Design Project Fall01

You might also like

Download as rtf, pdf, or txt
Download as rtf, pdf, or txt
You are on page 1of 4

CVEN 3323 HYDRAULICS: WATER DISTRIBUTION SYSTEM DESIGN

PROJECT

This project involves the design of a water distribution system for a hypothetical small
community.   The community consists of single family homes, apartment buildings, a
warehouse facility, a small hospital and a shopping center.  A site plan for the community
is given is Figure 1.  A skeleton of the pipe network model for the community is given in
Figure 2.  Water is piped from a ground storage facility through a set of pumps into an
elevated storage tank, which then feeds the community.   The dimensions of the pipes
within the network can be determined from the site map.  The various steps you need to
follow in the design are:

1.Estimation of the demands
2.Sizing of pipes and pumps
3.Checking your design for various operational scenarios, including potential fires.

1.Estimation of demands

Domestic Indoor Demands

The domestic indoor demands are computed from the per capita demand, which are given
as: 

57 gpcd (gallons per capita per day) for the low density residential units

61 gpcd for the medium density residential units, 64 gpcd for the high density residential
units

55 gpcd for the apartment units.  

The average occupancy is taken to be 3.5 persons per single family home and 2.5 persons
per apartment unit.  

Domestic Outdoor Demands

Domestic outdoor demands occur during 5 months in each year, and amount to 350 gpd
per single family home and 1350 gpd per apartment building.
Irrigation

Irrigation demand for the green belt is computed using an application of 1/2" of water per
2
unit area, 20 times during the irrigation season, over an area of 3 x 470 x 150 feet .  Note
that the green belt demand is not involved in the network design (see below), but should
be used in the calculation of annual water usage.  We are not assigning demand nodes for
the green belt nodes.

Warehouse Facility/Hospital/Shopping Center

The warehouse facility, hospital and shopping center, require:
an indoor supply of 500 gpd, 18000 gpd and 1000 gpd respectively
an   outdoor   supply   of   15000   gpd   is   required   by   each   of   these   consumers   during   the
irrigation season.

Fire Demand

Fire   demand  (gpm)   is   estimated   from  an  empirical  formula  and  yields   the   following
demands:

1000 gpm in each residential block (one hydrant per block), 

2000 gpm in a block containing apartments (one hydrant per block) 

4000 gpm in the commercial sector (one hydrant for each unit)

An additional amount of 1000 gpm for 30 minutes is required per month for testing fire
hydrants.

The   green  belt  and   fire  hydrant   testing   demands  are   not  used  in  the   computation   of
maximum   hourly,   maximum   daily   and   average   daily   demands,   because   they   can   be
scheduled   for   periods   of   low   water   demand.     However,   they   contribute   to   the   total
amount of water used and the total cost of water.

(a)Estimate the total annual demand of water for this community
(b)Exclude the green belt demand, fire hydrant testing and fire demands and use the
other demands to compute the average daily summer demand at each node.

(c)The   maximum   daily   demand   and   maximum   hourly   demand   are   determined   as
some multiples of the average daily demand (see e.g. Table 3.6 in the textbook for
values of these "demand factors").  The demand factors also depend on the size of the
community, and are significantly larger than the values given in Table 3.6 for small
communities.  Use demand factor values of 7.1 for the max. hourly demand and 6.2
for the max. daily demand.

2.  Design Criteria

The water distribution system should satisfy the following criteria:
1.Simulated   nodal   pressures   should   be   larger   than   40   psi   for   maximum   hourly
demand
2.Simulated nodal pressures should be larger than 20 psi for maximum daily demand
combined with a fire demand at any one of the demand nodes (the fire demand can
occur at any demand node, and the design should be checked for all possibilities.
3.The maximum allowed pressure in a pipe is 100 psi.
4.The flow velocity should not exceed 10 feet/second in any pipe.
5.The storage tank is constrained to have a diameter of 50 feet.  The elevated storage
facility should not have a water elevation higher than 100 feet; and the lower the
better, to keep construction costs down. The height of water in the storage tank should
not exceed 20 feet and can come down to 5 feet in case of a fire emergency demand
that lasts 2 hours.
6.Try to keep costs as low as possible (we will provide a schedule of costs on the
web).

3.  Materials

Assume ductile iron pipes are available in diameters at 2" intervals beginning from 6".
The American Turbine catalog (accessible on the web) can be used to select pumps with
the desired characteristic curves.

4. Suggested Approach
1.Use   a   demand   node   within   each   block   in   the   community   to   represent   all
demands within that block.  
2.Assigning the demand values corresponding to the maximum hourly demand at
each of these nodes.  
3.With these flow rates, size the pipes  and arrive at a height for the elevated
storage   tank,   to   ensure   that   all   pressures   are   acceptable   at   maximum   hourly
demand.  Note that we would like to use as small a pipe as possible in each line,
to   keep   costs   down.     Once   the   height   of   the   elevated   storage   tank   has   been
determined, the domestic supply pump can be designed to move water from the
ground storage reservoir to the tank.
4.The   next   step   is   to   check   the   above   network   design   under   conditions   of
maximum daily demand + a fire demand in any of the residential or commercial
units.  The demands at the nodes are modified to represent this condition, moving
the fire demand around to different nodes to determine the critical conditions.
Note that the fire demands are highest for the commercial units, which are also
farthest from the supply, so these are likely to be the critical fire demands.  The
design for fire conditions can include additional pumps located anywhere in the
system, between the ground storage reservoir and the commercial units.

You can adjust pipe diameters in EPANET at any stage, to revise your design.

5.  Report
Your report should include: 
(1)network map showing final pipe diameters and pump numbers 
(2)Map of flows and pressures during max. hourly demand 
(3)map of flows and pressures during critical fire demand 
(4)cost estimate for network.

You might also like