT-1/48/2758
DATED 09/08/2018
MANUFACTURER : YAMUNA CABLE ACCESSORIES (P) LTD.
ITEM DESCRIPTION : HEAT SHRINKABLE OUTDOOR TERMINATION & STRAIGHT THROUGHT JOINT.

SCHEDULE OF GUARANTEED TECHNICAL PARTICULAR FOR


L.V. HEAT SHRINKABLE OUTDOOR TERMINATION & STRAIGHT TH. JOINTS
FOR XLPE/PVC CABLE

1. MANUFACTURER'S NAME & ADDRESS : M/s YAMUNA CABLE ACCESSORIES (P) LTD.
SARDANA NAGAR, AMBALA ROAD,
JAGADHRI - 135 003 [INDIA]

2. BRAND NAME & COUNTRY OF ORIGIN : DENSONS (INDIA)


3. MAKE : DENSONS

4. PRODUCT TYPE : HEAT SHRINKABLE

5. VOLTAGE GRADE : 1.1 KV


6. TYPE OF KITS OFFERED : HEAT SHRINKABLE

7. APPLICABLE STANDARDS : IS:13573 (2011) & ENATS 09 13

8. INSTALLATION TIME : 30 MINUTES AFTER PREPARATION OF CABLE


9. CURING TIME : N.A.

10. TIME REQUIRED FOR ENERGISATION : IMMEDIATE AFTER COMPLETION


AFTER COMPLETION OF JOINT

11. SPECIAL DEVICES REQUIRED, IF ANY : NO

12. KIT STORAGE TEMPERATURE : NORMAL AMBIENT TEMPERATURE, AWAY


FROM DIRECT SUNLIGHT

13. KIT SHELF LIFE : UNLIMITED IF KEPT UNDER SEALED CONDITION AND
AWAY FROM DIRECT SUN / HEAT

14. METHOD OF INSULATION BUILT UP : HEAT SHRINKABLE TUBING


15. DIELECTRIC STRENGTHOF INSULATION : 10 KV/MM (MIN.)
MATERIAL (KV/MM)
16. VOLUMERESISTIVIEY
INSULATING TUBING : 1 x 1012 OHM CM.(MIN.)
17. WATER ABSORPTION INSULATING TUBING : 1.0 % (MAX.)

18. TENSILE STRENGTHINSULATING TUBING : 8 N/SQ.MM. (MIN.)

19. ULTIMATE ELONGATION INSULATING TUBING : 200 % (MIN.)

Contd....2....
GTP (KEI INDS - WBSEDCL).PM5

CUSTOMER : WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (WBSEDCL)


CONTRACTOR : KEIINDUSTRIES LTD
PROJECT : CONVERSION OF HT AND LT OVERHEAD NETWORKS INTO UNDERGROUND SYSTEM AT
CHINSURAH TOWN IN DISTRICT-HOOGHLY, WEST BENGAL UNDER SPECIAL
INFRASTRUCTURE PROJECT (IPDS SPECIAL) SCHEME.
LOI NO. : CE/PROJECT-III/UG CABLE/LOI/CHINSURAH/SUPPLY/2017-18/NIT-1/48/2758
DATED 09/08/2018
MANUFACTURER : YAMUNA CABLE ACCESSORIES (P) LTD.
ITEM DESCRIPTION : HEAT SHRINKABLE INDOOR/ OUTDOOR TERMINATION & STRAIGHT THROUGHT JOINT.

SCHEDULE OFGUARANTEED TECHNICALPARTICULARS FOR


HEAT SHRINKABLE INDOOR/ OUTDOOR TERMINATION & STRAIGHTTH. JOINT
FOR ARMOURED XLPE/PVC CABLE

1. MANUFACTURER'S NAME & ADDRESS : M/s YAMUNA CABLE ACCESSORIES (P) LTD.
SARDANA NAGAR, AMBALA ROAD,
JAGADHRI - 135 003 [INDIA]

2. BRAND NAME & COUNTRY OF ORIGIN : DENSONS (INDIA)

3. VOLTAGE GRADE : 11 KV

4. TYPE OF KIT OFFERED : HEAT SHRINKABLE

5. APPLICABLE STANDARDS : IS:13573 (2011) & ENATS 09 13

6. MATERIAL OF TUBING : POLYOLEFIN

7. INSTALLATION TIME : 45 MINUTES FOR TERMINATION AFTER


PREPARATION OF CABLE
60 MINUTES FOR STRAIGHT JOINT AFTER
PREPARATION OF CABLE

8. CURING TIME : N.A.

9. TIME REQUIRED FOR ENERGISATION : IMMEDIATELY


AFTER COMPLETION OF TERMINATION

10. SPECIAL DEVICES REQUIRED, IF ANY : NO

11. KIT STORAGE TEMPERATURE : NORMAL AMBIENT TEMPERATURE


(DEGREECENTIGRADE)

12. (a) KIT SHELF LIFE : UNLIMITED IF KEPT UNDER SEALED


CONDITION AND AWAY FROM DIRECT
SUN LIGHT

13. LIST OF CONTENTS OF KIT : ENCLOSED


(TO BE FURNISHED SEPARATELY)

14. MATERIAL USED FOR STRESS CONTROL : POLYOLEFIN

15. DIELECTRIC STRENGTHOF INSULATION : 10 KV/MM (MIN.)


MATERIAL (KV/MM)

Contd....2....
GTP (KEI INDS - WBSEDCL).PM5

:: 2 ::

16. MATERIAL USED IN ENCAPSULATED : ADHESIVE LINE POLYOLEFIN COMPONENTS


COMPOUND & ENVIRONMENTAL SEALING

17. VOLUMERESISTIVIEY
1) STRESS CONTROL TUBING : 1 x 109 Ohm CM. (MIN.)
2) NON TRACKING TUBING : 1 x 1012 Ohm CM.(MIN.)

18. WATER ABSORPTION


1) STRESS CONTROL TUBING : 0.5 % (MAX.)
2) NON TRACKING TUBE : 0.5 % (MAX.)

19. TENSILE STRENGTH


1) STRESS CONTROL TUBE : 10 N/SQ.MM. (MIN.)
2) NON TRACKING TUBE : 8 N/SQ.MM. (MIN.)

20. ULTIMATE ELONGATION


1) STRESS CONTROL TUBE : 200 % (MIN.)
2) NON TRACKING TUBE : 200 % (MIN.)
GTP (KEI INDS - WBSEDCL).PM5

CUSTOMER : WEST BENGAL STATE ELECTRICITY DISTRIBUTION COMPANY LIMITED (WBSEDCL)


CONTRACTOR : KEIINDUSTRIES LTD
PROJECT : CONVERSION OF HT AND LT OVERHEAD NETWORKS INTO UNDERGROUND SYSTEM AT
CHINSURAH TOWN IN DISTRICT-HOOGHLY, WEST BENGAL UNDER SPECIAL
INFRASTRUCTURE PROJECT (IPDS SPECIAL) SCHEME.
LOI NO. : CE/PROJECT-III/UG CABLE/LOI/CHINSURAH/SUPPLY/2017-18/NIT-1/48/2758
DATED 09/08/2018
MANUFACTURER : YAMUNA CABLE ACCESSORIES (P) LTD.
ITEM DESCRIPTION : HEAT SHRINKABLE INDOOR/ OUTDOOR TERMINATION & STRAIGHT THROUGHT JOINT.

SCHEDULE OFGUARANTEED TECHNICALPARTICULARS FOR


HEAT SHRINKABLE INDOOR/ OUTDOOR TERMINATION & STRAIGHTTH. JOINT
FOR ARMOURED XLPE/PVC CABLE

1. MANUFACTURER'S NAME & ADDRESS : M/s YAMUNA CABLE ACCESSORIES (P) LTD.
SARDANA NAGAR, AMBALA ROAD,
JAGADHRI - 135 003 [INDIA]

2. BRAND NAME & COUNTRY OF ORIGIN : DENSONS (INDIA)

3. VOLTAGE GRADE : 33 KV

4. TYPE OF KIT OFFERED : HEAT SHRINKABLE

5. APPLICABLE STANDARDS : IS:13573 (2011) & ENATS 09 13

6. MATERIAL OF TUBING : POLYOLEFIN

7. INSTALLATION TIME : 45 MINUTES FOR TERMINATION AFTER


PREPARATION OF CABLE
60 MINUTES FOR STRAIGHT JOINT AFTER
PREPARATION OF CABLE

8. CURING TIME : N.A.

9. TIME REQUIRED FOR ENERGISATION : IMMEDIATELY


AFTER COMPLETION OF TERMINATION

10. SPECIAL DEVICES REQUIRED, IF ANY : NO

11. KIT STORAGE TEMPERATURE : NORMAL AMBIENT TEMPERATURE


(DEGREECENTIGRADE)

12. (a) KIT SHELF LIFE : UNLIMITED IF KEPT UNDER SEALED


CONDITION AND AWAY FROM DIRECT
SUN LIGHT

13. LIST OF CONTENTS OF KIT : ENCLOSED


(TO BE FURNISHED SEPARATELY)

14. MATERIAL USED FOR STRESS CONTROL : POLYOLEFIN

15. DIELECTRIC STRENGTHOF INSULATION : 10 KV/MM (MIN.)


MATERIAL (KV/MM)

Contd....2....
GTP (KEI INDS - WBSEDCL).PM5

:: 2 ::

16. MATERIAL USED IN ENCAPSULATED : ADHESIVE LINE POLYOLEFIN COMPONENTS


COMPOUND & ENVIRONMENTAL SEALING

17. VOLUMERESISTIVIEY
1) STRESS CONTROL TUBING : 1 x 109 Ohm CM. (MIN.)
2) NON TRACKING TUBING : 1 x 1012 Ohm CM.(MIN.)

18. WATER ABSORPTION


1) STRESS CONTROL TUBING : 0.5 % (MAX.)
2) NON TRACKING TUBE : 0.5 % (MAX.)

19. TENSILE STRENGTH


1) STRESS CONTROL TUBE : 10 N/SQ.MM. (MIN.)
2) NON TRACKING TUBE : 8 N/SQ.MM. (MIN.)

20. ULTIMATE ELONGATION


1) STRESS CONTROL TUBE : 200 % (MIN.)
2) NON TRACKING TUBE : 200 % (MIN.)